Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity



Similar documents
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Trinergy from 200 to 1600 kw. High Power Modular Scalable UPS With Three Dynamic Functioning Modes

Liebert APM from kw. The Compact Row-Based UPS With FlexPower Technology TM

IT White Paper. N + 1 Become Too Many + 1?

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green

Increased power protection with parallel UPS configurations

SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity

Standardization and modularity as the foundation of data center UPS infrastructure

NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM

The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management

Liebert NXC from 10 to 200 kva

4.0 UPS dedicated to ICT for unmatched energy savings

Power protection for data centers

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime

Reference Guide: SmartDesign Approach: Common Data Center Challenges:

Phase Modular Finally the benefits of Modular ups are for all

Liebert 80-eXL from 100 to 1200 kw. Enhanced Design and Improved Efficiency

Chloride 80-NET from 60 to 500 kw. Secure Power for Mission Critical Applications

Galaxy VM. Three-phase power protection. schneider-electric.com

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Evaluating the Opportunity for DC Power in the Data Center

Advantages and Efficient Use of Programmable Sockets. By Miguel Rascon AC Power Senior Product Manager

Miracel 19 rack platform for data center, telecommunication and network technology. Rack & Integrated Enclosure Systems

Microsoft Technology Center: Philadelphia

NetSure DC Power Solutions with esure High-Efficiency Technology

Data Center Trend: Distributed Power in the White Space

The Trellis Dynamic Infrastructure Optimization Platform

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

The Pros and Cons of Modular Systems

Move beyond the expected.

Applying Data Center Infrastructure Management in Collocation Data Centers

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

How To Make A Data Center More Efficient

Power Distribution Considerations for Data Center Racks

Meeting the FCC Backup Power Mandate From Site Audit to Total Site Solutions. DC Power, Outside Plant & Services for Business-Critical Continuity

PX100 MBP with Configurable Distribution

Designed for uptime. Defining data center availability via a tier classification system

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

Case Study Nottingham Trent University

IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS

Product catalog ABB UPS products and solutions Power protection for critical infrastructures

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring

DISTRIBUTED REDUNDANCY:

Common Access Card Application

Protecting The Critical IT Infrastructure of the United States

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Protecting Our Information, Protecting Our Resources

How To Save Energy On A Power Supply

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity

Trinergy Cube from 300 kw to 3 MW. Beyond the Power Revolution

Five Essential Components for Highly Reliable Data Centers

High Availability for Non-Traditional Discrete and Process Applications Ensuring Continuous Operations With Increased Controller Reliability

Tough Decision: On-Line or Line-Interactive UPS?

HUAWEI TECHNOLOGIES CO., LTD. Huawei IDS2000-S Small Modular Data Center Solution

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) don@tubbesing.com

DataCenter.BZ. Background. Case Summary. & dark fiber solutions

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Overview brochure. Power management solutions for network closets, server rooms and data center environments

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

PowerGem Pro Uninterruptible Power Supply

Eaton 93PM UPS Efficient. Scalable. Innovative.

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Enterprise Remote Monitoring

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

One. Invest with confidence Smart Solar Inverter Solutions. solarinvertersolutions.com. Residential, commercial and large scale applications

Data centre experts. Advanced power protection for data centres

Microsoft s Open CloudServer

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

Qualitative Analysis of Power Distribution Configurations for Data Centers

How To Run A Data Center Efficiently

High-Availability Power Systems, Part II: Redundancy Options

ABB PSPS Erich Steinmann; Generator control-2013

Cisco Nexus 7000 Series.

ACTURA V DC, 3-40 kw, A. The Regional DC power system with Global Muscle

TLE Series UPS kva/kw three phase 400 Vac with best-in-class efficiency

IPSIP M series-m Modular Data Center

Efficient water management and sustainable solutions

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert CW kW Chilled Water Cooled Precision Air Conditioning For Data Centers

Seven Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide

Symmetra PX. Industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments

Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems

InstaPATCH ZERO Solution Guide

How To Upgrade An Hp Power Distribution Rack To A Power Distribution Unit

Cisco Nexus 7000 Series Power Supply Modules

Transcription:

Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity

Abstract Today, more than ever before, energy efficiency and cost-savings are among the top priorities for customers of all applications. The efficient use of energy however, is an issue that is particularly critical for the data center sector, both from an environmental and financial perspective. As a consequence, data center operators seek solutions that incorporate optimum performance and reliability in order to be able to achieve, not only the necessary energy and cost-savings, but also the uninterrupted support that they are expected to provide to their commercially critical applications. In turn, UPS systems are required to deliver optimum power quality at minimal cost whilst delivering levels of redundancy that ensure seamless operation and savings. In order to meet the demanding performance and efficiency requirements of today s ever growing data centers, it is becoming more and more common to adopt a modular approach to the design of high performance UPS solutions. Furthermore modular solutions are in line with the European Union Code of Conduct on Data Center Best Practices which specifically highlights the advantages to be gained from the use of modular concepts in energy efficient UPS systems. Introduction The modular approach to UPS architecture provides a number of advantages for the end user by broadening the scope for energy and cost-savings, system flexibility, adaptability, redundancy and fault tolerance. As a recognized leader in the UPS industry, Chloride UPS have long been known for anticipating market needs and developing benchmark solutions particularly in terms of technology. To this extent Emerson Network Power's Chloride business has developed Chloride Trinergy ; an intelligent modular solution designed to meet the highest standards of performance, serviceability, flexibility and scalability, while also incorporating maximum energy saving features. Furthermore, Chloride Trinergy meets all of the requirements set out in the European Union Code of Conduct on Data Center Best Practices mentioned with reference to modular concepts. Chloride Trinergy is like no other modular solution ever before seen in the market. We will take a closer look at the specific design features of the Chloride Trinergy modular architecture later in this paper, but first we need to understand exactly what modularity is and how the concept forms the basis of the latest milestone in UPS innovation. EU Code of Conduct on Data Centers: Energy Efficiency Best Practices The provisioning of excess power. in the data center drives substantial fixed losses and is unnecessary. Planning a data center for modular (scalable) expansion and then building out this capacity in a rolling program of deployments is more efficient. The European Code of Conduct recommends modular (scalable) UPS systems across a broad range of power delivery capabilities. Physical installation, transformers and cabling are prepared to meet the design electrical load of the facility but the.ups. are installed, as required, in modular units. This substantially reduces both the capital costs and the fixed overhead losses of these systems.

What is modularity? The modular design of a UPS consists of separating the system/ components into smaller parts (modules) that work together as a whole system. Each individual power module is built with the necessary hardware to be able to allow it to work together with other modules as a larger, more powerful system. Depending on the modular approach taken by the manufacturer, UPS modules can be arranged as a combination of power and/or battery modules housed within the same cabinet. In terms of UPS the configuration of a group of modules working together as a complete system helps eliminate the possibility of a single point of failure thus minimizing downtime. The basic concept of modularity has been used in our UPS in certain forms for some time. Existing modular arrangements already incorporated in Chloride UPS are the concepts of Vertical and Horizontal modularity. Chloride Trinergy Chloride Trinergy is designed to monitor the operating environment in which it works and intelligently select the most efficient functioning mode for resolving disturbance while maintaining top performance of the load. One of the elements that makes Chloride Trinergy a unique UPS is the combination of Vertical and Horizontal modularity together with the addition of a new third dimension referred to as Orthogonal modularity. Chloride Trinergy s three dimensions of modularity, allow the user to add power modules to a central I/O Box at anytime during the lifecycle of the UPS, allowing it to reach the highest active power rating available to date in a single UPS system: 9.6 MW. Vertical modularity: refers to the internal architecture of the UPS in which the component parts are configured as extractable sub-assemblies inside the UPS cabinet. This improves the flexibility and serviceability of the UPS and thus reduces the time needed for service, repair (MTTR - mean time to repair minimized) and maintenance. Chloride Trinergy has three dimensions of modularity; Vertical, Horizontal & Orthogonal, all incorporated to make it the best scalable solution available in the market. So how do Chloride Trinergy s three dimensions of modularity work? Vertical modularity: Internal view of UPS with sub-assemblies Horizontal modularity: refers to the option of increasing the overall system power by adding additional UPS modules to an existing modular infrastructure in order to increase power and/or redundancy. Horizontal modularity allows the end user to make an initial investment in line with their immediate (short-term) power protection needs and subsequently increase the power of the system as and when their future business needs change. Vertical modularity for serviceability As seen earlier, Vertical modularity essentially refers to the stacked drawers inside each cabinet module which can be individually extracted for ease of service and maintenance. Key characteristics of Chloride Trinergy s vertical modularity: Construction - Each individual UPS power module cabinet houses standard sub-assemblies for the rectifier, inverter and static bypass which together make up the component parts of a single 200 kw UPS. Accessibility - Modules are easily accessible from the front of the cabinets, allowing for simplified service and maintenance to be carried out. Front accessibility has the added benefit of space saving by eliminating the need for free space in the rear of the unit. Maintenance - Chloride Trinergy s 200 kw modules are based on easily withdrawable units, allowing maintenance on individual components to be greatly simplified. Horizontal modularity: Conventional horizontal modularity: UPS in parallel Installation - Chloride Trinergy s modular design facilitates installation by allowing the UPS to be assembled on-site, module-by-module, making it ideal even for sites with difficult accessibility. The maximum dimensions of any single Chloride Trinergy 200 kw unit are: W.1070 x D.850 x Ht.1780 mm.

Horizontal modularity for power upgrades Chloride Trinergy can scale up to 1.2 MW of power by adding complete 200 kw cabinet modules to an existing modular infrastructure. Key characteristics of Chloride Trinergy 's horizontal modularity include: Parallel Modules - A single Chloride Trinergy UPS system can consist of up to six 200 kw UPS cabinet modules. The number of UPS modules that can be connected depends on the initial choice of the central I/O Box which is available for two, four or a maximum of six 200 kw modules. Once the dedicated I/O Box has been installed, it can be configured to the power rating required by adding or removing modules to meet the installation power requirements. Distributed Control - Chloride Trinergy 's parallel control is distributed evenly between UPS modules so that there is no master/slave architecture, hence eliminating the possibility of a single point failure. The essence of this concept is that the overall multi-module system is controlled and monitored automatically by the integral controls within each individual UPS module. A closed loop data bus system enables data to be shared between modules and is configured such that a first fault in the data string will not affect operation or load support. In field upgradability: grows with load needs - A Chloride Trinergy system can initially be configured to meet the immediate load requirements without oversizing the system to cater to foreseeable future load requirements. Additional modules can easily be added at a later date as and when the load power requirements change. This helps minimize the initial capital investment and has the added advantage of ensuring that the UPS system operates at a significantly higher percentage load for optimum efficiency. Internal redundancy - Chloride Trinergy can be configured to provide different levels of system redundancy. A system is defined as redundant if the number of power modules installed is at least N+1, where N equals the number of power modules necessary to power the load and 1 is the redundancy coefficient. This essentially means that even in the rare case that a single power module fails, it will automatically be disconnected from the system and the remaining modules will continue to support the critical load. Concurrent maintainability - Chloride Trinergy is designed to allow individual power modules to be isolated for safe maintenance whilst the remaining modules continue to provide conditioned power to the load. Availability - Availability of power from a user s perspective is fundamental to the entire installation. It is essential that the user has the confidence and knowledge that the UPS is always in service, supplying conditioned and secure power to the critical load without interruption. The availability of power for the critical load is directly linked with reliability and maintainability. This means that the mean time between failure (MTBF) of the equipment must be high and the mean time to repair (MTTR) should be as short as possible in order to achieve a high system availability factor. Chloride Trinergy addresses both of these functions by using well proven 200 kw power modules for high MTBF and standard modular UPS sub-assemblies to ensure minimum MTTR for each UPS. Reliability (MTBF) - It is essential that the mean time between failure (MTBF) of a UPS system is as high as possible, especially to satisfy the demands of critical computer applications such as data centers. The concept of redundancy is a key element in designing highly reliable power supply systems with high MTBF. The advantage of Chloride Trinergy s modular system is the ease with which additional modules can be added in order to achieve the level of redundancy required by the system. The high MTBF of the Chloride Trinergy system has been achieved by basing the system on the well proven transformer-free free technology currently used for 200 kva Chloride UPS. Maintainability (MTTR) - The modular arrangement of Chloride Trinergy s internal sub-assemblies ensures a short mean time to repair (MTTR) for individual UPS modules. If spares are held on site, the MTTR can be further reduced. Batteries - The concept of modularity extends also to batteries. Whilst it is possible to use a common battery for the whole Chloride Trinergy system, reliability can be further enhanced by using distributed batteries i.e. a separate battery bank for each 200 kw UPS module. The I/O Box used for connecting the batteries provides the DC electrical connection facility to enable either one single battery or distributed batteries to be used.

Orthogonal modularity for parallelability Orthogonal modularity is the ability of Chloride Trinergy to work with up to eight complete UPS systems in parallel equaling a total of up to 9.6 MW. Key characteristics of Chloride Trinergy s orthogonal modularity: System Power Capability - Orthogonal modularity refers to the ability of Chloride Trinergy to connect up to eight 1.2 MW UPS systems, each consisting of six 200 kw UPS modules, to achieve a total system power capability of 9.6 MW. System Power Flexibility - Chloride Trinergy can also be configured to match existing site switchgear power requirements. For example, a 2 MW system can be configured as two systems of five 200 kw modules or it could equally be configured as five systems of two 200 kw in order to match existing electrical switchgear. The touch screen feature provides access to operational parameters and to the service history log in order to fast track maintenance. The main power isolators are located on the front of the I/O Box, including the rectifier and static bypass input switches, the system maintenance bypass switch, output switch and battery isolator. The arrangement enables any module to be isolated for maintenance purposes without disconnecting the load. The central I/O Box is available in three different ratings: 400 kw, 800 kw and 1200 kw. In its largest format, up to six 200 kw power modules can be connected to the I/O Box. The central I/O Box also contains the input and output terminals and is configured to allow either top or bottom cable entry as required. The I/O interface for both power and communication, greatly simplifies installation. Centralized and distributed battery configurations are also connected to the central I/O Box. System Power Redundancy - Redundancy can be built into the system at any point. For example, a 1 MW load may be supported by five 200 kw modules with an extra module added to achieve the redundancy required for the given load. Similarly, if eight groups of six 200 kw (N+1) systems were to be operated in parallel then the effective overall level of redundancy for this as an 8 MW system would be (N+8). In this way an exceptionally high level of security and availability of power protection can be configured to meet specific load requirements. If however, a lower level of redundancy is required (N+1) it is possible to achieve a higher power configuration of 9.4 MW while at the same time maintaining redundancy. Circular Redundancy - When using a redundant system it is quite common that UPS operate at light loads which in turn lower its efficiency. Chloride Trinergy however, has an inbuilt circular redundancy capacity which allows the system to automatically switch OFF excess UPS power capacity not used in meeting immediate load requirements. This allows Chloride Trinergy to operate with extremely high efficiency even at very light loads, while at the same time increasing the level of reliability of the system by activating only the required number of power modules. The use of automatic circular redundancy means that the overall system is able to run at optimum efficiency at all times while maintaining a high level of load protection. The system of circular redundancy ensures that the rested (excess) UPS modules are rotated so as to allow them to be operated for an equal amount of time. I/O Box Chloride Trinergy's three level of modularity are built around the I/O Box which is the major interface for connectivity and power connections. Traditional multi-module UPS systems require an input supply protection device for each UPS in the system. Chloride Trinergy simplifies this with the central I/O Box which serves as a central point for all connectivity and power connections of each group of up to six 200 kw power modules. The central I/O Box also houses a 12.1 inch LCD touch screen display which allows for easy monitoring of the system and the individual modules. Internal view of I/O Box Conclusion From the characteristics outlined in this paper it is evident that the modular architecture used in the design of Chloride Trinergy allows for never before seen flexibility and unprecedented efficiency. Not only is its modular architecture in line with European Union Code of Conduct on Best Practices, but it also offers attractive benefits for end users in terms of significant capital cost-savings and reduction in running costs. Chloride Trinergy s modular architecture is designed to give users the flexibility of expanding the system in small or large increments to cater for changes in the business power protection requirements. This naturally provides cost-savings for end users as they are able to make an investment based on their immediate power protection requirements with peace of mind knowing that in the future they can easily build on their existing infrastructure.

Chloride WORLD HEADQUARTERS Via Fornace 30 40023 Castel Guelfo (BO) Italy T +39 0542 632 111 F +39 0542 632 120 E Enquiries.Chloride@Emerson.com www.chloridepower.com Emerson Network Power. The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com AC Power Embedded Computing Infrastructure Management & Monitoring Precision Cooling Connectivity Embedded Power Outside Plant Racks & Integrated Cabinets DC Power Industrial Power Power Switching & Controls Services Emerson, Business-Critical Continuity and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. 2011 Emerson Electric Co.