A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

Similar documents
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

Understanding Arc Flash

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

Part 1 System Modeling & Studies for Existing Systems

Choosing the Best Solution for Reducing Arc Energy

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Arc Flash Energy Mitigation Techniques

misconceptions about arc-flash hazard assessments

2008 Eaton Corporation. All rights reserved.

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

What s up with Arc Flash?

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

PRESENTED AT THE 2011 IEEE IAS PULP & PAPER INDUSTRY TECHNICAL CONFERENCE, NASHVILLE, TN: IEEE PERSONAL USE OF THIS MATERIAL IS PERMITTED.

Arc Terminator Active Arc-Resistant Switchgear

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

2013WWOA Conference Technical Conference Program

NFPA 70E Updates Affect Your Most Valuable Assets

Low Voltage Circuit Breakers. Arc flash hazards

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

THE reliability, cost, and safety of electricity and industrial

Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.

Introduction to Arc Flash

How to reduce exposure to arc flash hazards

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Short Circuit Current Calculations

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment

Safety By Design. Strategies for Electrical Contractors

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

New standardized approach to arc flash protection

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

Electrical Safety Program

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

Low Voltage Switchgear

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac

Analyzing Electrical Hazards in the Workplace

Using Infrared Sightglasses to Protect Against Arc-Flash Exposure

Electrical Distribution Services for Mining and Metals Industries

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary

Secondary Unit Substations

Contents. Description. Product Selection Guide

A Survey of Arc Flash Computation Methods and Mitigation Strategies By Dr. Carl J. Spezia

SURGE PROTECTIVE DEVICES

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

The Performance of Voltage Rated Gloves in Arc Flash Exposures

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Automation & Power World Improving safety Through arc resistant switchgear and arc reducing components. ABB Wednesday, 23 March 2011 Slide 1

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

ELECTRICAL SAFETY RISK ASSESSMENT

Extend the Life of Existing Switchgear

Fault Characteristics in Electrical Equipment

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Arc Flash Standards - Australian Developments

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

Engineering Series Ratings: Is It Practical?

Alternate Methods to Short Circuit Breaker Coordination

Technical Guide. SKM Arc Flash Line Side vs. Load Side

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

UL Validated Testing of Arc-Resistant Motor Control Centers

Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC. BU 3101 Low Voltage Systems June 27, 2013 Slide 1

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Sample - No Commercial Use

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED

ETAP Arc Flash Analysis

Worldwide Thermography Headquarters

DOE HANDBOOK ELECTRICAL SAFETY

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Mission Critical Data Center Systems

Switchgear and Metal-Enclosed Bus

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

OSHA & ARC FLASH HAZARD ANALYSIS

21 st Century Facilities

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Unified requirements for systems with voltages above 1 kv up to 15 kv

Commercial/Industrial Electricity

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

UFES Active protection for switchgear

Transcription:

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John Jennings, Power Analytics, Raleigh, NC Brian Radibratovic, Power Analytics, San Diego, CA ABSTRACT This paper describes enhanced safety and maintenance features required within LV Motor Control Centers and Switchgear. Enhanced capabilities will include discussion of using NFPA 70E [1], ANSI C37.20.7 [2] and IEEE 1584 [3] in the development of low voltage arc resistance equipment. Highlights will include discussion of arc flash danger to personnel and the solutions used in the development of arc resistant low voltage switchgear and motor control centers. Arc flash software modeling shall be compared with actual testing of equipment per ANSI C37.20.7. INTRODUCTION An arc flash incident is defined as an enormous amount of concentrated radiant energy that explodes outward from electrical equipment, creating pressure waves that can damage a person s hearing; a highintensity flash that can damage their eyesight; and a super-heated ball of gas that can severely burn a worker s body and melt metal. Before starting out attempting to identify the reduction of arc flash hazards, priorities must be set, such as: Has an arc-flash study been done? Has the equipment been tested properly? How can I model the equipment properly What feature sets are required to reduce arc-flash hazards? Can the hazard be completely removed? For example, removing all power prior to work. IEEE Standard 1584 [3], IEEE Guide for Performing Arc Flash Hazard Calculations defines the practice for performing detailed arc flash calculations. This method has become the currently accepted industry practice used for calculating the prospective incident energy that could be available at a given location which can be used to determine the PPE requirements. A software model can be developed in order to identify the calculated amount of energy released. These software programs quickly identify the grade of clothing required by operators and easily provide protective signs for electrical equipment stating the type of protective clothing required when working around energized equipment. In addition, these programs quickly and accurately calculate the effects of flowing faults in three-phase, single-phase AC and DC power distribution systems. Multiple factors must be taken into account to evaluate the specific arc flash energy available, such as the site s available flash energy hazard, safety training, and safety program [6]. The equipment test procedure is well defined in ANSI C37.20.7 [2]. This standard establishes a method by which metalenclosed switchgear, as defined by IEEE Std C37.20.2 [7], can be tested for resistance to the effects of arcing due to an internal fault. The test procedure and actual test results for equipment are described in this document.

Conclusions are drawn based on theoretical modeling compared to actual test results of low voltage motor control center arc flash testing. IEEE 1584 9-STEP PROCESS FOR ARC FLASH ANALYSIS [8] Published by the Institute of Electrical and Electronics Engineers and titled "Guide to Performing Arc Flash Calculations," IEEE 1584 provides empirical formulas for determining arcing fault current, flash protection boundaries, and incident energy. The formulas are valid for systems ranging from 208 V to 15 kv. Theoretical formulas are provided for conditions outside this range. ARC FLASH ANALYSIS PROCESS IEEE 1584 establishes a nine-step process for gathering information and calculating arc flash hazards. The steps are: 1. COLLECT ELECTRICAL SYSTEM DATA Collecting system data is the most difficult and time-intensive step in performing an arc flash hazard analysis, but accurate information is vital to correctly calculating flash boundaries. A relatively small error at this point can invalidate all further calculations. Information collected should be recorded on a one-line diagram of the facility's electrical system. This diagram should be updated whenever modifications are made to the system, and a typical diagram is shown in Figure #1. Figure 1: Typical One-Line Diagram

2. DETERMINE MODES OF OPERATION Many electrical systems, especially in smaller facilities, have only a single mode of operation. In large facilities, however, it is common to find a number of operating modes, possibly including: emergency modes in which only backup generators provide power; multiple utility sources or generators that are switched in or out; and motors or portions of the system that may start or cease operation. All of these different modes cause changes in current at various points in the system, altering incident energy and flash boundaries. 3. DETERMINE BOLTED FAULT CURRENTS The bolted fault current is the current that would flow through a short circuit consisting of two conductors bolted together. It is the maximum current available to flow through a short circuit. This information is used to calculate the arc fault currents. Bolted fault currents should be determined for each piece of equipment likely to require maintenance or inspection while energized. 4. DETERMINE ARC FAULT CURRENTS The current that flows through an arcing fault is usually significantly less than the bolted fault current, due to greater resistance. Arc fault current calculations are based on voltage, bolted fault current, conductor gap distance, and other factors. IEEE 1584 presents two formulas for calculating arc fault currents, one for use with 0.208-1 kv systems, and the other for systems between 1 and 15 kv. For systems between 0.208 and 1 kv: lg Ia = K + 0.662(lg Ibf) + 0.0966(V) + 0.000526(G) + 0.5588(V)(lg Ibf) - 0.00304(G)(lg Ibf) For systems between 1 and 15 kv: lg Ia = 0.00402 + 0.983(lg Ibf) Where Ia = arc fault current in ka; K = -0.153 for open-air arcs and -0.097 for enclosed arcs; Ibf = 3-phase bolted fault current in ka; V = voltage in kv; G = conductor gap in mm 5. DETERMINE PROTECTIVE DEVICE CHARACTERISTICS AND DURATION OF ARCS The time-current curves of upstream protective devices are a major factor in determining how long an arcfault will last. An effort should be made to determine the actual settings rather than relying on standard values, as these may cause incident energy to vary greatly. Another consideration when analyzing protective devices is that incident energy depends on both fault current and time. Since protective devices are slower at lower currents, minimum fault currents often pose the worst-case arc flash scenario. 6. DOCUMENT VOLTAGES AND EQUIPMENT CLASSES Voltage and equipment class determine what equation should be used to find the flash boundary, as well as the bus gap distances required by the equations. Systems operating at <1 kv use a different equation than those operating between 1 kv and 15 kv. In

addition, IEEE 1584 recognizes six equipment classes, as shown in table #1. The bus distances used to help determine the arcing fault current. Classes of equipment Typical bus gaps, mm Open Air 10 40 Low-voltage switchgear 32 15kV switchgear 152 5kV switchgear 104 Low-voltage MCCs and panelboards 25 Cable 13 7. ESTABLISH WORKING DISTANCES Table 1: Classification of Equipment with typical bus gaps The working distance is the distance from a potential arc source to a worker s face and chest. It is a critical quantity in determining the flash hazard boundary, as even an increase of a few inches in working distance can cause a significant drop in incident energy. 18 inches is the working distance most commonly assumed in calculations, but efforts should be made to determine actual working distances. Some usual working distances are shown in table 2. Classes of equipment Typical working distance, in Low-voltage switchgear 24 15kV / 5kV switchgear 36 Low-voltage MCCs and panelboards 18 Cable 18 Table 2: Typical Working Distances. 8. DETERMINE INCIDENT ENERGIES Incident energy is defined in NFPA 70E as "the amount of energy impressed on a surface, a certain distance from the source, generated during an electrical arc event." In an arc flash hazard study, the "surface" is the worker's body at the assumed working distance. Incident energy is expressed in cal/cm 2. IEEE 1584 uses the following formulas: (1) E = 4.184(Cf)(En)(t/0.2)(610x/Dx)

Where E = incident energy in joules/cm2; Cf is a calculation factor (1.0 for voltages above 1 kv, and 1.5 for voltages below 1 kv); En = normalized incident energy (from equation (2) below); t = arc duration in seconds; D = distance from arc in mm; x = distance exponent (see table 3 below) Equipment Type D (Distance Exponent) Open air 2.0 Low-voltage (.208-1 kv) switchgear 1.473 High-voltage (1-15 kv) switchgear 0.973 Low-voltage MCCs and panels 1.641 Cables 2.0 Table 3: Distance Exponent (2) lg E n = K 1 + K 2 + 1.081(lg I a ) + 0.0011(G) Where En = energy normalized for distance of 610 mm and arc duration of 0.2 seconds, in joules/cm2; K1 = -0.792 for open-air arcs and -0.555 for enclosed arcs; K2 = 0 for ungrounded/high-z systems and - 0.113 for grounded systems; G = arc gap in mm; Ia = predicted 3-phase arc fault current in ka 9. DETERMINE FLASH PROTECTION BOUNDARY (FPB) The FPB is the distance at which incident energy is 1.2 cal/cm2, which is the amount of heat needed to cause second-degree burns. [8] The IEEE formula for calculating FPB is D B = [4.184(C f )(E n )(t/0.2)(610 x /E B )] 1/x Where EB is the desired incident energy at the boundary (usually 1.2 cal/cm 2, but occasionally set at a value matching proposed PPE rating), with other variables defined as for the incident energy equations above. ARC FLASH SOFTWARE MODELING There is very few credible arc flash software modeling tools available on the market. In order to be successful in modeling an arc flash event, three critical items are required. Precise information for every aspect of the power system with an extensive library of devices to easily add to the model, software compliance to national standards such as IEEE 1584, and expert service available to support any questions or enhancement requirements to the model. An arc flash calculation study requires calculating the equivalent arcing short circuit current at each location under study. The arcing current is used to evaluate the time current characteristic of the upstream overcurrent device that would interrupt the arc flash. Electrical network modeling software was used to model the simple circuit for testing the low voltage motor control center at the lab prior to actual testing. Generator parameters and breaker output

characteristics were provided by the testing power lab, including the bus connection sizing and ampacity rating. This allowed a model to be created as shown in figure 2. Figure 2: Software modeling for arc-flash testing Based on the modeling from software, the electrical system model is graphed comparing incident energy (cal/cm 2) with arc flash duration (cycles) [9]. Various characteristics are entered into the model and can have dramatic changes on the incident energy released as shown in figure 3. 350 300 250 200 150 100 50 0 cal/cm 2 1 3 5 10 15 20 30 50 100 Incident Energy vs Duration (cycles) 65 ka 480V BUS 100 ka 480V BUS 65 ka 600V BUS

Figure 3: Software modeling analysis results for arc-flash testing Once the arcing current and clearing time have been established, the IEEE 1584 formulas provide methods to calculate the incident energy in cal/cm 2 which can be used for the selection of personal protective equipment (PPE) as shown in table 4. The incident energy, flash protection boundary and category of PPE along with approach limits for shock protection can become part of the detailed arc flash label. Min Incident Energy, cal/cm^2 Max Incident Energy, cal/cm^2 Risk Category 0 Eb* 0 Required Min Rating of PPE, cal/cm^2 Eb* + 0.001 4 1 4 4.001 8 2 8 8.001 25 3 25 25.001 40 4 40 40.001 and above Not Available N/A * Eb is Incident Energy to second degree burn for bare skin exposure. Table 4: Hazard Risk Categories Another important feature of the software shows a comparison of arc duration vs. PPE level required as shown in figure 4. It is clear to see that faster clearing times significantly reduce the PPE requirements. 8 7 6 5 4 3 2 1 0 cal/cm 2 PPE Level (Above 4 is DANGER) 1 3 5 10 15 20 30 50 100 PPE Level vs Duration (cycles) 65 ka 480V BUS 100 ka 480V BUS 65 ka 600V BUS Figure 4: PPE level vs. Duration (cycles) In order to graphically show above Category 4 PPE this graph maximum value is 8 for anything greater than 4.

Once the arc flash study has been completed from your software model, a detailed analysis can be performed. This analysis includes providing all information for required labels on equipment and should provide a function of printing labels directly from the software as shown in figure 4. Figure 5: Typical Arc flash label required on equipment Although NFPA 70E does not mandate calculations be performed according to the IEEE 1584 methods, it is the method most people use. In addition, a credible software modeling tool can provide valuable insight into your electrical system performance. ARC FLASH TESTING SETUP Arc flash risk factors within a low voltage motor control center or switchgear lineup are generally associated with the modular design of the gear. A particular risk concern is the primary connection points known as stabs which consists of a moveable breaker or unit - connector that engages a vertical bus in the section. The connection is made during the removal and plugging in of the bucket at 480/600Vac levels. The testing comprised of creating an arc flash incident by placing a 10AWG bare copper wire across the three phases creating a bolted fault condition. Testing parameters for this series of tests were defined as: 1. Voltage Rated maximum voltage of the equipment 480V or 600V 2. Current (+5, -0%) Tolerance Applies for prospective SCCR current 65kA (68.2>x>65kA). 3. (480V@65kA, 480V@100kA and 600V@65kA) a) 600V@65kA b) 480V@100kA c) 480V@65kA 4. Peak Current (+5, -0%) Tolerance 2.3 Times the values of the internal arcing short-circuit current at 60 Hz a) 65kA x 2.3 = 149.5kA + 5% = 157kA b) 100kA x 2.3 = 230kA + 5 % = 241.kA 5. Frequency +/- 10% = 60 Hz (66>x>54Hz) 6. Current (+10, -0%) Tolerance The current shall not be less than the specified value at least for the first 3 half-cycles 25ms.

7. Peak Current At least 90% of the rated peak value if the voltage at the start of the test is lower than the rated voltage. 8. Arcing duration 0.5 sec 500ms preferred The testing was monitored by an array of thermocouples and cotton indicators. The array captured the amount of incident energy released and simulated cotton clothing worn does not ignite. Figure 6: Typical array arrangement per Ansi C37.20.7 TESTING REQUIREMENTS: IEEE 1584 specifies procedure to determine energy released in cal/cm2. ANSI C37.20.7 identifies specific pass/fail criteria. Testing is performed with covers and doors properly secured, therefore, arc resistance ratings are based on doors and covers being properly secured. Pass/Fail Criteria per ANSI C37.20.7 are: 1. Doors, covers, etc. do not open. Bowing or other distortion is permitted except on those which are to be used to mount relays, meters, etc. 2. That no parts are ejected into the vertical plane defined by the accessibility type 3. There are no openings caused by direct contact with an arc 4. That no indicators ignite as a result of escaping gases or particles 5. That all grounding connections remain effective ARC FLASH ENGINEERING MODEL VS TEST RESULTS The arc test results can be compared between IEEE 1584, ANSI C37.20.7, NFPA 70E and actual test results. Designbase software was used and compared to the actual test results from low voltage motor control center testing that was performed in March, 2012 at Kema test labs [10]. Results of arc-flash testing compared to calculated value shall be discussed at the IEEE PES conference in May, 2012 at San Antonio. Actual test results are not available at time of paper submission.

CONCLUSION Reduction of arc-flash hazards in equipment is an essential requirement for the future requirements of electrical equipment. There are multiple standards in place ensure to minimize energy released during an arc flash event. Credible design software is a key engineering tool to determine arc flash requirements to protect personnel and equipment. The duration of the arc has a significant effect on incident energy released and incident energy exposure to personnel. The goal is to minimize personnel exposure to the arc flash incident energy by applying the above solutions into a modern switchgear and motor control center configuration, minimizing arc flash energy levels. Note: 1.2 cal/cm2 max. (Hazard category 0). The best arc-flash protection for low voltage equipment assemblies needs to be addressed in a comprehensive manner. The best solutions take into account multiple aspects of design, maintenance and operations of equipment. Enhanced design features and capabilities provide a better environment for personnel. The bottom line is to provide a system that reduces the likelihood of an arc-flash hazard to occur! [5] REFERENCES [1] NFPA70E: Standard for Electrical Safety in the Workplace, 2012 Edition [2] ANSI C37.20.7 - IEEE Guide for Testing Medium-Voltage Metal-Enclosed Switchgear for Internal Arcing Faults [3] IEEE 1584: IEEE Guide for Performing Arc Flash Hazard Calculations. http://www.ieee1584.com/ [4] ARC-FLASH HAZARD ANALYSIS, Putting the Pieces of the Puzzle Together, John Lane, PE, Electrical Safety Engineer, AVO Training Institute [5] Power Analytics Software definition. http://www.poweranalytics.com/designbase/ [6] REDUCTION OF ARC-FLASH HAZARDS IN LOW VOLTAGE MOTOR CONTROL ASSEMBLIES Presented at 2007 IEEE PCIC Conference. [7] IEEE C37.20.2-1999 - IEEE Standard for Metal-Clad Switchgear [8] Arc Flash Hazard Electrical Safety Information. The Electricity Forum. www.electricity forum.com [9] Study conducted by Power Analytics Corporation [10] KEMA Power Labs - Generator and testing equipment data

DEFINITIONS 1. Arc flash hazard: A dangerous condition associated with the possible release of energy caused by an electric arc [1] 2. Incident energy: The amount of energy impressed on a surface, a certain distance from the source, generated during an electrical arc event. One of the units used to measure incident energy is calories per centimeter squared (cal/cm2) [1] 3. Arc flash boundary: When an arc flash hazard exists, an approach limit at a distance from a perspective arc source within which a person could receive a second degree burn if an electrical arc flash were to occur. [1] 4. Bolted fault current: A short circuit between two or more different phase conductors in which the impedance is virtually zero. [4] 5. Arcing fault current: Flow of current through a path consisting of vapor. The vapor has a substantial higher resistance than the solid metal. For low voltage circuits the arc consumes most of the available voltage leaving only the difference between system voltage and arc voltage, it is this difference that forces the current through the system impedance. The arc flash is like a laser but not quite as hot. A laser can create heat as high as 100,000 degrees K while the arc-flash can approach 20,000 or 35,000 degrees C. Essentially an arc creates a radiation burn. [4] 6. Voltage levels and ratings: Voltage is a representation of the electric potential energy per unit charge. If a unit of electrical charge were placed in a location, the voltage indicates the potential energy of it at that point. In other words, it is a measurement of the energy contained within an electric field, or an electric circuit, at a given point. Voltage can be rated in mv, V, kv, and MV. 7. Software modeling programs: gives electrical engineering professionals the means to create both a detailed design and knowledge base of the performance specifications of their entire electrical distribution system. [5]