Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop



Similar documents
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

SECTION 13XXX CONTROL DESCRIPTION (DICP Models NC, 412, 622, 826, 1030)

Controllers Model 353 Process Automation Controller with Ethernet Communication (Design Level B) Introduction

RCDC1 Radio Controlled Device Controller- 1 Channel

Programming A PLC. Standard Instructions

Bristol ControlWave Redundant Control

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

EXPERIMENT 2 TRAFFIC LIGHT CONTROL SYSTEM FOR AN INTERSECTION USING S7-300 PLC

WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Combi B Alarm box. Mounting instructions

The Child Reminder System Installation Manual

Fire Alarm Control Panel. Family. Operating Manual

Allen-Bradley/Rockwell

The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages.

Part Number Revision A, January Monitoring System Rack Configuration and Utilities Guide

Programmable Logic Controllers

INSTALLATION MANUAL PC2525. Version 1.1

Using your LED Plus keypad

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

GTS-4E Hardware User Manual. Version: V1.1.0 Date:

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

Study Guide for the Electronics Technician Pre-Employment Examination

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

SenseLink TM. End-Point Controller. Addendum

Operational Overview and Controls Guide

conventional system operation

CHAPTER 11: Flip Flops

Tebis application software

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Application/Connection Examples

CipherLab 5100 Time Attendance Utility Manual

L16. Quectel GNSS Engine. EVB User Guide L16_EVB_UGD_V1.0

AC-115 Compact Networked Single Door Controller. Installation and User Manual

How to read this guide

L5354 ControlNet Communications Interface

Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction Software Installation 2

ic-mq EVAL MQ1D EVALUATION BOARD DESCRIPTION

APPLICATION. si32library. Callback CMSIS HARDWARE. Figure 1. Firmware Layer Block Diagram

GLOLAB Two Wire Stepper Motor Positioner

The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages.

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Programmable Logic Controller PLC

Controller Automation, Model II+

ROC800-Series Advanced Pulse Module

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

GAE953 Electrical Alarm Unit 19" with Indicator

Mobile Data Power Model: MDP-25

Car Alarm Series 2 B 2 Buttons

Twido Simulator - Online Help Scope What's in this Part? Twido Simulator Overview What's in this Chapter? How to Use Twido Simulator

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev:

SECTION CONTROL SOFTWARE

VEHICLE THEFT/SECURITY SYSTEMS

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

210E - 210ECL ECL ECL RMS Signal Monitor. Operations Manual

MANUAL FOR RX700 LR and NR

How To Use A Watt Saver On A Microcontroller (Watt Saver) On A Cell Phone Or Mp3 Player

Micro Motion Net Oil Computer Software and NOC System

Safety Requirements Specification Guideline

Beckhoff TwinCAT. Configuring the TwinCAT I/O System

Temperature & Humidity SMS Alert Controller

DC LOAD TESTING Gian Trento June 18 th, 2004

WD-AMX Water Detection Controllers

Master Programming Manual for TotalCare, CareSoft Elite, CareSoft Pro, Ion Pro and CareClear Pro Models

Shadow TX(A) Shadow RX

EDI Distributor Control Interface Wiring and Setup Instructions

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

INTERFACING SECURITY SYSTEMS TO HOMEVISION

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

Build The Universal Alarm System

NX Series Inverters. HVAC Pocket Programming Guide

Alarms Trips: The Ups and Downs

Series Six Plus Programmable Controller

Digital Keypad Use s Manual

Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter

VLT 6000 HVAC. Contents

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46

M68EVB908QL4 Development Board for Motorola MC68HC908QL4

Animated Lighting Software Overview

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

ANTI-THEFT SYSTEM Volvo 850 DESCRIPTION & OPERATION BASIC ALARM ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems

WITURA CORPORATION SDN BHD

TRILOGI 5.3 PLC Ladder Diagram Programmer and Simulator. A tutorial prepared for IE 575 by Dr. T.C. Chang. Use On-Line Help

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

AN141 SMBUS COMMUNICATION FOR SMALL FORM FACTOR DEVICE FAMILIES. 1. Introduction. 2. Overview of the SMBus Specification. 2.1.

Contents. Document information

Conventional Fire Detection and Extinguishant Control System Specification

DKWF121 WF121-A B/G/N MODULE EVALUATION BOARD

EGCP-3 LS Revision L. Explanation of Software Changes Made for the EGCP-3 LS Control. Application Note 51294

Frequently Asked Questions for TFT Remote Controlled Monitors. First Rev 4/6/2005 SGMc Second Rev 5/7/2005 Third Rev 11/15/2005

Variable Air Volume - VAV

TC 1818a. Operating Guide. Control Module SWM-015.5

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

T Sentry 4 Multi-Point Digital Alarm Instruction Manual

Transcription:

APPLICATION DATA AD353-109 Rev 3 April 2012 Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop In critical control applications, a dedicated backup controller can provide increased security. This paper provides guidelines for designing, wiring, and configuring a single variable process control loop that includes a dedicated backup controller. The controllers shown are Siemens Procidia series Model 353 Process Automation Controllers 1, highly reliable, multiple-loop controllers frequently used in process control applications. See Figure 1. Primary Controller s 2 F I PB1 PB2 A M LOOP CLOSE 423. 45 C2 05. P S P 100 80 60 40 20 0 0 100 OPEN FT L ACK S D UNITS Tracking Watchdog On-Line Status Annunciator Backup Controller s 2 423. 45 F I C2 05. P S P 100 L PB1 ACK 80 S 60 PB2 D 40 A 20 UNITS M 0 LOOP 0 100 CLOSE OPEN Figure 1 Dedicated Backup Application features include: Watchdog monitoring of both primary and backup controllers Controlled element variable output signal tracking for bumpless control transfer Setpoint tracking Controller on-line and off-line transfer configuration 1 See Application Support at the back of this publication for a list of controllers. MG00197c Operation A single variable process control loop consists of one measured variable (e.g. flow rate) and one controlled element variable (e.g. flow control valve). In a dedicated backup controller application, both the primary and backup controllers monitor the measured variable. The primary controller generates the controlled variable output signal while the backup controller tracks the signal. Since both controller outputs are wired to the control valve, the backup controller is configured to disconnect its analog output block from the load. This prevents the backup controller from interfering with the process. The primary controller controls the process while the backup controller is off-line. While off-line, the backup controller tracks both the output variable and setpoint signals from the primary controller. Tracking these signals allows for a bumpless transfer. Watchdog monitoring is critical to a back up control system. In this application, each controller monitors the status of the other. For example, if the primary controller fails, the watchdog status changes. The backup controller reads the status change, switches to on-line mode to take control of the process control loop, and activates an external alarm to notify operating personnel. Since the dedicated backup control strategy depends on a functioning backup controller, the primary controller monitors the backup controller s watchdog status and activates an alarm if there is a failure. Hardware Requirements Hardware requirements are modest. Two Model 353 Process Automation Controllers with the I/O Expander Board option are needed. Several hardware options are available. Specifying the Ethernet Communication Board for each controller can

reduce station-to-station wiring by transferring the output tracking, setpoint tracking, and on-line status values across the Ethernet network. Some process applications can consume a portion of the controller s internal I/O needed for the dedicated backup circuits. External Ethernet I/O modules can be added when the Ethernet Communication Board option is selected. Wiring and Configuration Figure 2 shows the basic wiring needed for this application. Additional connections will be needed for either controller to operate and for the options discussed above. Refer to the controller s User s Manual for additional information. Figure 3 shows the configuration for primary and backup controllers. Either controller can be the primary or backup. The on-line controller is identified by the lighted green LED next to PB1 on its faceplate. Table 1 itemizes the I/O requirements for a single variable control loop with dedicated backup. The transmitter is also connected to the analog input 1 function block, AIN1+, in both controllers. A voltage signal is needed so a precision 250Ω resistor is installed to convert the transmitter s 4-20 ma signal to 1-5 Vdc. Controlled Element Output Signal The single-variable control configuration uses analog output 1 function block, AOUT1, to manipulate the controlled element. The output is a 4-20 ma signal. As only one controller s output signal may regulate the controlled element, the off-line controller disconnects its analog output signal from the load. AOUT1 is disconnected when the not on-line state, NOT3, is high (1). The configuration allows only one controller to be on-line at a time, otherwise current summing would occur. Setpoint and Output Variable Tracking Tracking signals are wired from one controller to the other. The setpoint tracking signal is wired from SIGNAL PRIMARY BACKUP Measured Variable AIN1 AIN1 Setpoint Tracking AIN2 AIN2 Output Variable Tracking AIN3 AIN3 Controller Element Variable Output AOUT1 AOUT1 Setpoint AOUT2 AOUT2 Output Variable AOUT3 AOUT3 On-Line Status Monitoring DIN1 DIN1 Watchdog DIN2 DIN2 On-Line Status DOUT1 DOUT1 Controller OK Status ROUT1 ROUT1 External Alarm ROUT2 ROUT2 Table 1 I/O Requirements Measured Variable In this application example, the measured variable is supplied by a 2-wire transmitter (FT) that is powered through a diode OR circuit connected to both controllers. If the 26 Vdc power supply of one controller fails, the remaining controller will power the transmitter. AOUT2 to AIN2 and the output tracking signal is wired from AOUT3 to AIN3. These current output signals are converted to a voltage by precision 250Ω resistors. The backup controller is in an off-line stand-by and track mode. In Figure 3, the not on-line state, NOT3, maintains the A/M and SETPT blocks in a stand-by and track mode. The A/M block tracks the time delayed output from DTM2, and the SETPT block tracks the time delayed setpoint from DTM1. When the controller goes on-line, the A/M and PID blocks go into automatic mode and the external signal relay is energized. 2

+ FT - Primary Controller Case Terminals 5 XMTR+ 6 Transmitter/Station Common 7 XMTR+ 8 DOUT1+ 9 10 11 DIN1+ 13 DIN2+ 17 AOUT1+ 19 AOUT2+ 20 AIN1+ Back-Up Controller Case Terminals XMTR+ 5 6 XMTR+ 7 DOUT1+ 8 9 DOUT2+ 10 DIN1+ 11 DIN2-14 DIN1-12 DIN2+ 13 12 DIN1-14 DIN2- AOUT1+ 17 AOUT2+ 19 AIN1+ 20 21AINC 22 AIN2+ 23 AIN3+ 24 AINC 28 ROUT1c 29 ROUT1no 33 AOUT3+ 40 COM Transmitter/Station Common AINC 21 AIN2+ 22 AIN3+ 23 AINC 24 ROUT1c 28 ROUT1no 29 AOUT3+ 33 COM 40 I P MG00196C Notes: 1. Transmitter/Station Common ground connection shown by 2. Range Resistor, typically 250 Ohms, shown by 3. Terminal numbers are for Models 353 and 354. Model 352P terminal numbers will be different. Only the terminals used in this application are shown. Controller must have an I/O Expander Board. 4. Function block IDs are for Models 352P, 353 and 354. 5. TR = Tracking; WD = Watchdog; OLS = On-Line Status Figure 2 Basic Wiring 3

The variable tracking and setpoint tracking values in the backup controller are time delayed a few seconds. As shown below, in the event of failure of the on-line controller, the backup controller has access to the tracking data produced seconds before the on-line controller failed and uses this data when it goes online. This minimizes the bump that can occur when there is a transfer of control. Tracking Signal Time Delayed Tracking Value On-Line Controller Failure Seconds 4 ma 0 ma Tracked values are saved in a dead-time table function block, DTM (see Figure 3). The DTM block has a minimum dead time of 0.1 minutes. The table is subdivided into 50 registers and the value in any register can be accessed by specifying the appropriate AT Input value. To configure a time delay of 3 seconds, for example, set the dead time in the DTM block to 0.1 minutes and set the value in HOLD block, HLD1, to 25. Watchdog and On-Line Status: The watchdog circuit monitors the status of the primary and backup controllers. If the primary controller goes off-line, the watchdog signals the online status circuit to initiate a bumpless switchover to the backup controller. The watchdog also provides a relay transition to annunciate the event. If the backup controller fails, the watchdog annunciates the event so that the system can be serviced. Each controller has two internal relays: ROUT1 and ROUT2. ROUT1 is used in the watchdog circuit and ROUT2 is used in the annunciation circuit. The watchdog signal is a closed circuit from one controller through the contacts of the second controller s ROUT1 relay. Each controller holds ROUT1 energized so the normally open contacts are closed. Should the primary controller s power supply or microprocessor fail, for example, the relay deenergizes and the watchdog circuit opens. The backup controller reads the open circuit, goes on-line, and activates an external alarm to notify operating personnel. The on-line status circuit includes digital output 1, DOUT1, and digital input 1, DIN1. It allows the transfer of control of the process from one controller to the other. DOUT1 is a switching gate that pulls DIN1- low to initiate switchover. As shown in Figure 3, watchdog logic includes a NOT block, NOT1, that enables the controller s OK status, ROUT1. The watchdog input, DIN2, monitors the other controller s OK status. If the status goes low, the external alarm, ROUT2, is annunciated and a message is flashed on the alphanumeric display, using the U1 input of the ODC block. The on-line control logic is key to the dedicated backup control strategy. Once a primary or backup controller failure is detected, the functioning controller will maintain control of the process. This permits the replacement of a failed controller without shutting down the process. A controller will go on-line when one of the following occurs: the watchdog signal goes low the other controller goes off line an operator pushes On-Line Toggle pushbutton PB1 A controller will go off-line when one of the following occurs: the other controller goes on-line an operator pushes the On-Line Toggle pushbuttom PB1, and the other controller s OK status is high The On-Line Control logic consists of a Set-Reset Flip- Flop block, SRF1, two AND blocks and a NOT block. The AND blocks filter input signals to either the S or R input depending on the state of the SRF block. This is the basis of the toggle configuration. The NOT3 block is used to enable the AND1 gate. Note that the ESN 2 number of NOT3 is less than that of SRF1. This forces a one scan cycle break in the logic and prevents the SRF block from resetting itself. When using an SRF block, logic needs to be initiated from a change of state event rather than the state of a logic condition. Rising Edge Trigger, RTG, and Falling Edge Trigger, FTG, blocks provide the transitions. Controller Scan Time Consideration When the primary controller is taken off-line or experiences a power failure, the analog output signal to the controlled element is interrupted. It takes the backup controller at least two scan cycles to restore the control signal to the control element. Depending on the 2 Execution Sequence Number 4

response characteristic of the control element, it is important to consider the signal interruption that occurs during the control transfer. The control strategy for a single-variable control loop, as illustrated in figure 3, has a scan cycle time of 40 milliseconds. The loss of the watchdog or on-line status signal of the primary controller is the event that triggers the transfer of control. This event can occur anytime during a scan cycle of the backup controller. After the first complete scan cycle, the backup controller s on-line state block, SRF1, goes high. After completion of the second scan cycle, the controller is in automatic mode and the controlled variable output block has been enabled. Note that the ESN of the not on-line state block, NOT3, is lower than that of the SETPT, PID and A/M blocks. There are a few instances where both controller outputs are enabled causing a momentary current summing spike. The duration of the spike will depend on the difference in scan cycle times between the primary and backup controllers. If the backup controller is brought on-line by pressing the PB1 pushbutton, it may be in control before the primary controller can disconnect its analog output block. Start-Up Considerations Several process start-up scenarios can be developed through configuration alternatives and setting of the controller s Real Time Clock jumper for a warm or a cold start. When primary and backup controllers are configured for a cold start and have had input power removed, both controllers will power up in the off-line state, because that is the power up state of the SRF block. They will both track a value of zero for the setpoint and output variable. Put the primary controller on-line by pressing On-Line Toggle pushbutton PB1 and adjusting the setpoint to the desired value. Application Support User manuals for controllers and transmitters, addresses of Siemens sales representatives, and more application data sheets can be found at www.usa.siemens.com/ia. To reach the process controller page, click Process Instrumentation and then Process Controllers and Recorders. To select the type of assistance desired, click Support (in the right-hand column). See AD353-138 for a list of Application Data sheets. The configurations shown in this publication were created in Siemens i config Graphical Configuration Utility. Those with CF353 in parenthesis in the figure title are available using the above navigation, then click Software Downloads > 353 Ratio Control (Reference AD353-109). Configurations can be created and run in a: Model 353 Process Automation Controller Model 353R Rack Mount Process Automation Controller* i pac Internet Control System* Model 352Plus Single-Loop Digital Controller* * Discontinued model Procidia, i pac, i ware, i config, and 352Plus are trademarks of Siemens Industry, Inc. Other trademarks are the property of their respective owners. All product designations may be trademarks or product names of Siemens Industry, Inc. or other supplier companies whose use by third parties for their own purposes could violate the rights of the owners. Siemens Industry, Inc. assumes no liability for errors or omissions in this document or for the application and use of information in this document. The information herein is subject to change without notice. Siemens Industry, Inc. is not responsible for changes to product functionality after the publication of this document. Customers are urged to consult with a Siemens Industry, Inc. sales representative to confirm the applicability of the information in this document to the product they purchased. Control circuits are provided only to assist customers in developing individual applications. Before implementing any control circuit, it should be thoroughly tested under all process conditions. Copyright 2012, Siemens Industry, Inc. 5

ESN = 20 ESN = 25 AD353-109 ESN = 15 6 SIEMENS Figure 3 Controller Configuration (CF353-109)