Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application



Similar documents
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Power Monitoring for Modern Data Centers

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Extend the Life of Existing Switchgear

Switchgear Application Issues for Mission Critical Power Systems, Part One

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

Bypass transfer switch mechanisms

What s up with Arc Flash?

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

Primary and Secondary Electrical Distribution Systems

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Enhancing Personnel Safety with Arc Resistant Equipment

Power-Zone 4 Arc Resistant Low Voltage Switchgear

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Alternate Methods to Short Circuit Breaker Coordination

Engineering Series Ratings: Is It Practical?

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

The Intelligent AX1 Switchgear for Medium Voltage

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions

Secondary Unit Substations

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

The Application of Circuit Breakers to Reduce Downtime in Datacentres

ELECTRICAL SAFETY RISK ASSESSMENT

The following components are common to most cubicles; this example is an ABB HK cubicle.

Electrical Distribution Services for Mining and Metals Industries

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

How To Choose A Transformer

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Contents. Description. Product Selection Guide

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

Choosing the Best Solution for Reducing Arc Energy

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

understanding medium frequency induction melting furnace and its components

A Deeper Look into Switchgear and Switchboards

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Paralleling Switchgear

Engineers Edge, LLC PDH & Professional Training

Fundamentals of Power

Increasing safety, reliability and efficiency for today s data centers

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

Electrical Grounding. Appendix C

Analyzing Electrical Hazards in the Workplace

Houston Service Center Medium Voltage Service and Aftermarket Solutions

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

SWITCHGEAR. EGP Switchgear

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Charging what can be more simple? SAE J1772

Arc Flash Safety in 400V Data Centers

PowlVac Vacuum Integrity Tester

Sample - No Commercial Use

Applications for Infrared Thermography at Computer Centers

Switchgear and Metal-Enclosed Bus

UFES Active protection for switchgear

Fusible Disconnect Switch

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac

Low Voltage Switchboards The Best Technical Solution for Your Ship

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

Short Circuit Current Calculations

Which switchboards equip your building facilities for the future?

PX100 MBP with Configurable Distribution

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

WHAT IS INFRARED (IR) THERMOGRAPHY

Medium voltage indoor circuit breakers ANSI/IEC solutions

Engineering innovation

The complete range of consumer switchboards and switchgear

HIGH VOLTAGE SHORE CONNECTION

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

2008 Eaton Corporation. All rights reserved.

Safe and secure distribution of medium voltage with AX1

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Ralf Christian, CEO Low and Medium Voltage. Making Things Right with Totally Integrated Power (TIP)

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

The Tesla Roadster battery pack is comprised of about 6800 of these cells, and the entire pack has a mass of about 450kg.

Low Voltage Switchgear

Offshore oil platform power and control system

SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Understanding Arc Flash

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

Atlanta Chapter IEEE Industry Applications Society

Understanding Emergency Power Off (EPO)

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

ICM Project Station Infrastructure and Equipment

Transcription:

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS) provide the critical power for computer equipment. The UPS equipment is supplied from commercial power or local generator power. Multiple sources are switched in various arrangements to provide continuous power to the UPS equipment. This requires frequent circuit breaker operation. Therefore, circuit breaker reliability is the key to data center reliability. And it is of utmost importance to perform a detailed evaluation of the circuit breaker design and functionality at the design stage of the data center. This paper serves to provide basic circuit breaker application guidelines for consulting engineers and the end users of data center power systems. I- INTRODUCTION Low voltage power circuit breakers are used in modern data centers for the main switching and power transfer operations (Figure 1). Power circuit breakers differ from molded case circuit breakers in that they must comply with rigorous testing criteria established by the American National Standards Institute (ANSI) standard C37. In comparison, molded case circuit breakers are constructed and tested to UL standard 489. Circuit breakers impact the reliability of data centers in three distinct ways: 1. Design of the circuit breaker must provide reliable continuous operation. Yet, the circuit breaker must act to interrupt the circuit with great speed and efficiency under abnormal conditions. 2. Circuit breakers must be applied in such a way that minimizes human operation errors. 3. The design and application of circuit breakers must optimize the maintenance process. The ideal circuit breaker will measure and communicate its own maintenance needs. This paper serves to illustrate the basic principles and provides a guideline for the end users and consulting engineers who specify these systems.

Utility Source GEN UPS ENERGY STORAGE BY- PASS TO PDU Figure 1: Simple Data Center Power. Circuit Breakers are used Extensively II- CIRCUIT BREAKER DESIGN Circuit breakers are the most complex of power distribution equipment because they must be optimized for two contradictory functions. Much the same as all other power distribution equipment (transformers, lines, etc) circuit breakers are optimized to carry their normal current continuously. But circuit breakers must also be able to interrupt currents efficiently an action that is contradictory to carrying continuous current. Current interruption is a dynamic action where the circuit breaker and the power system work against each other. When the circuit breaker contacts part, an electric arc is formed. Power system inductance forces the current to flow continuously through the gap created by the open contacts. The circuit breaker must oppose this force in order to interrupt the current. The result is an enormous energy exchange, which brings about heat and air ionization inside the circuit breaker s interruption chamber. Insulated Case Versus Iron Frame Construction Power apparatus are made of three main components. The design of each component has traditionally demanded a different set of requirements: 2

1. The current path usually copper - must provide excellent conductivity. 2. An insulating material is provided, which separates the current path from the supporting structure. This insulation - usually polymeric material - must provide excellent dielectric and thermal characteristics. 3. The supporting structure was originally made from steel. Steel provided the rigidity to withstand normal operation and short circuit forces. There has been a consistent shift towards combining components 2 and 3 above (the insulating medium and the supporting structure) into one molded design. When circuit breakers were first introduced, polymeric material could not withstand the pressure created inside the interruption chamber by the interruption process. However, a combination of insulating material and rigid steel was found workable. In order to make polymeric material suitable for replacing steel, the strength of advanced polymers has been greatly improved. The polymer used to construct modern power circuit breakers is an engineered thermoset composite resin. The electrical power industry has over 30 years of experience in advancing and refining thermoset materials for use in circuit breakers. Further, using a single molding reduces the number of parts, which helps improve the overall product quality. The thermoset resin is strong and lightweight, provides better insulation and isolation, and is molded to support and hold the internal parts with no need for adjustment. Figure 2: Molded Thermoset Polymer Used as Circuit Breaker Enclosure as well as the Insulating Medium. UL 489 Versus ANSI C37 Fundamental differences in the design and test philosophies of UL 489 and ANSI C37 bring about construction differences between circuit breakers. UL 489 circuit breakers are not intended to be opened for maintenance. These circuit breakers are designed with no user replaceable parts. But ANSI C37 circuit breakers are designed for access to the contacts and arc chutes so field maintenance can be performed. Another key characteristic of the ANSI C37 rated circuit breakers has been the short time (30 cycle) rating. The circuit breaker is designed to stay latched in the closed position during a short time event while downstream circuit breakers clear the fault. Passing the short time test requires a more robust circuit breaker both thermally and mechanically. But many manufacturers of molded case circuit breakers have also been designing and testing their UL 489 rated circuit breaker for short time withstand. Therefore, in today s market, the main difference between the UL and ANSI rated circuit breakers continues to be maintainability. 3

Traditionally for applications where frequent switching is required, such as power generating stations, ANSI C37 circuit breakers have been used. Those in charge of operating these systems would like to open the circuit breaker and inspect the contacts for wear and functionality. Much the same as generating stations, data center application subjects the circuit breakers to frequent operation. Therefore, ANSI C37 circuit breakers are the circuit breaker of choice. III- CIRCUIT BREAKER APPLICATION Drawout circuit breakers are universally used on critical power switching circuits. The drawout feature significantly reduces the downtime in case a circuit breaker must be removed from service, either for maintenance or because of a malfunction. But the drawout feature can also be the cause of a lot of confusion where communicating trip units are used. Communicating trip units are a common feature of modern circuit breakers. These trip units communicate significant information about the circuit breaker and about the electrical circuit. In order to network circuit breakers together, each circuit breaker must be provided with a unique identity or address. Figure 3 depicts the communication network. Modern circuit breakers communicate the circuit s current and a number of other metering parameters. As the circuit identity (address) is embedded in the circuit breaker trip unit, we encounter a problem with drawout construction. Figure 4 presents the idea of removing the circuit breaker in cell 1A and placing it in cell 1D. Let us assume that cell 1A feeds a chiller and cell 1D feeds an UPS. When we move the circuit breaker in cell 1A to cell 1D, the circuit breaker is now placed on the UPS circuit. However, the address inside the trip unit still points to the chiller. We will have information pertaining to the UPS circuit being communicated as the chiller circuit. One major circuit breaker manufacturer has resolved this problem by developing a Cradle Communication Module. The address is assigned to the switchgear cell. Each time a circuit breaker is installed in the cell, it learns its new address (or identity) from the cell. This innovation has generated a family of smart switchgear. Local Client Web Server Ethernet Figure 3: Circuit Breaker Communication Network 4

Figure 4: Trip Unit Communications and Drawout Circuit Breakers IV-CIRCUIT BREAKER MAINTENANCE Dependability can be engineered and built into equipment, but effective maintenance is required to keep it dependable. Experience shows that equipment lasts longer and performs better when covered by an electrical preventive maintenance program. In the case of modern data centers, the investment in maintenance is small compared to the cost of production losses associated with an unexpected equipment shutdown. Manufacturers service manuals typically have a recommended frequency of inspection. The frequency given is based on standard or usual operating conditions and environments. It is impossible for the manufacturer to list all combinations of environmental and operating conditions. 5

Typically, inside of a power circuit breaker, the main contacts are the components needing inspection and repair. Each time an interruption takes place, a small amount of the surface material of electrical contacts are ionized. Metallurgical science has made major advances in producing advanced metals for contact material. Yet contact wear continues to be a cause of concern for maintenance personnel. With the significant advancements we have made in using microprocessor technology, one may wonder if it is possible to manufacture a circuit breaker, which communicates its contact maintenance needs. Based on significant testing, a new algorithm computes a contact wear factor on the basis of the magnitude of the current being interrupted. The cumulative contact wear can be estimated on the basis of the number of current interruptions and the magnitude and duration of each interruption. One major circuit breaker manufacturer provides this algorithm with their communicating trip units. Therefore, maintenance personnel are provided with a real time tool to estimate the condition of the circuit breaker contacts. V- SPECIFICATIONS The following are recommended as minimum specifications for circuit breakers used in data center applications: 1. Circuit breaker cases shall be constructed of molded thermoset resin material for durability and ease of maintenance. 2. Circuit breakers shall be of drawout construction and designed to meet ANSI C37 standard requirements. 3. Circuit breakers with communicating trip units shall obtain their network address from the drawout cell. When a circuit breaker is moved from one cell to another, the circuit breaker must recognize and assume the identity of the new circuit. 4. Circuit breaker trip units shall provide an estimate of contact wear based on the number and severity of current interruptions. Contact wear information shall be available through communications for remote indication. 6