CMS/Accreditation Surveys The Physical Environment



Similar documents
Environment of Care Fire Safety Management Plan 2014

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

Duke University Hospital Fire/Life Safety Management Plan 2007

Program No Section Heading

How To Understand The Safety Management Program

EXHIBIT A SCOPE OF WORK

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Winnipeg Fire Department Fire Prevention Branch

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

City of Columbus Department of Building and Zoning Services

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

Maintaining Fire Protection Systems

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Michael Catalano 24 Nassau Avenue, Islip NY Phone (631) Chief Fire Marshal Fax (631)

Sprinkler and Fire Alarm Systems for the Building Official

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

FIRE-FIGHTING DESIGN BRIEF REPORT

Environment of Care Utility Systems Management Plan 2014 Updated

HERNANDO COUNTY FIRE ALARM GUIDELINES

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Module 4, Lesson 12 Fire Alarm Systems

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

Inspection and Testing Program Fire Protection Equipment

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

Prime Power Services, Inc. Georgia, Carolinas NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

2014 Limited Plan Submittal Checklist

HFAP Accreditation And the Physical Environment

The New Life Safety Chapter What It Applies to and How Organizations Can Comply with It

CBD-233. Fire Alarm and Detection Systems

Bold items are particular to the City of Euless

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

NFPA Edition Fire dampers shall be permitted to be installed in exhaust systems in the following situations:

UNIVERSITY OF TOLEDO

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

Overview of Hotel Fire Safety Requirements

Automatic fire-extinguishing systems for commercial cooking

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE

Fire Alarm System Monitoring - CAN/ULC-S561-03

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

Fire Alarm System Plans Review Checklist Property location Date of Review

Commercial Fire Inspections

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

Inspection, Testing and Preventive Maintenance

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Storage of freestanding medical gas cylinders: compliance and safety tips Storing cylinders in the means of egress: Storing cylinders: Bulk storage:

Module 5. Fire and Emergency Alarm System Part I- Basics

City of Bettendorf Fire Alarm System Requirements

The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Facilities Maintenance Standards rev

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY

Name Of Occupancy Date. Yes No Describe

Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Columbia University Medical Center. Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado

COMMISSIONING OF FIRE ALARM SYSTEMS

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

SECTION FIRE ALARM AND DETECTION SYSTEMS

FIRE DETECTION AND ALARM

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

INSPECTION AND TESTING OF EMERGENCY GENERATORS

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM

2015 Annual Fire Safety Report

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

Fire Safety PROCEDURES January 2011

NYC Department of Education Building Condition Assessment Survey BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004

FIRE INSPECTION CHECKLIST

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

Building Permit Application

FIVE YEAR CERTIFICATION REPORT

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY

SECTION MECHANICAL: ELECTRICAL: PLUMBING

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL Phone: (708) Fax: (708)

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE

Transcription:

CMS/Accreditation Surveys The Physical Environment Critical Aspects for 2013 Presenter Robert H. Bartels, CHFM CHSP CHEP SASHE President Safety Management Services, Inc. A program presented by: SAFETY MANAGEMENT SERVICES, INC. Arlington Heights, IL (877) 577-6550 ** info@safemgt.com SMS, Inc., 2013 1

Managing Accreditation in The Physical Environment Accreditation Options What is CMS? - Centers For Medicare/Medicaid Services http://www.cms.hhs.gov/ SMS, Inc., 2013 2

Managing Accreditation in The Physical Environment Deemed Status What is Deemed Status? How does one receive deemed status? - Meet CMS Conditions of Participation (COP) - Be Surveyed & Approved by an Authorized Accrediting Body SMS, Inc., 2013 3

Managing Accreditation in The Physical Environment Accreditation Options Why Seek Accreditation? - To Obtain Deemed Status - Residency Program Requirements - Recruitment - Public Image SMS, Inc., 2013 4

Managing Accreditation in The Physical Environment Accreditation Options What Is the Benefit of Accreditation? - Leads to Deemed Status - Allows Collection of Medicare / Medicaid Funds SMS, Inc., 2013 5

Managing Accreditation in The Physical Environment Accreditation Options Who Can Grant Deemed Status? - Centers For Medicare/Medicaid (CMS) - The Joint Commission (TJC) - American Osteopathic Association (AOA) - Det Norske Veritas (DNV) SMS, Inc., 2013 6

Managing Accreditation in The Physical Environment Accreditation Options What is TJC? - The Joint Commission http://www.jointcommission.org/ SMS, Inc., 2013 7

Managing Accreditation in The Physical Environment Accreditation Options What Is AOA? - American Osteopathic Association Healthcare Facilities Accreditation Program (HFAP) http://www.osteopathic.org/ SMS, Inc., 2013 8

Managing Accreditation in The Physical Environment Accreditation Options What is DNV? - Det Norske Veritas National Integrated Accreditation for HealthcareOrganizations (NIAHO) http://www.dnv.com/ SMS, Inc., 2013 9

Managing Accreditation in The Physical Environment Accreditation Options What are the Differences? Owner/Board Requirements Inspection Cost Survey Type CMS Federal Government COP Triennial Free Unannounced TJC AHA/AMA/ACS AMH Triennial $$ Unannounced AOA AOA Board HFAP Triennial $$ Unannounced DNV Det Norske Veritas NIAHO ISO 9001 Bi-Annual $$ Unannounced SMS, Inc., 2013 10

Managing Accreditation in The Physical Environment Accreditation Options What about DNV & ISO 9001? http://www.iso.org/ SMS, Inc., 2013 11

Managing Accreditation in The Physical Environment ISO Key Elements Quality Management System Documentation Records Internal Auditing Monitoring & Measurement SMS, Inc., 2013 12

Survey Preparation Opening Day Documents Management Plans Annual Evaluations SOC/PFI esoc/epfi Safety/Security Job Descriptions SMS, Inc., 2013 13

Survey Preparation Environment of Care Session Documents to be Available Policies & Procedures Sample Documentation Aggregated Documentation Matrices, Charts & Graphs SMS, Inc., 2013 14

Survey Preparation Tab Set Photo SMS, Inc., 2013 15

Life Safety Code Documentation Checklist Standard Requirement Frequency Checked Fire Safety Equipment EC.02.03.05 EP1 Supervisory Signaling Devices Quarterly EC.02.03.05 EP2 Tamper Switches & Water Flow Devices Quarterly EC.02.03.05 EP3 Duct Detectors Every 12 months EC.02.03.05 EP3 Smoke Detectors Every 12 months EC.02.03.05 EP3 Heat Detectors Every 12 months EC.02.03.05 EP3 Manual Fire Alarm Boxes Every 12 months EC.02.03.05 EP3 Electromechanical Release Devices Every 12 months EC.02.03.05 EP4 Audible Devices-Bells, Chimes, Speakers Every 12 months EC.02.03.05 EP4 Visual Devices; Strobes Every 12 months EC.02.03.05 EP5 Off-site Fire Responders Verification Every quarter EC.02.03.05 EP6 Fire Pump Churn Test Every week EC.02.03.05 EP7 Water Tank Level Alarms Every 6 months EC.02.03.05 EP8 Water Tank Freeze-Up Alarms Every month during cold weather EC.02.03.05 EP9 Main Drain Test Every 12 months EC.02.03.05 EP10 Fire Department Connections EC.02.03.05 EP11 Fire Pump Flow Test EC.02.03.05 EP12 Water-Flow Test Standpipe EC.02.03.05 EP13 Automatic Fire Extinguishing Systems Inspected - Kitchen (no disch req) EC.02.03.05 EP14 Other Gaseous Extinguishing Systems - Inspected (no disch req) EC.02.03.05 EP15 Fire Extinguishers - Inspection EC.02.03.05 EP16 Fire Extinguishers - Maintenance EC.02.03.05 EP17 Hose Test - Hydrostatic 5 years after install, every 3 years after that EC.02.03.05 EP18 Dampers-New Installation EC.02.03.05 EP18 Dampers- Operational Test EC.02.03.05 EP19 Fan Shut Down devices - Operational Test EC.02.03.05 EP20 Rolling Dire Doors and Shutters - Operational test Emergency Power Systems Every quarter Every 12 months Every 5 years Every 6 months Every 12 months Monthly Every 12 months 5 yrs. / 3 yrs. 1 year after installation Every 6 years Every 12 months Every 12 months EC.02.05.07 EP1 Battery-powered lights required for egress for 30 seconds 30 day intervals EC.02.05.07 EP2 Battery-powered lights required for egress for 1 1/2 hours or replacement and random test of 10% of batteries for 1 1/2 hours Every 12 months EC.02.05.07 EP3 Stored Emergency Power Supply (SEPSS) - 5 minutes Every quarter EC.02.05.07 EP3 SEPSS - full load for 60% of its class or rating for recharge Annually EC.02.05.07 EP4 Generator tested - intervals not < 20 or > 40 days apart for 30 continuous minutes with dynamic load at least 30% nameplate rating or 12 times a year manufacturers recommended prime movers' exhaust gas temperature EC.02.05.07 EP5 If above not met, supplemental loads of 25% nameplate for 30 min, followed by 50% nameplate rating for 30 min, followed by 75% Every 12 months nameplate rating for 60 min for a total of 2 continuous hours EC.02.05.07 EP6 ATS - All Transfer Switches tested not < 20 or > 40 days apart 12 times a year Generator tested for minimum of 4 hours - 30% nameplate rating or EC.02.05.07 EP7&8 manufacturers recommended prime movers' exhaust gas temperature EC.02.05.07 EP9 If required test fails, interim measures are made until repairs are done EC.02.05.07 EP10 Equipment if retested after repairs or corrections are finished Medical Gas and Vacuum Systems Every 36 months EC.02.05.09 EP1 Inspects, tests and maintains critical components of piped medical gas defined by hospital EC.02.05.09 EP2 EC.02.05.09 EP3 Maintains supply valves for purity, correct gas, proper pressure Main as supply zones and valves are accessible and clearly labeled Electronic Statement of Conditions LS.01.01.01 EP1 Assign individual to assess compliance with LSC,complete e-soc, manage defic N/A LS.01.01.01 EP2 Maintains a current e-soc quarterly? LS.01.01.01 EP3 When resolving deficiency through e-soc meets time frames identified in accepted PFI LS.01.01.01 EP4 Maintains documentation of any inspections and approvals made by state and local fire control agencies Interim Life Safety Measures (ILSM) Written ILSM policy including criteria for evaluating where and what LS.01.01.01 EP3 extent the hospital follows special measures LS.01.01.01 EP4-12Implements ILSMs as defined by the policy N/A N/A

Life Safety Code Documentation Checklist Standard Requirement Frequency Checked Fire Safety Equipment EC.02.03.05 EP1 Supervisory Signaling Devices Quarterly EC.02.03.05 EP2 Tamper Switches & Water Flow Devices Quarterly EC.02.03.05 EP3 Duct Detectors Every 12 months EC.02.03.05 EP3 Smoke Detectors Every 12 months EC.02.03.05 EP3 Heat Detectors Every 12 months EC.02.03.05 EP3 Manual Fire Alarm Boxes Every 12 months EC.02.03.05 EP3 Electromechanical Release Devices Every 12 months EC.02.03.05 EP4 Audible Devices-Bells, C himes, Speakers Every 12 months EC.02.03.05 EP4 Visual Devices; Strobes Every 12 months EC.02.03.05 EP5 Off-site Fire Responders Verification Every quarter EC.02.03.05 EP6 Fire Pump C hurn Test Every week EC.02.03.05 EP7 Water Tank Level Alarms Every 6 months EC.02.03.05 EP8 Water Tank Freeze-Up Alarms Every month during cold weather EC.02.03.05 EP9 Main Drain Test Every 12 months EC.02.03.05 EP10 Fire Department C onnections Every quarter EC.02.03.05 EP11 Fire Pump Flow Test Every 12 months EC.02.03.05 EP12 Water-Flow Test Standpipe Every 5 years EC.02.03.05 EP13 Automatic Fire Extinguishing Systems Inspected - Kitchen (no disch req) Every 6 months EC.02.03.05 EP14 Other Gaseous Extinguishing Systems - Inspected (no disch req) Every 12 months EC.02.03.05 EP15 Fire Extinguishers - Inspection Monthly EC.02.03.05 EP16 Fire Extinguishers - Maintenance Every 12 months EC.02.03.05 EP17 Hose Test - Hydrostatic 5 years after install, every 3 years after that 5 yrs. / 3 yrs. 1 year after EC.02.03.05 EP18 Dampers-New Installation installation EC.02.03.05 EP18 Dampers- Operational Test Every 6 years EC.02.03.05 EP19 Fan Shut Down devices - Operational Test Every 12 months EC.02.03.05 EP20 Rolling Dire Doors and Shutters - Operational test Every 12 months 17

Life Safety Code Documentation Checklist Standard Requirement Frequency Checked Emergency Power Systems EC.02.05.07 EP1 Battery-powered lights required for egress for 30 seconds 30 day intervals EC.02.05.07 EP2 Battery-powered lights required for egress for 1 1/2 hours or replacement and random test of 10% of batteries for 1 1/2 hours Every 12 months EC.02.05.07 EP3 Stored Emergency Power Supply (SEPSS) - 5 minutes Every quarter EC.02.05.07 EP3 SEPSS - full load for 60% of its class or rating for recharge Annually EC.02.05.07 EP4 Generator tested - intervals not < 20 or > 40 days apart for 30 continuous minutes with dynamic load at least 30% nameplate rating or 12 times a year manufacturers recommended prime movers' exhaust gas temperature EC.02.05.07 EP5 If above not met, supplemental loads of 25% nameplate for 30 min, followed by 50% nameplate rating for 30 min, followed by 75% Every 12 months nameplate rating for 60 min for a total of 2 continuous hours EC.02.05.07 EP6 ATS - All Transfer Switches tested not < 20 or > 40 days apart 12 times a year Generator tested for minimum of 4 hours - 30% nameplate rating or EC.02.05.07 EP7&8 manufacturers recommended prime movers' exhaust gas temperature EC.02.05.07 EP9 If required test fails, interim measures are made until repairs are done EC.02.05.07 EP10 Equipment if retested after repairs or corrections are finished Every 36 months SMS, Inc., 2013 18

Life Safety Code Documentation Checklist Standard Requirement Frequency Checked Medical Gas and Vacuum Systems EC.02.05.09 EP1 Inspects, tests and maintains critical components of piped medical gas defined by hospital EC.02.05.09 EP2 EC.02.05.09 EP3 LS.01.01.01 EP1 Maintains supply valves for purity, correct gas, proper pressure Main as supply zones and valves are accessible and clearly labeled Electronic Statement of Conditions Assign individual to assess compliance with LSC,complete e-soc, manage defic LS.01.01.01 EP2 Maintains a current e-soc quarterly? LS.01.01.01 EP3 LS.01.01.01 EP4 When resolving deficiency through e-soc meets time frames identified in accepted PFI Maintains documentation of any inspections and approvals made by state and local fire control agencies Interim Life Safety Measures (ILSM) Written ILSM policy including criteria for evaluating where and what LS.01.01.01 EP3 extent the hospital follows special measures LS.01.01.01 EP4-12Implements ILSMs as defined by the policy N/A N/A N/A SMS, Inc., 2013 19

Survey Preparation Life Safety Document Review-1 Surveyor will ask you to provide: 6 stepladder Strong/bright flashlight Keys to open all doors Tape Measure Any special tools needed to open access panels, air handler doors, inspections doors, etc. SMS, Inc., 2013 20

Survey Preparation Life Safety Document Review-2 After the building tour, have documents gathered together in order to expedite the review. These documents should be collected in a separate room from the general meeting room designated for The Joint Commission survey team. Please have individuals available to answer any questions that might arise pertaining to these documents. SMS, Inc., 2013 21

Survey Preparation Life Safety Document Review-3 The original SOC from the last survey, with the list of PFI items that were approved during the last TJC survey The current SOC and the current list of PFI items Drawings of the hospital showing all of the rated walls, smoke compartments, suites-of-rooms & occupancy separations (carry them with you during the building tour) SMS, Inc., 2013 22

Survey Preparation Life Safety Document Review-4 Any equivalencies or Fire Safety Evaluation System (FSES) pre-approved by Accrediting Body Building Maintenance Program documentation (if used) Fire Alarm Test Reports, including: Supervisory Signals Tamper Switches & Water Flow devices Duct, heat, smoke detectors; pull stations, releasing devices, interface devices Emergency services notification transmission equipment Smoke Detection Shut-down devices for HVAC SMS, Inc., 2013 23

Survey Preparation Life Safety Document Review-5 Fire Pump Test Reports (Weekly & Annual) Fire Protection Systems Test & Inspection records, including: Main Drain tests Fire Department Connections Kitchen fire suppression systems CO2 and/or Clean Agent suppression systems Portable Fire Extinguishers Standpipe Occupant Use Fire Hoses Water Storage Tank high & low level alarms (if used) Water Storage Tank low water temp alarms (if used) SMS, Inc., 2013 24

Survey Preparation Life Safety Document Review-6 Interim Life Safety Measures (ILSM) Policy & Implementation documents Fire & Smoke Damper Testing (4-year test) Horizontal & Vertical sliding/rolling doors SMS, Inc., 2013 25

Survey Preparation Life Safety Document Review-7 Emergency Power System, including: Generator Testing Automatic Transfer Switch (ATS) testing Battery Powered Lights Stored Emergency Power Supply Systems (SEPSS) Medical Gases & Vacuum Systems, including: Maintenance Program & testing documentation Documentation for testing of cross-contamination during installation Purity & Pressure documentation SMS, Inc., 2013 26

Managing Accreditation in The Physical Environment Questions? SMS, Inc., 2013 27

Contact Information Safety Management Services, Inc 1502 North Arlington Heights Road Arlington Heights, IL 60004 (847) 577-6550 info@safemgt.com www.safemgt.com SMS, Inc., 2013 28