Mitigating data center harmonics

Similar documents
Data Center Trend: Distributed Power in the White Space

Distributed versus centralized power backup strategies

Harmonics in your electrical system

Alternative data center power

Is an energy-wasting data center draining your bottom line?

415V DISTRIBUTION FOR GREEN DATA CENTERS

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Common Power Problems & Power Protection Solutions

415V DISTRIBUTION FOR GREEN DATA CENTERS

Optimizing Power Distribution for High-Density Computing

Powering Converged Infrastructures

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

Evaluating the Opportunity for DC Power in the Data Center

Power Management for Server Virtualization

Considering the effects of UPS operation with leading power factor loads

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

The Different Types of UPS Systems

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Engineering innovation

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Increased power protection with parallel UPS configurations

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Survey of Harmonics Measurements in Electrical Distribution Systems

Product Data Bulletin

Specifying a Variable Frequency Drive s

Impact of Leading Power Factor on Data Center Generator Systems

The Different Types of UPS Systems

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

Data center power dynamics within the settings of regional power grid

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

Simplifying power management in virtualized data centers

Choosing Close-Coupled IT Cooling Solutions

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Electrical Systems. <Presenter>

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Introduction. Harmonics and IEEE 519 Page 1 of 19

Single Phase UPS Management, Maintenance, and Lifecycle

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

Galaxy VM. Three-phase power protection. schneider-electric.com

Low Voltage Products

Energy Cost Reduction through Load Balancing & Load Shedding

Maximizing UPS Availability

MGE Galaxy /200/250/300/400/500 kva Power efficiency for business continuity

FACTS. Solutions to optimise network performance GRID

Fundamentals of Power

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

SG Series UPS kva three phase 400 Vac

Eaton 93PM UPS Where aesthetics meet intelligence.

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

Technical Comparison of On-line vs. Line-interactive UPS designs

Which UPS is right for the job?

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Energy Savings in the Data Center Starts with Power Monitoring

UPS For Efficient Data Data Centers Centers

IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS

Power System Harmonics

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions

Right-Sizing Your Power Infrastructure

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

Data center solutions Medium & large enterprise, multi-tenant and hyperscale. Energize your data center, maximize the value of your investment

UPS Basics. Everything you ever wanted to know about uninterruptible power systems but were afraid to ask.

Power protection for data centers

Electricity Meter in the age of Photovoltaic

The necessary convergence of IT and Facilities

Tough Decision: On-Line or Line-Interactive UPS?

Power to the adaptable data center

The Different Types of UPS Systems

Digital Signal Controller Based Automatic Transfer Switch

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Power backup in data centers. Something going on. 24 I MTU Report 03/10

Parallel UPS configurations Connecting multiple UPS modules for added capacity or redundancy

Analysis of AC-DC Converter Based on Power Factor and THD

Power Quality Standards for Electric Service

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

APPLICATION OF IEEE STD HARMONIC LIMITS

Reducing Data Center Energy Consumption

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

TLE Series UPS kva/kw three phase 400 Vac with best-in-class efficiency

ECONOMIC AND ELECTRICAL BENEFITS OF HARMONIC REDUCTION METHODS IN COMMERCIAL FACILITIES

Seize the benefits of green energy and the smart grid

Intelligent Power Distribution in the Data Center

Degree programme in Automation Engineering

Data center energy efficiency and power quality: an alternative approach with solid state transformer

Standardization and modularity as the foundation of data center UPS infrastructure

PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS

Increasing safety, reliability and efficiency for today s data centers

Transcription:

Mitigating data center harmonics Patricia Matwijec Product Manager Eaton Ed Spears Product Marketing Manager Eaton Executive summary Line harmonics can have costly and disruptive effects on electrical distribution systems. However, thanks to innovations like faster switching devices, power factor-corrected power supplies and harmonic-mitigating transformers (HMT), many data center operators no longer consider harmonics a serious issue. In actuality, fluctuating loads, equipment, and operating conditions can still produce harmonics, power factor problems, and load balancing issues even at facilities that use newer technologies. This white paper discusses the ways harmonics can impact data centers and examines strategies for addressing harmonic problems, with a particular focus on the benefits for some facilities of deploying the latest harmonic-mitigating energy-saver uninterruptible power systems (UPSs). Table of contents Understanding harmonics... 2 Why harmonics matter... 2 Options for mitigating harmonics... 3 Harmonic mitigation in UPSs... 3 Harmonic mitigation in energy saver UPSs... 4 Sample applications for harmonic mitigating energy saver UPSs... 5 Selecting a harmonic mitigation strategy... 5 Conclusion... 6 About Eaton... 6 About the author... 6 WP156001EN www. powerquality.eaton.com January 2014

Page 2 of 7 Understanding harmonics Most utilities provide power with a reasonably smooth waveform. However, non-linear loads such as servers, variable frequency drives (VFDs), florescent lighting, and other electronic devices can distort current and voltage waveforms. Known as harmonics, those distortions appear as supplemental frequencies higher than the fundamental frequency, which is 60 Hz in the U.S. and 50 Hz in most other countries. Figure 1. Harmonics are distorted waveforms caused by supplemental frequencies higher than the fundamental frequency. Harmonics come in two basic varieties, current distortion and voltage distortion. Non-linear loads are the most common source of current distortion, while voltage distortion is most commonly produced when an electrical device pulls current distortion through an impedance. Additionally, poor harmonics at facilities that share a point of common utility coupling can impact neighboring structures as well, so harmonic pollution from nearby buildings can cause current distortion, voltage distortion or both. Why harmonics matter Minimizing energy costs and maximizing reliability are top priorities for most data center operators today. Harmonics makes both goals harder to achieve by causing these problems: Reduced energy-efficiency: Harmonic currents increase losses on the power system conductors and transformers, adding heat to the power chain that drives up power and cooling costs. Decreased reliability: The heat created by harmonics can increase downtime by causing premature equipment failure or malfunctions, overheated wiring, and other hardware issues, including generator transfer switch and control malfunctions. Higher capital expenses: Harmonics can reduce the lifespan of electrical equipment, forcing companies to purchase replacement devices sooner than would otherwise be necessary. They can also compel data center managers to compensate for increased heating and distortion by investing in oversized generators, neutral conductors, and transformers. Costly utility penalties: Electrical utilities must compensate for harmonic-related waste by deploying additional generating capacity. For that reason, and to discourage harmonic pollution, many utilities penalize customers that exceed distortion limits defined by the IEEE-519 standard. In addition, many utilities penalize customers with a power factor below 0.9. Inconsistent meter readings: Phase imbalances and high harmonic voltages and currents can cause electrical meters to report figures that are inaccurate by as much as 20 percent.

Page 3 of 7 Options for mitigating harmonics Data center operators have a range of options of varying complexity and cost for mitigating harmonics. Companies can employ these singly or in combination, and the ones that make the most sense for a given facility will vary based on the loads it supports, its budget, and the site s specific harmonic-related problems. Some of the most common options are: Oversized generators: Generators have two to three times the impedance of a typical transformer, so pulling distorted current through a generator distorts the voltage as much as 2 to 3 times more than the same load on the utility service transformer. Using larger generators than electrical loads would otherwise require stabilizes their output and helps compensate for the increased heating distortion can cause, improving data center reliability and lengthening the generator s lifespan. Oversized generators also cost more, however, and therefore drive up capital expenses. Low distortion electronic ballasts: Like harmonic mitigating transformers (HMTs), low distortion electronic ballasts use passive filtering technology to ease line harmonics. However, they re usually more expensive than the standard magnetic ballasts they typically replace. Active filters: These provide the most comprehensive cancellation of harmonic distortion available. Active filters inject an additional current into the line that s identical to but 180 degrees opposite of the harmonic current coming from the load. Much as noise-canceling headphones cancel out sonic disturbances, active filters cancel the entire spectrum of harmonics, usually up to the 50th order. Lowering the current distortion served by the utility source or generator consequently reduces voltage distortion and can also correct the power factor of the load by modifying the fundamental current displacement. Although they are generally considered the most effective harmonic solution, active filters are unfortunately also the most expensive. Figure 2. Data center operators have access to variety of technologies for mitigating harmonics. Harmonic mitigation in UPSs Since UPSs and the loads they serve have historically been considered some of the most significant harmonic loads on a power system, companies can also use harmonic-mitigating UPSs to reduce line harmonics. Much like active filters, harmonic-mitigating UPSs eliminate harmonic distortion by inserting

Page 4 of 7 equal and opposite current into the line. They also compensate for reactive power from low power factor loads and balance loads across three phases to avoid stranded capacity, while providing clean and continuous power during utility outages or in response to electrical disturbances. ithd is 28% ithd is 4.1% vthd is 4.3% vthd is 1.3% UPS injects identical harmonic current inverted 180 degrees The principal objective of IEEE- 519 is to reduce the voltage distortion caused by load current distortion to less than 5% Figure 3. Sample effects of a harmonic-mitigating UPS on a waveform with harmonic distortion. Note the distortion is corrected within one-fourth of a second. Harmonic mitigation in energy-saver UPSs In their quest to boost efficiency, data centers are increasingly deploying UPSs with energy-saver operating modes. Such products save money and enhance sustainability by reducing data center energy waste up to 10 percent under typical loading conditions. Energy saver UPS are particularly beneficial for loads less than 40%, the point at which traditional UPS efficiency levels sharply decline. Figure 4. Energy-saver UPSs deliver significant improvements in power efficiency.

Page 5 of 7 Those savings aren t automatic, however, since most UPSs equipped for eco mode operation mitigate harmonics, perform power factor correction and balance loads only while in double-conversion mode. As a result, data center operators with harmonics problems who wish to use energy-saver UPSs have traditionally been forced to choose between installing additional mitigation technologies or exposing their facilities to the potentially expensive impact of harmonic distortion. More recently, harmonic-mitigating UPSs capable of keeping distortion within pre-determined and adjustable limits, correcting power factor, and balancing loads while in energy-saver mode have finally begun to reach the market. Moreover, these new systems typically remain within one percent of energysaver levels while performing these functions, providing a significant improvement over double-conversion efficiency levels. Furthermore, the harmonic mitigation technology in the latest energy-saver UPSs is a built-in feature that requires no additional footprint, so it doesn t consume valuable data center floor space or inflate installation and maintenance costs. If the source of harmonic current distortion is on the critical bus connected to the UPS, this mitigation technique is convenient and economical. Sample applications for harmonic-mitigating energy-saver UPSs Energy saver UPSs with integrated harmonic mitigation can help any organization improve energyefficiency without exposing electrical systems to the effects of harmonic distortion and low power factor. They can be especially beneficial, however, in these settings: Harmonic-rich environments: Manufacturing systems and medical imaging devices are large, nonlinear loads that often add harmonics to electrical distribution systems. As a result, data centers and server rooms located near factories, hospitals and clinics tend to experience high levels of harmonic distortion. Deploying harmonic-mitigating energy-saver UPSs in such facilities reduce harmonics while enabling industry-leading energy-efficiency. Containerized/modular data centers: Operators of containerized and modular data centers typically pursue every opportunity to increase operating efficiency, but they also utilize identical servers in large quantities, which can magnify the severity of harmonics issues. Harmonic-mitigating energy-saver UPSs allow containerized and modular data centers to overcome those problems while collecting the moneysaving rewards of energy saver UPS operation. Facilities that place non-linear loads on the UPS bus: At one time, most data centers only placed IT loads on the UPS critical bus. Today, however, many facilities put VFDs, computer room air conditioning units and other non-linear loads on the UPS bus as well, creating added potential for harmonic distortion. Harmonic-mitigating energy-saver UPSs enable such data centers to limit distortion, correct power factor and balance loads while also lowering power consumption. Selecting a harmonic-mitigation strategy As helpful as energy-saver UPSs with harmonic-mitigation technology can be, there s no single correct strategy for addressing harmonics. Both equipment manufacturers and the IEEE-519 standard define maximum harmonic limits; data centers with distortion below those thresholds may not require mitigation at all, and different combinations of harmonic-mitigating technologies may better serve other facilities. In the design phase, modeling programs can reveal potential harmonic problems, allowing for a comparison of techniques that meet the site requirements and budget. To determine the best harmonic-mitigation strategy for your data center when harmonic issues are suspected, follow these steps: 1. Look for symptoms of high harmonics These include: Generator synchronization failure or generator instability Local utility company fines for unacceptable distortion or poor power factor Overheated wiring or transformers in your building 2. Perform a facility assessment

Page 6 of 7 Collect precise measurements of the harmonics affecting your data center, and diagnose their origin. If you re experiencing voltage distortion, for example, the source could be current distortion in your load, a source impedance problem or harmonic pollution elsewhere on the grid. Trained and qualified engineers can assist you with this often-complex analysis. 3. Determine if you need harmonic mitigation Once hard numbers are available, compare your power system s harmonic distortion to the maximum levels specified by your equipment manufacturers and the IEEE-519 standard. Then, calculate your aggregate harmonic-related expenses, including the cost of replacing IT equipment prematurely, suffering added downtime and wasting electricity. Finally, consider the intangible value of being a good corporate citizen by operating your data center in an environmentally sustainable manner and not exposing nearby buildings to the impact of your facility s distortion. If the total value of deploying harmonic mitigating technologies outweighs what harmonics are currently costing you and the harmonics you re experiencing exceed the limits set by equipment manufacturers and the IEEE-519 standard, implementing harmonic-mitigation measures will probably prove cost-effective. If neither condition is met, you may not require harmonic-mitigation technologies. 4. Design and deploy a harmonic-mitigation strategy If you decide to take action regarding your data center s harmonics, an experienced electrical consultant can help you determine the right mix of mitigation solutions for your specific environment. 5. Analyze the results After your harmonic reduction solution is in place, repeat the facility assessment you executed in step 2 to see how effectively your mitigation solution has reduced distortion, and how much power and money you re saving as a result. Conclusion Line harmonics continue to be a costly issue for data centers, with implications for both reliability and efficiency. Fortunately, IT and facilities managers today have access to a wide array of harmonic-mitigation technologies. In particular, organizations eager to maximize both harmonic reduction and energy-efficiency should investigate the new energy-saver UPSs with built-in harmonic-mitigation capabilities that are now reaching the market. Though not all data centers require them, such systems enable companies to achieve the highest efficiency possible while actively correcting for harmonics as they occur. About Eaton Eaton s electrical business is a global leader with expertise in power distribution and circuit protection; backup power protection; control and automation; lighting and security; structural solutions and wiring devices; solutions for harsh and hazardous environments; and engineering services. Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges. Eaton is a power management company providing energy-efficient solutions that help our customers effectively manage electrical, hydraulic and mechanical power. A global technology leader, Eaton acquired Cooper Industries plc in November 2012. The 2012 revenue of the combined companies was $21.8 billion on a pro forma basis. Eaton has approximately 102,000 employees and sells products to customers in more than 175 countries. For more information, visit www.eaton.com. About the authors Patricia Matwijec is product manager for Three-Phase Large UPS Systems in Eaton s Critical Power Solutions Division in Raleigh, North Carolina. She has been in the electrical industry for over 20 years, with experience in power distribution, control, and power quality for data center, commercial, and industrial applications. Besides product management, Patty has held roles in operations and sales for Eaton. She can be reached at PatriciaEMatwijec@eaton.com.

Page 7 of 7 Ed Spears is a product marketing manager in Eaton s Critical Power Solutions Division in Raleigh, North Carolina. A 34-year veteran of the power systems industry, Ed has experience in UPS systems testing, sales, applications engineering and training as well as working in power quality engineering and marketing for telecommunications, data centers, cable television and broadband public networks. He may be reached at EdSpears@Eaton.com.