Cable Failure, Diagnostics and. Steven Boggs



Similar documents
Total System Reliability - Extending the Life of Electrical Cable Systems

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

A Power Cable Reliability Solution

How To Test For Safety On A Power Cable

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable

Medium Voltage Cable Defects Revealed by Off-Line Partial Discharge Testing at Power Frequency

WIRE AND CABLE ENGINEERING GUIDE

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

On-Line Partial Discharge Testing. Skip Hicks Director - New Business Development

Development of a 500-kV DC XLPE Cable System

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE

WIRE AND CABLE ENGINEERING GUIDE

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Fault location on power cables. Fault location on power cables

Section kv Power Cables

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT ON SOLID DIELECTRIC DC CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

A Practical Guide to Dielectric Testing

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Power-factor testing of rotating machinery is another valuable test

THE USE OF AFTER-INSTALLATION COMMISSIONING TESTS TO ASSURE MV POWER CABLE SYSTEMS MEET MANUFACTURERS STANDARDS

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

Electrical Predictive and Preventative Maintenance

Extending Power Cable Life an Additional 40 Years Richard K. Brinton & Glen J. Bertini Novinium, Inc.

AORC Technical meeting 2014

Notes from Underground

IN USE: CABLE AGING MANAGEMENT

Troubleshooting accelerometer installations

VALIDATING CABLE "DIAGNOSTIC TESTS"

THE OKONITE COMPANY. Ramsey, New Jersey Fax:

Sub sea Cable Technology

POWER AND VOLTAGE RATING

Charger Output AC Ripple Voltage and the affect on VRLA batteries

Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge

Why Buy HVI VLF Products?

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables

IEEE802.3poep Study Group Revision of isolation requirements in IEEE802.3 clause 33.

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

Oscar E. Morel UtilX Corporation

Avoiding AC Capacitor Failures in Large UPS Systems

Charged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

Nexus Technology Review -- Exhibit A

DIELECTRIC SPECTROSCOPY AS A DIAGNOSTIC TEST METHOD FOR THE DETERMINATION OF MECHANICAL DAMAGE IN MARBLE SAMPLES

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

White Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards.

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

Network Standard Advice No. 1420C 9/6/2011

A Study of a MV Cable Joint

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

On-line PD Monitoring Makes Good Business Sense

LONG-LIFE XLPE INSULATED POWER CABLE

SECTION 13. Multipliers. Outline of Multiplier Design Process:

Cable Condition Monitoring to Improve Reliability

W-2. Stranding Comparison

Stephen G. Whitley, Senior Vice President & Chief Operating Officer

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Water Pollution. A Presentation for Café Scientifique Cherie L. Geiger, Ph.D. Department of Chemistry, UCF

Digital Systems Ribbon Cables I CMPE 650. Ribbon Cables A ribbon cable is any cable having multiple conductors bound together in a flat, wide strip.

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

Electrochemical Impedance Spectroscopy (EIS): A Powerful and Cost- Effective Tool for Fuel Cell Diagnostics

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

Testing of Power Transformers. Routine tests, Type tests and Special tests

Reactive Sputtering Using a Dual-Anode Magnetron System

Design Techniques for High Power RF Coaxial Cable Assemblies

A wave lab inside a coaxial cable

Yaffs NAND Flash Failure Mitigation

Optimal Replacement of Underground Distribution Cables

World Leader in HV Testing Technology

100% EMI Emission Containment

UGVCL/SP/591/11KV HT AB CABLE

Metal-Oxide Varistors (MOVs) Surface Mount Multilayer Varistors (MLVs) > MLN Series. MLN SurgeArray TM Suppressor. Description

6 ELECTRICAL PARAMETERS

F05D Meeting on Damped AC Voltage Testing

All Wires and Cables Are Not Created Equal

13 common causes of motor failure

AC-Synchronous Generator

AN3022. Establishing the Minimum Reverse Bias for a PIN Diode in a High-Power Switch. 1. Introduction. Rev. V2

GenTech Practice Questions

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Unit 12 Practice Test

Explaining and avoiding faults Increasing availability

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

A Method to Detect and Locate Roof Leaks Using Conductive Tapes

Supercapacitors. Advantages Power density Recycle ability Environmentally friendly Safe Light weight

Rock Bolt Condition Monitoring Using Ultrasonic Guided Waves

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

Complete Solar Photovoltaics Steven Magee. Health and Safety

The Impact of Transmission Cable System Construction and Design on Commissioning Test Options & Results

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables /15 kv XLPE insulated cables /20 kv XLPE insulated cables 35

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

AMSC s Superconductor Cable Technologies for Electric Utilities

Insulation Resistance Testing of Low Voltage Cables in the Field

Transcription:

Cable Failure, Diagnostics and Rejuvenation Steven Boggs

The History PE Cables The Zeigler catalyst was invented in 1953 and mass production of HDPE started in the late 1950 s. Chemically cross linked PE was invented by GE in 1963. The first generation of shielded PE cables started to fail after ~7 years from water trees caused by cotton tape conductor shields. Few remain in service. The second generation of shielded PE cables used dirty extruded shields, steam curing, and lasted a few years longer before starting to fail. Through subsequent generations of PE cables, the semicons, dielectric, and manufacturing have been improved to produce much more reliable cable.

The History EPR Cables The first generation of black EPR was introduced around 1962 and, while much more reliable than the first generation of PE cable, did not meet utility expectations. The second generation of orange EPR cable was introduced around 1970 and has provided very reliable service for over 35 years with no known systematic cause of failure.

350 300 250 200 150 100 50 0 Medium Voltage Cable Installation History Replacement EPR TRXLPE XLPE HMWPE >2 billion feet of pre-1980 PE cable of Feet 1964 1966 1968 1970 1972 1974 1976 1978 1980 1982 1984 1986 1988 1990 1992 1994 1996 1998 2000 Year of Installation Millions

1400 1200 1000 800 35 30 25 20 FIeld (V/mil) Field (kv/mm) 600 400 200 0 The Problem XLPE 0 5 10 15 20 25 30 Age (Years) 15 10 5 0 Breakdown Breakdown HMWPE

1400 1200 1000 800 35 30 25 20 Breakdown Field (V/mil) Breakdown Field (kv/mm) 600 400 200 0 XLPE 99% 63% HMWPE 1% 0 5 10 15 20 25 Age (Years) 15 10 5 0

Why are some Years Worse? Source of Supply Utilities often put out yearly tenders for cable and the source varies from year to year Location of Installation Regional expansion varies from year to year, and some locations may have better cable environments than others If the cause of such variations can be identified, it may be important to decision making

The Cause Electrochemical degradation ( water treeing ), which occurs in hydrophobic polymers which can be electro-oxidized to a substantially more hydrophillic state. Vented water trees tend to grow from ionic impurities at the semicon-dielectric interface Bowtie water trees tend to grow from cavities and impurities in the dielectric.

Vented Water Tree (Shown here with Electrical Tree) Vented water trees are generally initiated at ionic impurities at the interface between the dielectric and semiconducting layers. Steam cured XLPE cable had a halo of microvoids in the middle of the insulation that gave rise to very large numbers of bowtie trees, the spatial correlation of which could compromise impulse breakdown Bow Tie Water Trees The visible paths in the water trees are strings of water filled microcavities connected by nm scale tracks of electrooxidized polymer. Bow Tie water trees usually initiate inside the bulk of the dielectrics at voids or contaminations.

Model for Water Tree Growth in TR-XLPE What is a Water Tree? A water tree is a pattern water-filled cavities connected by electro-oxidized tracks which is selfpropagating because the electro-oxidized polymer is substantially more hydrophillic than the base polymer, which causes water to condense from the base polymer into the electro-oxidized regions. Formation of a water tree requires a polymer which can be electro-oxidized from a highly hydrophobic state to a substantially more hydrophilic state.

History of Water Treeing First recognized in 1969 Laboratory investigations tended to be carried out on samples grown at very high field. Mechanical water trees can grow, and the degree of chemical vs mechanical damage depends on the electric field. Spectroscopic sensitivity was limited (no micro FTIR) Most of the investigators were EE s, not chemists. Only when investigators started to look at field grown trees did they see chemical evidence of electro-oxidation. By the time significant progress was made, the funding agencies were sick of sinking money into water treeing with little to show for it.

Technical Aspects of PE-Based Shielded Distribution Cable are Dominated by Electro-oxidation Requirements to grow a water tree AC field above about 1 kv/mm Hydrophobic polymer which can be electro-oxidized to substantially more hydrophillic Water, but not very much A source of ions to provide the appropriate electrical conductivity Not too high, and not too low Water tree in cable taken from the desert of Saudi Arabia

Facts About Water Trees At moderate electric fields, water trees grow from ionic impurities, not stress enhancements Growth of a water tree at moderate electric fields requires a source of ions Long termgrowth of bowtie trees is probably limited by diffusion of water through the polymer The tendency to grow water trees goes as approximately the square of the electric field Water tree growth tends to increase roughly linearly with frequency to at least 3 khz.

Water Treeing Stops Without Ions

Characteristics of a Chemical Potential for Water Treeing 1. Results in self-propagation through the dielectric 2. Requires an electric field 3. Frequency dependent 4. Depends heavily on ion concentration

Basis for Computation

Chemical Potential for Sphere What is the relevant chemical potential? Positive Peak or DC Offset? Total energy or energy in polymer? Zeller believed the DC offset was the relevant potential. But for a rapid, irreversible reaction, it might be the positive peak.

Chemical Potential for Water Treeing

Numerical Method Use program for transient nonlinear FEA Compute several cycles with a water conductivity, σ Compute several cycles with a water conductivity 1.05σ Compute energy at each time, take difference, and convert to chemical potential

Numerical & Analytical Computation

Analytic Approximation (Zeller) and Numerical Computation of Chemical Potential for Two, 1 μm Diameter Spheres Connected by a 10 nm dia., 5 μm Long Channel. Background field: 5 kv/mm Chemical potential goes as square of field.

Chemical Potential Zeller s explanation for chemical potential seems likely and is a major step forward. The chemical potential can be computed numerically for axisymmetric configurations. The chemical potential is typically large enough to drive electro-oxidation over several orders of magnitude of water conductivity But knowledge of the chemical potential does not imply knowledge of the chemistry.

Laboratory Growth of Water Trees Water trees grow from water needle electrodes readily and rapidly but are more electromechanical than electrochemical Test used for very preliminary screening of materials A good simulation of field conditions requires semicon electrodes and takes months to grow. Provides a comparative test with good correlation to field experience.

Lab Test for Water Treeing

Vented Tree Length Distribution vs Time

Mechanisms of Water Tree Resistance Make the polymer more hydrophillic Make any water in the polymer very conductive Add a salt to the polymer Make any water in the polymer nonconductive Place an ion filter in the system

TR-XLPE An early experimental compound from used powdered NaCl in the XLPE, which was effective. Present TR-XLPE involves a hydrophilic additive One assumption would be that this additive stops water tree channels by inhibiting condensation of moisture in the electro-oxidized region. This can be treated as a mean free path problem.

Paths to Inhibit Water Tree Growth Low water conductivity Filter the water (mineral filled jacket) Clean semicons, jacket, and blocked conductor High water conductivity - add salt to the polymer Hydrophilic system (TR-XLPE and EPR) Low water permeability semicons Water tree growth is a balance between field effects and hydrophobicity. For example if you take TR-XLPE in thin wall model cable, you can grow water trees through the wall

Water Trees and Diagnostics Water trees increase dielectric loss (tan(δ)) Water trees cause dielectric absorption Absorption of charge which is released, slowly, if the sample is shorted Water trees cause (small) harmonic currents Water trees decrease insulation resistance But only if they grow all the way through Water trees cause formation of electrical trees which generate PD.

What is being Measured? A water tree is much more conductive than the polymer. In the trip region τ must be comparable to power frequency Such a time constant implies that the current and voltage are out of phase substantially, i.e., dielectric loss In the root region, a dielectric time constant in the range of μs Important for the effect of lightning impulses on water trees. In the water tip region, a gradient of conductivity occurs from the water tree to the base polymer Current density and position-dependent resistivity imply formation of space charge. J=current density ε=dielectric constant ρ=resistivity

What is Measured? Under AC voltage, variation in conductivity near the water tree tip causes dissipation & increases tan(δ) For isothermal relaxation or recovery voltage, space charge causes a current after the cable is shorted for a few seconds In all cases, an average property is being used to diagnose an extreme value This only works if a correlation has been established between the average property and the extreme value. This correlation may be cable or system specific, depending on operating conditions

Insulation Resistance Unless the water tree has grown ALL the way through the dielectric, a change in IR can seldom be observed. Under field conditions, leakage paths caused by accessories pose a major problem. Good way to locate water trees which have grown through the insulation in the lab. Generally TERRIBLE diagnostic under field conditions.

Impulse Reflection from Water Trees DC voltage was applied to cause space charge at water trees, then a pulse was sent down the cable, and reflections were detected from the water trees. This approach was developed in the Russia and applied in North America but damaged the cable. When AC is applied, the space charge causes a field enhancement for the reverse polarity which tends to initiate electrical trees.

Water Trees and PD All past work indicates that water trees do not cause partial discharge However, non-pd electrical signals have been observed fromwater trees under laboratory conditions by Dorris et al. Consistent with rapid yielding of the polymer causing a step increase in capacitance. Electrical trees can be associated with water trees

Water Trees with Electrical Trees The electrical trees were detected in the field with PDIV of 2to 2.5 25 pu. The electrical trees were detected at the same location two or three years in a row. This suggests that a heavily water treed cable is likely to have some electrical trees which may not grow to failure rapidly. M. S. Mashikian and A. Szatkowski, Medium Voltage Cable Defects Revealed by Off-Line Partial Discharge Testing at Power Frequency. IEEE EI Magazine, Vol. 22, No. 4, July/Aug 2006. pp. 24-32.

Water Trees & Electrical Trees We have very little knowledge about electrical trees grown at low fields (~2 kv/mm) Researchers do not have sufficient patience At laboratory stresses, electrical trees normally progress to failure rapidly Evidently, electrical trees in medium voltage distribution cable can last for years But are the trees active at 1 pu? If not, how did they grow? Probably the PD at 1 pu is too small to detect in the time domain under field conditions. At higher fields, multiple discharges cascade down tree channels.

Frequency Domain PD Detection PD detection is generally more sensitive, if less quantitative, when carried out in the frequency domain. Cablewise conducts PD detection in-service and in the frequency domain to improve sensitivity Discharge is normally observed for any heavily water treed cable and is an indication of cable condition. Water trees do not generate discharge, so this must be caused by electrical trees.

Conclusions PE Diagnostics Diagnostics based on averaged parameters are only of value if a statistical correlation has been developed with typical cable condition. The degree to which such correlations can be transferred from one system to another is not known. PD from electrical trees associated with water trees is a clear indication of poor cable condition Diagnostics based on non-pd electrical signals, if real, appear promising but are not yet developed.

How Big is My Problem? If we analyze historical data, we can estimate future failure rates based on an assumed inground population But how much as already failed and been replaced? The number of splices in direct buried cable is often much greater than utility records show In a duct-based system, this implies that more cable may have been replaced than utility records indicate Thus the in-ground population of low quality cable may be smaller than utility records suggest.

Options Replace Impractical in the short term Need basis to prioritize replacement Field testing can provided limited insight Rejuvenate About half the cost of replacement Requires that neutral be in acceptable condition Has a good track record for reducing failure rates Wait until failure

Replace but Where? Routine Field Test Programs (e.g., PPL) Conduct continuous, system wide tests PD, tan(δ), depolarization current, etc. With criteria for accept, rejuvenate, replace Requires taking circuits out of service Over time, the failure rate has been reduced substantially In-Service Test Programs PD & concentric neutral assessment is possible inservice (without an outage) Objective is typically to prioritize replacement or reduce the likelihood of failure on critical circuits

Present State-of-the-Art A range of approaches to field PD measurement are being marketed While they differ in detail, they can generally diagnose unambiguously very bad cable and very good cable - the devil is in the details between Field PD measurement is most effective to address a known problem For use to assess overall condition, PD measurements are best combined with other techniques such as dielectric loss, spectroscopy, etc.

Silicone Injection Cable Rejuvenation Commercialized by Dow Corning in 1987. Inject a low molecular weight silicone into the conductor strands which then diffuses into the dielectric and gels through a reaction with moisture in the dielectric, thereby replacing water trees with gelled silicone. Applied widely as a lower cost alternative to replacement when the neutral is in acceptable condition.

Incomplete data for 2005 William R. Stagi, Silicone Injection Technology, IEEE Latin American Conference, 2006

Dielectric Strength Improves Over Time Treatment cost is in the range of $8/ft compared with replacement costs of $20 to $50/ft. Over the past 20 years, 80 million cable feet have been treated, 99+% of which is still in service and failure-free.

Conclusion In the long run, most of what remains of the >2 billion feet of pre-1980 PE cable will have to be rejuvenated or replaced prematurely. We have a huge technical and economic problem, but one which may not be as large as our records show, as we really do not know how much of this cable remains in the ground. We have to start from the cable as it is all we can do technically is develop better ways to prioritize rejuvenation and replacement.

What Can Technology Contribute? We need a (preferably in-service) diagnostic which is sensitive to the worst water trees rather than the present diagnostics which tend to react similarly to many small trees or a few large trees. Do water trees act as nonlinear mixers for high frequency radiation in the cable? If so, this effect is probably a strong function of tree length. Certainly water trees generate harmonic currents, which suggests nonlinearity.