SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS



Similar documents
PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Energy Procedia Energy 00 Procedia (2011) (2012) 56 65

Mohan Chandrasekharan #1

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

UNIT 2 REFRIGERATION CYCLE

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

How To Calculate The Performance Of A Refrigerator And Heat Pump

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

REFRIGERATION (& HEAT PUMPS)

Chapter 3.4: HVAC & Refrigeration System

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

FEASIBILITY OF A BRAYTON CYCLE AUTOMOTIVE AIR CONDITIONING SYSTEM

Warm medium, T H T T H T L. s Cold medium, T L

The Second Law of Thermodynamics

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

Condensers & Evaporator Chapter 5

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Thermodynamics - Example Problems Problems and Solutions

Increasing the evaporation temperature with the help of an internal heat exchanger

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

Open Cycle Refrigeration System

The Second Law of Thermodynamics

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

New Trends in the Field of Automobile Air Conditioning

Development of a model for the simulation of Organic Rankine Cycles based on group contribution techniques

Waste Heat Recovery through Air Conditioning System

An analysis of a thermal power plant working on a Rankine cycle: A theoretical investigation

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

DESIGN AND APPLICATION OF AMMONIA HEAT PUMP SYSTEMS FOR HEATING AND COOLING OF NON-RESIDENTIAL BUILDINGS

UNDERSTANDING REFRIGERANT TABLES

Chapter 10: Refrigeration Cycles

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No1, 2010

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

How To Know If A Refrigeration System Is Efficient

How does solar air conditioning work?

Research on the Air Conditioning Water Heater System

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Modelling and Simulation of the Freezing Systems and Heat Pumps Using Unisim Design

Part A: Fluid properties

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

AMMONIA AND CARBON DIOXIDE HEAT PUMPS FOR HEAT RECOVERY IN INDUSTRY

Transient Analysis of Integrated Shiraz Hybrid Solar Thermal Power Plant Iman Niknia 1, Mahmood Yaghoubi 1, 2

How To Design A Refrigeration System

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

Automobile Air Conditioning Primer

Analysis of Alternative Refrigerants to HCFC-22

AN EXPERIMENTAL STUDY OF EXERGY IN A CORRUGATED PLATE HEAT EXCHANGER

LG Electronics AE Company, Commercial Air Conditioning

ME 201 Thermodynamics

The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Module 5: Combustion Technology. Lecture 34: Calculation of calorific value of fuels

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Energy Efficient Ammonia Heat Pump. Energy and Climate Refrigeration and Heat Pump Technology

High Pressure Ammonia Systems New Opportunities

a) Use the following equation from the lecture notes: = ( J K 1 mol 1) ( ) 10 L

Ambient Energy Fraction of a Heat Pump

News in Data Center Cooling

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

Heat Recovery In Retail Refrigeration

Efficiency of Hydrogen Liquefaction Plants

Characteristics of Evaporators

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Testing methods applicable to refrigeration components and systems

Energy Efficiency Best Practice Guide Industrial Refrigeration

AIR REVERSING R744 AIR CONDITIONING SYSTEM

Purpose of Refrigeration

New absorption chillers for high efficient solar cooling systems

THE POSSIBILITY OF USING LIQUIFIED PETROLEUM GAS IN DOMESTIC REFRIGERATION SYSTEMS

CO MPa (abs) 20 C

C H A P T E R T W O. Fundamentals of Steam Power

Diesel Cycle Analysis

A comparison of heterogenous and homogenous models of two-phase transonic compressible

DET: Mechanical Engineering Thermofluids (Higher)

Basics of Low-temperature Refrigeration

GEOTHERMAL POWER PLANT CYCLES AND MAIN COMPONENTS

APPLIED THERMODYNAMICS. TUTORIAL No.3 GAS TURBINE POWER CYCLES. Revise gas expansions in turbines. Study the Joule cycle with friction.

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

Optimal operation of an Ammonia refrigeration cycle

P08 Köldmedier med låg växthuseffekter

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Refrigeration Basics 101. By: Eric Nelson

SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING

Transcription:

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6340 (Print) ISSN 0976 6359 (Online) Volume 6, Issue 1, January (2015), pp. 71-91 IAEME: www.iaeme.com/ijmet.asp Journal Impact Factor (2014): 7.5377 (Calculated by GISI) www.jifactor.com IJMET I A E M E SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS Mr. PARTHIBAN KASI Assistant Professor, Department of Mechanical Engineering, Velammal Institute of Technology, Chennai, India ABSTRACT The main aim of this project is to analyses the cascade refrigeration system by employing various alternative refrigerant pairs and choosing the best pair for higher temperature circuit (HTC) and lower temperature circuit (LTC). The analysis was done in various refrigerants pairs which are R134a/R23, R290/R23, R404A/R23, R407C/R23, R410A/R23, R134a/R508B, R290/R508B, R404A/R508B, R407C/R508B, R410A/R508B, R134a/R170, R290/R170, R404A/R170, R407C/R170 and R410A/R170. Assuming the degrees of sub cooling and superheating as 5 C and 10 C, respectively. The condenser temperature in higher temperature circuit (HTC) was varied from 30 C to 50 C and evaporator temperature in lower temperature circuit (LTC) was varied from -70 to -50 C. The intermediate heat exchanger temperature is about -20 C. Furthermore, the efficiencies of the compressors are assumed to be equal as 0.7. It has been found that the coefficient of performance (COP) of the cascade refrigeration system increases and the mass flow rate of higher temperature circuit increases, along with the work of compressor with rise in evaporator temperature for all refrigerant pairs. On the other hand, the COP of the cascade refrigeration system decreases and the mass flow rate of higher temperature circuit increases, also there is increase in work of compressor with increase in condenser temperature. Finally, the refrigerant pair R134a R170 has the highest COP and lowest mass flow rate, while R404A R508B has the lowest COP and highest mass flow rate. Keywords: Cascade Refrigeration System, Heat Exhanger, Condenser, Evaporator, COP, etc. 1. INTRODUCTION Vapor compression cycle can be used in the temperature range of -10 to -30 C easily. And low-temperature refrigeration systems are typically required in the temperature range from 30 C to 100 C for applications in food, pharmaceutical, chemical, and other industries, e.g., blast freezing, 71

cold storages, liquefaction of gases such as natural gas, etc. At such low temperatures, single-stage compression systems with reciprocating compressors are generally not feasible due to high pressure ratios. A high pressure ratio implies high discharge and oil temperatures and low volumetric efficiencies and, hence it has low COP values. Screw and scroll compressors have relatively flat volumetric efficiency curves and have been reported to achieve temperatures as low as 40 C to 50 C in single-stage systems. Fig.1: Cascade refrigeration system Cascade refrigeration cycle can be used to achieve low temperatures, where series of single- stage units are used that are thermally coupled through evaporator/condenser cascades, as shown in Fig. 1 for a two-circuit cascade unit. Each circuit has a different refrigerant suitable for that temperature, the lower temperature units are progressively using lower boiling point refrigerants. Generally, two-circuit and rarely three-circuit cascade systems are used. In general, if the desired temperature it can be easily achieved in a single-stage machine, it will be more efficient than a cascade system due to irreversibility and losses associated with a large number of components. 2. THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM Fig. 2 shows vapor compression cascade refrigeration system under consideration, which consists of low and high side refrigeration systems indicated as A and B. Refrigeration systems A and B are coupled to each other by means of a heat exchanger in which the total heat from refrigeration system A is rejected to refrigeration system B. The refrigerants flowing in both systems are usually different from each other although there are some cases where the same refrigerant can be used in both systems. Fig. 2: P-H diagram of cascade refrigeration system 72

Thermodynamic analysis is based on the energy and irreversibility analyses of the elements of the two stage vapor compression cascade refrigeration system. Each element in the system is treated as a control volume. The equations energy and continuity for a control volume can be written as 2 2 Vi dec. v Vo c. v + i i + + i = + o o + + o + c. v Q m h gz m h gz W 2 dt 2 d m c. v + m o m i = 0 d t where Q c.v, W c.v and E c.v are the heat transfer rate to the control volume, the actual power done by the control volume and the energy within the boundary of the control volume respectively, while m, h, V 2 /2, gz are the mass flow rate specific enthalpy, specific kinetic energy and potential energy of the fluid at the inlet or outlet conditions. It is assumed that sub cooling occurs in the liquid line while superheating occurs in the suction line inside the refrigerated space, changes in kinetic and potential energies and pressure drop through the cycle are negligible. It is assumed that steady-state and uniform flow conditions exist through the components of the cascade refrigeration system, in other words, the condition of the mass at each point of the components doesn t change with time. It is also assumed that isentropic efficiencies of the compressors which are equal, and the heat loss from the compressors, heat exchanger and expansion valves are negligible. d E c. v = 0 d t m = m = m o i A The heat transfer rate of the evaporator (refrigeration capacity) Q e is Q e = m A q e where q e and m A are the specific refrigeration capacity of system A and the refrigerant mass flow rate flowing through system A, respectively. The total work input to the compressors in both systems can be calculated from W tot = m Aw compa + m Bw compb where m B is the refrigerant mass flow rate flowing through system B, while w compa and w compb are the specific work of compressions in system A and system B, respectively. The coefficient performance of the cascade system COP cas is C O P c a s = Q W e t o t 73

2.1 Low Temperature Side of the Cascade Refrigeration System As mentioned earlier, the low temperature side of the cascade refrigeration system consists of compressor A, one side of the heat exchanger, thermostatic expansion valve A, and the evaporator. In the refrigeration cycle A, the refrigerant enters compressor A at state 1 as superheated vapour at low pressure and low temperature. From state 1 to 2, the refrigerant is compressed and discharged as superheated vapour at high pressure and high temperature. Then, it enters the heat exchanger where it condenses and rejects heat to the evaporator of system B. It leaves the heat exchanger at state 3 as high pressure saturated liquid. From state 3 to 4, the refrigerant is sub cooled as a result of heat transfer to the condensing medium. At state 4, the refrigerant enters expansion valve A, where its pressure is reduced in a throttling process to the evaporator pressure. After leaving the valve at state 5, it enters the evaporator, where it absorbs heat from the refrigerated space. At state 6, it leaves the evaporator as saturated vapour at low pressure and low temperature. When the assumptions mentioned previously are taken into consideration, specific work of compression for the compressor can be written as w = h h c o m p A 2 1 where h 1 and h 2 are the specific enthalpies across compressor A. The refrigerants are simulated as ideal gases during compression process. Hence the specific work of compression can also be expressed by m η w c o m p = r ( h 2 h 1) c o m p where P c, P e, and T comp,i are the condenser pressure, evaporator pressure, and the temperature at compressor inlet, respectively, while η isen is the isentropic efficiency of the compressor; c p and K are constant pressure specific heat and specific heat ratio of the refrigerant, respectively. Isentropic efficiency of the compressor can be expressed in terms of polytrophic efficiency η p ; pressure ratio and specific heat ratio. The specific heat rejected in the heat exchanger can be written as H E ( 2 4 ) q h h = A where h 4 is the enthalpy of the refrigerant at the expansion valve inlet. The enthalpy of the sub cooled liquid at state 4 can be calculated by assuming that saturated liquid at point 3 is cooled to state 4 at a constant pressure. Therefore, specific enthalpy at state 4 can be expressed as 4 3 p, l ( 3 4) h = h c T T where c p,l is the specific heat at constant pressure of refrigerant in liquid state between states 3 and 4, h 3 the enthalpy of saturated liquid at the heat exchanger exit, T 3 the saturation temperature in the heat exchanger and T 4 is the temperature at the expansion valve inlet. During the throttling process in the expansion valve, it is assumed that there is no heat transfer to the environment, which results in h 4 = h 5 74

The specific refrigeration capacity of refrigeration cycle A can be written as q = mr( h h ) e 1 5 where h 5 is the enthalpy of refrigerant at evaporator inlet. The enthalpy of superheated vapour at state 1 can be calculated by assuming that saturated vapour at state 6 which is heated to state 1 at a constant pressure. Therefore, specific enthalpy at state 1 can be expressed as ( ) h = h + c T T 1 6 p, v 1 6 Where c p,v is the constant pressure specific heat of refrigerant in vapor state between states 6 and 1, T 6 is the evaporator temperature, and T 1 is the temperature at the compressor inlet. 2.2 High Temperature Side of the Cascade Refrigeration System In refrigeration system B, the same processes exist and same assumptions are valid as in system A. The specific work of compression for the adiabatic compression process in system B can be written as w = h h com pb 8 7 where h 7 and h 8 are the specific enthalpies across compressor B. m η w co m p = r ( h 8 h 7) co m p The rate of enthalpy change of the condenser can be determined from q = m r( h h ) c 10 8 where h 10 is the enthalpy of the refrigerant at the expansion valve inlet. The enthalpy of sub cooled liquid can be calculated using the same approach. Therefore, specific enthalpy at state 10 can be expressed as ( ) h = h c T T 10 9 p, l 10 9 where c p,l is the constant pressure specific heat of the refrigerant in liquid state between states 9 and 10, T 9 is the condenser temperature and T 10 is the temperature at the expansion valve inlet. The assumption in refrigeration system A can also be used for the throttling process in expansion valve B, h 10 8 where h 10 and h 11 are the enthalpies of refrigerant at the expansion valve inlet and exit, respectively. = h 75

The specific heat absorbed in the heat exchanger can be written as H E ( 7 1 1) q h h B = The specific enthalpy of superheated vapor at state 7 can be expressed by ( ) h = h + c T T 7 1 2 p, v 7 1 2 where c p,v is the constant pressure specific heat of the superheated refrigerant vapor between states 12 and 7, h 12 is the enthalpy of saturated vapor at the heat exchanger exit, T 12 is the saturation temperature in the heat exchanger, and T 7 is the temperature at the compressor inlet. 2.3 Heat Exchanger Combining refrigeration systems A and B, the heat exchanger is the key component of the cascade system. The heat rejected from the refrigeration system A is transferred to the refrigeration system B in the heat exchanger. It is also well insulated to provide that the total heat rejected from refrigeration cycle A be equal to the total heat absorbed by the refrigeration system B. As a result, the first law of thermodynamics for the heat exchanger can be written as B ( 7 11) = A ( 2 4) m h h m h h A computer code based on the thermodynamic models presented above has been developed to calculate the COPs and mass ratio of various refrigerant pairs. 3. SIMULATION METHODOLOGY The engineering calculation and simulation of the cascade refrigeration cycle system requires the availability of simple and efficient mathematical methods for the determination of thermodynamic property values of the operating fluid. Values of the thermodynamic property are necessary both at the key points in the cycle and along the process taking in the various components. 3.1 Input Data for Simulation Condenser Temperature T c = 30 to 50 C Evaporator Temperature T E = -70 to -50 C Intermediate temperature T INT = -20 C Compressor efficiency of the system η comp = 0.7 Refrigerant in high temperature circuit R-134a, R-290, R-407C, R-404A, R410A Refrigerant in low temperature circuit R-23, R508B, R170 Sub cooling (in HTC and LTC) 5 C Superheating (in HTC and LTC) 10 C By carrying out the thermodynamic analysis of the system for the conditions stated above the values at various state points of the cascade refrigeration cycle have been obtained. 76

In the present work, following parameters have been computed. Coefficient of performance of a cascade refrigeration cycle. Mass Flow rate of HTC. Work of compression. 3.2 Selection of Working Fluid Many factors need to be considered Ozone depletion potential Global warming potential Combustibility Thermal factors Toxicity Cost Environmental friendliness, etc. 3.2.1 Low Temperature Circuit Table.1: Properties of LTC refrigerants REFRIGERANTS PROPERTIES R-23 (Trifluormethane) BP: -82.1 C Tcrit:25.9 C ODP:0, GWP:12000 R-170 (Ethane) BP: -88.6 C Tcrit:32.2 C ODP: 0, GWP:20 R-508B BP: -87.6 C Tcrit:11.2 C ODP:0,GWP:13000 3.2.2 Higher Temperature Circuit Table.2: Properties of HTC refrigerants REFRIGERANT PROPERTIES R-134a (Tetrafluoroethane) Boiling point: -26.1 C Critical temperature:101.1 C ODP: 0, GWP:1300 R-290 (Propane) Boiling point: -42.2 C Critical temperature:96.6 C ODP: 0, GWP:-20 R-407C Boiling point: -43.6 C Critical temperature:85.8 C ODP: 0, GWP:1800 R-404A Boiling point: -46.2 C Critical temperature:72 C ODP: 0, GWP:3900 R-410A Boiling point: -51.3 C Critical temperature:70.5 C ODP: 0, GWP:2100 77

4. RESULTS & DISCUSSIONS Using the developed computer code, the COPs and mass flow rates of the HTC refrigerant in the cascade refrigeration system and work of compression are determined as functions of the evaporator temperature, condenser temperature, the intermediate temperatures of the lower and higher temperature systems in the heat exchanger and the compressor efficiency. Then, COPs and mass flow rates and work of compression of the considered pairs are compared and the best refrigerant pair among them is selected. 4.1 Variation of COP with the Condenser Temperature The changes in the COP of the cascade system will vary in the condenser temperature for an evaporator temperature of -70 C intermediate temperature as -20 C and compressor efficiency of 0.7 respectively. As the condenser temperature of the cascade system increases, the condenser pressure increases, while the evaporator temperature, intermediate temperature and compressor efficiency are kept in constant. On increasing the condenser pressure, more compressor power is obtained, which makes the COP of the cascade system for all considered refrigerant pairs to decrease. T e =-70 C, T int =-20 C, η c =0.7 COP 1.1 1 0.9 0.8 0.7 0.6 30 35 40 45 50 T c C Fig.3: COP as a function of condenser temperature 4.2 Variation of mass flow rate with the Condenser Temperature R134a-R23 R290-R23 R404A-R23 R407C-R23 R410A-R23 T e =-70 C, T int =-20 C, η c =0.7 m r2 0.8 0.7 0.6 0.5 0.4 0.3 30 35 40 45 50 T c C R134a-R23 R290-R23 R404A-R23 R407C-R23 R410A-R23 Fig.4: Mass Flow Rate as a Function of Condenser Temperature 78

The changes in the mass flow rate of the HTC refrigerant will change in the cascade refrigeration system with respect to the condenser temperature for an evaporator temperature of - 70 C, intermediate temperature as -20 C and compressor efficiency of 0.7 respectively. As the condenser temperature of the cascade system increases, the condenser pressure increases, while the evaporator temperature, intermediate temperature and compressor efficiency are kept in constant. On increasing the condenser pressure, more compressor power is obtained, which causes the mass flow rate of the HTC refrigerant in the cascade refrigeration system for all considered refrigerant pairs to increase. As the condenser temperature of the cascade system increases, the mass flow rate of the HTC refrigerant in the cascade refrigeration system increases. It is seen that R290 R23 has the lowest mass flow rate, while R134a R23 has the highest one. The mass flow rate of R404A R23, R407C R23 and R410A R23 place in the middle range and increases and they are parallel to each other. 4.3 Variation of work of compression with the Condenser Temperature 2.5 2.3 T e =-70 C, T int =-20 C, η c =0.7 W c kw 2.1 1.9 1.7 1.5 30 35 40 45 50 T c C R134a-R23 R290-R23 R404A-R23 R407C-R23 R410A-R23 Fig.5: Changes in Compressor Work with Condenser temperature The change in compressor work of the refrigerant pairs increase with respect to the condenser temperature. The figure shows, the evaporator temperature is -70 C, intermediate temperature is - 20 C and compressor efficiency is 0.7 which are kept constant. As the condenser temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases, but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these are to increase the work done. In the considered condenser temperature range, R404A R23 has the highest work done values, while R134a R23 has the lowest ones. The work done of refrigerant pairs placed in the middle range, namely R290 R23, R407C R23 and R410A R23, increases and they are parallel to each other. 4.4 Variation of COP with the Evaporator Temperature The changes in the COP of the cascade system with respect to the evaporator temperature for an condenser temperature of 40 C, intermediate temperature as -20 C and compressor efficiency of 0.7, respectively. When condenser temperature, intermediate temperature and compressor efficiency which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the COP of the cascade refrigeration system increases. It is seen that R134a R23 has the highest COP, while R404A R23 has the lowest one. The COPs of R290 R23, R407C R23, and R410A R23 place in the middle range and increase parallel to each other. 79

T c =40 C, T int =-20 C, η c =0.7 COP 1.3 1.2 1.1 1 0.9 0.8-50 -55-60 -65-70 T e C R134a-R23 R290-R23 R404A-R23 R407C-R23 R410A-R23 Fig.6: Changes in COP with Evaporator Temperature 4.5 Variation of mass flow rate with the Evaporator Temperature The variation in mass flow rate with the evaporator temperature for a constant condenser temperature is 40 C, intermediate temperature is -20 C and compressor efficiency is 0.7. When the condenser temperature, intermediate temperature and compressor efficiency which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the mass floe rate of the HTC cascade refrigeration system increases. In the considered evaporator temperature range, R410A R23 has the lowest mass flow rate values, while R404A R23 has the highest ones. The mass flow rate of refrigerant pairs placing in the middle range, namely R134a R23, R407C R23 and R290 R23, increases parallel to each other. m r2 0.7 0.6 0.5 0.4 0.3 0.2 T c =40 C, T int =-20 C, η c =0.7 R134a-R23 R290-R23 R404A-R23 R407C-R23 R410A-R23-50 -55-60 -65-70 T e C Fig.7: Variation of mass flow rate as a function of evaporator temperature 80

4.6 Variation of work of compression with the Evaporator Temperature T c =40 C, T int =-20 C, η c =0.7 2.1 1.9 W c kw 1.7 1.5 1.3-50 -55-60 -65-70 R134a-R23 R290-R23 R404A-R23 R407C-R23 R410A-R23 T e C Fig.8: Variation in compressor work as a function of Evaporator temperature The changes in compressor work of the refrigerant pairs with respect to the evaporator temperature. The figure shows, the condenser temperature of 40 C, intermediate temperature as - 20 C and compressor efficiency of 0.7 which are kept constant. As the evaporator temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these are to increase the work done. In the considered evaporator temperature range, R404A R23 has the highest work done values, while R134a R23 has the lowest ones. The work done of refrigerant pairs placing in the middle range, namely R290 R23, R407C R23 and R410A R23, increase parallel to each other. 4.7 Variation of COP with the Condenser Temperature The changes in the COP of the cascade system will vary in the condenser temperature for an evaporator temperature of -70 C intermediate temperature as -20 C and compressor efficiency of 0.7 respectively. As the condenser temperature of the cascade system increases, the condenser pressure increases, while the evaporator temperature, intermediate temperature and compressor efficiency are kept in constant. On increasing the condenser pressure, more compressor power is obtained, which makes the COP of the cascade system for all considered refrigerant pairs to decrease. In the considered condenser temperature range, R134a R170 has the highest COP values, while R404A R170 has the lowest ones. The COPs of refrigerant pairs placing in the middle range, namely R410A R170, R407C R170 and R290 R170, decrease parallel to each other. 81

COP 1.1 1 0.9 0.8 0.7 0.6 T e =-70 C, T int =-20 C, η c =0.7 30 35 40 45 50 R134a-R170 R290-R170 R404A-R170 R407C-R170 R410A-R170 T c C Fig.9: Changes in COP with Condenser Temperature 4.8 Variation of mass flow rate with the Condenser Temperature The changes in the mass flow rate of the HTC refrigerant in the cascade refrigeration system with respect to the condenser temperature for an evaporator temperature of -70 C, intermediate temperature as -20 C and compressor efficiency of 0.7, respectively. As the condenser temperature of the cascade system increases, the condenser pressure also increases, while the evaporator temperature, intermediate temperature and compressor efficiency are kept constant. On increasing the condenser pressure, more compressor power is required, which causes the mass flow rate of the HTC refrigerant in the cascade refrigeration system for all considered refrigerant pairs to increases. As the condenser temperature of the cascade system increases, the mass flow rate of the HTC refrigerant in the cascade refrigeration system increases. It is seen that R404A R170 has the lowest mass flow rate, while R407C R170 has the highest one. The mass flow rate of R134a R170, R290 R170, and R410A R170 place in the middle range and increases any they are parallel to each other. T e =-70 C, T int =-20 C, η c =0.7 m r2 0.8 0.7 0.6 0.5 0.4 0.3 30 35 40 45 50 T c C R134a-R170 R290-R170 R404A-R170 R407C-R170 R410A-R170 Fig.10: Changes in Mass Flow Rate with Condenser Temperature 82

4.9 Variation of work of compression with the Condenser Temperature T e =-70 C, T int =-20 C, η c =0.7 5 W c kw 4.5 4 3.5 3 30 35 40 45 50 T c C R134a-R170 R290-R170 R404A-R170 R407C-R170 R410A-R170 Fig.11: Variation in Compressor Work as a Function of Condenser Temperature The changes in compressor work of the refrigerant pairs with respect to the condenser temperature. The figure shows, the evaporator temperature of -70 C, intermediate temperature as - 20 C and compressor efficiency of 0.7 are kept constant. As the condenser temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these are to increase the work done. In the considered condenser temperature range, R404A R170 has the highest work done values, while R134a R170 has the lowest ones. The work done of refrigerant pairs placing in the middle range, namely R290 R170, R407C R170 and R410A R170, increase parallel to each other. 4.10 Variation of COP with the Evaporator Temperature T c =40 C, T int =-20 C, η c =0.7 COP 1.3 1.2 1.1 1 0.9 0.8-50 -55-60 -65-70 T e C R134a-R170 R290-R170 R404A-R170 R407C-R170 R410A-R170 Fig.12 Variation in COP as a Function of Evaporator Temperature The changes in the COP of the cascade system with respect to the evaporator temperature for an condenser temperature of 40 C, intermediate temperature as -20 C and compressor efficiency of 0.7 respectively. When condenser temperature, intermediate temperature and compressor efficiency 83

which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the COP of the cascade refrigeration system increases. It is seen that R134a R170 has the highest COP, while R404A R170 has the lowest one. The COPs of R290 R170, R407C R170, and R410A R170 place in the middle range and increase parallel to each other. 4.11 Variation of mass flow rate with the Evaporator Temperature The variation in mass flow rate with the evaporator temperature for a constant condenser temperature of 40 C, intermediate temperature of -20 C and compressor efficiency is 0.7. When the condenser temperature, intermediate temperature and compressor efficiency which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the mass flow rate of the HTC cascade refrigeration system increases. In the considered evaporator temperature range, R404A R170 has the lowest mass flow rate values, while R134a R170 has the highest ones. The mass flow rate of refrigerant pairs placing in the middle range, namely R410A R170, R407C R170 and R290 R170, increases parallel to each other. T c =40 C, T int =-20 C, η c =0.7 m r2 0.7 0.6 0.5 0.4 0.3-50 -55-60 -65-70 T e C R134a-R170 R290-R170 R404A-R170 R407C-R170 R410A-R170 Fig.13: Mass Flow Rate as a Function of Evaporator Temperature The variation in mass flow rate with the evaporator temperature for a constant condenser temperature of 40 C, intermediate temperature of -20 C and compressor efficiency is 0.7. When the condenser temperature, intermediate temperature and compressor efficiency which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the mass flow rate of the HTC cascade refrigeration system increases. In the considered evaporator temperature range, R404A R170 has the lowest mass flow rate values, while R134a R170 has the highest ones. The mass flow rate of refrigerant pairs placing in the middle range, namely R410A R170, R407C R170 and R290 R170, increases parallel to each other. 4.12 Variation of work of compression with the Evaporator Temperature The changes in compressor work of the refrigerant pairs with respect to the evaporator temperature. In this figure, the condenser temperature of 40 C, intermediate temperature as -20 C and compressor efficiency of 0.7 are kept constant. As the evaporator temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these are to increase the work done. In the considered evaporator temperature range, R404A R170 has the highest work done 84

values, while R134a R170 has the lowest ones. The work done of refrigerant pairs placing in the middle range, namely R290 R170, R407C R170 and R410A R170, increase parallel to each other. 4.5 4 T c =40 C, T int =-20 C, η c =0.7 W c kw 3.5 3 2.5-50 -55-60 -65-70 T e C R134a-R170 R290-R170 R404A-R170 R407C-R170 R410A-R170 Fig.14: Compressor Work as a Function of Evaporator Temperature 4.13 Variation of COP with the Condenser Temperature The changes in the COP of the cascade system will vary in the condenser temperature for an evaporator temperature of -70 C intermediate temperature as -20 C and compressor efficiency of 0.7 respectively. As the condenser temperature of the cascade system increases, the condenser pressure increases, while the evaporator temperature, intermediate temperature and compressor efficiency are kept in constant. On increasing the condenser pressure, more compressor power is obtained, which makes the COP of the cascade system for all considered refrigerant pairs to decrease. In the considered condenser temperature range, R290 R508B has the highest COP values, while R404A R508B has the lowest ones. The COPs of refrigerant pairs placing in the middle range, namely R410A R508B, R407C R508B and R134a R508B, decrease parallel to each other. T e =-70 C, T int =-20 C, η c =0.7 COP 1.1 1 0.9 0.8 0.7 0.6 30 35 40 45 50 T c C R134a-R508B R290-R508B R404A-R508B R407C-R508B R410A-R508B Fig.15: Variation in COP as a function of condenser temperature 85

4.14 Variation of mass flow rate with the Condenser Temperature T e =-70, T int =-20 C, η c =0.7 m r2 0.7 0.6 0.5 0.4 0.3 0.2 0.1 30 35 40 45 50 T c C R134a-R508B R290-R508B R404A-R508B R407C-R508B R410A-R508B Fig.16: Variation in Mass Flow Rate as a Function of Condenser Temperature The changes in the mass flow rate of the HTC refrigerant in the cascade refrigeration system with respect to the condenser temperature for an evaporator temperature of -70 C, intermediate temperature as -20 C and compressor efficiency of 0.7, respectively. As the condenser temperature of the cascade system increases, the condenser pressure also increases, when evaporator temperature, intermediate temperature and compressor efficiency which are kept constant. On increasing the condenser pressure, more compressor power is required, which causes the mass flow rate of the HTC refrigerant in the cascade refrigeration system for all considered refrigerant pairs to increases. As the condenser temperature of the cascade system increases, the mass flow rate of the HTC refrigerant in the cascade refrigeration system increases. It is seen that R404A R508B has the lowest mass flow rate, while R407C R508B has the highest one. The mass flow rate of R134a R508B, R290 R508B, and R410A R508B place in the middle range and increases parallel to each other. 4.15 Variation of work of compression with the Condenser Temperature The changes in compressor work of the refrigerant pairs with respect to the condenser temperature. In this figure, the evaporator temperature of -70 C, intermediate temperature as -20 C and compressor efficiency of 0.7 which are kept constant. As the condenser temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these are to increase the work done. In the considered condenser temperature range, R404A R508B has the highest work done values, while R290 R508B has the lowest ones. The work done of refrigerant pairs placing in the middle range, namely R134a R508B, R407C R508B and R410A R508B, increase parallel to each other. 86

W c kw 1.6 1.5 1.4 1.3 1.2 1.1 1 T e =-70 C, T int =-20 C, η c =0.7 30 35 40 45 50 T c C R134a-R508B R290-R508B R404A-R508B R407C-R508B R410A-R508B Fig.17: Compressor Work as a Function of Condenser Temperature 4.16 Variation of COP with the Evaporator Temperature The changes in the COP of the cascade system with respect to the evaporator temperature for an condenser temperature of 40 C, intermediate temperature as -20 C and compressor efficiency of 0.7, respectively. When condenser temperature, intermediate temperature and compressor efficiency which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the COP of the cascade refrigeration system increases. It is seen that R290 R508B has the highest COP, while R404A R508B has the lowest one. The COPs of R134a R508B, R407C R508B, and R410A R508B place in the middle range and increase parallel to each other. T c =40 C, T int =-20 C, η c =0.7 COP 1.3 1.2 1.1 1 0.9 0.8-50 -55-60 -65-70 T e C R134a-R508B R290-R508B R404A-R508B R407C-R508B R410A-R508B Fig.18: COP as a Function of Evaporator Temperature 87

4.17 Variation of mass flow rate with the Evaporator Temperature m r2 0.6 0.5 0.4 0.3 0.2 T c =40 C, T int =-20 C, η c =0.7-50 -55-60 -65-70 T e C Fig.19: Changes in Mass Flow Rate with Evaporator Temperature The variation in mass flow rate with the evaporator temperature for a constant condenser temperature of 40 C, intermediate temperature of -20 C and compressor efficiency is 0.7. When the condenser temperature, intermediate temperature and compressor efficiency which are kept constant. The refrigeration effect of the cascade system increases and the specific work of compression decreases on increasing the evaporator temperature. Consequently, the mass flow rate of the HTC cascade refrigeration system increases. In the considered evaporator temperature range, R404A R508B has the lowest mass flow rate values, while R407C R508B has the highest ones. The mass flow rate of refrigerant pairs placing in the middle range, namely R410A R508B, R134a R508B and R290 R508B, increases parallel to each other. 4.18 Variation of work of compression with the Evaporator Temperature The changes in compressor work of the refrigerant pairs with respect to the evaporator temperature. In this figure, the condenser temperature of 40 C, intermediate temperature as -20 C and compressor efficiency of 0.7 are kept constant. As the evaporator temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these is to increases work done. In the considered evaporator temperature range, R404A R508B has the highest work done values, while R290 R508B has the lowest ones. The work done of refrigerant pairs placing in the middle range, namely R134a R508B, R407C R508B and R410A R508B, increase parallel to each other. W c kw 1.4 1.3 1.2 1.1 0.9 1 0.8 T c =40 C, T int =-20 C, η c =0.7-50 -55-60 -65-70 T e C Fig.20: Changes in Compressor Work with Evaporator Temperature 88 R134a-R508B R290-R508B R404A-R508B R407C-R508B R410A-R508B R134a-R508B R290-R508B R404A-R508B R407C-R508B R410A-R508B

The changes in compressor work of the refrigerant pairs with respect to the evaporator temperature. The figure shows, the condenser temperature of 40 C, intermediate temperature as - 20 C and compressor efficiency of 0.7 are kept constant. As the evaporator temperature increases, the low temperature circuit compressor s work done (W COMP1 ) decreases but the high temperature circuit compressor s work done (W COMP2 ) increases, and the combined effect of these is to increases work done. In the considered evaporator temperature range, R404A R508B has the highest work done values, while R290 R508B has the lowest ones. The work done of refrigerant pairs placing in the middle range, namely R134a R508B, R407C R508B and R410A R508B, increase parallel to each other. CONCLUSION Coefficient of performance, mass flow rate and compressor work of the cascade refrigeration system for the various refrigerant pairs have been analyzed and compared with the evaporator temperature, condenser temperature, the temperature difference between the saturation temperatures of the lower and higher temperature systems in the heat exchanger ( T), intermediate temperature and the compressor efficiency of the cascade refrigeration system. Refrigerant pair R134a R170 is found to be best pair for the vapour compression cascade refrigeration systems among all considered pairs. NOMENCLATURE C p - constant pressure specific heat of (kj kg-1 K -1 ) E - Energy (kj) h - Specific enthalpy of refrigerant (kj kg -1 ) K - Ratio of constant specific heats m - Mass flow rate (kg s -1 ) q - Specific capacity (kj kg -1 ) Q - Heat transfer rate (kw) P - Pressure (kpa) T - Temperature (K) T - temperature difference between the saturation temperatures of the lower and higher temperature systems in the heat exchanger (K) w - Specific compressor capacity (kj kg -1 ) Greek words η c - efficiency of the compressor Subscripts A B refrigeration system A refrigeration system B 89

c cas condenser cascade comp compressor crit e HE i l o v critical evaporator heat exchanger inlet liquid outlet vapour Abbreviations BP HTC LTC COP ODP GWP Boiling Point Higher Temperature circuit Lower Temperature circuit Coefficient of Performance Ozone Depletion Potential Global Warming Potential REFERENCES 1. Alberto Dopazo.J, Jose Fernandez-Seara, Experimental evaluation of a cascade refrigeration system prototype with CO 2 and NH 3 for freezing process applications, International journal of refrigeration 34 (2011) 257-267. 2. Alberto Dopazo.J, Jose Fernandez-Seara, Jaime Sieres, Francisco J. Uhia, Theoretical analysis of a CO 2 NH 3 cascade refrigeration system for cooling applications at low temperatures, Applied Thermal Engineering 29 (2009) 1577 1583. 3. Agnew.B, Ameli.S.M, A finite time analysis of a cascade refrigeration system using alternative refrigerants, Applied Thermal Engineering 24 (2004) 2557 2565. 4. Calm. J. M. and Hourahan. G. C, Refrigerant Data Summary, Engineered Systems, 18(11) 74-88, November 2001. 5. Eric B. Rattsa, Steven Brown.J, A generalized analysis for cascading single fluid vapor compression refrigeration cycles using an entropy generation minimization method, International Journal of Refrigeration 23 (2000) 353-365. 6. Getu.H.M, Bansal.P.K, Thermodynamic analysis of an R744 R717 cascade refrigeration system, International journal of refrigeration 31 (2008) 45-54. 7. Jianlin Yu, Hua Zhao, Yanzhong Li, Application of an ejector in auto cascade refrigeration cycle for the performance improvement, International journal of refrigeration 31 (2008) 279-286. 8. JIN Hongguang, LI Bingyu, FENG Zhibing, GAO Lin, HAN Wei, Integrated energy systems based on cascade utilization of energy, Energy Power Eng. China 2007, 1(1) 16 31. 9. Jose Fernandez-Seara, Jaime Sieres, Manuel Vazquez, Compression absorption cascade refrigeration system, Applied Thermal Engineering 26 (2006) 502 512. 90

10. Kim.S.G, Kim.M.S, Experiment and simulation on the performance of an auto cascade refrigeration system using carbon dioxide as a refrigerant, International Journal of Refrigeration 25 (2002) 1093 1101. 11. Marimon.M.A, Arias.J, Lundqvist.P, Bruno.J.C, Coronas.A, Integration of trigeneration in an indirect cascade refrigeration system in Supermarkets, Energy and Buildings 43 (2011) 1427 1434. 12. Mafi.M, Mousavi Naeynian.S.M, Amidpour.M, Exergy analysis of multistage cascade low temperature refrigeration systems used in olefin plants, International journal of refrigeration 32 (2009) 279-294. 13. Murat HOSOZ, Performance Comparison of Single-Stage and Cascade Refrigeration Systems Using R134a as the Working Fluid, Turkish J. Eng. Env. Sci. 29 (2005), 285-296. 14. Omid Rezayan, Ali Behbahaninia, Thermo economic optimization and exergy analysis of CO2/NH3 cascade refrigeration systems, Energy 36 (2011) 888-895. 15. Anirban Sur and Dr.Randip.K.Das, Review on Solar Adsorption Refrigeration Cycle, International Journal of Mechanical Engineering & Technology (IJMET), Volume 1, Issue 1, 2010, pp. 190-226, ISSN Print: 0976 6340, ISSN Online: 0976 6359. 16. Peethambaran K M, Asok Kumar N and John T D, Adsorption Refrigeration System for Automobiles an Experimental Approach, International Journal of Mechanical Engineering & Technology (IJMET), Volume 5, Issue 2, 2014, pp. 122-132, ISSN Print: 0976 6340, ISSN Online: 0976 6359. 91