Power over Ethernet Requirements and Limitations due to the Cabling System



Similar documents
Panduit 28 AWG Patch Cords Installation Guideline

FACT-FINDING STUDY ON POWERING OVER DATA CABLES. Anthony Tassone Principal Engineer Wire & Cable, Commercial & Industrial

Ampacity simulation of a high voltage cable to connecting off shore wind farms

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA

POWER AND VOLTAGE RATING

Power over Ethernet with Panduit Copper Cabling

White Paper. Power over Ethernet Plus Update and Cabling Considerations

Power Rating Simulation of the new QNS connector generation

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Electrical Resistance Resistance (R)

AS COMPETITION PAPER 2007 SOLUTIONS

CHAPTER 2 EXAMPLES AND TABLES

HARTING Ethernet Cabling 8-poles Overview

Temperatures of Bundled Electrical Cables Installed in Bored Holes in Residential Wood Framing

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Keystone Network Isolator with ESD- and Lightning Protection

Electrical Grounding. Appendix C

Insulation Resistance Testing of Low Voltage Cables in the Field

Specification SFTP CAT6 Network Cable 23AWG CU

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES

Sound, Alarm & Security Cable 7

SPI/UL Cable Hea.ng Study AUTHOR- FRED DAWSON THE CHEMOURS COMPANY NEC PANEL 16 PRINCIPAL MEMBER

6 ELECTRICAL PARAMETERS

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Standards Affecting a Premise T-1 Installation

CS4525 Power Calculator

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

Voltage Drop (Single-Phase)

Understanding Shielded Cable

APPLICATION ORIENTED DESIGN OF CABLES

Universal MATE-N-LOK Connectors

Trends and Standards in LAN Cabling Systems Intelligent Buildings

Cable Tray Selection-

PROFIBUS cable. for PROFIBUS-PA and -DP 10/ EN

Electrical Code (NEC) Snake Tray Cable Management Solutions

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

with Component Rating A Simple Perspective

Automation Solutions. LÜTZE LCOS empty housing for Industrial Automation

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

Tri-Rated Flexible PVC Equipment Wire

600V Power Cable 600V SOOW SOW

CONDUCTOR SHORT-CIRCUIT PROTECTION

8-Port PoE Network Switch

Grounding Demystified

How to Choose the Right Cable Category

Short Circuit Current Calculations

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts

Accelerating Light. Copper Cabling Solutions. Category 6A

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

emobility WAGO Leading the Charge

MapIT G2 Infrastructure Management

Copper wire figures. AWG Table

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

Power Dissipation Considerations in High Precision Vishay Sfernice Thin Film Chips Resistors and Arrays (P, PRA etc.) (High Temperature Applications)

AWG: Cat5e: Cat6: Cat6A:

100% EMI Emission Containment

The Do s and Don ts of Pressure Transducers

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Safely Installing, Maintaining and Inspecting Cable Trays

Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Everline Module Application Note: Round LED Module Thermal Management

SELECTION GUIDE INPUT CHARACTERISTICS. Voltage set point accuracy. Overall voltage error. Temperature coefficient of output voltage (slope)

white paper Ferrules: Your Best Insurance Against Costly Connection Failure Executive Summary

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Laying the groundwork for a new level of Power over Ethernet

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

UGVCL/SP/591/11KV HT AB CABLE

1788 Linking Device Specifications

Power over Ethernet (PoE) Explained

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

Ontario Electrical Safety Code 25 th Edition/ 2012

Digital Systems Ribbon Cables I CMPE 650. Ribbon Cables A ribbon cable is any cable having multiple conductors bound together in a flat, wide strip.

SECTION CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

Conductor Sizing and the National Electrical Code

Copper Patch Cords. Impact On Network Performance and Reliability

WHITE PAPER Fire & safety performance standards

SELECTION GUIDE. Nominal Input

Component acceptability for CE product Safety

LevelOne IFE Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

Integration of a fin experiment into the undergraduate heat transfer laboratory

Comparative study for cables and busbars

Ethernet Patch Cord Wiring

Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.

QuickSpecs. HPE OfficeConnect 1410 Switch Series. Overview. HPE OfficeConnect 1410 Switch Series. Models. Key features.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

THE OKONITE COMPANY. Ramsey, New Jersey Fax:

Power Distribution & Terminal Blocks

INSTALLATION INSTRUCTION SPEC. SHEET 7/00. City of New York Calendar #40747 ETL LISTED UNDER U.L. STD LOW VOLTAGE TRACK LIGHTING SYSTEM

PoE+ Extender Switch User's Manual. Rev W

Transcription:

Power over Ethernet Requirements and Limitations due to the Cabling System

Power over Ethernet - Code Requirements and Approvals - the meaning of Cable Rating in NEC and UL 444/CSA 22.2 No. 214 (and any other code) - Requirements to meet the IS 11801 Standard and the TIA Premises Cabling Standard - IEC Cable Requirements: - Attenuation as a function of temperature - Internal heat generation due to current - IEC RJ-45 Connector Requirement - Repetitive un-plugging of a live load circuit

The codes consider three critical Temperatures for cable rating: Conductor surface temperature Insulation or jacket surface temperature Ambient temperature

Background and History : - the rating temperature is all to often confounded with ambient temperature, especially in the user base - the reason for this is a past oversight of all standard organizations. The currents were so low, that in fact the temperature difference, rating temperature minus ambient temperature, was so small that it fell into the temperature range of measurement accuracy so nobody cared!!! - but, most of the deployed cables are RATED to 60 oc conductor surface temperature!!!

NEC Code (2005) Article 310-10 NEC (2005): Temperature limitations of conductors: No conductor shall be used in such a manner that its operating temperature exceeds that designated for the type of insulated conductor involved. In no case shall conductors be associated together in such a way, with respect to type of circuit, the wiring method employed, or the number of conductors, that the limiting temperature of any conductor is exceeded.

NEC Code (2005) Article 310-15 NEC (2005): Ampacity for conductors rated 0 2000 Volts : Gives a formula to calculate the maximum allowed current under Engineering Supervision, taking into account the influence of skin effect and proximity effect.

To cope with the NEC and CEC code, UL444/CSA 22.2 No. 214 rates data grade cables according the temperature the insulation / jacketing material can sustain, going from 60 C o to 250 C o

According to NEC and CEC code data cables are Class CL2 or CL3 powerlimited cables. NEC has no power limits in article 800 for communication cables, but they are understood to be within the Class CL3 limits. Premises o o Cables are rated 60 C (few are 75 C). o That means a maximum of 60 C or 75 oc conductor surface temperature.

The attenuation increase of the cables over temperature is already standardized in IEC 61156 5 and 6 and the corresponding test method will be included in IEC 61156 1. In North America the test method is already included in ASTM D 4566-2005. Limits will be set if it is not yet already done by ICEA (Insulated Cable Engineers Association)

The attenuation increase has to be considered as having an integral impact over the length of the installed cable due to longitudinally varying temperatures. There are no major problems to be expected, as the attenuation improved substantially over the last couple of years. This does not alleviate the problem of overheating due to current loading over the rated temperature due to bundling

Impact of the Current loading The current yields a temperature increase of the conductor. The heat generated inside a cable containing insulated conductors is dissipated into the environment (here assumed to have infinite boundaries) by conduction, convection and radiation through the insulation and the jacket. This can be calculated.

The conductor surface temperature for different cable configurations has been calculated under lenient conditions, i.e. a uniform heat dissipation throughout the cable bundle has been assumed. The current has then been reduced for the center cable or cables by 75 % per surrounding cable layer (also lenient)

Max. Conductor Current [ A ] 1.4 1.2 1 0.8 0.6 0.4 0.2 The Current is 0 [ A ] at any "Rated" Temperature 6 around 1 cable 18 around 1 cable 36 around 1 cable ISO/IEC 11801 Limit 0 55 60 65 70 75 Ambient Temperature [ deg. C ] Maximum conductor current as a function of the ambient temperature for different cable configurations under assumption of different rating temperatures

Max. Conductor Current [ A ] 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 6 around 1 Cable 18 around 1 Cable 36 around 1 Cable ISO/IEC 11801 Limit 0 1 2 3 4 5 "Rated" minus Ambient Temperature [ deg. C ] Maximum conductor current as a function of the difference of rated and ambient temperature

At least for the 18 around 1 and 36 around 1 cable configuration the temperature deviation between ambient and rated temperatures are greater than 1 oc. Hence, it cannot be argued anymore that the difference falls within the measurement accuracy. Furthermore it has to be reiterated that the calculations yield very lenient results, and it has to be anticipated that the real conductor surface temperatures in the center cable are higher.

As a Result : - the Cables for the Power over the Ethernet have to have a higher Temperature Rating than 60 oc. The next higher Class has a Rating of 75 oc. - PoE, even at the actual Current Specification Limit of ISO/IEC 11801 cannot be legally deployed over the installed Base, without having 75 oc rated Cables already in Place.

The Cables close to the Equipment Rooms, and inside the Equipment Rooms are frequently tightly bundled in Numbers vastly exceeding those considered here. Therefore it has to be re-iterated that the here presented Results are based on extremely lenient Conditions.

Cables for the Power over the Ethernet are not specifically covered by any code article. However, the existing installed base can legally not be used for this application. A higher temperature rating is mandatory for such cables

However, the Cable Performance of the installed Base is not the only limiting Factor to be seriously considered. The Connectors themselves represent another Hurdle, especially upon (plugging) and un-plugging under Load. IEC SC 48B, responsible for the Standardization of the RJ-45 Connectors considers towards this Purpose the following Load Circuit Schematics:

Load Circuit Schematics for Contact testing upon Un- plugging, as proposed in IEC SC 48B (RLC values not yet finalized!)

Arcing damage to outlet contact surface Test Plug after 750 cycles with no power applied Test Outlet after 750 cycles with 31 Watts applied Note: Plugging under load has a minor impact on contact deterioration. The un-plugging is the main culprit! Pictures supplied graciously by the Siemon Company Deterioration of the gold plated contact surface due to plugging and un-plugging under load

Conclusion: - Deployment on installed base is legally in most cases impossible - Cables with a temperature rating o of 75 C have to be used - Extreme care has to be taken with respect to the connectivity - Eventually a more resistant connector may have to be selected