SPI/UL Cable Hea.ng Study AUTHOR- FRED DAWSON THE CHEMOURS COMPANY NEC PANEL 16 PRINCIPAL MEMBER
|
|
|
- Florence Todd
- 9 years ago
- Views:
Transcription
1 SPI/UL Cable Hea.ng Study AUTHOR- FRED DAWSON THE CHEMOURS COMPANY NEC PANEL 16 PRINCIPAL MEMBER
2 Overview - Increasing power demands - Increasing power creates a poten2al problem - The Na2onal Electrical Code (NEC) controls installa2ons - Where does the NEC apply - Installa2ons with high cable loading - The problem - A solu2on - SPI/UL Project - Some ini2al findings
3 Increasing Power Demands - Providing power over communica2ons cabling is a rapidly growing area of the industry - Forma2on of IEEE 802.3bt Task Force Current up to 1 amp/pair Power poten2ally up to 100 waqs - Other powering schemes HDBaseT (PoH) poten2ally up to 200 waqs Other proprietary powering systems
4 Increasing Power Creates a Poten.al Concern - Heat Dissipa2on decreases with the number of cables grouped together Smaller wire gauges generally produce more heat Raceway (conduit) selec2on and fill ra2o can affect heat dissipa2on
5 The NEC Controls Installa.on - TIA and other standards as well as manufacturers warran2es provide guidance on installa2on - The NEC (Na2onal Electrical Code) is law where it is adopted Installa2ons are based on the requirements of the NEC Installa2ons are inspected based on the requirements of the NEC - The NEC controls copper communica2ons/data cabling in two primary places Ar2cle 725 Class1, Class 2 and Class 3 Remote- control, Signaling and Power Limited Circuits Chapter 8 Communica2ons Systems - The NEC does not have any specific provisions for powering of communica:ons equipment Most applica2ons fall under Ar2cle 725 Class 2 Power Limited Circuits Most communica2ons applica2ons have no guidance. Most AHJ s will reference Ar2cle 725 as the applica2ons are similar
6 NEC Ar.cle Class 2 Power Limited Circuits have the following limits from Table 11(B) Max 100 VA Max current =1.67 amps - Ar2cle (3) Temperature Limita2on of Conductors. No conductor shall be used in such a manner that its opera2ng temperature exceeds that designated for the type of insulated conductor involved. - Listed informa2on technology equipment limited- power circuits references UL UL interpreta2on of UL Up to 100 waqs per circuit allowable Up to 400 waqs possible with 4 pair twisted pair cable.
7 Where does the NEC apply
8 Installa.ons with high cable loading
9 Installa.ons with high cable loading
10 The Problem - The NEC has no guidelines for powering over communica2ons cabling as it is currently being implemented - Many exis2ng cabling installa2ons aren t designed to manage the heat from higher power levels - The poten:al exists for cable overhea:ng with: Previously installed cabling plants when higher (allowable) currents or power is used by newly installed higher power devices New installa2ons that don t make provision for hea2ng during installa2on - The overhea:ng of cables is a safety concern for the NEC
11 A Solu.on - Provide a solu:on before someone else does - Make changes to the NEC to provide guidance on the safe applica2on of powering over communica2ons cables SPI submiqed a number of PI s to enable powering over communica2ons cabling in Ar2cles 725 and 840 and to supplement exis2ng ampacity tables Data is needed to support the PI s The SPI/UL study was ini2ated to provide data to support and op2mize the PI s - The PI s specifically provide for the use of exis:ng and newly installed Category cable - One PI proposes a listed and labeled cable that can be used for most applica2ons without concern This may have some restric:ons
12 SPI/UL Project - SPI manages the study at UL - Most communica2ons cabling manufacturers were approached to par2cipate in the study - All members of CCCA (Communica2ons Cabling and Connec2vity Associa2on) were invited to join the study. - Phase 1 of the project is developing data to support the SPI PI s that enable the safe use of exis2ng and new installa2ons of powered communica2ons cabling within the NEC
13 Some Ini.al Findings
14 Ini.al findings from Phase 1 as of mid June Larger bundles get hoqer with less current applied Enclosed cables get hoqer Cables exceed 60 o C at current levels well below that permiqed by the NEC Class 2 tables Cable failures occurred at current levels well below that permiqed by the NEC Class 2 tables In some configura2ons, cable failures occurred at current levels permiqed by UL (1.3 amperes) and even at the lower current used by high Power Source Modules (1 ampere)
FACT-FINDING STUDY ON POWERING OVER DATA CABLES. Anthony Tassone Principal Engineer Wire & Cable, Commercial & Industrial
FACT-FINDING STUDY ON POWERING OVER DATA CABLES Anthony Tassone Principal Engineer Wire & Cable, Commercial & Industrial With the increased use of remotely powered devices and increasing levels of power
UAB Cyber Security Ini1a1ve
UAB Cyber Security Ini1a1ve Purpose of the Cyber Security Ini1a1ve? To provide a secure Compu1ng Environment Individual Mechanisms Single Source for Inventory and Asset Management Current Repor1ng Environment
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Public Safety VoIP + Bridging
Public Safety VoIP + Bridging Anna Paulson Electronics Engineer Public Safety Communica=ons Research Program [email protected] 1 2 Department of Homeland Security Office for Interoperability and
Power over Ethernet Requirements and Limitations due to the Cabling System
Power over Ethernet Requirements and Limitations due to the Cabling System Power over Ethernet - Code Requirements and Approvals - the meaning of Cable Rating in NEC and UL 444/CSA 22.2 No. 214 (and any
Electrical Code (NEC) Snake Tray Cable Management Solutions
Cable Pathway Use and Selection and the National Electrical Code (NEC) By Eric J. Sadler, BSME MIT Snake Tray Cable Management Solutions References: All references to the NEC in this presentation are taken
CONDUCTOR SHORT-CIRCUIT PROTECTION
CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
IT Change Management Process Training
IT Change Management Process Training Before you begin: This course was prepared for all IT professionals with the goal of promo9ng awareness of the process. Those taking this course will have varied knowledge
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
Electrical Drawings - Table of Contents
Electrical Drawings - Table of Contents E1.0 Lighting Plan E1.1 Power Plan E2.0 Electrical Specifications E2.1 Electrical Specifications E3.0 Panel Schedule E3.1 Load Summary 1 2 1 Panel Schedule LP1
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
Case Study. The SACM Journey at the Ontario Government
Case Study The SACM Journey at the Ontario Government Agenda Today s Objec=ves The Need for SACM Our SACM Journey Scope and Governance Process Ac=vi=es Key Process Roles Training and Measurement Lessons
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
Power over Ethernet with Panduit Copper Cabling
Power over Ethernet with Panduit Copper Cabling Introduction Power over Ethernet (PoE) is a common way to reduce installation costs and time by allowing power and data onto a single twisted-pair cable.
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
VoIP Security How to prevent eavesdropping on VoIP conversa8ons. Dmitry Dessiatnikov
VoIP Security How to prevent eavesdropping on VoIP conversa8ons Dmitry Dessiatnikov DISCLAIMER All informa8on in this presenta8on is provided for informa8on purposes only and in no event shall Security
Cloud Compu)ng in Educa)on and Research
Cloud Compu)ng in Educa)on and Research Dr. Wajdi Loua) Sfax University, Tunisia ESPRIT - December 2014 04/12/14 1 Outline Challenges in Educa)on and Research SaaS, PaaS and IaaS for Educa)on and Research
Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
CSER & emerge Consor.a EHR Working Group Collabora.on on Display and Storage of Gene.c Informa.on in Electronic Health Records
electronic Medical Records and Genomics CSER & emerge Consor.a EHR Working Group Collabora.on on Display and Storage of Gene.c Informa.on in Electronic Health Records Brian Shirts, MD, PhD University of
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
HARTING Ethernet Cabling 8-poles Overview
Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs
Request for Proposals for Photovoltaic System Installation
Request for Proposals for Photovoltaic System Installation Presented by: Prepared by: Location: Contact: Date: Capitol Hill Housing Foundation Bonneville Environmental Foundation, Renewable Energy Group
BASIC FIRE ALARM TRAINING
BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate
benefit of virtualiza/on? Virtualiza/on An interpreter may not work! Requirements for Virtualiza/on 1/06/15 Which of the following is not a poten/al
1/06/15 Benefits of virtualiza/on Virtualiza/on Which of the following is not a poten/al benefit of virtualiza/on? A. cost effec/ve B. applica/on migra/on is easy C. improve applica/on performance D. run
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Specification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
NFPA 70E: What Contractors and Employers Need to Know
2014 NFPA Conference & Expo NFPA 70E: What Contractors and Employers Need to Know Presented by: Michael J. Johnston Execu
MOBILE HOME SERVICE REQUIREMENTS GAS
ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
Voltage Drop (Single-Phase)
Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
Design Guidelines for PoE Based Security Systems. Carlos Carle, P.E. SignaMax Systems, Inc.
Design Guidelines for PoE Based Security Systems Carlos Carle, P.E. SignaMax Systems, Inc. What is PoE? Power Over Ethernet or PoE Technology describes a system to safely transfer electrical power, along
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
Kaseya Fundamentals Workshop DAY THREE. Developed by Kaseya University. Powered by IT Scholars
Kaseya Fundamentals Workshop DAY THREE Developed by Kaseya University Powered by IT Scholars Kaseya Version 6.5 Last updated March, 2014 Day Two Overview Day Two Lab Review Patch Management Configura;on
DPS Preliminary Review: Verizon FIOS Customer Premises Installation NEC Compliance Issues
DPS Preliminary Review: Verizon FIOS Customer Premises Installation NEC Compliance Issues OVERVIEW A key aspect of providing telecommunications services is the provision of those services in a safe and
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
How Much Voltage Drop Is Acceptable?
How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022. Train now for affordable Electrician careers and get wired for success. Residential Electrician Diploma Program
Poten&al Impact of FDA Regula&on of EMRs. October 27, 2010
Poten&al Impact of FDA Regula&on of EMRs October 27, 2010 Agenda The case for regula&ng Impact on manufacturers Impact on providers Recommenda&ons and best prac&ces 2 A Medical Device Is an instrument,
Building Cables and Wires
Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
Cable Tray Selection-
Cable Selection- For allowable cable types see the Appendix page A-9. The following guidelines are based on the 2002 National Electrical Code, Article 392. I) Number of Multiconductor Cables rated 2000
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance
Wire types and sizes
Wire types and sizes This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
The Quality Connection. High Performance Cable Solutions for the World of Semiconductors
The Quality Connection High Performance Cable Solutions for the World of Semiconductors 2 Total Flexibility for Applications with the Toughest Requirements LEONI is your long-term, reliable partner supplying
The Quality Connection. High Performance Cable Solutions for the World of Semiconductors
The Quality Connection High Performance Cable Solutions for the World of Semiconductors 2 Total Flexibility for Applications with the Toughest Requirements LEONI is your long-term, reliable partner supplying
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
Help Framework. Ticket Management Ticket Resolu/on Communica/ons. Ticket Assignment Follow up Customer - communica/on System updates Delay management
Help for JD Edwards Our Help Framework Ticket qualifica/on Ticket crea/on Ticket Rou/ng Closures L1 issues Resolu/on KG SOPs Co- ordinate Ticket Assignment Follow up Customer - communica/on System updates
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems
White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems Originally ratified by IEEE in 1999 and 2003 respectively, gigabit Ethernet (1000BASE-T) and power over Ethernet
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
Parallel Redundant Uninterruptible Power Supply
9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------
SECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines
PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
Safety instructions VEGADIS DIS81.CEIA/V****
Safety instructions VEGADIS DIS81.CEIA/V**** CSA 14.2662675 Ex d IIC T6 T1 Gb 0044 Document ID: 48926 Contents 1 Area of applicability... 3 2 General information... 3 3 Technical data... 3 4 Application
QSE-CI-NWK-E Control Interface
QSE-CI-NWK-E Control Interface 369373e 1 04.05.16 The QSE-CI-NWK-E is a versatile integration access point for Lutron QS-based systems. Through either RS232 or TCP / IP over Ethernet, third-party devices
Proposed Task Group: Electrical Cable and Condition Monitoring Codes and Standards for Nuclear Power Plants
Proposed Task Group: Electrical Cable and Condition Monitoring Codes and Standards for Nuclear Power Plants Dr. Stephanie Watson Engineering Laboratory, NIST Cables in NPPs Categories Medium voltage power
HMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
City of San Diego Residential Photovoltaic Systems Inspection Guidelines
City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes
Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC
Mike Holt s Illustrated Guide to NEC Requirements for Generators and Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated Guides
Journeyman Class Schedule
Journeyman Class Schedule San Diego Electrical Training Center Fall 2015 semester 4675 Viewridge Avenue Vol. 2015-3 tri-annual San Diego, CA 92123-1644 The classes listed in this schedule are designed