s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective devices are used for personnel, material and fire protection, as well as for protection against direct contact. This protects human lives and prevents electrical fires. The new model for more comfort The improved design of the residual current protective devices with a separate switch position indicator and a handle imprint provides greater safety and ease-of-use. They are also suitable for the quick and easy mounting of additional components such as auxiliary switches, fault signal contacts, shunt trips and undervoltage releases. Easy and safe installation The new 5SV residual current operated circuit breakers can be released quickly and easily from the bus-mounted assembly with the help of the latching slide no other tool is needed. Highlights 7 More convenience and safety through an improved design 7 Uniform and comprehensive additional components as well as a wide range of accessories 7 Consistent busbar concept throughout the residual current protective devices range 7 Replacement of a device from the busbar-mounted assembly requires no tools Answers for infrastructure and cities.
Residual Current Protective Devices Introduction Overview Residual current protective devices are used in all supply systems up to 240/415 V AC. Devices of type AC trip in the event of sinusoidal AC residual currents, type A also trips in the event of pulsating DC residual currents. RCCBs with a rated residual current of maximum 30 ma are used for personnel, material and fire protection, as well as for protection against direct contact. RCCBs with a rated residual current of 10 ma are primarily used in areas that represent an increased risk for personnel. Since the introduction of DIN VDE 0100-410, all socket outlet current circuits up to 20 A must also be fitted with residual current protective devices with a rated residual current of max. 30 ma. This also applies to outdoor electrical circuits up to 32 A for the connection of portable equipment. Devices with a rated residual current of maximum 300 ma are used as preventive fire protection in case of insulation faults. RCCBs with a rated residual current of 100 ma are primarily used outside Europe. Benefits Instantaneous type A devices have a surge current withstand capability with current waveform 8/20 s of more than 1 ka. Auxiliary switches, fault signal contacts, undervoltage releases or shunt trips are also available as additional components. By means of internal contacts, effective touch protection is provided when grasping and manually operating the latching slide. To facilitate entry of pin busbars with connection cables up to 35 mm², the devices are equipped with rectangular terminals for the accommodation of funnel-shaped cable entries. By means of standardized clearances of the terminals in modular width dimensions, the RCCBs and MCBs can be optionally connected to busbars on the top or on the bottom. Technical specifications Instantaneous SIGRES Super resistant Selective Standards IEC/EN 61008-1 (VDE 0664-10); IEC/EN 61008-2-1 (VDE 0664-11); IEC/EN 61543 (VDE 0664-30); IEC/EN 62423 (VDE 0664-40) Surge current withstand capability Type A with current waveform 8/20 µs Acc. to EN 60060-2 ka > 1 > 3 > 5 (VDE 0432-2) Type F with current waveform 8/20 µs Acc. to EN 60060-2 ka -- -- > 3 -- (VDE 0432-2) Minimum operational voltage for test function operation V AC 100 Test cycles: Insulation coordination Overvoltage category III Pollution degree 2 5SV terminal conductor cross-sections 1 conductor -Solid( 10 mm 2 ) / stranded ( 16 mm 2 ) mm 2 1.5... 50 - Finely stranded with non-insulated end sleeve mm 2 1.5... 25 - Finely stranded with insulated end sleeve mm 2 1.5... 25 - Finely stranded without end sleeve mm 2 2.5... 50 2-wire, same cross-section, same conductor type -Solid( 10 mm 2 ) / stranded ( 16 mm 2 ) mm 2 0.75... 10 - Finely stranded with non-insulated end sleeve mm 2 0.75... 4 - Finely stranded with insulated end sleeve mm 2 0.75... 4 - Finely stranded without end sleeve mm 2 1... 4 1-wire + busbar (pin thickness 1.5 mm) -Solid( 10 mm 2 ) / stranded ( 16 mm 2 ) mm 2 10... 25 - Finely stranded with non-insulated end sleeve mm 2 6... 25 - Finely stranded with insulated end sleeve mm 2 6... 16 Terminal tightening torque Up to I n 80 A Nm 2.5... 3.0 At I n = 100 A, 125 A Nm 3.0... 3.5 Mains connection Top or bottom Bottom Top or bottom Mounting position (on a standard mounting rail) Any Degree of protection Acc. to EN 60529 IP20, if the distribution board is installed, with connected conductors (VDE 0470-1) Touch protection Acc. to EN 50274 Finger and back-of-hand safe (VDE 0660-514) Service life Average number of switching cycles > 10000 Test cycle acc. to IEC/EN 61008 Storage temperature C -40... +75 Ambient temperature C -25... +45, marked with -25 Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 C; 95 % rel. air humidity) CFC and silicone-free Yes 2 Siemens 2013
Residual Current Protective Devices 5SV3 RCCBs, Type A Selection and ordering data (Type A) -25 Rated residual current Rated current Max. permissible short-circuit back-up fuse Mounting width DT Article No. Price per PU PU (UNIT, SET, M) PS*/ P. unit PG Weight per PU approx. I n I n ma A A MW kg RCCBs, type A, instantaneous 1P+N; 125... 230 V AC; 50 Hz 10 000 10 16 63 2 5SV3111-6 1 1 unit 011 0.200 30 16 63 2 5SV3311-6 1 1 unit 011 0.204 25 5SV3312-6 1 1 unit 011 0.204 40 5SV3314-6 1 1 unit 011 0.204 63 100 5SV3316-6 1 1 unit 011 0.200 80 5SV3317-6 1 1 unit 011 0.200 100 25 63 2 5SV3412-6 1 1 unit 011 0.197 40 5SV3414-6 1 1 unit 011 0.197 63 100 5SV3416-6 1 1 unit 011 0.200 80 5SV3417-6 1 1 unit 011 0.200 300 25 63 2 5SV3612-6 1 1 unit 011 0.196 40 5SV3614-6 1 1 unit 011 0.194 63 100 5SV3616-6 1 1 unit 011 0.200 80 5SV3617-6 1 1 unit 011 0.200 3P+N; 230... 400 V AC; 50 Hz 30 25 100 4 5SV3342-6 1 1 unit 011 0.350 40 5SV3344-6 1 1 unit 011 0.350 63 5SV3346-6 1 1 unit 011 0.398 80 5SV3347-6 1 1 unit 011 0.399 100 25 100 4 5SV3442-6 1 1 unit 011 0.350 40 5SV3444-6 1 1 unit 011 0.350 63 5SV3446-6 1 1 unit 011 0.350 80 5SV3447-6 1 1 unit 011 0.350 300 25 100 4 5SV3642-6 1 1 unit 011 0.350 40 5SV3644-6 1 1 unit 011 0.350 63 5SV3646-6 1 1 unit 011 0.358 80 5SV3647-6 1 1 unit 011 0.358 500 25 100 4 5SV3742-6 1 1 unit 011 0.350 40 5SV3744-6 1 1 unit 011 0.350 63 5SV3746-6 1 1 unit 011 0.356 80 5SV3747-6 1 1 unit 011 0.356 * You can order this quantity or a multiple thereof. Siemens 2013 3
Residual Current Protective Devices 5SV4 RCCBs, Type AC Selection and ordering data (Type AC) -25 Rated residual current I n I n Rated current Max. permissible short-circuit back-up fuse Mounting width DT Article No. Price per PU PU (UNIT, SET, M) PS*/ P. unit PG Weight per PU approx. ma A A MW kg RCCBs, type AC, instantaneous 1P+N; 125... 230 V AC; 50 Hz 10 000 10 16 63 2 5SV4111-0 1 1 unit 012 0.200 30 16 63 2 5SV4311-0 1 1 unit 012 0.202 25 5SV4312-0 1 1 unit 012 0.202 40 5SV4314-0 1 1 unit 012 0.203 63 100 5SV4316-0 1 1 unit 012 0.200 80 5SV4317-0 1 1 unit 012 0.200 100 25 63 2 5SV4412-0 1 1 unit 012 0.197 40 5SV4414-0 1 1 unit 012 0.197 63 100 5SV4416-0 1 1 unit 012 0.200 80 5SV4417-0 1 1 unit 012 0.200 300 25 63 2 5SV4612-0 1 1 unit 012 0.196 40 5SV4614-0 1 1 unit 012 0.194 63 100 5SV4616-0 1 1 unit 012 0.200 80 5SV4617-0 1 1 unit 012 0.200 3P+N; 230... 400 V AC; 50 Hz 30 25 100 4 5SV4342-0 1 1 unit 012 0.350 40 5SV4344-0 1 1 unit 012 0.350 63 5SV4346-0 1 1 unit 012 0.397 80 5SV4347-0 1 1 unit 012 0.399 100 25 100 4 5SV4442-0 1 1 unit 012 0.350 40 5SV4444-0 1 1 unit 012 0.350 63 5SV4446-0 1 1 unit 012 0.350 80 5SV4447-0 1 1 unit 012 0.350 300 25 100 4 5SV4642-0 1 1 unit 012 0.350 40 5SV4644-0 1 1 unit 012 0.350 63 5SV4646-0 1 1 unit 012 0.358 80 5SV4647-0 1 1 unit 012 0.358 500 25 100 4 5SV4742-0 1 1 unit 012 0.350 40 5SV4744-0 1 1 unit 012 0.350 63 5SV4746-0 1 1 unit 012 0.356 80 5SV4747-0 1 1 unit 012 0.356 4 Siemens 2013 * You can order this quantity or a multiple thereof.
Residual Current Protective Devices 5SV4 RCCBs, Type AC Dimensional drawings 35,8 71 64 43,9 20 71,8 71 64 43,9 20 89,8 45,15 45,15 6,2 I201_18655 89,8 6,2 I201_18656 RCCBs, type A and type AC 1P+N, 2 MW RCCBs, type A and type AC 3P+N, 4 MW Circuit diagrams Graphic symbols 1 N 1 3 5 N 2 N I201_13636 2 4 6 N I201_13637 1P+N 3P+N Siemens 2013 5
Appendix Siemens AG 2013 Article No. index incl. export markings Overview Article No. Page Export markings 5SV3 ECCN 5SV3111-6 3 EAR99H N 5SV3311-6 3 N N 5SV3312-6 3 N N 5SV3314-6 3 N N 5SV3316-6 3 N N 5SV3317-6 3 N N 5SV3412-6 3 EAR99H N 5SV3414-6 3 EAR99H N 5SV3416-6 3 EAR99H N 5SV3417-6 3 EAR99H N 5SV3612-6 3 N N 5SV3614-6 3 N N 5SV3616-6 3 EAR99H N 5SV3617-6 3 EAR99H N 5SV3342-6 3 N N 5SV3344-6 3 N N 5SV3346-6 3 N N 5SV3347-6 3 N N 5SV3442-6 3 N N 5SV3444-6 3 N N 5SV3446-6 3 N N 5SV3447-6 3 N N 5SV3642-6 3 N N 5SV3644-6 3 N N 5SV3646-6 3 N N 5SV3647-6 3 N N 5SV3742-6 3 EAR99H N 5SV3744-6 3 EAR99H N 5SV3746-6 3 EAR99H N 5SV3747-6 3 EAR99H N 5SV4 5SV4111-0 4 EAR99H N 5SV4311-0 4 N N 5SV4312-0 4 N N 5SV4314-0 4 N N 5SV4316-0 4 N N 5SV4317-0 4 N N 5SV4412-0 4 EAR99H N 5SV4414-0 4 EAR99H N 5SV4416-0 4 EAR99H N 5SV4417-0 4 EAR99H N 5SV4612-0 4 N N 5SV4614-0 4 N N 5SV4616-0 4 EAR99H N 5SV4617-0 4 EAR99H N 5SV4342-0 4 N N 5SV4344-0 4 N N 5SV4346-0 4 N N 5SV4347-0 4 N N 5SV4442-0 4 N N 5SV4444-0 4 N N 5SV4446-0 4 N N 5SV4447-0 4 N N 5SV4642-0 4 N N 5SV4644-0 4 N N AL Article No. Page Export markings ECCN AL 5SV4646-0 4 N N 5SV4647-0 4 N N 5SV4742-0 4 EAR99H N 5SV4744-0 4 EAR99H N 5SV4746-0 4 EAR99H N 5SV4747-0 4 EAR99H N A product's export markings are updated daily at www.siemens.com/industrymall. 6 Siemens 2013
Appendix Conditions of sale and delivery Overview By using this catalog you can acquire hardware and software products described therein from Siemens AG subject to the following terms. Please note! The scope, the quality and the conditions for supplies and services, including software products, by any Siemens entity having a registered office outside of Germany, shall be subject exclusively to the General Terms and Conditions of the respective Siemens entity. The following terms apply exclusively for orders placed with Siemens AG. For customers with a seat or registered office in Germany The General Terms of Payment as well as the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry shall apply. For software products, the General License Conditions for Software Products for Automation and Drives for Customers with a Seat or registered Office in Germany shall apply. For customers with a seat or registered office outside of Germany The General Terms of Payment as well as the General Conditions for Supplies of Siemens, Automation and Drives for Customers with a Seat or registered Office outside of Germany shall apply. For software products, the General License Conditions for Software Products for Automation and Drives for Customers with a Seat or registered Office outside of Germany shall apply. General The dimensions are in mm. In Germany, according to the German law on units in measuring technology, data in inches only apply to devices for export. Illustrations are not binding. Insofar as there are no remarks on the corresponding pages, - especially with regard to data, dimensions and weights given - these are subject to change without prior notice. The prices are in (Euro) ex works, exclusive packaging. The sales tax (value added tax) is not included in the prices. It shall be debited separately at the respective rate according to the applicable legal regulations. Prices are subject to change without prior notice. We will debit the prices valid at the time of delivery. Surcharges will be added to the prices of products that contain silver, copper, aluminum, lead and/or gold if the respective basic official prices for these metals are exceeded. These surcharges will be determined based on the official price and the metal factor of the respective product. The surcharge will be calculated on the basis of the official price on the day prior to receipt of the order or prior to the release order. The metal factor determines the official price as of which the metal surcharges are charged and the calculation method used. The metal factor, provided it is relevant, is included with the price information of the respective products. You will find an exact explanation of the metal factor the text of the Comprehensive Terms and Conditions of Sale and Delivery of Siemens AG in the Internet under www.siemens.com/automation/salesmaterial-as/catalog/en /terms_of_trade_en.pdf Export regulations Siemens shall not be obligated to fulfill this agreement if such fulfillment is prevented by any impediments arising out of national or international foreign trade or customs requirements or any embargoes or other sanctions. If Purchaser transfers goods (hardware and/ or software and/ or technology as well as corresponding documentation, regardless of the mode of provision) delivered by Siemens or works and services (including all kinds of technical support) performed by Siemens to a third party worldwide, Purchaser shall comply with all applicable national and international (re-) export control regulations. In any event Purchaser shall comply with the (re-) export control regulations of the Federal Republic of Germany, of the European Union and of the United States of America. If required to conduct export control checks, Purchaser, upon request by Siemens, shall promptly provide Siemens with all information pertaining to particular end customer, destination and intended use of goods, works and services provided by Siemens, as well as any export control restrictions existing. Purchaser shall indemnify and hold harmless Siemens from and against any claim, proceeding, action, fine, loss, cost and damages arising out of or relating to any noncompliance with export control regulations by Purchaser, and Purchaser shall compensate Siemens for all losses and expenses resulting thereof, unless such noncompliance was not caused by fault of the Purchaser. This provision does not imply a change in burden of proof. The products listed in this catalog / price list may be subject to European / German and/or US export regulations. Therefore, any export requiring a license is subject to approval by the competent authorities. According to current provisions, the following export regulations must be observed with respect to the products featured in this catalog / price list: AL ECCN Number of the German Export List Products marked other than N require an export license. In the case of software products, the export designations of the relevant data medium must also be generally adhered to. Goods labeled with an AL not equal to N are subject to European or German export authorization when being exported out of the EU. Export Control Classification Number Products marked other than N are subject to a reexport license to specific countries. In the case of software products, the export designations of the relevant data medium must also be generally adhered to. Goods labeled with ECCN not equal to N are subject to US re-export authorization. Even without a label, or with label "AL:N" or "ECCN:N", authorization may be required due to the final end-use and destination for which the goods are to be used. In addition, you can preview the export designations via our "Industry Mall" online catalog system in the respective product description. The deciding factors are the AL or ECCN export authorization indicated on order confirmations, delivery notes and invoices. Errors excepted and subject to change without prior notice. Siemens 2013 7
Siemens AG Infrastructure & Cities Sector Low and Medium Voltage Division Low Voltage & Products Postfach 10 09 53 93009 REGENSBURG GERMANY Subject to change without prior notice PDF only: (E86060-P8280-E020-A1-7600) MP.R3.LP.0000.00.3.09 PI 1013 En / valid until 09/14 Produced in Germany Siemens AG 2013 The information provided in this catalog contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners. www.siemens.com/sentron