BUILDING DYNAMICS, LLC

Similar documents
DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

Water should be removed as soon as possible once the safety of the structure has been verified.

Case Studies. Disaster Recovery Restoration Remediation Decontamination

Water Incursion Standard Operating Procedure

Old Dominion University Mold Management Plan

Mold Response and Remediation Plan

Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project

MOLD RESPONSE AND REMEDIATION PLAN

Guidelines for Mold Remediation (Removal)

Core & Shell Construction. Rules and Regulations

WATER DAMAGE INVESTIGATION. Massachusetts Gaming Commission 101 Federal Street Boston, Massachusetts

University of Vermont

TO TEST OR. NOT TO TEST Redefining the Role of Third-party Consultants CLEANING & RESTORATION A PUBLICATION OF THE RESTORATION INDUSTRY ASSOCIATION

Building and Grounds Maintenance Checklist

INDOOR AIR QUALITY ASSESSMENT MOLD INVESTIGATION. Department Of Children and Family 810 Memorial Drive Cambridge, Massachusetts

APPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details)

UNIVERSITY OF TOLEDO

March Get The Mold Out: Mold Clean-Up Guidance for Residences. Introduction

Now that Your Building Experienced Water Damage What Must You and Your Water Damage Restoration Contractor Agree On?

Controlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY

Mold and Mildew Mold and mildew can be detected by sight, smell and touch.

Radford University. Indoor Air Quality Management Plan

Coastside County Water District Board of Directors

How To Restore A House After A Fire

<< Previous Home Next >>

Get The Mold Out: Mold Clean-Up Guidance for Residences. Introduction

<< Previous Home Next >>

INDOOR WATER INTRUSION (INDOOR WATER LINE BREAKS) Region 8 Sustainability & Environmental Management System

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

MOLD REMEDIATION KEY STEPS

Mold Management Plan Operations & Maintenance

Signature on File For Custodial Supervisor Use Only

Restoring Peace of Mind.SM

Disasters Happen. We take care of them all.

NORMI Professional Guidance for DIY Projects

Government Commercial Residential. CA License # NV License #

MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS

MOLD REMEDIATION PROCEDURES

ASBESTOS MANAGEMENT PROGRAM

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

Clean Water: Supply side potable water, not wastewater. Gray Water/Sewage: Wastewater originating from a drain (sink, toilet, urinal).

IUB Water Damage Restoration Guideline

How to Reduce Your Exposure to Chemicals at Home, Work, and Play

How To Prevent And Manage A Flood And Mold

Queen's University Environmental Health & Safety. 1.0 Introduction

FIRE DAMAGE RESTORATION. Fire Damage Restoration in Colorado Springs, CO. Serving El Paso County and surrounding areas

UNIVERSITY OF TOLEDO

University of Nevada, Reno Facilities Services Department STANDARD OPERATING PROCEDURE. Facilities Maintenance Services

Specification. Indoor Air Quality Management

WATER DAMAGE FOLLOW-UP INVESTIGATION. Massachusetts Department of Children and Families 33 East Merrimack Street Lowell, Massachusetts

Integrating Healthy Housing Considerations into Weatherization Inspections. Jim LaRue

UI Procedures for Asbestos Management

EVERYONE'S RESPONSIBILITY

CONTROL METHODS. There are five ways to control the release of asbestos fibers:

POSITION DESCRIPTION NORTHFIELD PUBLIC SCHOOLS September 2007

The Local Government Purchasing Cooperative

Wellesley College Mold Management Program March 2009

STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION

DIVISION 1 THIRD FLOOR COUNTY ATTORNEY. Remediation Plan Remove approximately 6 SF of mold impacted drywall Remove all carpeting in hatched.

Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals

Fire - Smoke - Soda Blasting

Managing Water Infiltration into Buildings. Water Damage Check List

ASBESTOS SCIENCE TECHNOLOGIES, INC.

Saxe Middle School Auditorium Renovation February 4, 2015

SCHOOL DISTRICT 70 - ALBERNI JOB DESCRIPTION

Facilities Maintenance Standards rev

Polygon & Property Damage Restoration

Mold In Your Home and at Work

Response to Water Intrusion and Mold/Microbial Growth

ASBESTOS AWARENESS IN THE WORKPLACE. This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation.

Quality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Houston ISD Deadly Middle School RR Renovations- Phase 3 VCS Architects, LLC

STATEMENT OF WORK (SOW) 2. Contract Title. HEPA Supply/Exhaust fans for Clean room USP 797 Compliance

Mold Prevention and Remediation Program

Number Northern Arizona University Facility Services Section Page. Effective April 1, 2011

City of Goldsboro. After the Fire. Fire Department. 204 South Center Street, Goldsboro, NC (919)

Guidelines for Cleaning Staff on Managing Mould Growth in State Buildings

#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check

Name Of Occupancy Date. Yes No Describe

WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts

Invesco Advisers, Inc. Minimum Vendor / Contractor Insurance Requirements and Risk Category Schedule

HUD Healthy Homes Grantee Program Sample Program Evaluation Plan

ASBESTOS CONTAINING MATERIALS OPERATIONS & MAINTENANCE PLAN 2015

Gramercy Place Condo Association, Inc.

SECTION HVAC AIR-DISTRIBUTION SYSTEM CLEANING

Walkthrough Inspection Checklist

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS

It is a violation of U.S. Federal Law to use this product in a manner inconsistent with its labeling.

WATER DAMAGE/MOLD INVESTIGATION. Massachusetts Department of Developmental Services 68 North Main Street Carver, Massachusetts

PAST PERFROMANCE. Post testing was performed in all areas to ensure the building was safe for all visitors and employees.

Oakland Unified San Jose Unified Stanford University Santa Ana Unified Newhall Unified Clovis Unified Merced Union High School Grossmont Union High

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

Asbestos WHAT TO DO? Studies of people who were exposed to high levels of asbestos in factories and shipyards, are at increased risk of:

British Columbia Institute of Technology. BCIT Safety Manual ASBESTOS MANAGEMENT

Mold Basics. Why is mold growing in my home?

WATER DAMAGE RECOVERY G U I D E

Every insurance claim is different but with Rapid Recovery Services the outcomes are all the same. Insured Satisfaction.

PLUMMER ELEMENTARY SCHOOL

Mould Mould A Basic Guide

Planning For Future Emergencies. Presented by: Rudi Suminski Director of Consulting Services

Transcription:

BUILDING DYNAMICS, LLC www.building-dynamics.com INDUSTRIAL HYGIENE 1216 Ashton Road Ashton, MD 20861 240.899.6926 (mobile) elight@building-dynamics.com HVAC ENGINEERING 703.963.0824 (mobile) jbailey@building-dynamics.com GLENWOOD MIDDLE SCHOOL FIRE RESTORATION (report) January 20, 2016 Prepared by: Prepared for: Ed Light, CIH Howard County Public School System 1

1.0 Executive Summary On January 5, 2016, an electrical fire occurred at Glenwood Middle School (GMS) and smoke spread through a portion of the building. No classrooms were affected. Smoke damage was limited to the Boiler Room, Custodial Office, Kitchen, Cafeteria, Gym, Boys Locker room, Main Office (back hall, rest room and work room only) and the corridors adjacent to the cafeteria. The fire generated contaminants typical for most home and building fires. Elimination of combustion residues was completed following procedures consistent with Restoration Industry Association guidance. Building Dynamics, LLC cleared GMS for re-occupancy based on surface streak testing per ASTM Standard D6602 and elimination of soot odor. As part of this report, next steps are included. 2.0 Introduction At approximately 11:20AM on January 5, 2016, an electrical fire occurred at Glenwood Middle School (GMS) and smoke spread through a portion of the building. Students and staff were immediately evacuated and the fire extinguished. Classes were relocated pending restoration of smoke damage and power. HCPSS had a restoration contractor onsite within a few hours to initiate assessment, containment, disposal of damaged materials and cleaning. HCPSS brought Building Dynamics, LLC onsite the afternoon of the fire. BDL was tasked with: 1. Identify areas contaminated by fire residue (soot, ash, char) 2. Recommend remedial procedures. 3. Recommend containment measures to isolate affected areas from the rest of the building. 4. Evaluate impact on HVAC systems. 5. Periodically inspect building to ensure safety of visitors to non-affected areas and confirm cleanup and containment procedures are followed. 6. At completion of work, re-assess the building and clear areas for re-occupancy when they are fully restored and there is no exposure to fire residue. Primary objectives of smoke damage restoration are to eliminate surface residues of combustion products (i.e., soot) and smoke odor. There are no governmental standards health criteria for smoke damage restoration. Guidance is provided by, RIA Guidelines for Fire and Smoke Damage Repair (Restoration Industry Association, 2007). A procedure for clearance testing (surface streak testing) is included in ASTM Standard D6602. 3.0 Smoke Damage Assessment of damage was performed consistent with RIA Guidelines. Fire residue was identified by surface wipe testing per ASTM Standard D6602. Eye witnesses were interviewed as to where smoke was observed. Potential pathways for smoke distribution were identified based on building construction and HVAC designs. Areas with detectable smoke odor were also identified. Based on this assessment, smoke damage was limited to: Boiler room Custodial office Kitchen Cafeteria Gym Boys locker room Main Office back hall, rest room work room Corridors adjacent to cafeteria 2

No classrooms were affected. The fire generated contaminants typical for most home and building structure fires. Structure fires produce a variety of chemical products and particles. Materials burned included plastic components of the electrical system. Chemicals from burned plastic generally adhere to combustion particles. Building Dynamics Incorporated reported that no hazardous materials (i.e., asbestos, PCB s) were present in affected areas. Regarding inquiries about asbestos or mold, Building Dynamics determined that neither substance was detected in Glenwood MS. There are no known asbestos containing materials located in the electrical room where the switchgear fire occurred. 4.0 Remediation HCPSS retained several restoration contractors to do the following in impacted areas Dispose heavily smoke-damaged materials and non-cleanable furnishings Vacuum with high efficiency filters (HEPA-vac) and wipe down surfaces with smoke residue After cleaning, seal porous surfaces (i.e., drywall under decking and insulation on chilled water pipes) Fog areas where surfaces might retain smoke residues (i.e., boiler room, crawl space) Clean ducts and clean/seal air units Launder affected clothing and furnishings Shampoo/Extract carpets HEPA-vac and wipe down affected furniture and other materials Clean kitchen and electrical equipment De-odorize above ceilings in rooms adjacent to affected areas Contractors erected barriers and isolated work areas in negatively pressurized containments. Air scrubbers and deodorizers were operated in these areas during remediation. Standard products commonly used in smoke damage restoration were used by HCPSS contractors. These included cleaning solutions and surface treatments. In most cases, these products do not leave a residue after cleanup. A paint used to seal cleaned surfaces left acrylic paint dust above some ceilings. This is isolated from occupied space and will be re-sealed next summer. HCPSS personnel did the following: Cleaning of electrical, plumbing and HVAC controls Reconstruction Custodial cleaning of non-affected areas and final cleaning of impact areas Custodial cleaning of non-affected areas and re-construction by Building Services personnel used products approved through the Office Safety and Risk Management and are Green Seal 42 certified. After classrooms had been cleaned and isolated from affected areas, parents and staff were allowed to retrieve materials on January 6 and 7. The air unit serving the kitchen was heavily damaged and could not be completely cleaned. This was locked off and sealed up to prevent building contamination, and Kitchen air diffusers were left sealed with plastic. The kitchen can continue to operate with supplemental heating and cooling units and the damaged air unit will be removed during next summer s HVAC renovation. 3

5.0 Clearance for Re-Occupancy After contractors completed the cleaning of each area, BDL conducted a detailed inspection to determine if all combustion residue had been eliminated. This included a streak test as specified by ASTM Standard D6602. Following this procedure, surfaces are wiped and the absence of dark stains on the media is considered negative for the presence of combustion residue. In several cases, BDL would not accept an area until it was re-cleaned by the contractor. A similar process was used to check cleaning of ducts and air units. After it was noted that one of the sealers used by contractors left a residue of acrylic paint dust, BDL would not clear areas until surfaces were free of white dust. At the completion of cleanup, BDL based approval for re-occupancy on two detailed odor evaluations. During the first walkthrough, all HVAC systems were operating and air discharging from diffusers in each zone were evaluated for soot odor. During the second walkthrough, all ventilation systems were off. Without dilution, any odors emanating from the structure are concentrated, and thus easier to detect. The latter survey was conducted below and above ceilings in all building areas. No soot-type odor was detected in either survey. BDL will also re-evaluate cleaned contents as they are returned to GMS (i.e., check the cleanliness and odor of laundered items). 6.0 Mold Update Mold growth in GMS was eliminated in 2015 (see Building Dynamics, December 01, 2015 report). The electrical fire was outside the school and the only water released inside GMS was from a sprinkler head in the electric room (porous materials were not wet). BDL investigated parent concerns that smoke restoration work uncovered additional mold growth and found that this was not the case. The gym ceiling was cleaned for soot and no mold growth was present. 7.0 Next Steps HCPSS Facilities Department will work collaboratively with BGE to conduct an analysis of each facility s electric usage and ensure the BGE s electric service is appropriate for the demand of each location. 4

Equipment Purchased The Howard County Public School System is attempting to recover all losses incurred by the fire. Although a list of equipment is being finalized, lists of materials were purchased as part of the restoration in order for the building to fully function as a school. According to the fire department incident report, a 13,000-volt underground BGE electrical feed was the source of fire in the switchgear inside the school s electrical vault. BGE s underground wire, where the fire began, and the switchgear, where BGE s wires enter the building, have been replaced. Kitchen manager desk, file cabinet and chair Ice maker Walk-in freezer Switch gear Electrical room lights Ceiling tile replaced in kitchen, cafeteria, custodial office, halls Walk off mat at boiler room Stage curtains cleaned Duct Bank Incoming Power Cables from Transformer BGE Set New Larger Transformer New Power Cable to Sprinkler/Fire Pump/Underground Vault Fire Alarm System; Duct Detectors (several), smoke Detectors (several) Security System: New Key Pad & Three Motion Detectors Sprinkler Heads; 15 in Mechanical room New Phone Lines/Service From Street Into Building Filters for all HVAC Systems throughout Building (Over 150 Filters) Pneumatic Air Dryer