CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements



Similar documents
3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

SECTION UNDERGROUND ELECTRIC SERVICE

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING

Merrimac Municipal Light Department. Residential Developments Policy

MOBILE HOME SERVICE REQUIREMENTS GAS

SECTION STORM DRAINAGE SYSTEM

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

Underground Service Requirements and Instructions

SECTION STORM DRAIN SYSTEM

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

Section 2100-Trenching and Tunneling

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

Specification Standards Communications Underground Ducts, Raceways and Structures

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SECTION PRECAST CONCRETE UTILITY STRUCTURES

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

COMMERCIAL CONDUIT RULES AND REGULATION

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

4 Installation Requirements

C. Section TESTING LABORATORY SERVICE.

CITY OF SELMA, TEXAS Inspection Checklist: Commercial

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

SECTION STORM DRAINAGE TABLE OF CONTENTS

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

Checklist for plans to Construct, Alter or Repair An Individual Subsurface Sewage Disposal System

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

16300 MEDIUM VOLTAGE DISTRIBUTION

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

Raceway and Boxes for Electrical Systems Page 1 of 7

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.

Town House Center Highway North Huntingdon, PA 15642

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

EXHIBIT "A. Technical Specifications for Water and Sewer Service Lines

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

SECTION GRAVITY SANITARY SEWERS

SECTION SIGNAL WIRE AND CABLE

TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. GENERAL... Page 3

INDEX. Sec. No. Items Page Nos.

CABLE TRENCH INSTALLATION GUIDE

For a building with a crawl space, see Figure

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

Specifications for Residential Property Owners Connection to New Public Sewer

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

EFFECTIVE FEBRUARY note: drainage permit required to call for a dampproof inspection

SANITARY SEWER SPECIFICATIONS

SECTION 22 LIGHTNING PROTECTION SYSTEM

1 Town of Lyons Electrical Distribution System Design Standards

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

SECTION ABANDONMENT OF SEWER MAINS

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

Chapter 7 Plumbing Connections

Section SEWER PIPE INSTALLATION AND TESTING

SPECIAL SPECIFICATION 5757 Power Duct System

Section 402. STORM SEWERS

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

DIVISION 4300 STORM DRAINAGE

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

Beacon Hill Sewer District Standard Specifications

Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

Wastewater Capital Projects Management Standard Construction Specification

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

Medium Voltage Electrical Distribution

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

SECTION GROUND WATER STORAGE TANKS

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION EARTH MOVING

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

IRRIGATION PUMPING Table of Contents - Section 900

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

Utilities and existing services

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

STRUCTURES Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

HIGHLAND VALLEY SUPPLY, INC STANDARD TERMS AND CONDITONS OF SALE

Reticulation sewers in basements Technical guidelines

Utility Distribution Systems

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

SECTION FACILITY STORM DRAINAGE PIPING

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

CHAPTER 6 - SANITARY SEWER

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA (7300 Short Road, Serene Lakes)

OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003

Residential Electrical Inspection. Checklist

Transcription:

16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes on drawings. Refer questions and comments regarding the content and use of this document to the Yale University Project Manager. CONTENTS A. Summary B. System Design and Performance Requirements C. Submittals D. Product Standards E. Manufacturers F. Materials G. Accessories or Special Features H. Special Requirements I. Installation Guidelines J. Quality Control K. Startup and Training Change History Date Description of Change Pages / Sections Modified Change Approver Initials 10/17/14 Amend text in section E (Manufacturers), paragraph #2 (Manhole Covers) to update vendor 10/17/14 Amend text in section F (Materials), paragraph #1 (Ductbank) subparagraph a. for clarity 10/17/14 Amend text in section H (Special Requirements), paragraphs #1 and #7 for correction. 10/17/14 Amend text in section I (Installation Guidelines) paragraphs #6. & #11. 10/17/14 Add paragraphs #12 & #13 to section I (Installation Guidelines) 2-16600, E. #2. (Underground Electrical Duct Bank; Manufacturers) 3-16600, F. #1. a (Underground Electrical Duct Bank; Materials) 3>4 16600, H. #1. & #7. (Underground Electrical Duct Bank; Special Requirements) 5-16600, I. #6. & #11. (Underground Electrical Duct Bank; Installation Guidelines) 5-16600, I. #12. & #13. (Underground Electrical Duct Bank; Installation Guidelines) A. Summary This section summarizes the design criteria for underground exterior electrical distribution systems. B. System Design and Performance Requirements 1. The minimum allowable concrete duct compressive strength is 5,000 psi at 28 days. 2. Design all underground electrical raceways and duct banks for seismic zone 2. 3. Steel reinforcement ASTM A-615, grade 60 minimum cover to steel reinforcement 1. Subdivision 16600: Underground Electrical Duct Bank 1

Section 16600: Underground Electrical Duct Bank 4. Vault shall be designed to meet ASTM C857 and ACI 318 with AASHTO HS-20 loading. 5. Construction joint shall be sealed with BUTYL rubber resin or equivalent. C. Submittals Submit the following design and construction documents to Yale University. 1. Design Documents Plan and profile views of all design drawings Maximum wire pulling tension calculations for proposed conduits 2. Construction Documents Product data on manholes, hand holes, and fittings Equipment and machinery proposed for bending metal conduit D. Product Standards The following products are standard for Yale University: Underwriters Laboratories ANSI/NEMA 70: National Electrical Code National Electrical Manufacturers Association (NEMA) TC6: PVC and ABS Plastic Utilities for Underground Installations National Fire Protection Association (NFPA) 70: National Electrical Code (NEC) National Electrical Contractors Association, Inc. (NECA) 5055: Standard of Installation E. Manufacturers Subject to compliance with the design requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to, the following. 1. Pre-cast Manholes Arrow, Ditullio, Rotondo, or a Yale University approved equivalent 2. Manhole Covers Campbell Foundry 1108 or a Yale University approved equivalent with the word Electrical cast into the upper surface. The cover opening shall be 36 diameter as a minimum. All new covers shall have manhole numbers welded on surfaces (TIG Weld). Subdivision 16600: Underground Electrical Duct Bank 2

Section 16600: Section 16600: Underground Electrical Duct Bank F. Materials 1. Ductbank 2. Manhole a. Use 5 schedule 40 (encased in concrete by 2 minimum) or schedule 80, rigid, nonmetallic conduit in straight sections, unless otherwise noted or specified. Use rigid galvanized steel 5 conduit for bends, kicks, sweeps, elbows, offsets, and within five feet of ductbank wall penetrations. b. All conduits penetrating to the wall of manhole shall have end bells, or if not, conduits shall have grounding bushing attached to ground rod. There shall be a minimum of two ground rods per manhole. a. All electrical devices in the electrical manholes, such as plugs, receptacles, outlets, switches and terminal blocks, shall be made by Hubbell Marine Grade products. b. Lighting fixtures in electrical manholes shall be made of Simkar OV451 with polycarbonate lens, wet location stainless steel latches and fittings, and low temperature universal ballasts with 2-32 watt T8 lamps and with T8 ballast. c. Install fault indicator on all feeders using Power Delivery Products Cat # 29-3114-000 with auto reset and trip with 4 hours delay. G. Accessories or Special Features 1. All end seals, gland seals, and anchors must be designed and factory prefabricated to prevent the ingress of moisture into the system. 2. All subassemblies must be designed to allow for complete draining and drying of the conduit system. 3. Anchors must be manufactured to minimize the heat transfer from the carrier pipe to the jackets. H. Special Requirements 1. Provide heavy duty non-metallic cable racks with demountable insulated cable brackets by Underground Devices, Inc in all manholes. 2. Provide a sump at the bottom of each manhole with sump pump wired to a ground fault outlet. The sump pump discharge must be piped to an adjacent storm sewer or to the surface. Cords for the sump pump shall be Type OW. 3. Pulling wiring irons shall be on all walls and floor. 4. Each manhole shall have a ground bus with two separate connections to ground rods. Subdivision 16600: Underground Electrical Duct Bank 3

Section 16600: Underground Electrical Duct Bank 5. Maintain a minimum grade of 4" in 100 feet, either from one manhole, hand hole, or pull box to the next, or from a high point between them, depending on surface contour. 6. Pipe bends must have at least a 10' radius. 7. Manhole and vault shall be sized per design requirements. Number of cables, splices, elbows, etc, but minimum size shall be 8 x11 x7 high. 8. All grounding wires shall be 4/0 AWG as a minimum. 9. Fiberglass ladder shall be installed in each manhole. I. Installation Guidelines 1. Pipe bedding: Where possible, provide a uniform pipe bedding of granular material conforming to the requirements of SW, SP, or SP-SW soil classifications for on-site material. If suitable material is not available, backfill the trench with sand. Using a material similar to the bedding, backfill the entire trench width evenly in 6" lifts to 6" above the top of the pipe. Compact the lifts to at least a 95% Standard Proctor density, meeting ASTM D1556 standards at optimum moisture (or as recommended by the soils engineer). Backfill the remaining trench in lifts not to exceed 12" up to the sub-grade height for the surface condition encountered. Compact the lifts to a 95% Standard Proctor density, meeting ASTM D1556 standards at optimum moisture (or as recommended by the soils engineer). Backfilling and compacting above the sub-grade must be determined by the soils engineer or by the recommended paving design for the project. Salvage existing topsoil and reuse it, where possible, as directed by Yale University grounds personnel. Replacement topsoil must meet Yale University grounds personnel requirements. 2. Leave a nylon fish tape in all spare conduits. 3. All conduits entering a building structure must terminate with a threaded end that will accept a lock nut, connector, or grounding bushing. 4. Bury all ducts at least 30" below grade, unless otherwise noted. The top of the ductbank must be dyed red with warning tape. Maintain 12" of vertical and horizontal separation with other piping systems. 5. Unless noted otherwise, encase conduits with 3,000 psi concrete, with 4-5 steel reinforcing steel re-bars running the length of ductbank. In addition #5 reinforcing steel wraps is required every 5 feet for the entire run of the ductbank. Subdivision 16600: Underground Electrical Duct Bank 4

Section 16600: Section 16600: Underground Electrical Duct Bank 6. For each manhole, place a plaque on the manhole wall adjacent to the duct. Indicate the name of the manhole at the other end and the distance to the next structure. Plaques shall be made by Seton Cat # MO929, with a red back ground and white letters indicating manhole numbers. 7. Where duct banks enter buildings, vaults, or other structures, dowel into the concrete wall with #5 reinforcing steel at the four corners of the duct bank (minimum) and every 12" around the perimeter of the duct bank. Extend the dowels at least to the depth of the wall and the same distance into the duct bank. 8. Empty raceways must have a permanent removable cap over each end. 9. Install a metal lined, plastic, 6" wide warning tape 18" above all raceways and duct banks. 10. Furnish and install a Danger High Voltage sign at each manhole, cable chamber, junction box, pull box, and vault. 11. Install #4/0 bare copper ground cable the length of the duct bank to be used to connect the manholes to grounding system. 12. New manholes shall have a plaque visible upon entry to manhole with the manhole number. Plaque shall be red with white lettering. 13. New manholes shall have a plaque at each compass point, north, south east and west, visible upon entry to the manhole with compass point, the next destination/source (building or manhole) of the cables leaving/entering that face of the manhole as well as the distance to that location. J. Quality Control Work on exterior electrical distribution systems must conform to the following quality control standards. 1. Testing Laboratory a. Yale University will retain the services of a qualified, independent testing laboratory to perform soil compaction tests, as directed, during construction. b. All materials within the scope of Underwriters Laboratories must conform to UL standards and have an applied UL listing mark. 2. Testing Methodology and Extent a. Inspect and test in accordance with NETA-ATS requirements, except section 4. b. Perform inspections and tests listed in NETA-ATS, section 7.3.2. Subdivision 16600: Underground Electrical Duct Bank 5

Section 16600: Underground Electrical Duct Bank K. Startup and Training 1. A final inspection of electrical systems is required before final payment. 2. Contractors must provide competent instructors to train Yale University personnel in the care, adjustment, and operation of all parts of the electrical system. End of Section Subdivision 16600: Underground Electrical Duct Bank 6