Non Invasive Roof Leak Detection Using Infrared Thermography



Similar documents
Infrared Thermography and Water Damage Assessment

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

BLUESTAR INFRARED. Description: Thermal Properties Comparison. Project Location: Client: 759 South Federal Hwy 225 Bayshore Drive

Preventing Ice Dams on Roofs

How To Find Out Where Water Is Leaking

Infrared Moisture Detection

1.0 Introduction. 2.0 Importance of Integrity Testing. 3.0 How Does EFVM Work? 6.0 Conclusion

FIELD TESTING SERVICES

INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box Houston, Texas (713)

December 24, SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216

RODENT PROOFING CHECKLIST

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Evaluating Roof Performance and Diagnosing Moisture Intrusion into Roofing Systems

Thermal Imaging Scan Reveals the Truth Behind the Wall

Vision Home Inspection

Water Management & Damage Prevention:

Shingle Roofing: What s below the surface is important

Infrared Cameras Can Aid Building Inspectors in Detecting Roof Leaks, Water Damage, Mold and Other Moisture Related Problems

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007

NAIOP OF SOUTHERN NEVADA SUSTAINABILE DEVELOPMENT COMMITTEE - EDUCATION SERIES

ROOFS, SNOW AND ICE DAMS

Safeguarding our clients interests. Active Roof Leaks

If you touch buildings, YOU can benefit from the Moisture Encounter Plus

Tiled Shower Pan Leaks - Investigation And Repair FAQ

Prestige Home Inspection LLC

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

CONDENSATION IN REFRIDGERATED BUILDINGS

Home Warranty Inspection Report

TechPractices: Home Front Homes:

MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION

StuccoSpec Moisture Testing Inspection

HomeSpec REPORT SUMMARY

Techniques for Finding and Documenting Moisture Intrusion in Buildings with an Infrared Imager by: R.W. Olsen & Greg Stockton

Roof Inspection. Summary Report

Basement & Foundation Damage

EXISTING FACILITIES EVALUATION REPORT

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract

Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

ProScan v.1.2. Owner s Manual

Roof Damage Reconveys 2014

CertainTeed. Protecting Your Home From Ice Dams Homeowner s Guide

RDH Building Sciences Inc.

STRUCTURAL ASSESSMENT

GreenGuard Housewrap Installation Guide

How To Repair A House

KNOW YOUR RIGHTS AND

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

When dealing with a potential moisture problem, time is of the essence. Taking a proactive approach will save you money and headaches down the road.

High R-Value Does Not Always Mean High Performance

PRE-PURCHASE INSPECTION REPORT

Thermal Imaging Specialists Consultancy - Camera Sales - Training

Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

Moisture Challenges & Solutions: Proactive Construction Strategies

Big Stone County Courthouse Slate Roof Shingle Replacement. Request For Proposals

GHS Flood Final Report CTA Architects Engineers March 31, 2011

Mold Inspection Report (Initial Assessment)

REPLACE YOUR ROOF TO VISUALLY INSPECT YOUR ROOF REGULARLY SO YOU CAN DISCOVER PROBLEMS WHILE THEY ARE STILL MINOR AND CAN BE REPAIRED.

How To Prevent Water Damage To A Home

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX

Attachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers

Thermographic Inspection of Building and Roof Water Intrusion in the State of Florida

Home inspectors are not mold inspectors, however they do inspect for defects that

TIMBER PEST INSPECTION AGREEMENT

WHAT IS INFRARED (IR) THERMOGRAPHY

Block Lofts Condominiums

Common Problems with Walls

How To Fix A Gutter Clog

Architectural Testing

Response, Reliability and Results in the delivery of leak detection services

Retrofitting an Insulated Cold Roof

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

Stucco Moisture Inspection Report

Simplify. Homeownership

Molds and mildew are fungi that grow

3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations

THE IC Y N E N E AD V A N T A G E

March 14, Installation of Bay, Bow and Garden Windows

Home Inspection Report

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at Forest Drive, Annapolis, MD. Provided by: HurleyIR

Commercial buildings often have flat roofs, which are

ROOFS - Guidance for Repair, Maintenance and Replacement

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

The ability to professionally test

Exterior Repair Project. By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek. Building Technology Consultants, PC BTC

ELIGIBLE REPAIR PROJECT PARAMETERS

Inspecting to a higher standard.

Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION

Assessing Curtain Walls

Home Performance with ENERGY STAR. Evaluation Report

The Uniform Building Inspection Report Condensed

Finegan Inspection Services, Inc.

Central Location: 30 Buchanan Street, Colorado Springs, Co Point Roof Inspection Report + Bonus

Chapter 9: INSTALLING ROOFING

Estero. Estero office serves southwest Florida

Transcription:

Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing scaffolding and probing the ceiling for water intrusion with a moisture meter. This paper discusses infrared thermography s ability to probe the ceiling for water intrusion without physical contact with the ceiling. Water was applied to the roof in a controlled manner, starting at the lower sections, then moving to the peak of the roof. During the water application, continuous scanning of the ceiling with a FLIR E4 infrared camera allowed instant discovery of the water intrusion. Keywords: Moisture detection, noninvasive leak detection, roof leak detection, testing criteria, infrared thermography, building diagnostics. INTRODUCTION Roof leaks are typically discovered by direct observation. If the roof sheathing is not visible from below, such as in an attic, the wallboard or ceiling covering must first be removed. This removal is necessary in order to visualize the intrusion point at the underside of the roof sheathing. Before the ceiling is removed all contents must be removed from the affected area. The floor is then protected from falling debris and the ceiling is removed, possibly requiring a scaffold system. Infrared thermography is an invaluable tool in the discovery of roof leak intrusion source without the need to remove the ceiling or contents of the room. The thermal properties of water are unique, allowing water to be observed on the surface of building material or even within the building material being examined. When water evaporates on the surface of building materials it cools. If the building material is at a different temperature, the water s thermal difference may be detected by conductance through the building material. When infrared thermography is used to observe the ceiling prior to, during, and following water testing these thermal differences enable moisture to be located on or within the wall or ceiling structures. No portion of the ceiling needs to be removed, allowing for a nondestructive means of finding the roof leak. BACKGROUND In April of 2003 a leak occurred at the ceiling-wall joint of a residence. Water entered the home at the supply duct register and the windows at the front wall of the living room. Water testing indicated the intrusion might have been the transition between the stucco wall and roof (see figure 1). Corrective measures were performed in October 2003 that included replacing the roof flashing as well as the stucco siding of this area. On February 25th, 2004 a rainstorm again caused water intrusion within the same area previously noted before flashing and wall stucco replacement (see figure 2). Evidence of this intrusion is visible in figure 2. InfraMation 2004 1

Figure 1. Exterior views of the front of the residence showing the location of water exiting the stucco surrounding the center window (blue arrows) indicating water had entered the wall system above the window. Figure 2. Visual image of the living room ceiling showing the water staining caused by the roof leak. The blue arrows show the staining along the ceiling-wall joint directly under the supply register. black marks (pieces of tape indicated by red arrows) are reference points for the wallboard separation only visible upon close examination between the tape marks. VISUAL INSPECTION PROCESS On March 31, 2004 an inspection of the affected area including a water test of the roof was performed. The vaulted ceiling did not allow direct access to the underside of the roof sheathing. In the absence of infrared thermography the ceiling would have been removed to inspect the roof sheathing for the water intrusion point(s). A non-infrared inspection is accomplished by removing the room's contents protecting InfraMation 2004 2

the floor as well as installing scaffolding to reach and remove the ceiling wallboard. With infrared thermography it was not necessary to remove contents, wallboard, or erect scaffolding, nor was floor protection necessary. Visual inspection of the roof exposed two potential water intrusion points, the gutter and chimney areas as shown in figures 3-5. The gutter had foam installed at the upper slope of the gutter (see figure 4). Since this was an unusual use of foam, it may have hidden imperfections or water entry points behind the gutter. Water testing was directed as described later in this paper at the gutter area to determine if it was a leak site. Figure 3. Visual images of the roof showing the cement roofing tiles intact (without cracking, separation or missing tiles). The gutter system at the right (see blue arrow) did have unusual construction as shown in figure 4. Figure 4. Visual images showing a close-up of the gutter system (as shown in figure 3) where foam was applied. The foamed area (blue arrows) may be covering a possible water intrusion point. InfraMation 2004 3

Figure 5. No flashing is visible at the chimney s top and side, but may be incorporated within the chimney s cladding, which is stucco. This is apparent in the visible flashing of the chimney s lower edge as shown on the image at the left (see blue arrow). BASELINE DETERMINATION Following the visual inspection a complete infrared thermographic inspection of the interior of the affected area was performed (see figure 6). This was to provide a reference point of the thermal characteristics of the walls and ceiling of the affected area. Areas that were cooler or showed temperature abnormalities were examined closer with moisture survey equipment that consisted of conductive and dielectric meters. No moisture differences were found in the cooler areas visible in the infrared thermograms. The temperature differences of the lower sections of the ceiling (indicated with green arrows in figure 6) were due to the condition of the insulation within the ceiling. It is unclear what may have caused the cooler areas indicated by the red arrows shown in figure 6. These unknown cooler areas are located near where the first water intrusion points were discovered and may be related to past water intrusions or missing insulation. InfraMation 2004 4

Figure 6. Visual image of the ceiling as well as infrared thermograms showing a thermo baseline of the ceiling where the water leak should be visible. The cooler areas indicated by the green arrows area due to insulation gaps. It is unclear why the areas indicated by the red arrows were cooler than the surrounding wallboard. Moisture readings show no moisture differences in all the areas visible in this image. WATER TESTING Water was applied to the roof from a spray rack system for 30 minutes at each location or 15 minutes using the hand held spray applicator (see figure 7). Figure 9 shows the positions of the rack system for each 30-minute test. Soon after the spray rack system was moved into position 8, water intrusion was found in the ceiling of the residence. The first water intrusion point was the cool area visible in figure 10. This area was tested for moisture using a moisture meter, which confirmed the presence of a leak. InfraMation 2004 5

To test the suspected gutter area, the hand held applicator was used (see figure 8). During this test no water intrusion was found, indicating no water intrusion points for this area of the roof. Figure 7. Images of the spray rack system (left) and the hand held spray applicator (right) used to apply water to the roof. The handheld applicator was used to apply water to the suspect area located at the gutter. Figure 8. Image of the hand held applicator and its position during the water test of the gutter area as well as the positioning of the spray rack system. InfraMation 2004 6

Figure 9. Diagram of the roof showing the positions, 1-13, of the location of the spray rack. MOISTURE DISCOVERY During the water application process infrared thermography was used to scan the ceiling surface of the living room. No moisture was detected until the spray rack system reached position 8 (figure 9). Figure 10 shows the beginnings of the water intrusion as indicated by the cool spot noted by the arrow. InfraMation 2004 7

FLIR Systems Figure 10. Thermogram/photo pair showing the beginnings of the water intrusion. Cool spot indicated by the arrow was tested for moisture with a moisture meter to confirm the presence of moisture. As the roof water test continued, the water intrusion increased, moving to the front wall of the living room. Figure 11 indicates the location of the water within the wall as it moves behind the wall, surfacing at the top and bottom of the window. At this point of the test water was dripping from the window header onto the floor of the living room. Water testing continued with the spray rack positions 9 through 13. As the rack moved away from the valley of the roof the water intrusion decreased, finally stopping with the completion of the water testing. FLIR Systems Figure 11. Thermogram/photo pair showing the water intrusion moving to the front living room wall. INTRUSION DISCOVERY Once it was determined through water testing where the approximate location of the roof leak was, roof tiles were removed to examine the underlayment and roof sheathing. InfraMation 2004 8

Figure 12. Images showing water under the tiles (left) and under the roof s underlayment (right). Note the location of the area in reference to the gutter at the upper left side of the left image. Figure 13. Image on the left showing the underlayment and roof sheathing as well as two nails (red arrows) found laying on the roof sheathing. The heads of the nails penetrated the underlayment causing water to flow onto the roof sheathing and then into the residence. The image on the right shows the remains of the debris dam and the edge of the flashing (green arrow) where the water spilled over (blue arrow) Figure 14. Image showing the debris dam at the roof valley before the tile was removed. InfraMation 2004 9

By following the water visible below the underlayment, the source of the intrusion was found. Two nails were discovered that had been dropped onto the roof sheathing, then covered by the underlayment and having punctured the underlayment (as shown in figure 13). Since the roofing tiles prevent water from entering the underlayment it was important to determine how the water got under the roofing tiles to begin with. Further exploration of the roof revealed a debris dam at the valley of the roof. Roofing codes in the area required the tiles to be installed without a gap at the roof valley. This allowed debris to accumulate in the valley eventually damming the valley causing water to spill over onto the underlayment (figures 13-14). SUMMARY Infrared thermography was able to save the customer time and reconstruction costs during a water intrusion study. It allowed the water test to be performed without inconveniencing the homeowner with a destructive tear out, typical of most water testing when no infrared thermography is used. By viewing with an infrared camera the ceiling of the living room the approximate location of a roof was determined. Once located, a small section of the roofing system was removed and the punctures to the underlayment as well as the debris in the roof valley were discovered. REFERENCES 1. ASTM International D 4444-92 (reapproved 2003) Standard Test Methods for Use and Calibration of Hand-Held Moisture Meters. 2. IFAS publication DH 511: The Disaster Handbook 1998 National Edition Institute of Food and Agricultural Science University of Florida, Finding and Repairing Leaks in Roofs, Section 5.11. 3. ASTM International E 1105-00: Standard Test Method for Field Determination of Water Penetration of installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Differnece. InfraMation 2004 10