IN USE: CABLE AGING MANAGEMENT



Similar documents
Proposed Task Group: Electrical Cable and Condition Monitoring Codes and Standards for Nuclear Power Plants

Cable System Aging Management Implementation and Its Affect on Cable System Longevity. Gary Toman

Stephanie Watson. Service Life of Electrical Cable and Condition Monitoring Methods

Improving regulatory practices through the OECD-NEA Stress Corrosion Cracking and Cable Ageing Project (SCAP)

WIRE AND CABLE ENGINEERING GUIDE

Long Term Operation R&D to Investigate the Technical Basis for Life Extension and License Renewal Decisions

THE OKONITE COMPANY. Ramsey, New Jersey Fax:

Nuclear Power Plant Electrical Power Supply System Requirements

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

A Regulatory Approach to Cyber Security

PNNL Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830

Online Transformer Insulation Monitoring System BushingGard Product Focus. Maximizing Transformer Uptime and Reliability

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION OFFICE OF NEW REACTORS WASHINGTON, DC

ICM Project Underground Infrastructure and Cable

ATTACHMENT I TO IPN RELATED TO LOAD TESTING AND,24 MONTH OPERATING CYCLES

Insulation Resistance Testing of Low Voltage Cables in the Field

Verification of Safety for Reinstalled Class-1E Cable in Shin-Kori Unit 3

Proposal to Consolidate Post-Fukushima Rulemaking Activities

PRODUCT / APPLICATION INFORMATION

Module 6 Fire Probabilistic Risk Assessment (PRA) Methodology for Nuclear Power Facilities

Fault location on power cables. Fault location on power cables

Cable Failure, Diagnostics and. Steven Boggs

How To Test For Safety On A Power Cable

DRAFT REGULATORY GUIDE

WIRE AND CABLE ENGINEERING GUIDE

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

Nuclear Consultancy & Engineering Services

Investigation of VLF Test Parameters. Joshua Perkel Jorge Altamirano Nigel Hampton

Guidance for the Quality Assurance of Fire Protection Systems

electrical services

Development and Application of POSAFE-Q PLC Platform

Published in the Official State Gazette (BOE) number 166 of July 10th 2009 [1]

NEW HIGH PERFORMANCE, ENVIRONMENTALLY FRIENDLY MV POWER CABLE INSULATIONS

Applying NQA-1 Requirements for Computer Software Used in Nuclear Facilities ASME 2014 Small Modular Reactors Symposium April 17, 2014

Direct Attach Cable with Micro Coaxial Wire for Data Center

Nuclear Energy Standards Coordination Collaborative (NESCC)

Total System Reliability - Extending the Life of Electrical Cable Systems

Cable Insulation Resistance Measurements Made During Cable Fire Tests

Reconsideration of Application of GDC-4 Exclusion of Local Dynamic Effects to Local Debris Generation

A Power Cable Reliability Solution

On-Line Partial Discharge Testing. Skip Hicks Director - New Business Development

FIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION

Introductions: Dr. Stephen P. Schultz

Steven A. Arndt Division of Engineering Office of Nuclear Reactor Regulation

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

NORTH CAROLINA EASTERN MUNICIPAL POWER AGENCY SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1. Renewed License No. NPF-63

Spreading the Word on Nuclear Cyber Security

DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision 2 of Regulatory Guide 1.128, dated October 1978)

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

THE USE OF AFTER-INSTALLATION COMMISSIONING TESTS TO ASSURE MV POWER CABLE SYSTEMS MEET MANUFACTURERS STANDARDS

L.S. de Carvalho, J. M de Oliveira Neto 1. INTRODUCTION IAEA-CN-164-5P01

Executive Director for Operations AUDIT OF NRC S CYBER SECURITY INSPECTION PROGRAM FOR NUCLEAR POWER PLANTS (OIG-14-A-15)

Notes from Underground

THE VALUE OF POWER FACTOR TESTING

C.I.8.2 Offsite Power System. C.I Description

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C February 1, 2006

Cyber Security for Nuclear Power Plants Matthew Bowman Director of Operations, ATC Nuclear IEEE NPEC Meeting July 2012

Results and Insights of Internal Fire and Internal Flood Analyses of the Surry Unit 1 Nuclear Power Plant during Mid-Loop Operations*

Industrial Cable Solutions for Variable Frequency Drives

HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY

FLEXTREME AND FLEXTREME IF

Regulatory Guide Configuration Management Plans for Digital Computer Software Used in Safety Systems of Nuclear Power Plants

Cable Discharge Event

Training in Emergency Preparedness and Response

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

Low Voltage Asset Management (LVAM) The key to reliable and safe electricity

MLCC Voltage Strength

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Oscar E. Morel UtilX Corporation

Continuous Emissions Monitoring - Program 77

RTP s NUCLEAR QUALITY ASSURANCE PROGRAM

PV O&M Best Practices Nadav Enbar, Sr. Project Manager,

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

Submerged Medium Voltage Cable Systems at Nuclear Power Plants: A Review of Research Efforts Relevant to Aging Mechanisms and Condition Monitoring

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

Why Buy HVI VLF Products?

HTS Cables: Pitfalls and Potential LIPA Cable Project. J. Maguire American Superconductor. DOE Wire Workshop January, 2007 Panama City, FL

NETWORK OUTPUT MEASURES METHODOLOGY Authors: National Grid, SP Transmission PLC, Scottish Hydro Electric Transmission Limited

STEP 3 ELECTRICAL SYSTEMS ASSESSMENT OF THE WESTINGHOUSE AP1000 DIVISION 6 ASSESSMENT REPORT NO. AR 09/019-P

Second License Renewal Roadmap. May 2015 Prepared by the Nuclear Energy Institute

Power-factor testing of rotating machinery is another valuable test

CAROLFIRE The Cable Response to Live Fire Project

VIPERFLEX ELECTRIC CABLE

BALLOT PREVIEW PRESENTATION P497 STANDARD CRITERIA FOR ACCIDENT MONITORING INSTRUMENTATION FOR NUCLEAR POWER GENERATING STATIONS

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

W-2. Stranding Comparison

Stator Winding Hipot (High Potential) Testing

AGING CHARACTERISTICS OF NUCLEAR PLANT RTDS AND PRESSURE TRANSMITTERS

NRC Cyber Security Regulatory

TOOLS FOR CLOSURE PROJECT AND CONTRACT MANAGEMENT: DEVELOPMENT OF THE ROCKY FLATS INTEGRATED CLOSURE PROJECT BASELINE

UNITED STATES NUCLEAR REGULATORY COMMISSION ADVISORY COMMITTEE ON REACTOR SAFEGUARDS WASHINGTON, DC July 17, 2012

100% EMI Emission Containment

MDEP Generic Common Position No DICWG 02

International Conference on Human Resource Development for Nuclear Power Programmes: Building and Sustaining Capacity

GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT

Evaluating Water-Damaged Electrical Equipment

Transcription:

IN USE: CABLE AGING MANAGEMENT ISSUE STATEMENT Concerns exist that cable aging-related failures may impact nuclear plant safety and reliability. As a result, plant owners and regulators are requiring the implementation of electrical cable aging management programs and processes. Improvements to cable aging management processes, condition monitoring techniques, acceptance criteria, and aging models are necessary to support resolution of cable aging concerns DRIVERS Safety A nuclear plant s safety-related electrical cable system must be reliable. Cable failures can challenge safety system operability. Equipment Reliability Medium voltage off-site feed cable and safety-related motor feed cable failures have caused outages of 2 to 3 weeks in duration. Medium voltage cable replacement is costly and generally difficult. Regulatory The U.S. Nuclear Regulatory Commission (NRC) is requiring per Reg Guide 1.218 that cable aging management and condition monitoring be put in place. Non-U.S. regulators are following the NRC lead regarding aging cable systems. While some differences in cable materials and installation practices exist from country to country, deterioration of low and medium voltage cables is a concern to the world nuclear community. Limitations of Inspection Technology The design of nuclear plant cables limits the types of tests that may be used. While standardized, the tests provide information on cable condtion, but limited information on long-term operability of the cable and cannot estimate remaining life. Condition monitoring acceptance criteria is providing value but more data analysis is required to determine if it can be useful in determining the rate of aging. Limitations of Applicable Standards IEEE, ICEA, and AEIC have established cable testing and manufacturing standards, but these standards provide little information on aging management of nuclear plant cable systems. RESULTS IMPLEMENTATION This research effort will result in knowledge and methodologies to effectively implement cable aging management programs. The following will be provided: Resolution of issues that arise during implementation of cable aging management programs. Recommended testing methodologies applicable to specific cable types and vintages. Advanced testing and predictive methodologies. Additional understanding of electrical cable failure modes allowing improved testing methodology and acceptance criteria to be developed. Test applicability matrices and ongoing EPRI technical support. PROJECT PLAN Utility Actions Utilities are in process of implementing their cable aging management program. Medium voltage cables in adverse environment have mostly been identified and condition assessment through dissipation factor (tan delta testing) is ongoing. Identification of low voltage cable scope is in progress and condition assessment is expected to continue on through the next several refueling cycles. Another important effort is collecting actual, field aged cables to assess their current condition compared to the actual environmental conditions they saw in service. Utilities are urged to supply EPRI their abandoned, failed, or replaced low and medium voltage cables to support condition evaluation through forensic investigation of the cable condition. Such research will provide insight into cable aging and failure mechanisms known or yet to be identified. This forensics work very likely is one of the key means of supporting cable capability assessments for long term operation. Failure Mechanism Research Through a pilot project started in 2010, EPRI will produce age-accelerated medium voltage cable specimens. The hope was that these specimens would permit accelerated testing and forensics, accelerated development of aging models, and development of improved condition monitoring techniques. This project did not prove successful in creating specimens that would degrade due to accelerated aging, but they failed due to random manufacturing issues. Equipment Reliability January 2016

Failure mechanism research for wet cables has completed for cable types from plants in service in the 1970s.. Results have shown that tan delta testing has been successful in identifying degraded cables. A correlation has been established between the level of cable degradation and tan delta test results. A forensic method has been developed to isolate the degraded insulation and the level of degradation can be confirmed by ac breakdown testing. The final report, 3002005232, showed that elemental metal (Al, Fe, Pb,Si, Ti, Zn) were found at water tree roots. These elements are believed to act as catalyst (along with water and dielectric stress). A field guide for proper harvesting of service aged cables was issued in 2014. Report 3002003994 is a web-based guide that can be used on a desk-top, laptop, or tablet device (for electronic work package usage). This document was in September 2014. Sufficient funding was available to perform testing of two harvested cables in 2014. Additionally funding is available through 2017 to continue evaluations of service aged cables harvested from operating or plants entering recommisioning. The second evaluation and assessment of medium voltage Tan δ test results was completed and issued in September, 2015. The report summarizes the data analyzed so far, Key insights are the correlation of poor tan delta results to reduced ac breakdown values of the degraded cable identified through the failure mechanism research (see above). The report also provides guidance for members to use in analyzing their test results. To support the development of advanced testing practices/ technologies, EPRI s Nuclear Sector continues to look for opportunities to collaborate and coordinate activities and research with the Power Delivery and Utilization Sector. No activities are currently planned Cable Program Support, Implementation, and Sustainability Cable program implementation support is being managed through issuance of EPRI guidance such as the aging management guides (1020804, 3002000557, and 10216929), implementation lessons learned guide (1022968) and support provided via the Cable User Group semi-annual meetings. In addition, in August, 2012 the end of life guide (1025259) was issued, as well as research into the effects of dewatering cable (1025263). An update to report 1020805 for the medium voltaged cable aging management guidance (3002000557) was issued in the June of 2013. The revision clarifies some issues identified during initial implementation such as testing methodology, frequency, and analysis. Funding has been approved for 2014-2017 to develop a handbook of medium, low and instrument and control cables describing there formulation, aging degradation mechanisms for EPR insulations to allow differentiation of them for aging management. The medium voltage cable guide, 3002005321 was issued in December, 2015. In 2016 the section covering he low voltage power cables will be done and instrument and control cables will be addressed in 2017. In addition, EPRI attended the initial International Atomic Energy Agency (IAEA) meeting for development of an international guidance on low voltage cable qualification, condition monitoring and aging management. This effort, supported by over 14 international cable experts, will complete in 2015. The third meeting was held in China in October, 2014 which was a follow-up to the second meeting held at AMS in Knoxville Tennessee. Round robin testing results were reviewed and further work was done towards developing the format and responsible persons for final report development. Supporting the IAEA in this effort allows EPRI to influence the research and identify information on diagnostic and condition monitoring testing techniques to see if they can be applied by our membership. The final report was received in September, 2015 and is being evaluated for consideration of any changes that should be made to our cable research strategy based on these results. Cable Diagnostics Condition monitoring of low and medium voltage cable is the key to establishing the current state of cables. Much has been learned about medium voltage cables in wet adverse environments by evaluating the tan delta test data that members have been supplying EPRI. The initial report (1025262) evaluating this data was issued in July, 2012. Additional insights into degradation rate can be gathered if we can evaluate second and third test data from the same equipment. Funding has been obtained to continue this effort through 2015 when a second report will be issued to include the additional insights of this additional data. EPRI will continue to identify and evaluate condition monitoring and diagnostic techniques, both existing and new, to ensure that our members have the best techniques available to them to evaluate the condition of their cable systems and obtain information needed to make informed decisions on those cables that are approaching end of life. This will be done through staying abreast of research in other EPRI sectors, involvement with the Insulated Conductors Committee of the IEEE, and through collaboration, monitoring or supporting the research projects of the NRC, the Department of Energy, and the National Laboratories. Long Term Operations Support of long term operations is indirectly covered by many of the project in the other swim lanes. Items such as submergence qualification, Black EPR rejuvenation experiments, developing a methodology for assessing risk and reliability for cables are specific to this area. EPRI Nuclear Sector Roadmaps January 2016

EPRI is continuing the submergence qualification project based on IEEE Std 323-1974 qualification methodology to provide a basis for allowing medium voltage cables to be submerged. The initial qualification activities for brown ethylene propylene rubber (EPR) are now in the accelerated aging stage, The second insulation type, pink EPR, via supplemental funding began in June, 2015. This qualification is only being considered for modern cable types that are known to never have failed in submerged conditions. Manufacturer and insulation specific qualifications will be performed; generic insulation type qualification is not possible. Because certain cable types, such as most black EPRs and butyl rubber, have experienced water related degradation at about 30 years, submergence qualification will not be attempted. Little information is available on longevity of low-voltage cable under wet and submerged conditions. In late 2011, a year long, pilot test program was begun that subjects common low voltage insulations to energized, submergence testing in 90 C water to determine if these insulations are susceptible to long-term wet aging. This work is ongoing and thesecond phase was started in April, 2015to gather data on jacketed, multi-conductor cables and the results will be evaluated and reported in 2016. Funding was obtained for 2013 for the development of a guidance document for performing an evaluation of a plants specific cable infrastructure aging and how that can be used to understand the risk and reliability that can be expected in the period of long term operation. Information will be gathered via site visits to both a pressurized water reactor and boiling water reactor to obtain cable condition assessment information. That data will be used to estimate current cable condition and estimated remaining life and then extrapolated to estimate the degree of exposure of the site. The associated cost of maintaining the cable system at acceptable risk levels through long term operation will be demonstrated. This report will serve as a guide for others to repeat such analysis for their sites. This work has been delayed to allow performance of a gap analysis of EPRI cable research and develop an integrated research plan with DOE, NRC, and the National Laboratories.This work will be re-evaluated upon completion of this integrated research roadmap. RISKS It may not be possible to develop accelerated aging techniques for EPR insulations or an enhanced cable test methodology. RECORD OF REVISION This record of revision will provide a high level summary of the major changes in the document and identify the Roadmap Owner. revision de scr ipt ion of ch ang e 0 Original Issue: August 2011 Roadmap Owner: Gary Toman 1 Revision Issued: November 2011 Roadmap Owner: Gary Toman Changes: Revised to update for 2012 added Design Recommendations for Longevity of Cable Systems 2 Revision Issued: August, 2012 Changes: The roadmap has been completely redesigned. The previous roadmap flowchart revision had a single swim lane for equipment reliability. The revised roadmap flowchart has five swim lanes covering utilities roles, failure mechanism research, cable program support, cable diagnostics, and long term operations. In addition, the 2011 year has been removed and 2012 2016 have been modified to include milestones and both funded and unfunded work. 3 Revision Issued: December 2012 Changes: Research work completed in 2012 has been annotated on the flowchart. Cable user group meetings in second half of years when International Cable Symposiums occur have been removed (2013 and 2015). Research for project in 2013 that were shown as not being funded have been updated to show funding in 2013. 4 Revison Date: August 2013 Changes: Research work completed so far in 2013 has been annotated on the flowchart. Research for project work to be requested in 2014 has been added to the flowchart (Cable Materials Handbook, Service-Aged Cable Evaluation) and flowchart have been adjusted for projects extended due to need for additional information (Low Voltage Wet Susceptibility, MV Failure Mechanism). Equipment Reliability January 2016

revision de scr ipt ion of ch ang e 5 Revision Issued: December 2013 Changes: Update provided on negative results of age accelerated medium voltage cable samples and the September issueance of MV failure mechanism report 3002000554. Dates were revised for funding of Tan Delta test data analysis. Added information on newly approved funding for cable harvesting guidance and testing for 2014 2016. Sustainability section updated to reflect funding for cable polymer handbook. The delay of LTO funded guidance for evaluating cables to replaced for long term operation to perform gap analysis of research and coordinate with DOE, NRC and National Labs research was done instead. 6 Revision Issued: August 2014 Changes: Revised roadmap to show LTO support for DOE/NRC/EPRI research goes out to mid-2017 and that the Cable Polymer Handbook and Harvesting guide are funded projects. 7 Revision Issued: December 2014 Changes: Updated projects competed in 2014 and provided status updates for on-going research out to 2017 (medium voltage cable submergence, low voltage wet cable study, evaluation of service aged cables). Identified 2015 deliverables for Tan delta analysis report, failure mechanism research and medium voltage cable portion of the cable polymer handbook. 8 Revision Issued: August 2015 Changes: Updated project status for submergence, low voltage wet aging, failure mechanism research and IAEA CRP project status. 9 Revision Date: December 2015 Changes: Update project status for final failure mechanism research, summarized results of tan delta evaluation update report, and updated the cable polymer handbook project noting completion of medium voltage cable section. EPRI Nuclear Sector Roadmaps January 2016

Equipment Reliability January 2016