Approval Standard for Plastic Suspended Ceiling Panels

Similar documents
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts

Approval Standard for Flammability of Absorbent Battery Acid Spill Containment Pillows

Class Number May FM Approvals LLC. All rights reserved.

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

Approval Standard for Water Motor Gong

How To Test For Premer Retardant

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire

Tremco Fire Protection Systems Group Technical Bulletin

A.17. OXIDIZING PROPERTIES (SOLIDS)

Validation of Modeling Tools for Detection Design in High Airflow Environments

18 June 2001 GUIDELINES ON FIRE TEST PROCEDURES FOR ACCEPTANCE OF FIRE-RETARDANT MATERIALS FOR THE CONSTRUCTION OF LIFEBOATS

HOT WORK PERMIT PROGRAM TRAINING. John Braun

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012

Decree of the Ministry of the Environment on fire safety of ventilation systems

Fire Performance Standard

Fiberglas, Exterior Wall Thermal Insulation

WHITE PAPER Fire & safety performance standards

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

D A T A C O M M U N I C A T I O N S C O M P E T E N C E C E N T E R

Commercial Gas Furnace Upflow

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Specifications, Product Testing and Terminology

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

FLAMMABLE AND COMBUSTIBLE LIQUIDS

Excerpts from the Canadian National Building Code (NBC)

A. Fire Protection Plan. B. Access and Parking

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

Boiler & Pressure Vessel Inspection discrepancies and failures

FIRE SAFETY ONLINE TRAINING

Standard Test Procedures Manual

Extended Coverage Sprinklers

Automatic Fire Sprinkler Submittal Requirements

HOT WORK PERMIT PROCEDURES

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

Determination of the enthalpy of combustion using a bomb calorimeter TEC. Safety precautions

The replacement or modification of existing windows shall comply with the following requirements:

Arapahoe County Residential Water Heater Installation and Inspection Guide

CLEAR-DIVISIONS VARIOFOLD

Treatment of a surface or structure to resist the passage of water in the absence of hydrostatic pressure. presence of hydrostatic pressure.

SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES

Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158

Electrical Classification

Fire Pump Plan Review March 2010

RESPONSE TIME INDEX OF SPRINKLERS

Ducoterra Radiant Heating Panel Installation Manual

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

Approval Standard for Class 1 Fire Rating of Building Panels or Interior Finish Materials

Building Code Clarifications - 7. Fire Resistance

Fire Testing of Recycled Materials for Building Applications

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

CLEAR-DIVISIONS CENTERFOLD

February 2014 Alberta Fire Code Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities

SPILLS & SPILL KITS. Spills -General Guidelines:

Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems

HVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

furnishings flammability characteristics

Sun Vinyl New Construction Windows Homeowner's Warranty

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Fire or Ignition Resistant? Building Materials & Vegetation

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Cooling Capacity CFM in. w.c. (125 Pa)

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

Gas-Fired, Residential Storage Type Water Heaters

Comparative study for cables and busbars

Watermist fire suppression systems for commercial low hazard occupancies

FIRE SAFETY FOR OFFICE WORKERS

Builder Specifications for Solar Ready Homes

General Fire Code Requirements Within Commercial Tenant Spaces

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

OSHA Tank Venting DEFINITIONS

X-ray Imaging Systems

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

PAINT BOOTH LIGHTING

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:

OCFRD TENT STANDARD This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts.

Clark County Fire Prevention

Fire Security Systems

BS5839 Part 1:2002 Overview

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

CLEAR-DIVISIONS APERTO

1.0 Purpose Definitions Hot Work Operations. 5

Name Of Occupancy Date. Yes No Describe

Determination of the enthalpy of combustion using a bomb calorimeter TEC

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

HEAVY DUTY STORAGE GAS

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

Transcription:

Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved.

Foreword The FM Approvals certification mark is intended to verify that the products and services described will meet FM Approvals stated conditions of performance, safety and quality useful to the ends of property conservation. The purpose of Approval Standards is to present the criteria for FM Approval of various types of products and services, as guidance for FM Approvals personnel, manufacturers, users and authorities having jurisdiction. Products submitted for certification by FM Approvals shall demonstrate that they meet the intent of the Approval Standard, and that quality control in manufacturing shall ensure a consistently uniform and reliable product. Approval Standards strive to be performance-oriented. They are intended to facilitate technological development. For examining equipment, materials and services, Approval Standards: a) must be useful to the ends of property conservation by preventing, limiting or not causing damage under the conditions stated by the Approval listing; and b) must be readily identifiable. Continuance of Approval and listing depends on compliance with the Approval Agreement, satisfactory performance in the field, on successful re-examinations of equipment, materials, and services as appropriate, and on periodic follow-up audits of the manufacturing facility. FM Approvals LLC reserves the right in its sole judgment to change or revise its standards, criteria, methods, or procedures.

TABLE OF CONTENTS I INTRODUCTION... 1 II TEST MATERIAL... 1 III FIRE TEST PROCEDURES... 1 IV MANUFACTURING QUALITY CONTROL TESTS... 2 V MARKINGS... 3 VI QUALITY ASSURANCE IN-PLANT INSPECTION... 3 VII RE-EXAMINATION... 4 VIII MANUFACTURER S RESPONSIBILITY... 4

February 1978 4651 I INTRODUCTION 1.1 A suspended ceiling installed below an automatic sprinkler system can impede the operation of automatic sprinkler heads and their water distribution. By acting as an insulator, the suspended ceiling may delay sprinkler head operation. By obstructing sprinkler water flow and distribution, the suspended ceiling panels or tiles may contribute to fire spread at floor level and subsequent building damage. 1.2 Situations may also occur in which sprinklers adjacent to a fire area may be activated by elevated temperatures resulting from the entrapment of hot gases in the area above a suspended ceiling. The cooling effect of sprinkler water on the ceiling panels or tiles must not significantly alter their drop-out or melt-out behavior. 1.3 A suspended ceiling system installed in sprinklered or unsprinklered areas can be a hazard if the ceiling material itself contributes significant fuel to a fire or spreads the fire along its surface. 1.4 Suspended ceilings are available in materials which incorporate special features that will minimize the hazards mentioned above. These features include their melt-out properties which enable the ceiling tiles to decompose without flaming when subjected to heat, and/or drop-out properties which enable the panels to shrink when absorbing heat. These properties permit the ceiling panels to fall from their suspension grid allowing prompt and unobstructed sprinkler water flow. The melt-out or drop-out behavior of the panels minimizes the potential propagation of fire across the surface of the entire suspended ceiling. For this reason, no clips which limit drop-out of the ceiling panels shall be used with Approved ceiling panels unless they have been incorporated during the fire tests. 1.5 Approval examination will include appropriate fire tests to determine ease of drop-out or melt-out, the cooling effect of sprinkler water on drop-out behavior, surface flammability and quality control inspections of the product manufacturing facility. 1.6 Continued Approval will depend upon satisfactory field experience and periodic follow-up inspections of the manufacturing procedures. II TEST MATERIAL 2.1 The manufacturer shall furnish 500 sq ft (46.5 sq m) of the thickest ceiling panel in the shortest length and width for which Approval is sought and a sufficient amount of suspension grid system to support a 10 ft (3.05 m) 12 ft (3.66 m) test system. The ceiling panel submitted must be truly representative of productionrun material. The suspension grid supplied shall be of the inverted-t type, with no clips or ridges which might impair drop-out performance of the panels. III FIRE TEST PROCEDURES 3.1 Three series of fire tests are performed to evaluate the behavior of the ceiling panels. During Tests 1 through 6, a forced draft is created under the simulated ceiling arrangement by a 12 in. (30.5 cm) diameter fan, 1/4 hp, 1000 rpm, to induce surface flame spread, if possible. FM APPROVALS 1

4651 February 1978 3.2 Melt-Out or Drop-Out Behavior Before Sprinkler Operation 3.2.1 Tests 1, 2 and 3 are conducted to determine the effect of heat and flame on the ceiling tiles before sprinkler operation and their ability to melt out quickly. For each test, a 10 ft 12 ft (3.05 m 3.66 m) ceiling is assembled horizontally incorporating a suspension frame and centered over a fire exposure derived from a 1 in. (2.54 cm) depth of isopropyl alcohol in a1sqft(0.093 sq m) pan located 35 in. (88.9 cm) below the panels. The fire source is ignited, and the panels observed for decomposition and the elapsed time required for panels to fall free from the grid is noted. This arrangement is considered to simulate a fire with ceiling temperatures reaching 1000 F (538 C) in about 1 1 2 min. 3.2.2 If the ceiling panels directly above the fire melt out or drop out of the grid system within one minute and 45 sec., and if no spreading flame is observed on the surfaces of the panels, the performance is considered satisfactory. Full scale laboratory tests indicate this time lag will be little or no detriment to sprinkler effectiveness. 3.3 Melt-Out or Drop-Out Behavior When Sprinklers are Operating 3.3.1 Tests 4, 5 and 6 are conducted to determine if sprinkler water adjacent to a fire area would cool the ceiling panels and significantly delay fallout. The test set-up is essentially the same as described in Paragraph 3.2.1, except as follows: One pendant type sprinkler, 1 2 in. (12.7 mm) orifice, is centrally mounted 18 in. (45.7 cm) above the 10 ft (3.05 m) 12 ft (3.66 m) suspended ceiling. A sprinkler flow (10 gpm) is initiated 15 sec. prior to ignition of the fire source and is maintained at the same flow rate throughout each test. The panels above the fire exposure are timed for melt-out or drop-out performance under the cooling effect of the sprinkler flow. 3.3.2 If the ceiling panels drop free of the grid system within one minute and 45 sec. after ignition of the exposure, and if no spreading flame is observed on the surfaces of the panels, the performance is considered satisfactory. 3.4 Surface Flammability 3.4.1 Tests 7, 8 and 9 are performed to determine if the panels would contribute to a spreading fire over their surface. For each test, two ceiling panels are held vertically 1 2 in. apart and a Bernz-o-matic propane torch is placed between the panels at their base and held for a 15 sec. period. The torch is then removed and observations are made to determine if the panels support combustion. 3.4.2 When the exposure is removed, the flame shall not spread to the top of the panels. IV MANUFACTURING QUALITY CONTROL TESTS 4.1 For purposes of acquiring Quality Control data, original samples will be analyzed by the following methods: 4.1.1 Density: One sample of the submitted ceiling panel shall be measured and the volume shall be determined. The sample shall then be weighed and the density of the panel will be computed by dividing the panel weight by the panel volume. 2 FM APPROVALS

February 1978 4651 4.1.2 Total Ash: A section of the suspended ceiling panel shall be cut of minimum dimensions 2 in. 2 in. (50.8 mm by 50.8 mm) by submitted thickness. This section shall be weighed and placed in a tare of known weight. The tare shall then be subjected to sufficient heat to effect complete combustion of all combustible material in the tare. The weight of remaining ash shall be determined. The percent of total ash is determined by dividing the weight of the ash by the weight of the section before combustion. 4.1.3 Emerson Oxygen Bomb Calorimeter: A section of the suspended ceiling panel shall be cut of minimum dimensions 2 in. 2 in. (50.8 mm 50.8 mm) by submitted thickness. This section is weighed and placed in a pressure vessel or bomb which is then sealed. The bomb is completely immersed in water of known volume and temperature. Oxygen at a pressure of 300 psi (21.1 kg/cm 2 ) is introduced inside the bomb. The bomb is then fired by a hot wire. The heat release from the bomb is measured in Btu s by the rise in temperature of the volume of water. By dividing the heat release in Btu s by the weight of the section in pounds, we determine the heat of combustion in Btu s per pound. 4.1.4 Pyrolytic Gas Chromagraphy: A section of the suspended ceiling shall be cut of minimum dimensions 1 in. (25.4 mm) 1 in. (25.4 mm) by submitted thickness. A small portion of this sample material shall be weighted to the nearest milligram and introduced into the test apparatus. The test apparatus shall subject the material to metered quantities of heat sufficient to completely gassify the test material. The gases produced are passed through a glass column containing an inert gas and electrically recorded on a graph which plots response versus time. The areas under the peaks of this response curve are related to amounts of different compounds produced during gassification. 4.2 The data developed from these small scale quality control tests shall be maintained on file by FM Approvals. Results of these tests will be considered as nominal for the Approved product. Should periodic control testing of the Approved product at any time yield significantly different results from the original small scale test, re-examination of the Approved product may be necessary. V MARKINGS For purposes of identifying the Approved product, each panel shall be marked on its edge with the FM Approval mark and manufacturer s trade name as Approved. VI QUALITY ASSURANCE IN-PLANT INSPECTION An inspection of the product manufacturing facility is part of the Approval investigation. Its purpose is to determine that production procedures and manufacturing controls are properly maintained to produce the same quality of material as the tested product. Periodic re-inspections will be conducted to assure adequate quality control. Samples of the Approved product may be taken at this time for small scale quality control re-examination. FM APPROVALS 3

4651 February 1978 VII RE-EXAMINATION 7.1 A re-examination will be conducted periodically on the Approved ceiling material to determine that the quality and uniformity of the product has been maintained and that the product will provide the same level of performance as originally Approved. 7.2 Changes in formulation by the manufacturer, evidence of unsatisfactory performance of the Approved product, or significant variations between small scale re-examination results and original small scale test results may be cause for complete Approval re-examination. VIII MANUFACTURER S RESPONSIBILITY 8.1 The manufacturer shall notify FM Approvals of any change in the Approved product prior to general sale and distribution. Non-compliance with this provision is grounds for immediate withdrawal of FM Approval. 8.2 The manufacturer shall make every reasonable effort to supply all necessary instructions and other assistance to the installer to insure proper installation. 8.3 Approved ceiling tiles are not to be painted or altered in any way. The manufacturer shall be responsible for so advising distributors, installers, and customers. If tiles are painted or altered in any way, FM Approval is automatically voided. 4 FM APPROVALS