HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help?



Similar documents
Thermal and air quality effects on the performance of schoolwork by children. Field intervention experiments

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE

Lesson 36 Selection Of Air Conditioning Systems

Molds and mildew are fungi that grow

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

A new design guideline for the heating and cooling curve in AHU of HVAC systems

Air Conditioning, Comfort and Energy in India s Commercial Building Sector

Information paper 20. Prepared by: David Clark. book:

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

Energy Efficiency in Buildings

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Mechanical and Natural Ventilation

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions

BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015

AIR CONDITIONING - ENERGY CONSUMPTION AND ENVIRONMENTAL QUALITY

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

The Finnish Classification of Indoor Environment and Material Emissions

Absolute and relative humidity Precise and comfort air-conditioning

CEN/TC 156. pren Date: CEN/TC 156. Secretariat: BSI ICS: Descriptors:

HEATING, VENTILATION & AIR CONDITIONING

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

3-D Modeller Rendered Visualisations

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

Chapter 2 Indoor Air Standards and Models

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Adaptive thermal comfort in primary school classrooms: Creating and validating PMV-based comfort charts

Service & Maintenance:

Federation of European Heating, Ventilation and Air-conditioning Associations

Software Development for Cooling Load Estimation by CLTD Method

Integrated Solar Radiant Systems

bout your house before you start Renovating Your Basement Moisture Problems

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Energy savings in the residential area are essential in

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

How To Design A Room Air Conditioning System

Thermal destratification in buildings: The missing piece to the HVAC puzzle

Mapei systems for radiating floor heating with high thermal efficiency

THERMAL LOSSES Thermal Losses Calculations

INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes

bout your HOUSE before you start Renovating Your Basement Moisture Problems

Urban Environment: constraints and opportunities towards a sustainable quality

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Indoor Air Quality Issues for Hotels

Subtropical Cities September Design for Energy Efficiency in Commercial Buildings in Queensland

Glossary of Heating, Ventilation and Air Conditioning Terms

Radiant Panels and Chilled Sails.

Mistrale. Fusion Terminal

Temperature and Humidity

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

about your house Before You Start Renovating Your Basement Moisture Problems Figure 1 Moisture problems to solve

Energy Efficient HVAC-system and Building Design

Air Conditioning in Green Office Buildings?

Building and Grounds Maintenance Checklist

National Building Code of Canada 2010

Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice

DK2 IEA. Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark

Dehumidification Frequently Asked Questions

Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick.

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING

Energy Efficiency HOSPITALITY.

Advice to consumer Reference 50.1 May Condensation. Some causes, some advice.

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Energy efficient windows, doors and conservatories. Make a better choice

KONRAD. Hybrid Fancoil Series

Federation of European Heating, Ventilation and Air-conditioning Associations

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

How air conditioning works

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

Housing Fact Sheets. Moisture Condensation at the Windows

RESSÒ: energy efficiency urban rehabilitation

DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

Heating and Ventilation

How To Control Humidity With A Humidifier

Answers to Your Questions from the Webinar

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

HVAC Systems: Overview

Comfort Conditioning & Indoor Air Quality

How To Make Your House Breathe

TU/e Dept. of the Built Environment Building Performance group

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Transcription:

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help? Proceedings of Healthy Buildings 94 Ben Bronsema, Consulting Engineer ONRI Ketel Consulting Engineers Ltd, DELFT From the 1970s onwards thermal insulation of buildings has improved and air infiltration reduced. On the other hand, the internal thermal load has increased so much since the 1980s due to personal computers and peripheral equipment that cooling is nearly always required during working hours. In order to economise on the energy needed for cooling, it has become common practice to allow the inside temperature to rise as much as possible in accordance with the Fanger thermo-physiological model. Practical research has shown that office workers cannot appreciate the temperatures of 25 C and higher that occur in the application of that model. At higher air temperatures the emission of VOC s from inside also increases and the human sense of smell becomes keener; the result is more SBS complaints. For the sake of thermal comfort and a good perceived air quality; the temperature in offices should he limited to 23 C à 24 C while the ventilation supply must often be increased to 75-100 m3/hour/person, roughly double the usual volume. Both these measures augment the energy consumption and that is, of course, highly undesirable. However, air-conditioning technology can eliminate this unfavourable consequence by means of innovative techniques, and it appears that a better inside climate can be achieved at less energy consumption. The Indoor Climate in Summer: Conflict between Theory and Practice? Optimum thermal comfort is one of the most important conditions for achieving a hea1thy indoor climate. Many complaints disappear if the room temperature is well adjusted to the human activity. Too high a room temperature in particular can cause problems, but what is too high? HVAC engineers apply various norms and standards in answering that question. Mostly such norms are based on the thermo-physiological model developed by Fanger. At a clothing coefficient of 0.5-0.7., considered to he typical for office workers and an activity level of 1.2 met, the maximum allowable room temperature Ti max - is in the summer usually set at 25 C - 26 C. See Table 1. 363

Table 1. Maximum room temperature in the Summer Source Activity level Clothing Ti max ANSI/ASHRAE 55-199 1,2 met 0,5 clo 26 0 C DIN 1946 1,0 1,5 met 0,5 1,0 clo 25 0 C* ISSO 19 (NL) 1,2 met 0,7 clo 25,5 0 C* ISO 7730 1,2 met 0,5 clo 26 0 C * excess allowed for 10% of the working hours In the 1980 s various researchers undertook empirical investigation of the thermal climate in existing office buildings. The findings revea1ed considerable differences between the real appreciation of the interior climate and what it should have been according to the Fanger model. This is illustrated by Figure 1, taken from Brager's research [1]. Figure 1 - Thermal comfort and operative temperature according to Brager Fanger Brager PMV 2 1,5 1 0,5 0-0,5-1 -1,5 18 20 22 24 26 28 Operative temperature 0 C The neutral conditions (PMV = 0) occurred at 22 C, while the model predicts 24.5 C. Assuming that the tbermo-physiologica1 model is correct, the conclusion must be that the subjective parameters clothing and activity levels of Table 1 are too low. For clothing the coefficient of 0.5 is on the low side for Europe. Furthermore, normal office chairs insulate about 15% - 20% of the body surface. This can be compensated by increasing the clo value by 0.1 to 0.2; to, say, 0.75 [2]. For office activity a level of 1.2 met (= 70W/m2) is usually assumed. In practice, however, the activity/metabolic rate level may well he higher than defined above for the following reasons [2]: * Office staff usually spends some of the time walking to and fro and the effect of the corresponding activity level of 1.7 met does not cease abruptly when they sit down again. * Prevailing stress causes the metabolic rate to increase. * Coffee consumption also increases the metabolic rate. Five cups per day equals l0 W/m2 = 0.12 met * Many people are in a poor physica1 condition, contrary to those taking part in the model research. For all these reasons it seems reasonable not to set the activity/metabolic rate level below 1.4 for every day office conditions. 364

The recommended room temperature (Ti max ) within the parameters suggested above (0,75 clo/1,4 met) are shown in Table 2. Table 2 Recommended Room Temperature Parameter PMV>> -0,5 0 +0,5 0,5 clo / 1,2 met Ti 0 C 23 0 C 24,5 0 C 26 0 C 0,75 clo / 1,4 met Ti 0 C 20 0 C 22 0 C 24 0 C THE WARMER THE SMELLIER: SO KEEP IT COOL Office air is often not fresh. Many people are sensitive to that and stale air is therefore considered to be one of the causes of the Sick Building Syndrome [3). If the room temperature is higher than needed, the atmosphere is, or is perceived to be, stuffy. There are two causes for this phenomenon. First, the emission of Volatile Organic Compounds (VOC s) from finishing and furnishing materials usually becomes stronger as the temperature increases. Moreover, at higher temperatures the moisture of the skin is greater and so is the emission of body odour. Second, human perception of air, quality also depends on the room temperature and on the relative humidity. The air is perceived as being fresher and less stale at a lower temperature and humidity. Various scientists have investigated this phenomenon [4). The concussions all point in the same direction. Most noteworthy are Wyon's [5) findings.. He found that above 20 C - 21 C almost all SBS symptoms increase sharply as the temperature rises. At 20-21 only 10% of the persons interviewed comp1ained of headache and tiredness. At 24.5 C the proportion of complainants had risen to 60%. Wyon's dictum: * temperature down to the lower limit of the comfort range; * maximum humidity of 30 % R.H. Berglund and Cain [6) have investigated the relationship between room temperature and perceived air quality in laboratory conditions. They have set up a remarkable equation for the interdependence of air quality, air temperature, dew point temperature and metabolic rate. The author of the present article has converted the equation from o F to C. Figure 2 reflects the results. Figure 2. Air quality and room temperature (Berglund en Cain). M = 1,4 stuffy Stuffiness of the air (B) 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 fresh RH 50% RH 60% RH 70% 20 21 22 23 24 25 26 27 Air temperature Equation: B = 0,254T + 0,038T + 0,2095M 3, 88 a 365 dp

Where: B = Stuffiness T a = Air temperature T dp = Dewpoint temperature M = Metabolic rate Both field and laboratory research agree that there appears to be an interaction between the temperature and the perceived air quality, which deteriorates as the former rises. The effect is less at low humidity. As for the perceived air quality it is wise to keep the temperature at the lower limit of the comfort range. A glance at table 2 and Figure 2 shows that in summer conditions a design temperature of 22-24 C (23 C ± 1K) is a sound point of departure. INDOOR CLIMATE, AIR-CONDITIONING AND ENERGY CONSUMPTION Air-conditioning is intended to ensure a healthy and comfortable inside climate, and provided the system is well designed, well run and well kept, it can prevent about 80% of the SBS problems. But, airconditioning uses up energy and causes pollution through the emission of CO 2, NO x, SO 2, etc., which is bad for the environment. Energy saving is important in modem society; it should not, however, be done to the detriment of the indoor climate. Office workers are required to give optimum performance and are entitled to a good inside climate. It is incumbent upon the conscientious HVAC engineer to reconcile the opposing interests of the exterior and interior climates as much as possible. This task is not made any easier by the above arguments for lower temperatures in summer and, hence, more cooling. Moreover, better understanding of VOC emission and air quality leads to increased ventilation of 75-100 m3/h/person, or roughly double!he volume considered sufficient until recently. Both requirements increase energy consumption. That is not wanted! Several air-conditioning systems will be compared below as regards the quality of!he indoor climate in summer and the energy required. The basis for the comparison are the two office spaces as in Fig. 3, which are assumed to be part of a building where the ratio of useful surface to gross floor area is 0.7. The inside thermal load is assumed to be 40W/m 2 (people 8 - lighting 12 - P.C.'s etc. 20W/m 2 ). Figure 3 - Partial floor plan 1 = Stony façade 2 = Windows double glazing 40% of inner facade - outside screens 3 = Light partition walls 4 = Concrete floor with screed and carpet 5 = Acoustic false ceiling The following HV AC systems have been considered: A - V A V system with terminal reheat, C - 4-Pipe Fan-coil system, B - 4-Pipe induction system, D - 4-Pipe Ceiling heating/cooling. 366

Energy Consumption The annual energy consumption of the building, expressed in terms of Primary energy (kwh/m 2 gfa) has been calculated for indoor temperatures of 22-24 C (23 C ± 1 K) in summer and 20-22 C (21 C ± 1 K) in winter, corresponding to the optimum values mentioned earlier. See Table 3. Table 3.: Annual Energy Consumption of Four HVAC Systems - kwh/m 2 primary energy A B C D D* System Heating 134 104 83 89 51 Cooling 71 50 41 33 - Pumps / Fans 48 36 32 32 37 Total HVAC - kwh/m 2 253 190 156 154 88 Ditto % 100% 75% 62% 61% 35% Lighting - kwh/m 2 34 34 34 34 34 PC s etc. 66 66 66 66 66 Total building - kwh/m 2 353 290 256 254 188 Ditto % 100% 82% 73% 72% 53% System D requires less energy than the others, closely followed by C, which provides far less comfort. See Table 4, below. A further significant advantage of the ceiling system is the possibility of energy efficient heat and cold generation. Since the ceiling temperature is fairly high in Summer, cold can be abstracted from the soil, e.g. by means of a closed soil absorber, which can serve as a heat source for a heat pump in winter. The effects of the latter combination are shown under D*. To arrive at an overall view for the building, the power consumption for lighting and office equipment (P.C. 's, etc) bas been also calculated on the basis of a yield of 0.33 for converting primary energy into electrical energy. Ouality Comparison Besides the energy aspects, there are also quality differences between the systems with regard to providing a healthy indoor climate. See Table 4.. Table 4. Quality Comparison of four HV AC Systerns System A B C D Quality element 1- Air quality 0 + + ++ ++ = good 2- System pollution + 0 0 ++ + = fair 3- Maintenance + + 0 ++ 0 = passable 4- Noise nuisance + + + ++ 5- Thermal comfort + + + ++ 6- Flexibility 0 + ++ + 367

Explanations 1- Air Quality With system A, the air is usually recirculated in order to economise on energy. Thus, VOC s, ETS and fine dust particles that are not trapped in the normal filters remain in circulation and reduce the air quality. Systems B and C draw in 100% of the air supply from outside, but recirculate it in the rooms. With System D there is no recirculation al all. 2 - System Pollution. Systems B and C internally recirculate the room air and are the most sensitive to pollution. System D causes the least air movement and is the cleanest. 3 - Maintenance System C requires the most attention with the separate circulation fan and the filters. Cooled ceilings (D) need no maintenance. 4 - Noise Nuisance The circulation fan in system C is a source of noise, especially at full power. Cooling from the ceiling is silent since a large part of the thermal load is absorbed by radiation (Silent Cooling). 5 - Thermal Comfort System D causes the least air movement so the risk of draught is slight. Moreover, due to radiation, effective room temperatures are 1-1.5 C lower than the air temperature. That enhances comfort. 6- Flexibility System A cannot cope with thermal loads exceeding what it has been designed for. In system C the fan RPM can be easily increased, but that is to the detriment of both noise and thermal comfort. The flexibility in system D consists of replacing passive surfaces with active surfaces and/or adding cooling convectors to the existing system. CONCLUSION With regard to efficient use of energy and a healthy indoor climate, cooled ceilings are the best choice among the current HVAC systems. It should be preferred especially in. the case of high thermal loads. REFERENCES 1. Gail S Brager (1992). "Using laboratory based models to predict comfort in office buildings". ASHRAE Journal, April 1992. 2. B. Bronsema (1993). "Het binnenklimaat in de zomer in de zomer: Conflict tussen theorie en praktijk? Klimaatbeheersing 22 (1993) nr. 9 (in Dutch). 3. P.O. Fanger (1987). "A solution to the Sick Building Mysterie". Proceedings Indoor Air '87 - Volume 4 4. B. Bronsema (1994). Waar het warm is stinkt het: dus hou het koel. Klimaatbeheersing 23 (1994) nr. 4 and 5 (in Dutch) 5. David P. Wyon (1993). "Current indoor climate problems and their possible solution". Invited paper to the international Scientific Conference "Indoor IJr Quality Problems - fiom Science to Practice" Warschau, 24-26 november 1993. 6. I.G. Berglund, W.S. Cain (1989). "Perceived air quality and the thermal environment". Proceedings of the ASHRAE/SOEH Conference I.A.Q. '89 The Human Equation: Health and Comfort. 368