DK2 IEA. Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark
|
|
|
- Joel Horton
- 9 years ago
- Views:
Transcription
1 IEA Energy Conservation in Buildings and Community Systems, Annex 36 Case studies overview Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark 1 Photos DK2 Figure 1a: Photo showing the facade of Enghøjskolen Figure 1b: Photo showing the interior of Enghøjskolen 67
2 2 Project summary The purpose of the project was to document the effect of the school renovation. Low emission surfaces were introduced and mechanical ventilation was replaced by increased volume in classrooms as well as natural ventilation through windows, providing increased user-control. Problems in schools where indoor climate is controlled by building services, include lack of responsibility among occupants, recurring unsatisfactory conditions whereby load exceeds the capacity of installations and high-energy consumption caused by insufficient demand control. Problems in usercontrolled schools are often different. Attention to indoor climate control creates disturbances and climate requirements are only met when users intervene. An intervention study was performed in a poorly maintained school for children of preschool age up to grade 10. The intervention included removal of mechanical ventilation, increased ceiling height and larger hinged windows controlled by users, temperature sensors and a timer to open them during recess. Results from the renovated school show significantly reduced energy consumption, increased user satisfaction and slightly improved values for air pollution and temperature. Since users could better control conditions in the renovated school, occasional poor air quality or temperature levels did not cause notable dissatisfaction. 3 Site Denmark, latitude: 56.5 N, longitude: 8.5 E, altitude: 10 m. Temperate coastal climate. Mean annual temperature: 8 C, mean winter temperature: 4 C. 4 Building description /typology 4.1 Typology / Age Typology/Age Pre The side corridor school (before) The cluster school (after) Educational level: School (pre-school to grade 10) 4.2 General information Year of construction: 1974 Year of renovation (as described here): Total floor area (m 2 ): 10,000 Number of pupils: 500 Number of classrooms: 16 Typical classroom size (m 2 ) : number of pupils: 28 68
3 4.3 Architectural drawings Figure 2: Cross-section of the school after renovation. 5 Previous heating, ventilation, cooling and lighting systems The school was supplied with district heating. The district heating system was directly connected to the radiator system and the heating coils in the ventilation system without any heat exchanger. The ventilation system needed replacement. Originally the radiator system was the only source of heating. In order to obtain a greater heating capacity when outdoor temperatures droped below 0 C, the ventilation system was used as an auxiliary source of heat. The school was supplied with a building management system (BMS). The previous lighting system had fluorescent luminaires. 6 Retrofit energy saving features 6.1 Energy saving concept Worn-out installations and structures in Enghøjskolen, a Danish school in Hvidovre, situated just outside Copenhagen, made it necessary to carry out a comprehensive renovation. Façades, roofs, windows and all materials for inner surfaces were replaced. Teachers, students, parents, consultants and school maintenance staff decided in co-operation that the old ventilation system should be replaced by hinged windows only. This would allow school users to open the windows when required. Furthermore some of the ceiling and façade windows should open by motor control when temperatures increase and when the school bell sounds for recess. This way, windows would be open at least 10 minutes every hour of the school day. Moreover the ceiling height was increased in classrooms by replacing the original flat roofs with pitched roofs parallel with the ceilings. Prior to the renovation, walls had acrylic paint and floors were covered with linoleum. New and similar materials were used in the renovated school. 6.2 Building The insulation of the thermal envelope in the refurbished building was improved. The U-values of the new windows comply with the Danish Building Regulations. Furthermore the ceiling height was increased in classrooms by replacing the original flat roof with pitched roofs.
4 6.3 Heating Radiators with thermostats heat the classrooms. The heat output from the radiators covers transmission plus ventilation losses. The theoretical ventilation loss is set to 5 l/s per person plus 0.4 l/s per m2 when there are people in the room. 6.4 Ventilation Natural ventilation with hinged windows. The renovated school is not sized for 28 pupils per classroom as the old one, but for 24 and this means a bigger volume per person (at least 12 m3). This is the minimum volume demand if mechanical ventilation is to be avoided. 6.5 Lighting The new lighting system has luminaires with compact fluorescent lamp types (CFLs) and occupancy sensors. 6.6 Other environmental design elements Construction products are selected to be robust and durable and have a minimal impact on the environment when made and disposed of. 7 Resulting Energy Savings Table 1 shows that average heat consumption from 1992 to 1995 before renovation was 2.9 times higher than in Average electricity consumption before renovation was 1.7 times higher than after. Much energy was used in the old ventilation systems. Furthermore, the renovation provided better insulation of the school as required in the current Danish building legislation from Table 1: Energy consumption for heat (convectors, ventilation systems and hot tap water) and electricity (fans, pumps, lighting and other equipment). Table 2: Information on size, occupancy and ventilation with outside air for the classrooms investigated before and after renovation. In kwh/(m 2 year) Heat Electricity Large differences in ventilation rates existed between the rooms prior to renovation. This was probably a result of poor system maintenance. Recirculation was reported to be out of action during the final years before renovation. Nevertheless the investigator found some examples of recirculation dampers with their actuators disconnected. This probably caused some re-circulated air to be included in reported values. Air change measurements failed in two of the three rooms without mechanical ventilation in the renovated school. In the rooms with closed windows, air changes, as expected, were extremely low. Class Area m 2 Volume m 3 Number of students Air change h 1 Air flow per person l / (s person) Before 6a / 7a 7b / 8b 7g / 8g 8a / 9a After * 6a / 7a 7b / 8b 7g / 8g 8a / 9a * This room was on the first floor and had mechanical ventilation also after renovation.
5 DK2 Class Mean temp. Horizontal C Std. dev. Temp. Horizontal C Mean temp. increase. Horizontal C/h Std. Dev. temp. Vertical C Mean CO 2 conc. mg/m 3 Mean hydro-- carbon conc. microgm/m 3 Before 6a / 7a 7b / 8b 7g / 8g 8a / 9a Mean before After * 6a / 7a 7b / 8b 7g / 8g 8a / 9a Mean after * This room was on the first floor and had mechanical ventilation also after renovation. Table 3 shows descriptive statistics for measurements of temperatures in a horizontal layer, temperatures along a vertical line from floor to ceiling and measurements of CO 2 concentration and index of total hydrocarbons in a horizontal layer. Standard deviations were calculated for each set of measurements and then averaged. Reported values are based on measurements taken from 8.00 to hours on two consecutive school days. Values tend to be somewhat better in the renovated school. Temperatures in the renovated school show less variation between positions and over time as indicated by standard deviations and the temperature increase. Through comparison of measured ventilation rates to occupancy and CO 2 concentration, it seems obvious that re-circulation was applied before renovation and that ventilation in the renovated school was higher on average than during measurements with closed windows. The high index for hydrocarbon concentration before renovation may indicate significant air pollution sources among the old surface materials. Table 3: Statistics for measurements of temperature, CO2 and the index of total hydrocarbons before and after renovation. 8 User evaluation Figures 3 to 5 show information from an investigative questionnaire made just before the renovation and one year after. Approximately 80% of the replies Figure 3: Acceptability of air quality before and after renovation. 71
6 Figure 4: Perceived change of some unpleasant conditions after the school renovation. were from students, who participated in both years, while the remaining 20% came from students who only participated once. Perception of air quality was rated on the acceptability scale ranging from Clearly not acceptable to Clearly acceptable shown in figure 3. Acceptability increased significantly (p<0.5) for the two classes where mechanical ventilation was removed. The increase was less than significant for class 8a/9a that had a homeroom with mechanical ventilation also after renovation. Figure 5: Perceived change of some symptoms after the school renovation. Figure 4 shows the responses concerning improvement or worsening of unpleasant conditions. The sum is less than 100 % since some replies were unchanged. Most conditions improved after the renovation. Improvements were significant (p< 0.10) for Too high temperature and Too low temperature and significant (p<0.05) for Dry air and Dust and dirt. Other changes were lower than significant. The only annoying condition that worsened was Cold at feet. This was probably caused by cold air entering the room during periods of airing. 9 Renovation costs No information is available. 72
7 10 Experiences/Lessons learned 10.1 Energy use The average heating consumption before renovation was approx 3 times higher than after. A great part of the savings was due to increased insulation as required in the current building regulation. Much energy has been saved by hinged windows replacing mechanical ventilation Impact on indoor climate The school was in a poor condition before renovation. The mere fact that the school was finally renovated may have had a positive influence on the users. New and undamaged indoor surfaces, together with much improved daylight and contact with the surroundings through new and larger windows, may also have contributed to improved satisfaction. In spite of the very low ventilation rates and significant energy savings in the renovated school, measurements indicate that control of temperature and air quality improved slightly. The acceptability of the air quality improved significantly. It is quite possible that low emission construction products, increased room volume and demand control exercised by users, all together improved air quality. Despite rather low external temperatures during the measurement process, ventilation through windows was effective. The school is now running with significantly reduced environmental impact. Maintaining adequate air quality requires students to act regularly. This is in line with the idea that schools should prepare students to be able to take responsibility for their own health in an eco-conscious manner. Average CO 2 concentrations of around 1800 mg/m 3 or 1000 ppm both before and after renovation are rather high values. The users choice between air quality and the inconvenience of opening the windows determines the results. The air quality in the school is comparable to most other Danish schools Economics The gross construction costs including all the renovation done (insulation of thermal envelope and new constructions) were 6,027 DKK/m2 (804 EURO/m2). The total costs including design fees were 7,241 DKK/m2 (965 EURO/m2) Practical experiences of interest for a broader audience The school users were as good, or better, at obtaining comfortable temperature and air quality as the poorly maintained mechanical ventilation system with central automation Resulting design guidance Much energy may be saved in a school if hinged windows replace ventilation systems, automated control of window openings ensure frequent use and school users devote themselves to a coordinated effort for a good indoor climate. Increased ceiling height, use of materials with greater storage capacity for heat and air pollution, users motivated to share the responsibility for the quality of the indoor climate, and understandable and responsive buildings and installations are key issues in improving the indoor climate and reducing energy consumption in schools. 73
8 11 General data 11.1 Address of project Enghøjskolen, Hvidovre, Denmark 11.2 Existing or new case study Project initiation: Design completed: 1996 Renovation construction completed: 1999 Monitoring and evaluation completed: Date of report / revision no. August Acknowledgements Builder: Hvidovre Municipality Architects: Thure Nielsen and Rubow A/S. Consulting engineers: Birch & Krogboe A/S and Dominia A/S National, international support programmes: The Danish Ministry of Environment and Energy supported this study through its Energy Research Programme. Author (of this description): Lars Gunnarsen & Kirsten Engelund Thomsen, Danish Building and Urban Research 13 References 1. Ole Valbjørn, Jan Bach Nielsen, Lars Gunnarsen and Niels C. Bergsøe: Ventilation and air quality in office buildings (in Danish), SBI-Rapport 240, Danish Building Research Institute, Roman Meininghaus, Henrik Knudsen and Lars Gunnarsen: Measurement of diffusion and sorption properties for construction products, Proc. of EPIC 98, 2nd European conference on indoor climate in buildings, V 1 pp 33-38, Lyon, France, Birgitta Nordquist: Ventilation through windows A complement to normal ventilation? (in Swedish) Rapport TABK 98/1014. Lund University Lars Gunnarsen: Replacing mechanical ventilation with natural ventilation and increased user control an intervention study in a school. Proceedings of Healthy Buildings 2000, V2pp , Helsinki
Improving thermal insulation of concrete sandwich panel buildings
Improving thermal insulation of concrete sandwich panel buildings Jørgen Munch-Andersen Danish Building Research Institute, Aalborg University LCUBE conference, Vienna 17-18 April 2007 Outline A general
Energy savings in the residential area are essential in
Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations
IEA SHC Task 47 Renovation of Non-Residential Buildings towards Sustainable Standards
Date of revision: 15.6.2012 Osram Culture Centre Copenhagen, Denmark Valhalsgade 4, 2200 Copenhagen N 1. INTRODUCTION PROJECT SUMMARY Construction year: 1953 Energy renovation: 2009 No past energy renovations
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Dept. Building Environment Science &Technologies Politecnico di Milano Italy Research funded
Norwegian Tax Authority - Oslo Norway
1. INTRODUCTION Norwegian Tax Authority - Oslo Norway PROJECT SUMMARY Year of construction - 1980 No previous energy renovations SPECIAL FEATURES Main topics in the renovation are: High insulated pre fabricated
Energy Efficiency HOSPITALITY. www.energia.ie
Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real
Thermal and air quality effects on the performance of schoolwork by children. Field intervention experiments
Thermal and air quality effects on the performance of schoolwork by children David P. Wyon Technical University of Denmark Swegon Air Academy Leiden, NDL 07.04.2010 Field intervention experiments This
BUILDING ENERGY DEMAND AGGREGATION AND SIMULATION TOOLS A DANISH CASE STUDY
BUILDING ENERGY DEMAND AGGREGATION AND SIMULATION TOOLS A DANISH CASE STUDY P. Gianniou; A. Heller; C. Rode Department of Civil Engineering, Technical University of Denmark, Kgs. Lyngby ABSTRACT Nowadays,
Energy Efficiency. Bars & RestauRants. www.energia.ie
Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could
Exemplary Retrofitting of an Old School in Stuttgart - EROS -
Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
School in Schwanenstadt, Austria
School in Schwanenstadt, Austria 1. INTRODUCTION PROJECT SUMMARY - building period 1960s - numerous expansions SPECIAL FEATURES - Renovation to meet Passive House Standard - decentralized ventilation system
Green House, Hungary
Further information Skanska AB www.skanska.com Contact Noel Morrin, SVP Sustainability & Green Support [email protected] Green House, Hungary Case Study 109 Aspects of Sustainability This project
Priority School Building Programme
UPDATE Includes June 2013 changes to FOS Priority School Building Programme Making sense of the new Priority School Output Specification from the Education Funding Agency. How is the output specification
PROBIS SUPPORTING PUBLIC PROCUREMENT OF BUILDING INNOVATIVE SOLUTIONS
PROBIS SUPPORTING PUBLIC PROCUREMENT OF BUILDING INNOVATIVE SOLUTIONS Regione Lombardia ALER Bergamo Lecco Sondrio Treviglio via Dei Mulini n. 10/20 via Filzi n. 11/13 Prospectus Template provided by TEH-Ambrosetti.
Executive Order amending the Executive Order on the Publication of the Danish Building Regulations 2010 (BR10) 1)
Full text Executive Order amending the Executive Order on the Publication of the Danish Building Regulations 2010 (BR10) 1) 1. The following amendments shall be made to Executive Order no. 810 of 28 June
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)
Directorate for the Built Environment Building Standards Division
Directorate for the Built Environment Building Standards Division Energy Management Solutions Ltd Investigation of measures to improve the energy performance of a existing building: Retail JUNE 2009 Report
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
Klosterenga, Oslo, Norway, 1998-2000 page - 1
Klosterenga, Oslo, Norway, 1998-2000 page - 1 Introduction Klosterenga is an urban revitalisation project close to the city centre of Oslo. The 3 apartments were built with a focus on energy saving. Next
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...
DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS
DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS Ing. Maria-Anna Segreto LAERTE Laboratory - 1 EUROPEAN DIRECTIVE 2010/31/UE It 's well known that higher
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. A Diagrammatic representation of the relationship between the
HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM
01-147 The 2005 World Sustainable Building Conference, HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM Aleš KRAINER Prof. Dr. 1 Rudi Perdan 2 Gal Krainer 3 1 2 Faculty of Civil Engineering,
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
Parametric Analysis of School Classroom Typologies' Energy Performance
PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Parametric Analysis of School Classroom Typologies' Energy Performance MAUREEN TREBILCOCK
Investigation of sound insulation for a Supply Air Window field measurements and occupant response
Investigation of sound insulation for a Supply Air Window field measurements and occupant response Lars Sommer SØNDERGAARD 1 ; Søren Vase LEGARTH 2 1 DELTA, Denmark ABSTRACT The Danish Environmental Protection
Challenging the possibilities
Passivhus Norden 2013 Challenging the possibilities Olav Langenkamp, Architect ETH-MAA, Langenkamp.dk Architects, Tigervej 26 8400 Ebeltoft Denmark, [email protected] Martin Wikkelsø Brandt, Cand. Polyt.
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Innovative solution for heat recovery of ventilation air in older apartment buildings - with low intervention affecting the residents
Innovative solution for heat recovery of ventilation air in older apartment buildings - with low intervention affecting the residents Innovative solution for heat recovery of ventilation air in older apartment
Holistic Approach in Delivering Government Buildings The Low Carbon Concept
International Conference on Planning for Low Carbon Cities 22 May 2009 Holistic Approach in Delivering Government Buildings The Low Carbon Concept Ir. HO Sai-king, Assistant Director (Building Services),
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
The Reunion experience
Barcelona Workshop Experience on Net Zero Energy Buildings October 3rd 2012 1 The challenge of designing Net Zero Energy Buildings in Tropical Climates The Reunion experience Prof. François GARDE, PhD,
Energy Efficiency and Renewable Energy For Schools
Energy Efficiency and Renewable Energy For Schools Jesse Putzel & David Pitcher (energy conservation and solar centre) ecsc - who we are Environmental Charity involved in both energy efficiency and renewable
Case Study 13 Schools of Architecture and Design, Wellington tertiary education institute, New Zealand
Case Study Schools of Architecture and Design, Wellington tertiary education institute, New Zealand Winter Summer daylight intermediate, intermediate, climate temperate, oceanic altitude m heating degree
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Icopal Eco-Activ Product Range Overview. Noxite. Dalite Rooflights. Monarfloor Acoustics. ICOSUN Console. Sun-Activ. Therm X
Icopal Eco-Activ Product Range Overview Noxite Monarfloor Acoustics ICOSUN Console Therm X Dalite Rooflights Sun-Activ Icopal Eco-Activ Product Range The highly innovative Eco-Activ range provides architects
CO2 Emissions. Indirect CO 2. Emissions Electricity and Heat Production 25 % Direct Emissions AFOLU 24 % Energy 1,4% Buildings 6,4 % Industry 11 %
CO2 Emissions Direct Emissions AFOLU 24 % Buildings 6,4 % Transport 14 % 49 Gt CO2 eq (2010) Indirect CO 2 Emissions Electricity and Heat Production 25 % Energy 1,4% Industry 11 % Transport 0,3 % Industry
250 St Georges Tce, Perth, WA (QV1)
250 St Georges Tce, Perth, WA (QV1) Building Profile Building Construction date 1991 Refurbishment date Owner Building Size Refurbishment Team Building Management Awards Ratings QV.1, 250 St Georges Terrace,
Diego Ibarra Christoph Reinhart Harvard Graduate School of Design
Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #2 Load Schedules GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard Graduate School of Design OVERVIEW
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Air Conditioning, Comfort and Energy in India s Commercial Building Sector
Air Conditioning, Comfort and Energy in India s Commercial Building Sector THINK.CHANGE.DO Leena Thomas Richard dedear Rajan Rawal Ashok Lall PC Thomas University of Technology, Sydney Sydney University
Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX
Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Content Heating / Ventilation / Air Conditioning 3 The Right Room Climate 4 Optimised Energy Efficiency and well-being Room
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
Energy Management in Wuppertal
Energy Management in Wuppertal Organisation, Implementation and Financing Christian Gleim Gebäudemanagement der Stadt Wuppertal (GMW) 1 What do I want to tell you? Initial situation in Wuppertal Organisation
Aalborg Universitet. Energy upgrading measures improve also indoor climate Foldbjerg, Peter; Knudsen, Henrik Nellemose. Published in: REHVA Journal
Aalborg Universitet Energy upgrading measures improve also indoor climate Foldbjerg, Peter; Knudsen, Henrik Nellemose Published in: REHVA Journal Publication date: 2014 Document Version Publisher final
RESNET National Rater Test Study Guide Outline
RESNET National Rater Test Study Guide Outline The RESNET national home energy rating standard spells out a listing of the knowledge base and skills set for Home Energy Ratings. Trainers and Rating Quality
First Time Home Buyers Energy Efficiency Workshop Guide
First Time Home Buyers Energy Efficiency Workshop Guide Why is efficiency important when buying a home? Affordability: lower utility bills Environmental responsibility: reduces your carbon footprint and
ResearcH JournaL 2009 / VOL 01.01. www.perkinswill.com
ResearcH JournaL 2009 / VOL 01.01 www.perkinswill.com PERKINS+WILL RESEARCH JOURNAL / VOL 01.01 05. CONTEXT BASED DESIGN OF DOUBLE SKIN FACADES Climatic Considerations During the Design Process Ajla Aksamija,
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
Integrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
Report Date: 04/03/2014. Assessor: John Doyle Address: BLOCK K APT 108 SANDYFORD VIEW DUBLIN 18 BER: 106178106 MPRN: 10301589669
Report Date: 04/03/2014 Assessor: John Doyle Address: BLOCK K APT 108 SANDYFORD VIEW DUBLIN 18 BER: 106178106 MPRN: 10301589669 About this Advisory Report Energy use in our homes is responsible for almost
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING
THERMAL SCIENCE: Year 2015, Vol. 19, No. 3, pp. 865-880 865 ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING by Norbert L. HARMATI a*, Radomir J. FOLI] a,
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
A Roof Integrated Solar Heating System Without Storage
M. and W. Saman Sustainable Energy Centre University of South Australia Mawson Lakes Boulevard, Mawson Lakes, SA 5095, Australia E-mail: [email protected] Abstract A prototype of a roof integrated
U.S. Environmental Protection Agency. Business Decision: Manage Energy Costs
U.S. Environmental Protection Agency Business Decision: Manage Energy Costs EPA 430-F-06-008 April 2006 GETTING STARTED IS EASY. Start with simple, reliable, low-risk, high-return energy savers. 1 Change
3-D Modeller Rendered Visualisations
Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2
DIAGNOSING, BENCHMARKING AND TRANSFORMING THE LEED CERTIFIED FIU SIPA BUILDING INTO A NET-ZERO-ENERGY BUILDING (NET-ZEB)
DIAGNOSING, BENCHMARKING AND TRANSFORMING THE LEED CERTIFIED FIU SIPA BUILDING INTO A NET-ZERO-ENERGY BUILDING (NET-ZEB) Thomas Spiegelhalter Florida International University College of Architecture Miami,
Franciscan Monastery, Graz, Austria
Franciscan Monastery, Graz, Austria 1. INTRODUCTION PROJECT SUMMARY - first parts 1239 - main parts from 1250 to 1650 - protected monument SPECIAL FEATURES Mission of the Franciscans: conservation and
SELECTIVE GLAZING FOR SUN CONTROL
SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings
Net Zero Station Design for The Cooper Centre for the Environmental Learning in Tucson, Arizona: Improving the performance of existing buildings Alya Al-Hashim 1, Lena Spiric 2,and Nader Chalfoun 3 1,2
COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI
Proceedings of Healthy Buildings 2000, Vol. 2 675 COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI Mikko Saari 1, Juhani Laine 1, Sami Karjalainen 1 and Klaus Hamström
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
Data Collection Summary Report
Data Collection Summary Report Asilo Cologno Monzese Polo Territoriale per la Prima Infanzia con Asilo Nido 22/09/2011 The sole responsibility for the content of this report lies with the authors. It does
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is
Delivering on innovation and market uptake. Best-in-cases of nzeb. Ramon Pascual Bucharest May 8th, 2015
www.zebra2020.eu Delivering on innovation and market uptake. Best-in-cases of nzeb Ramon Pascual Bucharest May 8th, 2015 Outline nzeb Database Best in cases of nzeb Climates in Europe Preliminary results
VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING
VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEFINITION OF VENTILATIVE COOLING VENTILATIVE COOLING IS APPLICATION (DISTRIBUTION IN TIME AND SPACE) OF VENTILATION AIR FLOW TO REDUCE COOLING LOADS IN
Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:
PASSIVE Solar Design Solar Homes Catch the Sun Are you planning a new house? Discover how you can apply solar architecture principles to: keep your heating bills to a minimum enjoy the comfort of a warm
PROMOTION OF ENERGY EFFICIENCY THROUGH THE HOUSING MODERNISATION IN LITHUANIA
PROMOTION OF ENERGY EFFICIENCY THROUGH THE HOUSING MODERNISATION IN LITHUANIA Daiva Matonienė Vice-Minister Ministry of Environment Vilnius, Lithuania September,2013 RESIDENTIAL ENERGY EFFICIENCY 2 Lithuania
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi
Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction
Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study
The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study WARAPORN RATTANONGPHISAT 1,2,*, FEDERICO M. BUTERA 2, R.S. ADHIKARI 2 AND CHALERMPORN YOOPRATETH
Before You Start an Energy Efficiency Retrofit The Building Envelope
ABOUT YOUR HOUSE Before You Start an Energy Efficiency Retrofit The Building Envelope The building envelope is the outer layer of the building that separates the indoor living space from the outdoor environment,
Energy efficient buildings: The Swiss experience
Energy efficient buildings: The Swiss experience Chennai, October 7 th, 2010 Heinrich Gugerli, Head Sustainable Building Group [email protected] www.stadt-zuerich.ch/nachhaltiges-bauen City of
Energy Savings with Window Retrofits
Center for Energy and Environment Energy Savings with Window Retrofits Presentation to Energy Design Conference & Expo Duluth, MN February 25, 2014 Agenda v Background v Introduction: What are window retrofits?
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation
Connolly Hospital Blanchardstown makes rapid recovery on energy technology investment
Connolly Hospital Blanchardstown makes rapid recovery on energy technology investment Connolly Hospital, Blanchardstown (CHB) is a major teaching hospital and provides medical, surgical and support services
Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality
Energy Savings in High-Rise Buildings Using High-Reflective Coatings
Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per