A new design guideline for the heating and cooling curve in AHU of HVAC systems

Size: px
Start display at page:

Download "A new design guideline for the heating and cooling curve in AHU of HVAC systems"

Transcription

1 Document identification Type of documents: Glossary Cx process Project Tool Model Type of building: Type of commissioning: Initial-cx Re-cx Retro-cx Continuous-cx Glossary check: yes no MQC phase: Program Design Elaboration Realisation Operation Other remarks: A new design guideline for the heating and cooling curve in AHU of HVAC systems A method for the optimal adjustment of AHU in HVAC systems P.A. (Bert) Elkhuizen, H.C. (Henk) Peitsman TNO Building and Construction Research Delft The Netherlands KEYWORDS Control strategies, Building, Energy, Commissioning, HVAC ABSTRACT New Dutch office buildings are built under strict energy efficient legislation and are well euipped with insulation, condensing boilers, heat recovery systems, etc. Despite this, many buildings don t perform very energy efficiently and the comfort reuirements. This has led to a large number of complaints. The problem seems to be that common energy control strategies (heating/ cooling curves) are often used, most of the curves were based on buildings with low level of building shell heating resistance and no additional insulation and single glazing. When these control strategies are used in modern office buildings, too much energy is used due to a mismatch between heating and cooling demands. Energy savings of up to 35% can be realised without significant financial investments by devoting extra attention to the settings of the heating/ cooling curve in the central Air Handling Unit s (AHU s) of HVAC systems without loss of comfort. In most cases the number of complaints will also be reduced. The design method can be used in both new and existing buildings. The first part of this paper presents a brief description of the method used to realise this energy saving. The brief description follows with a practical example of this method. The intention is that the approach will generate a building-specific heating/cooling curve based on an energetic optimum between the demand for heating and cooling in the zone s. The input data used to generate the function cover the characteristics of the building, the organisation, and the HVAC euipment. A secondary effect for HVAC designers is that the way they design the type of installation can be changed. They will be able to see if their chosen HVAC system for the building design fits with the needs of the client. The new approach will be adapted for use in one of the most commonly used simulation programs for Dutch HVAC designers: VA 114. The program will generate the most energyefficient heating/cooling curve, but the designer will be able to change the function and will be given feedback about the effect of this on energy use. Figure 1 gives an example of a new heating/cooling strategy. Page: 1 of 26

2 BACKGROUND The majority of Dutch office buildings are euipped with HVAC systems that conditions the supply air in a centralised Air Handling Unit (AHU). A heating/cooling curve, as part of the control strategy, is used to condition the supply air to the zones. The common used settings to adjust the heating/cooling curve in most office buildings lead to problems relating to user comfort and excessive energy consumption. Even in the new office buildings, well build under the strict legislation, or in retrofit buildings the same problems occur and the predicted energy consumption or energy savings are far out of reach. Several studies on energy consumption confirm the existing gap between prediction and reality. Figure 1a presents visual the interaction between the central AHU and the cooling demand in the zones. Figure 1a: The control strategy determines the supply air temperature as a respond to the dynamic behaviour of the building The energetically optimised heating/cooling curve will help to decrease the existing gap between prediction and reality. The heating/cooling curves where for a long time no subject to further research and a forgotten subject. This project shows that it is a very interesting subject for research, since there is a strong relation between the actual heating/cooling curve and energy consumption and comfort. In the Dutch mild climate the need for space heating is reduced due insulation and airtightness, but on the other hand the need for room cooling is increased. During normal winter conditions or during summer conditions there seems no problem, there is a full load condition. But, with moderate temperatures there is a part load condition and a need for cooling and heating at the same time. Figure 1b shows a typical modern building heating and cooling demand profile. The demand for heating and cooling at the same time occur at 40% of the time. Figure 1b: Building related heating and cooling demand profile over a year period. (data points per hour) Page: 2 of 26

3 The control strategy determines how the HVAC installation responds to these conflicting energy demands. In the majority of the buildings there will be a contradicting heating and cooling supply at the same time, which will lead to excessive energy consumption. The development of control strategies stood still. The most common used control strategies are based upon knowledge from the past. These control strategies were developed during a time were the building had no insulation or double glazing, high internal heat loads, so the energy profile was clear. The standard control strategy fulfilled with no real problem, either you needed cooling or you needed heating. The uestion why the building should be controlled in that manner was never asked. The problem that nowadays occur with modern build office buildings or retrofit office building is that the control strategy doesn t fit the energy demands with the energy supply, too much energy is used due to a mismatch between demands and supply. Not only too much energy is used but there are also more comfort-related complaints than expected. In order to optimise the energy consumption and to reduce the complaints there should be much more attention to the control strategy and the heating/cooling curve. Despite many years of optimisation of single components, such as condensing boilers, there is no common knowledge about how to design your control strategy or how to design the heating/cooling curve. The fact is that there is no literature known about the relation between comfort, energy efficiency or energy consumption and heating/cooling curves. TNO Building and Construction Research developed the design method called Energetically optimised cooling/ heating curves, which allows designers and facility managers to design and check the optimal settings for their office buildings. The design method generates a buildingspecific heating/cooling curve for the centralised AHU system, which is optimally tuned to the building and the organisation occupying it. The optimal settings relate to the building's heating and cooling reuirements and the climate-control system's delivery of heating and cooling. Input data for the calculation method include building data, characteristics of the occupying organisation, and data relating to the climate-control system. Page: 3 of 26

4 1. INTRODUCTION Energy savings of up to 35% can be realised without significant financial investments by devoting extra attention to the settings of the central AHU in HVAC systems. The first part of this paper presents a brief description of the method used to realise this energy saving. The brief description follows with a practical example of this method. The second part describes in detail the methodology. 1.1 How is the calculation method used? The calculation method can be applied to office buildings yet to be designed and to existing office buildings. The calculation method can be used to: - Determine the energetically optimised heating/ cooling curve for individual buildings; - Estimate the possible energy saving; - Execute a uick scan for one building or large-scale building stocks; - Optimise the energy savings for other measures. 1.2 Who can use the calculation method? Customers for whom the calculation method is developed, are: (1) designers, (2) installers, (3) building managers, (4) TAB (Testing, Adjusting and Balancing) companies. Turnover temperature 25 Supply air temperature ['C] Standard Energetically Optimised heating AHU5 cooling AHU Transition range Outside air temperature ['C] Figure 1c: The new heating curve (T-outside = f(t-supply) of an AHU)) 1.3 How does the calculation method work? The calculation method is based on the hourly heating and cooling demand within the building, which can be determined using a building simulation program such the Dutch computer program VA114. TNO Building and Construction Research developed a simplified method, which was published in the Dutch ISSO publication 68. Input data for the calculation method include (1) building data, (2) characteristics of the occupying organisation, and (3) data relating to the climate-control system. 1.4 Turnover- or free temperature In general, when the outside temperature is eual to the Turnover temperature (figure 1c), no heating or cooling demand exists within the building. This is also called free temperature of the building. That means, no heating or cooling is supplied to the mechanical ventilation air. 1.5 Transition range The transition range (figure 1c) can be defined as the temperature interval for the outside temperature in which either a heating or cooling demand may exist. No heating or cooling is therefore added to the mechanical ventilation air. Page: 4 of 26

5 1.6 Standard heating/cooling curve A standard heating/ cooling curve such as often applied in practice does not take the abovementioned concepts (i.e. turnover temperature and transition range) into account. The mismatch between building and climate-control system is visualised clearly in figure Turn over temperature 00 Heating or cooling demand Outside air temperature Heating/cooling supply by standard curve Transition range Figure 2: Mismatch building and climate-control system. 2. An example from practice By paying additional attention to the settings of the HVAC systems, energy savings of up to 35% can be realised without large financial investments. This second part of the paper, using a example calculation, explains how this energy saving is realised in combination with an improvement in thermal comfort by means of a method developed by TNO Building and Construction Research. 2.1 Sample building This example relates to a recently completed office building (year of construction: 1998). A representative ground plan and the façade view are shown in figure 3. 22,8 m 14,4 m 68,4 m Figure 3: The ground plan and the façade of the selected building. Building - Gross Floor Area (GFA) : 6,895 m 2 - RC value building shell : 2.5 [m 2 K/W] - Window percentage exterior (North and South wall) : 40 % - Window system (HR+ glass) : U value glass = 1.5 [W/(m 2 K)] : ZTA value glass = 0.60 Page: 5 of 26

6 Organisation - Average internal heat production workspaces : 35 [W/m2 North East] (including freuency of use) HVAC system - Heated/cooled ventilation air, heating and cooling by means of 4-pipe induction system - Set point : winter = 22 C; summer = 24 C - Quantity of fresh air per person : 50 m 3 /h per person 2.2 Application of the method 'Energetically optimised heating and cooling curves' The energetically optimised heating and cooling curve is determined on the basis of the relation between the hourly heating and cooling reuirements and the outside temperature. The form of the energetically optimised heating and cooling curve diverges considerably from the standard heating and cooling curve that is generally used in actual practice (see figure 2). 2.3 Energy saving Energy saving 50% 40% % % 10% 0% Heating Cooling Heating 2.4 Improved comfort The comfort improvement is visualised in figure 4 by comparing the occurring room temperatures in the case building to the temperatures specified for the standard heating and cooling curve (in red colour) and the energetically optimised heating and cooling curve (in blue colour). In the situation with the standard heating and cooling curve, room temperatures of 24 C (set point cooling) occur at an outside temperature of 4 C. In the case of the energetically optimised heating and cooling curve, these room temperatures do not occur until an outside temperature of 10 C is reached. High room temperatures in a winter situation (4 C) will lead to complaints regarding the thermal comfort. Local cooling will be active to reach the comfort level. The number of comfort-related complaints is reduced considerably when the Cooling 35 W/m2 50 W/m2 Internal heat load/ production The energy saving that can be realised by adjusting the heating and cooling curve from the standard curve to the energetically optimised heating and cooling curve for the case building is as follows: - For heating 13 %, and - For cooling 10 %. If an organisation with an average internal thermal load eual to the thermal load as specified in the operational reuirements (= 50 W/m 2 N.E.) is occupying the same sample building, the energy saving is even higher (36 % for heating and 19 % for cooling). energetically optimised heating and cooling curve is applied. Inside Air temperature ['C] By Local cooling ['C] Setpoint Cooling Setpoint Heating Outside Air temperature ['C] Figure 4 Comfort improvement. Page: 6 of 26

7 W arm te- en koelbehoefte tijdens kantooruren Tbuiten [C] A40-E-M4-NL-TNO-1 3. Introduction Detailed description of the Energetically Optimised Heating/Cooling Curves in HVAC systems 3.1 Description of the method The method is build up in 5 steps. The separate steps are presented in figure 5. Step_1 Collect all necessary data (building properties and design data) for the project Step_2 Determine of the heat- and cooling demand of the building as a function of the outside air temperature Energiebehoefte [0,1 x kwh] Step_3 Determine the basic shape/ form of the new heating-/ cooling curve Step_4 Discount other aspects of the HVAC system (e.g. recirculation heat recovery) in the heating-/ cooling curve Step_5 Discount other preconditions/ limitations (draught, moisture, condensation) in the heating-/ cooling curve Figure 5: The steps to be executed for an optimised Heating/ Cooling curve. In this paragraph a brief description is given of the steps to be executed to find an optimised Heating/ Cooling curve of HVAC systems. The following paragraph provides a detailed explanation of the mentioned steps. Step 1 is based on the collection of the necessary Project data which are relevant for the determination of the Energetically Optimised Heating/Cooling Curve. The project parameters/data are related to (1) the building properties, (2) the type of HVAC system, (3) the building user. Step 2 is the determination of the heating/cooling demand of the building as function of the outside air temperature. The determination of the heating/cooling demand of the building is a complex analysis and is based on the use of building simulation programmes. Because not everybody is able to work with sophisticated building simulation programmes, a simplified method has been developed to solve this problem. In Step 3 the basic shape of the Energetically Optimised Heating/Cooling Curve is determined and is thus a description of the heating and cooling production of the HVAC system. This will be done on the outcome of the calculated heating and cooling demand as calculated in step 2. The outcome of step 3 is: (1) the calculated value of the turn-over temperature (free temperature) of the building. The turn-over Page: 7 of 26

8 temperature is the temperature where no heating and cooling is reuired. (2) the transition range and (3) the sensitivity of the heating and cooling demand in relation to the outside air temperature. In step 4, the energetic contribution of the different HVAC components (AHU, Fans, Heat recovery, etc.) to the basic shape (step 3) of the Energetically Optimised Heating/Cooling Curve will be determined. In step 5 account is taken of the physical boundary conditions of the HVAC system. It gives the limit within which the Energetically Optimised Heating/Cooling Curve could be defined without complaints being received from the users of the building. If the boundary conditions as calculated in this step hinder the right choice of the heating/ cooling curve, it may be necessary that the design conditions of the HVAC system must be adjusted. In this case we will have to go back to step Description of the method Energetically Optimised Heating/Cooling Curves in HVAC systems The description of the method focuses on the following HVAC types: Central heating and cooling of the mechanical ventilation air by AHU; Decentralised heating and cooling in the zones by e.g. induction units (local end -units/ terminal units) The method contains the following steps: Step 1 : Collection of the necessary Project / boundary conditions The following project data must be collected for each building part or for each zone: Building properties Gross Floor Area (GFA); Functional effective Floor Area (FFA); Area of facades, roofs, first floor; Orientation of facades; Window area of each facades; Percentages of window area in the facades. Building design physics Rc- value of the building shell Window system/ type U- value glass g- value glass U- value window frame Organisation/ Building user Maximum number of persons Internal thermal heat production zones/ workspaces Average Maximum Terms of references (Programme of reuirements) Internal thermal load corridors and other spaces; Number of persons per space Page: 8 of 26

9 HVAC system Type/ concept of central HVAC system Type decentralised (zone) HVAC end units Setpoint winter period Setpoint summer period Amount of fresh air per person total Humidity Amount of recirculation of return air Exhaust of air by lighting units Fan properties: Fan pressure of supply fan or electrical power capacity Fan pressure of exhaust fan or electrical power capacity Only in the case of existing buildings Capacity heating coils AHU Capacity cooling coil AHU split up in latent cooling and perceivable cooling. Current heating/cooling curve Step 2 : Determination of the heating/cooling demand of the building as function of the outside air temperature. A. Determine the turn-over point temperature (see figure 1 and 2) The value of the turn-over point temperature will usually be between 5 C and 15 C. All heat sources and heat flows are included to determine the turn-over point. (See appendix system boundary for the heating and cooling reuirement). The turn-over point temperature is determined by taking the average of the setpoint temperature for heating and the setpoint temperature for cooling, minus a ratio between heat gains (internal thermal heat production and solar energy) and the overall heat losses of the building to the outside air (transmission and ventilation). This is expressed in formula [1]: { φ + * A * g }* η INTERN; AVG SUN; AVG GLASS GLASS HEAT DISSIPATION TO = I; AVG [1] a* U * ALOSSES + VENT ; OUTSIDE* ρ * CP TO = the turn-over point(or free) temperature [ C] = the average AHU setpoint temperature for summer and winter period [ C] I ; AVG φ INTERN ; AVG = the average internal heat production [W] ; = the average daily solar radiation [W/m2] SUN AVG A GLASS = total glass surface area for the building section [m2] g = g value of the glazing (not including switching sun blind) [-] GLASS η HEAT = 0,64 = utilisation factor for the heat gains [-] φ = the heat dissipation of HVAC components [W] DISSIPATION + φ Page: 9 of 26

10 a = weighting factor [-] a = 1 for constructions that separate the building (section) from the outside air or water a = 1/(1+U) for constructions that separate the building (section) from the ground or from a crawling space a = 0 for constructions that separate the building (section) from a heated area a = 0.5 for constructions that separate the building (section) from an unheated area U = average thermal transmittance coefficient of the building shell (incl. glass) [W/m2.K] A = total loss surface of the building (section) [m2] Losses VENT ; OUTSIDE = fresh air uantity of mechanical ventilation air [m3/s] ρ = 1,2 = specific mass of the air [kg/m3] C P = 1000 = specific heat of air [J/kg.K] The expression: a * U * ALOSSES in euation [1] is eual to the specific heat loss through transmission as defined as the variable H TR in paragraph 6.4 of the Dutch standard NEN 2916 (Energy Performance of NON Residential buildings). This standard is available in English (1 pages). NB: Particularly for the management of the HVAC installation, it is advisable to keep the derived building data so that they are available to interested parties. These are the building properties relating to Energy : 1) the heat transmission ( a * U * ALOSSES ), 2) the total solar energy transmission of the glass ( A GLASS * ZTAGLASS ) and 3) the total necessary energy for the fresh air contribution for mechanical ventilation ( VENT ; OUTSIDE * ρ * CP ). It is often difficult to re-determine these data (no longer available) or extremely labour-intensive. If the details are directly available the heating/cooling curve can be adjusted more uickly if necessary. Taken on average, the figure value for the entrance of solar radiation is expressed in formula 2: 80* Z SUN ; AVG = ORIENTATION [2] Z ORIENTATION = orientation factor of the solar radiation. The following can be applied for a building or building section with opposite orientations: Z ORIENTATION =1.0. If the building or building section comprises several orientations, a glass surface area average orientation factor can be determined. For each orientation a value for Z ORIENTATION can be applied as shown in table 1. SUN ORIENTATION ORIENTATION FACTOR N 0.6 NE 0.7 E 0.9 SE 1.1 S 1.3 SW 1.3 W 1.2 NW 0.9 Horizontal 1.6 Page: 10 of 26

11 Table 1 : Values for the orientation factor Z ORIENTATION The formula for the turn-over point temperature can be worked out in more detail and all terms divided by the Gross Floor Area (GFA) yield in formula [3] in which as well as all properties of the building and the organisation the building form is also clearly presented as a variable. TO φintern ; AVG AGLASS φdissipation { + SUN; AVG * * gglas}* ηheat + = GFA GFA GFA I ; AVG [3] A LOSSES VENT ; OUTSIDE a* U * + * ρ * CP GFA GFA GFA = Gross Floor Area of the building (section) [m 2 ] φ /GFA = internal thermal heat production per m 2 gross floor area. [W/m 2 ] INTERN;AVG ; /GFA = the fresh air contribution (outside air) to the mechanical [m 3 /s.m 2 ] VENT OUTSIDE ventilation per m 2 floor area (comparable with the reuirements of the Dutch Building Decree for air circulation). Note: The terms A GLASS /GFA and A LOSSES /GFA depend importantly on the building shape. The term A LOSSES /GFA is designated as the shape factor. Possible values for the shape factor that are achieved in practice are given in figure 6. 6 Building shell losses / GFA Gross Floor Area (GFA) Figure 6 : Practical values for the shape factor It can be deduced from figure 6 that, especially for small buildings (GrossFloorArea < 2500 m 2 ), the effect of the shape factor is significant and that the shape factor partly determines the turn-over point temperature. For buildings with a GrossFloorArea exceeding 5000 m 2 the shape factor will be 0.5 to 1.0. The term φ DISSIPATION (see formula [4]) represents the heat dissipation of the HVAC components. This could include, for instance, heat dissipation through ventilators and heat that gets into the HVAC system due to armature extraction taking place in the lighting. Page: 11 of 26

12 φ = φ + φ * R + R [4] DISSIPATIO N DISSFAN1 DISSFAN 2 φdisslight * φ DISSIPATION = the heat dissipation of HVAC components [W] φ = the heat dissipation of ventilators in supply channel or area [W] DISSFAN1 φ = the heat dissipation of ventilators in the exhaust channel [W] DISSFAN 2 φ DISSLIGHT = the heat extracted in the lighting armatures [W] R = the recirculation factor (see step 4) [-] Ventilators Ventilators are normally used in the HVAC system to transport the centrally conditioned air in the AHU to the rooms. Ventilators are also used in some types of local systems (e.g. fan coil units). These ventilators use electrical energy that is partly fed back into the building as heat. The thermal energy emitted by the ventilators no longer necessarily has to be provided by the central AHU in the heating season. In the cooling season the same amount of thermal energy does however have to be extracted additionally in the central AHU. Q Q = Σ 0,65* P ) = Σ( * dp ) [5] DISSFAN1 ( FAN ; EPOWER;1 VENT ; TOTAL SUPPLY = Σ 0,65* P ) = Σ( * dp ) [6] DISSFAN 2 ( FAN; EPOWER;2 VENT ; TOTAL SUPPLY P FAN;EPOWER;1 = electrical power (capacity) of all ventilators in room or supply channel [W] P FAN;EPOWER;2 = electrical power (capacity) of all ventilators in the exhaust channel [W] 0,65 = the efficiency of the ventilator [-] ; = total air uantity of mechanical ventilation air [m 3 /s] VENT TOTAL dp SUPPLY = ventilator pressure of the supply ventilator(s) [Pa] dp = ventilator pressure of the exhaust ventilator(s) [Pa] EXHAUST Lighting armature extraction Part of the convection heat yielded by the switched-on lighting emitted to the ventilation discharge air (circa 50%) is emitted via the armature extraction. The heat emitted by convection is a fraction (average approx. 68%) of the lighting energy. The temperature of the ventilation discharge air increases as a result of the extracted heating light. There are a number of circumstances in which this emitted lighting output is supplied to the air supply circuit and thus affects the heating/cooling curve. This is the case in the event of recirculation and with the application of heat recovery. The expression of the light contribution is given in formula [7]. φ = Σ 0,34* ) [7] DISSLIGHT ( P LIGHT ;EPOWER φ DISSLIGHT = the heat extracted from the lighting armatures [W] P LIGHT ; EPOWER = average switched on lighting capacity [W] 0.34 = is the convection factor of the lighting (0.68) multiplied [-] by the extraction output from the armature (0.5) Page: 12 of 26

13 B. Determining the derivative of the heat/cooling demand as function of the outside temperature (see figure 2 and 8). The average slope of the derivative of the heat demand as function of the outside temperature can be expressed in: Slope H:. The average slope of the derivative of the cooling demand as function of the outside temperature can be expressed in Slope C:. These have been placed on par with each other for the simplified calculation method. The derivative of the heating and cooling demand of the building as a function of the outside temperature is determined using the formula [8]. Slope = Slope = a* U * A * ρ * C )*1.25 [8] h; φ C; φ ( LOSSES + VENT ; OUTSIDE P Slope H :φ = average slope of the heating demand as function of the outside temperature [W/ C] Slope C:φ = average slope of the cooling demand as function of the outside temperature [W/ C] a = weighting factor [-] a = 1 for constructions that separate the building (section) from the outside air or water a = 1/(1+U) for constructions that separate the building (section) from the ground or from a crawling space a = 0 for constructions that separate the building (section) from a heated area a = 0.5 for constructions that separate the building (section) from an unheated area U = average heat transmission coefficient of the building shell [W/m 2.K] A LOSSES = total loss surface of the building (section) [m 2 ] VENT ; OUTSIDE = fresh air uantity from mechanical ventilation air [m 3 /s] ρ = 1.2 = specific mass of the air [kg/m 3 ] C P = 1000 = specific heat of the air [J/kg.K] 1.25 = is the correction factor for static to dynamic heat balance and accounting for the energy losses as a result of air infiltration. The heat flows that are linked to the outside temperature are the heat losses resulting from transmission and ventilation of outside air. This dependence of the heating/cooling demand on the outside temperature must be translated into an increase in the temperature of the ventilation flow of fresh air (the effect of recirculation is accounted for in step 4). The slope is therefore a ratio between the sum of the overall heat losses as a result of transmission and ventilation of outside air divided by the heat losses as a result of ventilation (see [9]): Slope H ; T ( a* U * ALOSSES + VENT ; OUTSIDE * ρ * CP ) = SlopeC; T = *1.25 [9] * ρ * C VENT ; OUTSIDE P Slope : = average slope of temperature rise to the outside temperature [ C/ C] H T Slope : = average slope of the temperature reduction to the outside temperature [ C/ C] C T C. Determining the size of the transition area The size of the transition area for the building section is determined by variations in the thermal load resulting from the entrance of solar radiation and the difference in set points for heating and cooling. The determination of the heating curve as described here is for a building (section) that consists of a number of separate areas. Up until now the average internal heat production of all areas within the building Page: 13 of 26

14 (section) has been assumed. There can however be substantial mutual differences between the rooms in the building (section). (See figure 7). 1 person absent 2 persons AHU 1 person Average presence = 50% absent 2 persons = room with minimal heating demand = room with minimal cooling demand Figure 7 : The mutual differences between rooms The reuired level of comfort has to be brought about at all times for each room in the building (section). A worst-case scenario must be assumed to compensate for this dependence on rooms. This can be achieved by basing the calculation of the heating curve in the heating season on a minimum heating reuirement (with eual rooms this is the space with maximum internal thermal heat production) and the calculation of the cooling curve in the cooling season on areas with a minimum cooling reuirement (with eual rooms this is the room with minimum internal thermal heat production). This is processed into this methodology by assuming the maximum internal thermal heat production for the winter season and the minimum internal heat production for the summer season. The result of this is that the size of the transition area increases. This increase is related to the degree of mutual differences in internal thermal heat production per room (expressed in the variable F VAR ). The total size of the overall transition area can be determined as follows [10]: d TRANSITION {2.0* SUN ; AVG * AGLASS * gglass + φintern ; MAX * FVAR}* ηheat = + ( SET ; SUMMER SET ; WINTER ) [10] a* U * A + * ρ * C LOSSES VENT ; OUTSIDE P d TRANSITION = temperature interval size of the transition area [ C] F VAR = factor that indicates the spread between thermal internal heat production [-] load per room mutually = setpoint temperature in the heating season [ C] SET ;WINTER SET ;SUMMER = setpoint temperature in the cooling season [ C] Practical values for the size of the transition area vary (depending on the specific project conditions) between 5 C and 15 C. The average presence of people in a building provides information about the average internal thermal heat production. The maximum number of people in a room provides information about the concurrence of people (and therefore the thermal heat production) in the room. For a building with one person rooms, the spread of the internal thermal heat production will be large in each room since this depends on whether or not that person is present in the room. Page: 14 of 26

15 The spread of the internal heat production will reduce in keeping with the increase in people in the room. The biggest spread is found between a fully-occupied room (Ф INTERN;MAX ) and an empty room (Ф INTERN = 0). The spread of the internal heat production per room is expressed as the variable F VAR [11]. F VAR max min = [11] max F VAR = factor that indicates the spread between thermal heat production per room mutually [-] MAX = the maximum internal thermal heat production found in a certain room per m 2 area [W/m 2 ] = the minimum internal thermal heat production in a certain room per m 2 floor area [W/m 2 ] MIN For a single-person room this will be : F VAR = 0.5 to 1.0 Note: This is based on an eual distribution of the rooms with/without presence through the building. Because of the mutual heat exchange between the rooms (via open doors)the value of F will not be eual to 1.0 but will be lower. For rooms designated for more than one person the value of F VAR will be between 0.0 and 0.5. For large rooms with many work stations (e.g. open plan offices) the value of F VAR will be 0.0. VAR The figure values of F VAR given here are no more than indicative. The value of F VAR will have to be determined with the given formula for each individual situation. The limit values for the outside temperature to which the transition area applies are given by the temperatures L and H. The accompanying values L and H are determined by [12] and [13]: dtransition L = TO 2 [12] dtransition H = TO + 2 [13] L = low transition temperature [ C] H = high transition temperature [ C] KP = the turn-over point temperature [ C] d = temperature interval size of the transition area [ C] TRANSITION Step 3 : Determining the basic shape of the optimum heating/cooling curve The basic shape of the heating/cooling curve is derived from the variables that are determined in step 2. These variables are shown in figure 8. The red/blue line shows the basic shape of the heating and cooling of the ventilation air (outside air part). This basic shape indicates the extent to which the fresh outside air has to be conditioned to insure that the supply temperature is altered in such a way that the uantity of heat or cold added to the air is eual to the minimum reuirement for heat and cooling in the building (section). Page: 15 of 26

16 d = warming up of supply air AHU (K) Slope H; Outside air temperature E (ºC) L TO H Slope C; Figure 8: The basic shape of the desired heating and cooling of the ventilation air. In view of the fact that the heating/cooling curve is not expressed in temperature differences but in actual temperature levels, the desired heating and cooling must be added to the outside temperature. This is shown in figure 9. The dotted line is the Y=X line, which means that the base is eual to the outside temperature. To add the desired heating or cooling the basic form (see figure 8) is added to the Y=X line. 40 Supply air temperature AHU ( ºC) 10 Slope H; Y=X Slope C; E (ºC) Outside air temperature L TO H Figure 9 : The basic shape of the heating/cooling curve Page: 16 of 26

17 3.2.4 Step 4 : Discounting aspects of the air-conditioning system The steps given below relate to the central AHU of the HVAC system, which means that all zones belonging to an AHU have to be taken together. For each AHU a choice has to be made (in view of the underlying zones and the accompanying limits for heating/cooling curves) regarding which heating/ cooling curve is to be continued in the analysis. If one AHU is present in each zone, the analysis for each zone can be continued. A number of aspects of the HVAC system that affect the heating and cooling supply have not yet been included. These aspects are as follows: heat recovery (affects the heating and cooling supply in the AHU). recirculation (affects the temperature level of the heating/cooling curve). Heat recovery Heat recovery is an alternative for the AHU to apply the desired conditions to the ventilation air with the advantage that no primary energy is reuired for the recovered heat or cold. When heat recovery is applied, the fresh outside air is pre-heated or pre-cooled by heat recovery from the ventilation exhaust air. The uestion of whether or not to operate heat recovery is generally determined by the temperature difference between the outside air and the ventilation exhaust air. Reasoning from the perspective of the preceding description of the heating and cooling demand, it can be stated that this is not the correct regulation criterion. It is also the case with heat recovery that no more heat or cold must be fed to the mechanism that the heating or cooling reuirement prevailing at that moment in time. It is therefore important to make sure that when the heat recovery system is activated the optimum energetic heating/ cooling curve is not exceeded and/or that the cooling curve is not fallen short of. The energetic effect of heat recovery and the areas in which this should be activated is shown in figure 10. The heat recovery system may only be activated if water humidification (adiabatic) is applied so that the fall in temperature in the air humidifier can be compensated with the extra recovered heat. The example given in figure 10 is based on a situation in which the optimum energetic heating/cooling curve can be achieved without having to make adjustments under the influence of the filters from STEP 5. Heat recovery can achieve savings because the recovered heat or cold that is added to the fresh air no longer has to be fed into the AHU. d = warming up of supply air AHU by use of heat recovery unit (K) Heat recovery (HR) 0 heat recovery ON maximum L heat recovery ON, between 0-100% TO η H HR heat recovery OFF *( Exhaust E ) Outside air temperature E (ºC) Exhaust heat recovery ON maximum Page: 17 of 26

18 Figure 10: The effect by use of a heat recovery system Recirculation Recirculation can be used to make sure that the temperature difference between the supplied air and the room/ zone air does not become too big. Recirculation of air does not affect the building's heating and cooling reuirement, and therefore has no influence on the heating and cooling supply uantity as given in step 2 (which is the building's pure heat balance without taking account of the comfortable supply temperatures). The energy consumption for heating and cooling will therefore not be affected by recirculation (assuming that the amount of fresh outside air remains unchanged). It is possible that the ventilators will reuire a higher capacity for recirculation, which will result in an increase in the energy used for the ventilators. If recirculation is applied, it will be necessary to increase the mixing of the fresh outside air and the recirculation air. The final supply temperature will therefore consist of a mixture of the temperature given in figure 9 and the temperature of the recirculation air. The value of the exhaust temperature is eual to: EXHAUST φ + φ DISSFAN 2 DISSLIGHT = I + [14] VENT ; TOTAL * ρ *CP EXHAUST = temperature of the mechanical discharge air [ C] I = the room/ zone temperature [ C] (make a distinction between heating and cooling season) φ = the heat dissipation of ventilators in exhaust channel [W] DISSFAN 2 φ DISSLIGHT = the heat extracted at the lighting armatures [W] ρ = 1,2 = specific mass of the air [kg/m 3 ] C P = 1000 = specific heat of the air [J/kg.K] The level of recirculation is expressed in the recirculation fraction R: R VENT ; TOTAL VENT ; OUTSIDE = [15] VENT ; TOTAL R = the recirculation factor [-] ; = total air uantity of mechanical ventilation air [m 3 /s] VENT TOTAL ; = fresh air uantity of mechanical ventilation air [m 3 /s] VENT OUTSIDE The heating and cooling curve, including the recirculation air, can be calculated as indicated in figure 11. Page: 18 of 26

19 Supply air temperature AHU (ºC) 40 Basic shape Heat Exhaust (1-R) (R) Outside air temperature L TO E (ºC) H Exhaust Figure 11: Calculating the heating/cooling curve, including recirculation air The example given in figure 11 is based on a uantity of recirculation air that is eual to the amount of outside air. In this case, the recirculation factor R is 0.5. The effect of the recirculation factor R is shown in the figure. The resulting air temperature (= green dotted line) is determined on the basis of the course of the temperature of the fresh outside after treating for heat or cooling reuirement (= red/blue line) and the course of the exhaust temperature (= purple dotted line) using the recirculation factor R. The heat dissipation of the supply ventilator must be added to calculate the final heating/cooling curve. The level of the heating of the ventilation air can be calculated as follows: d SUPPLY, FAN = dpsupply /10 [16] = heating up of the supply air resulting from the supply ventilator [K] d SUPPLY, FAN dp SUPPLY = ventilator pressure of the supply ventilator [Pa] 10 = 10 = heat capacity of the air [J(/m3.K)] Use of free cooling In the greater part of the range of the outside temperature, it is advantage from a minimum energy consumption viewpoint to ventilate a minimum necessary uantity of fresh air. If reuired, the total air flow can be increased with a share of recirculation air. For a specific area in the temperature range of the outside temperature, it is worthwhile to have the amount of fresh outside air increased. This makes it possible to make use of what is known as 'free cooling', which makes optimum use of the cooling capacity of the outside air. There are two conditions that 'free cooling' has to meet: there is a cooling demand in the building (section) the outside temperature is lower than the exhaust temperature. The temperature area that meets both conditions and in which free cooling can be applied is the temperature area of the outside temperature between the high temperature of the transition area H and the exhaust temperature EXHAUST. Page: 19 of 26

20 The desired settings of the heating/cooling curve are not affected by the application of free cooling (the total air flow remains constant) Step 5 : Discounting all preconditions and limitations In order to finally calculate the heating/cooling curve, it is desirable to indicate which areas are still free to select the temperature level without this being accompanied by extra energy consumption (see steps 2 to 4) of that the heating/cooling curve leads to comfort complaints or other problems in the building. Use is made of filters in step 5 to prevent this from happening. These filters will indicate which temperature areas are undesirable for certain reasons. Filter 1 Filter relates to the minimum heating and cooling demand aspect of the building (see steps 2 to 4). The analysis of the building's heating and cooling reuirement makes it possible to define a temperature area of the central supply air in which the heating/cooling curve must be NOT located from the viewpoint of minimum energy consumption. This is shown in more detail in figure 12. The areas shaded blue and red are 'undesirable' (forbidden) because these areas no longer meet the condition of minimum heating or cooling demand. The green line in figure 11 forms the basis for the content of filter 1 (see step 4). The example given in figure 12 is based on mechanical ventilation without recirculation (R=0). Supply air temperature AHU (ºC) 40 Forbidden zone heating demand Slope C; 10 Slope H; Forbidden zone cooling demand Outside air temperature E (ºC) L TO H Figure 12: Filter 1, which is determined by the building's heating and cooling reuirement pattern. Page: of 26

21 Filter 2 Filter 2 is based on preconditions that are often set for technical reasons. These preconditions vary between projects. For this reason, the preconditions must be set individually for each project. The explanation given below is based on a model situation. Draught risk Comfort complaints resulting from draughts can be caused by the temperature difference between the supply temperature and the ambient temperature being too great. The risk of draughts depends significantly on the type of end device used. comfort criteria If the effect of turbulence and the temperature gradients is neglected, it will generally be the case that the following criteria must be operated for the air temperature and the air velocity: summer: Operative < 26 C and v < 0. m/s; (PMV = +0.5) winter: Operative > C and v < 0. m/s. (PMV = -0.5) Cooling and heating in the rooms can be achieved by mixing cold air or warm air with the ambient air. The end devices/ terminal units (air supply grids, fan coil units, induction units, etc.) are determinative for the air velocities and the distribute of the temperature in the room. This is of course within the restrictions of the room geometry, the positioning options and the necessary capacities (and/or temperature differences). Air supply grid The limits that can be set for the maximum and minimum temperatures of the supply air depend significantly on the specific situation (size of room, position of air supply grid, etc.) For this reason, the example is based on an average situation. Assuming the customary offices and the current air supply grid types, the design values given below are applicable to the maximum and minimum temperatures of the supply air. TYPE OF GRID TEMPERATURE DIFFERENCE BETWEEN THE SUPPLY AIR AND THE AMBIENT AIR [ C] Minimum (cooling) maximum (heating)* Wall grids Wall grid Ceiling grids Line grid Induction grid Vortex grid * The maximum temperature of the supply air is not critical. As things stand, when heating, a temperature difference higher than +10 C will not be selected. When selecting the air supply grid, account must be taken of matters such as the circulation multiple to be achieved. The maximum circulation multiple for a line grid is approximately 15. For a vortex grid, however, the circulation multiple can be a maximum of 50 to guarantee comfort. other end devices/ terminal unit The other end devices such as radiators, fan coil units, induction units and climate ceilings do of course have a considerable effect on the comfort aspect. For the fan coil units and induction units installed in the ceiling, the centrally conditioned ventilation air has already been mixed with ambient air that has been extracted from the room. The resulting temperature from both of these units will from the viewpoint of the draught risk resulting from an excessively large temperature difference between the supply Page: 21 of 26

22 temperature and the ambient temperature be lower than the units fitted to the wall in which the air is supplied to the habitation zone. Supply air temperature AHU (ºC) terminal unit Maximum over (surplus) temperature Maximum under temperature terminal unit I Outside air temperature E (ºC) TO Figure 13 : Filter 2 relating to the draught risk section Humidification in the winter period When humidifying, the air will have to be humidified to a moisture content of 5 to 6 g/kg. With an average moisture production level in the building of 1.5 g/kg ( =7 g/kg), at a room/ zone temperature of 22 C the relative humidity (RH) will be eual to approx. 40%. Following the humidification battery in the AHU there will be an RH of approx. 90%. To achieve 5.5 g/kg with RH=90%, the air temperature (assuming steam humidification) after the humidifying battery will have to be at least 7 C. Dehumidifying in the summer situation During the summer period, cooling to a minimum of 16 C (11.5 g /kg) must be applied in connection with dehumidifying the outside air. At an average humidity production of 1.5 g/kg ( =13 g/kg) and a room/ zone temperature of 24 C, the relative humidity will be 70%. If the ventilator dissipation is discounted, the supply temperature is eual to C. 40 Supply air temperature AHU (ºC) forbidden zone de-humidify (summer) forbidden zone humidify (winter) Outside air temperature E (ºC) Page: 22 of 26

23 Figure 14 : Filter 2, relating to the section humidifying and dehumidifying If filter 1 and filter 2 are combined, this results in a new filter that is shown in figure 15. Condensation risk Pipes For the end devices/ terminal units that are supplied with preheated or cooled water, temperature range under which they are mainly applied can be defined. The following temperature ranges are the most current ones: LTC MTC HTC LTH HTH radiators X X fan coil units X X X induction units X X X climate ceilings X X X X Cooling LTC: low temperature cooling (6-12 C); MTC: medium temperature cooling (12-16 C); HTC: high temperature cooling (16 - C); Heating VLTH: very low temperature heating (< 35 C) LTH: low temperature heating (35-45 C); MTH: medium temperature heating (45 55 C) HTH: high temperature heating (< 55 C). Air ducts The condensation risk in air ducts is partly determined by the surface temperature of the air ducts. This surface temperature is determined by the air temperature of the mechnical ventilation air, which is created by the central AHU. This air temperature is the result of the analysis described in this chapter. The condensation risk on pipes and on ducts can be estimated by making an assessment of the dewpoint temperature (which is an indicator of the absolute humidity) in the room and comparing it with the surface temperatures of pipes and ducts. If the surface temperature falls beneath the dewpoint temperature of the room/ zone air, condensation will occur. The air humidity in the room is determined by the air humidity of the mechanical ventilation air, the air humidity of the outside air (natural ventilation and infiltration), the moisture production and the moisture accumulation in the walls. Since the condensation risk depends greatly on the project-specific conditions (especially the air humidity achieved in the room), no further details of this section are given. It is however advisable always to make a risk assessment for condensation. Figure 15 shows the result of filter 1 and filter 2. Page: 23 of 26

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Adaptive strategies for office spaces in the UK climate

Adaptive strategies for office spaces in the UK climate International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Comparison between Decentralised and Centralised Air Conditioning Systems

Comparison between Decentralised and Centralised Air Conditioning Systems Comparison between De and Centralised Air Conditioning Systems (Summary) FassadenSystemLüftung FassadenSystemLüftung Telephone +49/ 28 45/ 2 02-711 GmbH & Co KG Telefax +49/28 45/2 02-2 25 Heinrich-Trox-Platz

More information

How To Get A Passive House

How To Get A Passive House Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Air Conditioning in Green Office Buildings?

Air Conditioning in Green Office Buildings? Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation

More information

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help?

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help? HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help? Proceedings of Healthy Buildings 94 Ben Bronsema, Consulting Engineer ONRI Ketel Consulting Engineers Ltd, DELFT

More information

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE 3 213 2 2 UPONOR LIFE CYCLE COST COMPARISON OF TAB VS. OTHER HVAC Contents Introduction... 4 Base building... 5 System and tested

More information

saving energy in comfort Factsheet Recair Enthalpy

saving energy in comfort Factsheet Recair Enthalpy saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

Energy Efficiency. Bars & RestauRants. www.energia.ie

Energy Efficiency. Bars & RestauRants. www.energia.ie Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1 Opening the Bonnet Prof Darren Woolf WYSINWYG 1 WYSINWYG What You See Is NOT What You Get: Looking inside the Pandora s Box Prof Darren Woolf WYSINWYG 2 WYSIWYG implies a user interface that allows the

More information

Energy Efficiency in Buildings

Energy Efficiency in Buildings Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:

More information

We have been working in an ideal climate for thirty years.

We have been working in an ideal climate for thirty years. Underfloor cooling We have been working in an ideal climate for thirty years. A climate that has brought us to a position of leadership in Italy in the field of radiant heating and cooling. RDZ was the

More information

SBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings

SBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings SBi 2013:14 Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Rouzbeh Norouzi,

More information

How To Control Humidity With A Humidifier

How To Control Humidity With A Humidifier Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2

More information

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING R.M.J. Bokel Department of Architecture, Delft Technical University, Delft, The Netherlands,

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING

ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING THERMAL SCIENCE: Year 2015, Vol. 19, No. 3, pp. 865-880 865 ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING by Norbert L. HARMATI a*, Radomir J. FOLI] a,

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

3-D Modeller Rendered Visualisations

3-D Modeller Rendered Visualisations Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2

More information

Exemplary Retrofitting of an Old School in Stuttgart - EROS -

Exemplary Retrofitting of an Old School in Stuttgart - EROS - Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in

More information

Scope of Work. See www.sei.ie for resources available

Scope of Work. See www.sei.ie for resources available HVAC SWG Summary Background Pool energy-efficiency knowledge Increase cost-competitiveness Develop resources aimed at assisting in reducing HVAC energy consumption Address barriers to energy-saving HVAC

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Dienstleistung. Certification as Quality Approved Passive House Criteria for Residential-Use Passive Houses Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Directorate for the Built Environment Building Standards Division

Directorate for the Built Environment Building Standards Division Directorate for the Built Environment Building Standards Division Energy Management Solutions Ltd Investigation of measures to improve the energy performance of a existing building: Retail JUNE 2009 Report

More information

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Content Heating / Ventilation / Air Conditioning 3 The Right Room Climate 4 Optimised Energy Efficiency and well-being Room

More information

HVAC Simplified Approach Option

HVAC Simplified Approach Option HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than

More information

Under sill units. Type FSL-B-ZAS

Under sill units. Type FSL-B-ZAS .1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract

More information

Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice

Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice A truly international certification The Eurovent Certification Programmes are managed by an autonomous

More information

Performance of low pressure mechanical ventilation concept with diffuse ceiling inlet for renovation of school classrooms

Performance of low pressure mechanical ventilation concept with diffuse ceiling inlet for renovation of school classrooms Downloaded from orbit.dtu.dk on: Jun 22, 2016 Performance of low pressure mechanical ventilation concept with diffuse ceiling inlet for renovation of school classrooms Terkildsen, Søren; Svendsen, Svend

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

AIR CONDITIONERS ROOF TOP & UNDERBUNK INSPIRED BY COMFORT NEW RELEASE DOMETIC FRESHJET

AIR CONDITIONERS ROOF TOP & UNDERBUNK INSPIRED BY COMFORT NEW RELEASE DOMETIC FRESHJET AIR CONDITIONERS ROOF TOP & UNDERBUNK INSPIRED BY COMFORT NEW RELEASE DOMETIC FRESHJET 2 HOW AIR CONDITIONING WORKS Air s work on basically the same principle as the cooling units of kitchen refrigerators.

More information

Residential HVAC System Sizing

Residential HVAC System Sizing Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)

More information

Example of audit of an air conditioning system

Example of audit of an air conditioning system Example of audit of an air conditioning system Authors and affiliations: André Philippe Hannay Cleide, Hannay Jules, Lebrun Jean University of Liège, Belgium Main author: Jean Lebrun Email : j.lebrun@ulg.ac.be

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

FLORIDA SOLAR ENERGY CENTER

FLORIDA SOLAR ENERGY CENTER FLORIDA SOLAR ENERGY CENTER Creating Energy Independence Since 1975 Impact of Energy-Efficiency Parameters on Home Humidity Rob Vieira Florida Solar Energy Center A Research Institute of the University

More information

AIRCONDITIONING Cooling Loads Calculations

AIRCONDITIONING Cooling Loads Calculations Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)

More information

Analysis of HVAC Control Strategies

Analysis of HVAC Control Strategies PUBLICATION DATE: Q1 2009 REF NUMBER: HVAC SWGII 006 03 HVAC SPECIAL WORKING GROUP Analysis of HVAC Control Strategies 06 Table of Contents 1 Introduction 2 2 Scope 3 3 Analysis 4 3.1 Strategy 1 4 3.2

More information

IDA Early Stage Building Optimization (ESBO) User guide

IDA Early Stage Building Optimization (ESBO) User guide IDA Early Stage Building Optimization (ESBO) User guide Version 1.09, Oct 2013 2 Contents What is IDA ESBO?... 4 How do I use IDA ESBO?... 4 IDA ESBO user interface... 7 Rooms tab... 7 Building tab...

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA

More information

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to: PASSIVE Solar Design Solar Homes Catch the Sun Are you planning a new house? Discover how you can apply solar architecture principles to: keep your heating bills to a minimum enjoy the comfort of a warm

More information

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction

More information

Klosterenga, Oslo, Norway, 1998-2000 page - 1

Klosterenga, Oslo, Norway, 1998-2000 page - 1 Klosterenga, Oslo, Norway, 1998-2000 page - 1 Introduction Klosterenga is an urban revitalisation project close to the city centre of Oslo. The 3 apartments were built with a focus on energy saving. Next

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - pcoolingandheating COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - Bjarne W. Olesen, Ph.D. D. F. Liedelt "Velta" Summary Due to intensive use of

More information

Software Development for Cooling Load Estimation by CLTD Method

Software Development for Cooling Load Estimation by CLTD Method IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS INTRODUCTION 1. There are no general EU regulations and standards for outdoor swimming pool heating. Local regulations in the member countries are covering most

More information

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information

DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS

DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS DISTRIBUTED GENERATION AND ENERGY EFFICIENCY FOR ACHIEVING ENERGY SELF-SUSTAINING INDUSTRIAL AREAS Ing. Maria-Anna Segreto LAERTE Laboratory - 1 EUROPEAN DIRECTIVE 2010/31/UE It 's well known that higher

More information

SIMULATION - ASSISTED AUDIT OF AN AIR CONDITIONED OFFICE BUILDING

SIMULATION - ASSISTED AUDIT OF AN AIR CONDITIONED OFFICE BUILDING SIMULATION - ASSISTED AUDIT OF AN AIR CONDITIONED OFFICE BUILDING Stephane Bertagnolio Research Assistant Jean Lebrun Professor Jules Hannay Research Engineer Cleide Aparecida Silva Research Engineer Thermodynamics

More information

Research Project F 2071. W. Richter. Manual of thermal comfort of Summer cooling mode

Research Project F 2071. W. Richter. Manual of thermal comfort of Summer cooling mode Research Project F 2071 W. Richter Manual of thermal comfort of Summer cooling mode Dortmund/Berlin/Dresden 2007 This publication is a summary of the final report of a project Development of a manual on

More information

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper

More information

Council s energy efficiency upgrades benefit community

Council s energy efficiency upgrades benefit community Council s energy efficiency upgrades benefit community Project Snapshot Objective: reduce energy, save money & improve comfort in public buildings Where: Meander Valley Council, Northern Tasmania Total

More information

Heating and cooling. Insulation. Quick facts on insulation:

Heating and cooling. Insulation. Quick facts on insulation: Heating and cooling Heating and cooling your home can be one of the biggest users of energy. Efficency in this area can bring great savings. Heating and cooling depend on many contributing factors. The

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Passive Solar Design and Concepts

Passive Solar Design and Concepts Passive Solar Design and Concepts Daylighting 1 Passive Solar Heating Good architecture? The judicious use of south glazing coupled with appropriate shading and thermal mass. Summer Winter Passive solar

More information

BER Assessors Dwellings Technical Bulletin

BER Assessors Dwellings Technical Bulletin BER Assessors Dwellings Technical Bulletin Issue No. 2/12 April 2012 Contents: 1. SUPPLEMENTARY ELECTRIC WATER HEATING IN SUMMER... 2 2. PITCHED ROOF U-VALUE CALCULATIONS... 8 2.1. PITCHED ROOF, INSULATED

More information

Optimum Solar Orientation: Miami, Florida

Optimum Solar Orientation: Miami, Florida Optimum Solar Orientation: Miami, Florida The orientation of architecture in relation to the sun is likely the most significant connection that we can make to place in regards to energy efficiency. In

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Energy savings in the residential area are essential in

Energy savings in the residential area are essential in Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations

More information

HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM

HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM 01-147 The 2005 World Sustainable Building Conference, HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM Aleš KRAINER Prof. Dr. 1 Rudi Perdan 2 Gal Krainer 3 1 2 Faculty of Civil Engineering,

More information

Resources for School Energy Managers

Resources for School Energy Managers Resources for School Energy Managers Cooling can present a substantial energy cost to schools. Temperatures of 24 to 27 C with less than 60% relative humidity give acceptable comfort in summer. Higher

More information

HDA -----------------------------------------------------------

HDA ----------------------------------------------------------- ----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.

THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. A Diagrammatic representation of the relationship between the

More information

VE Compliance FAQ. Top Tips for Achieving Compliance

VE Compliance FAQ. Top Tips for Achieving Compliance Integrated Environmental Solutions Ltd. VE Compliance FAQ The Building Regulations 2010: Conservation of fuel and power Approved Document L2A (2013 edition for use in England) Top Tips for Achieving Compliance

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free... Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions

Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions 2 Smart control Smart control 3 Savings have seldom felt so good. Comfort Sustainability

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information