1 TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February Copyright 2015 ASHRAE. Posted at This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit Part One Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE The use of radiant heating systems has several thousand years of history. 1,2 The early stage of radiant system application was for heating purposes, where hot air from flue gas (cooking, fires) was circulated under floors or in walls. After the introduction of plastic piping water-based radiant heating and cooling with pipes embedded in room surfaces (floor, wall, and ceiling), the application increased significantly worldwide. Earlier application of radiant heating systems was mainly for residential buildings because of its comfort and free use of floor space without any obstruction from installations. For similar reasons, as well as possible peak load reduction and energy savings, radiant systems are being widely applied in commercial and industrial buildings. This two-part article describes basic knowledge of radiant heating and cooling systems to give a principle understanding of the design and operation of this advantageous system including comfort, system load, heating/cooling capacity, installation and application of the system with examples. Embedded Radiant Heating and Cooling System Embedded radiant systems are used in all types of buildings. Due to the large surfaces needed for heat transfer, the systems work with low water temperature for heating and high water temperature for cooling. The water temperatures are operated at very close to room temperature, and, depending on the position of the piping, the system can take advantage of the thermal storage capacity of the building structure. Figure 1 shows the available types of embedded hydronic radiant systems. The embedded radiant systems, except thermally active building systems (TABS), are usually insulated from the main building structure (floor, wall and ceiling), and the actual operation mode (heating/cooling) of the systems depends on the heat transfer between the water and the space. Kwang Woo Kim, Arch.D., is a professor of architecture at Seoul National University, Seoul, South Korea, and president of Architectural Institute of Korea. Bjarne W. Olesen, Ph.D., is director, professor, International Centre for Indoor Environment and Energy, Technical University of Denmark in Lyngby, Denmark, and vice president of ASHRAE. 28 ASHRAE JOURNAL ashrae.org FEBRUARY 2015

2 TECHNICAL FEATURE Floor Ceiling Wall TABS FIGURE 1 Examples of water based radiant systems. 3 The radiant system is defined as a system where at least 50% of the heat transfer takes place by radiation. Figure 2 shows the total heat transfer coefficients between a heated-cooled surface and a room. The radiant heat transfer is, in all cases, 5.5 W/m² K (0.97 Btu/h ft² F). The convective heat transfer then varies between 0.5 and 5.5 W/m² K (0.09 and 0.97 Btu/h ft² F), depending on the surface type and on heating or cooling mode. This shows that the radiant heat transfer varies between 50% and 90% of the total heat transfer. The heat transfer coefficient for cold ceiling and warm floor will vary between 9 and 11 W/m² K (1.59 and 1.94 Btu/h ft² F), depending on the temperature difference between surface and room. The radiant heat transfer does not directly affect the room air temperature. The long wave radiation heats or cools the surrounding surfaces, which then indirectly heats or cools the room air. Standard for Radiant Heating and Cooling Systems As the heat transfer process between water and room is quite different from conventional air systems, an international standard on radiant heating and cooling systems has been developed based on system design and existing standards from different countries and was published in ISO 11855, Building Environment Design Design, Dimensioning, Installation and Control of the Embedded Radiant Heating And Cooling Systems, 6 11 consists of six parts: Part 1: Definition, symbols, and comfort criteria; Part 2: Determination of the design and heating and cooling capacity; Part 3: Design and dimensioning; Part 4: Dimensioning and calculation of the dynamic heating and cooling capacity of thermo active building systems; Btu/h ft 2 F Heating Cooling Floor FIGURE 2 Heat transfer coefficients between heated/cooled surface and room. 4,5 Part 5: Installation; and Part 6: Control. Ceiling Comfort Occupants thermal comfort is the primary objective in radiantly heated or cooled space. To provide an acceptable thermal environment for the occupants, the requirements for general thermal comfort shall be taken into account by using the index of predicted mean vote (PMV) or operative temperature, t o, and local thermal comfort, e.g., surface temperature, vertical air temperature differences, radiant temperature asymmetry, draft, etc. For radiant or convective systems the comfort requirements are the same when expressed by the PMV-PPD index ( 0.5 < PMV <+0.5) or expressed as an operative temperature range corresponding to: 20 C to 24 C (68 F to 75.2 F) for heating season and 23 C to 26 C (73.4 F to 78.8 F) for cooling season in spaces with sedentary activity. 12,13 The operative temperature 14,15 is the combined influence of air temperature and mean radiant temperature. The operative temperature can be approximated with Wall FEBRUARY 2015 ashrae.org ASHRAE JOURNAL 29

3 TECHNICAL FEATURE Fundamentals at Work Y 80% 60% 40% 20% 0 F 3.6 F 7.2 F 10.8 F 14.4 F 18 F Y 80% 0 F 9 F 18 F 27 F 36 F 45 F 54 F 63 F 60% 40% % 10% 8% 6% 4% 2% 10% 8% 6% 4% 2% 3 4 1% X = Air Temperature Difference Between Head and Feet Y = Dissatisfied FIGURE 3 Local thermal discomfort caused by vertical air temperature difference. 6 X 1% X X = Radiant Temperature Asymmetry Y = Dissatisfied 1 = Warm Ceiling 2 = Cool Wall 3 = Cool Ceiling 4 = Warm Wall FIGURE 4 Local thermal discomfort caused by radiant temperature asymmetry. 6 the simple average of air and mean radiant temperature in spaces with low air velocities (<0.2 m/s [39 fpm]), or with a small difference between mean radiant temperature and air temperature (<4K, 7 F). The operative temperature (t o ) is in spaces with low air velocities determined from the following expression: t o = 0.5(t a + t r ) Where t a = air temperature F ( C) t r = mean radiant temperature F ( C) The occupants can maintain the same comfort level with a lower air temperature in a radiantly heated space, and the same comfort level with a higher air temperature in a radiantly cooled space in comparison to convective heating and cooling systems. Therefore, reduction of the energy loss due to ventilation and infiltration is possible while maintaining the same comfort level compared with conventional heating and cooling systems. As the reference temperature for the transmission heat loss is closer to the operative temperature than to the air temperature, there will not be any significant difference of transmission heat loss between radiantly heated or cooled spaces. Interestingly enough, the difference between air- and mean radiant temperature is normally smaller in radiantly heated or cooled spaces. This is due to the fact that in winter the windows will have a lower surface temperature than the air temperature, which is compensated by a higher surface temperature of the radiant Dissatisfied (%) F F F Relative Humidity (%) FIGURE 5 Human satisfaction with the IAQ depending on relative humidity and air temperature. 3 system and vice-versa in summer. With air systems the colder window temperatures in winter will be compensated by a higher air temperature, which will result in an air temperature higher than the mean radiant temperature. For rooms with sedentary and/or standing occupants, the maximum permissible floor temperature for heating is 29 C (84 F), and the minimum floor temperature for cooling is 19 C (66 F). For spaces with occupants in bare feet (bathrooms, swimming pools, dressing rooms, etc.), the optimal floor temperature for comfort also depends on the floor covering material. For wall heating, a maximum surface temperature range of 35 C to 45 C (95 F to 113 F) is recommended. The maximum may depend on whether the occupants 1 Acceptability 30 ASHRAE JOURNAL ashrae.org FEBRUARY 2015

4 Advertisement formerly in this space.

5 TECHNICAL FEATURE Fundamentals at Work Type A and C 1 Type B 1 Type D Type G Flooring Material Joist 1 = Floor Covering 2 = Weight Bearing and Thermal Diffusion Layer (Cement Screed, Anhydrite Screed, Asphalt Screed or Wood) 3 = Thermal Insulation 4 = Structural Base 5 = Heat Diffusion Device FIGURE 6 Embedded radiant system types. 7 may easily get contact with the surface or whether occupants are more sensitive persons such as children or the elderly. Wall cooling is limited by the risk of condensation and the development of a downdraft of cold air. A vertical air temperature difference between head and feet of less than 3K (5.4 F) is recommended. Most heating and cooling systems will, in modern buildings, normally have vertical air temperature differences within this limit. In high ceiling spaces it is, for energy reasons, important to avoid large vertical temperature differences. This is why floor heating is especially recommended here (atrium, foyer, industrial space, etc.) People are very sensitive to radiant temperature asymmetry from a cold window and a warm ceiling. Occupants may feel discomfort caused by a temperature asymmetry of 5K (9 F) for warm ceiling, and a temperature asymmetry of 10K (18 F) for walls or windows (Figure 4, Page 30). The critical factor at cold surfaces (windows, walls) is, however, the risk of downdraft that may cause discomfort. The radiant heating and cooling system operates with less dust transportation, as it is not a convective system, and does not require the cleaning of heat emitters or filters. With the radiant floor heating systems, carpets are not necessary. Thus, the possible allergen sources of emitting pollutants and a sink source can be eliminated. The higher mean radiant temperature in radiantly heated space means that the air temperature can be kept lower than in convectively heated space. This has the advantage that the relative humidity in winter may be a little higher. Studies show that lower air temperature and lower air humidity have a significant effect on perceived air quality (Figure 5 3 ). Due to the higher heating surface temperatures, there is less chance for condensation and mold growth. The relationship between air temperature and humidity is one of important comfort issues in radiantly cooled spaces. Where the humidity is not controlled by the air system, as in naturally ventilated spaces, radiant cooling capacity will be limited to avoid the forming of condensation on the radiant surface (see section on control in Part 2 of this article in next month s Journal). With air heating or cooling system more air has to be circulated than the amount needed for providing acceptable air quality. This may increase the noise level in a space and also increase the risk for complaints related to draft. When a part of sensible heating and/ or cooling load is taken care of by a water-based radiant system, the ventilation system may have reduced duct size and lower air velocity because it will only treat the air renewal for required IAQ and, if needed, dehumidification. In buildings with thermally active building systems (TABS) you will normally prefer to have free access to the concrete surface to increase the heat transfer with the room. This may require special solutions for the acoustics. Acoustic panels on the ceilings and suspended ceiling panels will reduce heat transfer. It will be more efficient to hang down vertical acoustical panels. 16 The application of the raised floor or the thermal/acoustic insulation in floor will decrease the upper heat flow from the TABS, which normally is much less than the heat exchange from the ceiling. Load Calculations and Heating/Cooling Capacity At a given average surface temperature and indoor temperature (operative temperature, t o ), a surface will deliver the same amount of heat flux to a space 32 ASHRAE JOURNAL ashrae.org FEBRUARY 2015

6 Advertisement formerly in this space.

7 TECHNICAL FEATURE Fundamentals at Work Structure S4 q = 0 q = 0 Material Floor Covering λ = 0.08 Btu in/h ft 2 F s = 0.6 in. Screed λ = 0.40 Btu in/h ft 2 F s = 2.4 in. Thermal Insulation λ = 0.01 Btu in/h ft 2 F s = 1.2 in. Concrete λ = 0.70 Btu in/h ft 2 F s = 7.1 in. q up =112.6 Btu/h Temperature ( F) q down =22.3 Btu/h FIGURE 7 Temperature distribution and cooling effect up and down for a floor system calculated by FEM software for a floor cooling system with 19 C (66.2 F) water temperatures and 26 C (78.8 F) room temperature. regardless of the embedded radiant system type. Therefore, it is possible to establish basic formulas or characteristic curves of heating and cooling for the all heating and cooling surfaces independent of the embedded system types. The heat transfer between the surface and the space do, however, depend on the different surface heat transfer coefficients (Figure 2). The heat transfer between the water and surface is different for each system configuration. Therefore, the estimation of heating/cooling capacity of systems is very important for the proper system design. Two calculation methods included in ISO are simplified calculation methods depending on the type of system, and finite element method (FEM) or finite difference method (FDM). Given system types are Types A and C, Type B, Types D and G. The simplified calculation methods are specific for the given system types within boundary conditions. Based on the calculated average surface temperature at given heat transfer medium temperature and space temperature, it is possible to determine the steady state heating and cooling capacity. In case a simplified calculation method is not applicable for the considered system, either two- or three-dimensional finite element or finite difference method, or laboratory testing may be applied. The temperature distribution in floor cooling system, calculated using FEM software, is shown in Figure 7. Heat exchange coefficient is the parameter that determines the amount of heat transferred between surface and the space in relation with the system type. Acceptable surface temperature is determined based on comfort considerations and the risk of condensation. Heating/cooling capacity of the systems is: 7 Floor heating and ceiling cooling, q = 8.92 (t o t S,m ) 1.1 ; Wall heating and wall cooling, q = 8 ( t o t S,m ); Ceiling heating, q = 6 ( t o t S,m ); Floor cooling, q = 7 ( t o t S,m ). Where t o ( C) is the operative temperature in the space t S,m ( C) is the average surface temperature The ceiling has the capacity up to 100 W/m² (31.7 Btu/h ft²) for sensible cooling and 40 to 50 W/m² (12.7 to 15.9 Btu/h ft²) for heating. The floor has the capacity up to 100 W/m² (31.7 Btu/h ft²) for heating and 40 W/m² (12.7 Btu/h ft²) for sensible cooling. When direct sunlight strikes on the floor, the sensible cooling capacity of the floor may be more than 100 W/m² (31.7 Btu/h ft²). This is why floor cooling is often adopted in spaces with large window area like airports, atria and lobby halls. For the thermally active building systems (TABS), the steady-state heating/cooling capacity calculation is not sufficient, and analysis with a dynamic computational program that can predict the dynamic behavior and performance of the system together with the building 34 ASHRAE JOURNAL ashrae.org FEBRUARY 2015

8 TECHNICAL FEATURE is needed. 17,1 Several programs exist such Energy Plus, TRNSYS and IDA-ICE. One of the main advantages of TABS are reduced building height. For each story, you may save 500 to 600 mm (1.8 to 2 ft) of building height, which for a seven-story building amounts to an entire story and related building materials. As no suspended ceiling is needed to cover air ducts, significant saving of building materials is possible. It is also possible to operate the system at 30% to 50% lowered peak loads allowing reduced plants sizes and possible operation of heating/cooling systems with temperatures close to room temperature, allowing increased plants efficiency and use of renewable energy sources (ground heat exchanger, evaporative cooling, etc.). Thermally active building systems exploit the high thermal inertia of the slab to perform peak shaving. The peak shaving reduces the peak in the required cooling power, 7 so that it is possible to cool the structures of the building during a period in which the occupants are absent (during nighttime in office premises). This way, the cooling can be delayed and lower nighttime electricity rates can be used. At the same time, a reduction in the size of heating/cooling system components (including the chiller) is possible. During daytime, the heat is extracted from the occupied space by the ventilation system and stored in the concrete slabs. Then, during nighttime, the level of ventilation is reduced and the circulation of cool water in the slabs will remove the stored heat. For the conventional air system, the space load will be the instantaneous system load, because all the heat delivered to the space is immediately removed by the air system. For the radiant system and especially for a TABS the calculated design space load should not be used as system load. For both an air system and a TABS, it is important that the room load over a 24-hour day (Curve 1 in Figure 8) is removed within the 24 hours, else the room will get warmer and warmer day by day if the weather stays the same. The difference is that with a TABS this load is removed from the space in three ways: absorption in the concrete slab, removed by the ventilation system and removed by the water circulating in the slabs. Therefore, the load is removed by a slab system = Heat Gain 2 = Power Needed for Conditioning the Ventilation Air 3 = Power Needed on Water Side 4 = Peak Heat Gain Reduction FIGURE 8 Example of peak-shaving (reducing the peak load) effect (time vs. cooling power). 17 Cooling Power (Btu/h) over 24 hours and by an air system normally over 8 to 10 hours. After the water circulation in the slab may have been stopped during the day and will be started again in the evening, there will be a high peak cooling load between the heated slab and the cool water; but this should not be used to size the chiller as it is a very short peak and the capacity needed will after some minutes decrease significantly. It can be somewhat complicated to calculate the needed capacity on the water side (chiller, heat pump); therefore, a dynamic building simulation is recommended. System Design Radiant system design requires determining heating/cooling surface area, type, pipe size, pipe spacing, supply temperature of the heat transfer medium, and design medium flow rate. The design steps are as follows (ISO ): 1. Calculate the design heating and sensible cooling load in accordance with a standard for heating and cooling load calculation based on operative temperature. 2. Determine the minimum supply air quantity needed for ventilation and dehumidification. In cooling application, calculate latent cooling and sensible cooling available from supply air. Determine remaining sensible cooling load to be satisfied by radiant system. Also, designate or calculate the relative humidity and dew point, because the cooling system should operate within a surface temperature range above the dew point, which shall be specified depending on the respective climate conditions in the country. By limiting supply water 3 FEBRUARY 2015 ashrae.org ASHRAE JOURNAL 35

9 TECHNICAL FEATURE Fundamentals at Work temperature to be maintained above dew point, the risk of condensation can be easily avoided. 3. Determine the surface area for radiant system, excluding any area covered by objects immovable or fixed to the building structure. 4. Establish a maximum permissible surface temperature and a minimum permissible surface temperature in consideration of the dew point. 5. Determine the design heat flux, including the design heat flux of peripheral area and the design heat flux of occupied area. For the design of the cooling systems, determine the room with the maximum design heat flux. 6. Determine the radiant system such as the pipe spacing and the covering type, and design heating and cooling medium differential temperature based on the maximum design heat flux and the maximum and minimum surface temperature from the field of characteristic curves. 7. If the design heat flux cannot be obtained by any pipe spacing alternatives for the room of design, it is recommended to provide supplementary heating/cooling equipment. In this case, the maximum design heat flux for the embedded system may now occur in another room. 8. Determine the thermal resistance of backside insulating layer and the design heating/cooling medium flow rate. 9. Estimate the total length of circuit. Hydronic radiant surface systems are very often coupled with an airhandling system. The air-handling system usually operates only with the amount of air needed for acceptable indoor air quality, the required IAQ standard, or amount of air needed to remove latent heat from TABLE 1 System design example for panel cooling. STEP FIND EXAMPLE 0 A = 10 m 2 (108 ft 2 ), V = 30 m 3 (1,059 ft 3 ) Room is Given to be Installed with Radiant System and HVAC System 1 Calculate Cooling Load Based on Operative Temperature Cooling Load (Latent) Cooling Load (Sensible) 2 Determine Minimum Supply Air Quantity Calculate Latent Cooling Available From Supply Air Sensible Cooling Available From Supply Air Design the Relative Humidity And Dew Point Determine Remaining Sensible Cooling Load to be Satisfied by Radiant System Q c,latent = 150 W (512 Btu/h) Q c,sensible = 1,000 W (3,416 Btu/h) V HVAC,min = 0.7 ACH = 21 CMH (12.4 CFM) Q HVAC,latent = Q c,latent = 150 W (512 Btu/h) Assuming the SHF (Sensible Heat Factor) of HVAC, SHF = (Q HVAC,sensible / Q HVAC,total ) = 0.7 Q HVAC,total = Q HVAC,latent / (1 - SHF) = Q HVAC,latent / 0.7 = 500 W (1,708 Btu/h) Then, Q HVAC,sensible = Q HVAC,total Q HVAC,latent = 500 W 150 W = 350 W (1,196 Btu/h) is available from supply air of HVAC RH = 50 %, T dew = 14.8 C (58.6 F) Remaining Q c,sensible = Q c,sensible - Q HVAC,sensible = 1,000W 350 W = 650 W (2,220 Btu/h) 3 Determine the Available Surface Area A available = 5 m 2 (53.8 ft 2 ), 50% of ceiling area is available for radiant system 4 Establish a Minimum Permissible Surface Temperature T surf,min = 17 C (62.6 F) is acceptable for cooled ceiling * (which is higher than dew point temperature) 5 Determine Maximum Design Heat Flux Q c,max = 99 W/m 2 (31.4 Btu/h ft 2 ) is allowed for cooled ceiling * 6 Determine Radiant System Pipe Spacing Covering Type Design Cooling Medium Differential Temperature Design heating capacity of radiant system, 7 Select Supplementary Cooling Equipment 8 Determine Thermal Resistance of Backside Insulating Layer Cooling Medium Flow Rate Selected Radiant System has cooling capacity of 80 W/m 2 (25.4 Btu/h ft 2 ). m T = 0.2 m (8 in.) punched aluminum sheet T m = 2 C (3.6 F) 5 m 2 = 400 W (1,366 Btu/h) Required cooling capacity of Supplementary Cooling Equipment Q out = Remaining Q c,sensible Q des = 650 W 400 W = 250 W (854 Btu/h) R cover = m 2 K/W (0.12 h ft 2 F/Btu) m = kg/s (6.3 lb/min), ensured of fully developed flow in pipe If the resistance of backside insulation is high, the cooling medium flow rate could be lowered. 9 Estimate Total Length Of Circuit L cir = A available / m T = 5 m 2 / 0.2 m = 25 m (82 ft) * ISO : Building environment design Design, dimensioning, installation and control of embedded radiant heating and cooling systems Part 2: Determination of the design heating and cooling capacity. 36 ASHRAE JOURNAL ashrae.org FEBRUARY 2015

10 TECHNICAL FEATURE the space and control air humidity level, while the hydronic system supplies or removes the sensible heat depending on the seasonal conditions. In the cooling mode, the air system can play a key role in avoiding surface condensation. Part 2 of this article will cover control, operation, installation and application of the system. Acknowledgments This article was supported by VELUX guest professorship, and a grant from the National Research Foundation of Korea (NRF) funded by the Korean government (MEST) (No ). References 1. Bean, R., Olesen, B.W., Kim, K. W History of Radiant Heating & Cooling Systems, Part 1. ASHRAE Journal (1): Bean, R., Olesen, B.W., Kim, K. W History of Radiant Heating & Cooling Systems, Part 2. ASHRAE Journal (2): REHVA Guidebook No 7: Low Temperature Heating and High Temperature Cooling. 4. Olesen, B.W Possibilities and limitations of radiant floor cooling. ASHRAE Transactions 103(1): Olesen, B.W., Michel, E., Bonnefoi, F., De Carli, M Heat exchange coefficient between floor surface and space by floor cooling: theory or a question of definition. ASHRAE Transactions, Part I. 6. ISO :2012, Building environment design - Design, dimensioning, installation and control of the embedded radiant heating and cooling systems Part 1: Definition, symbols, and comfort criteria. 7. ISO :2012, Building environment design - Design, dimensioning, installation and control of the embedded radiant heating and cooling systems Part 2: Determination of the design and heating and cooling capacity ISO :2012, Building environment design - Design, dimensioning, installation and control of the embedded radiant heating and cooling systems Part 3: Design and dimensioning. 9. ISO :2012, Building environment design - Design, dimensioning, installation and control of the embedded radiant heating and cooling systems Part 4: Dimensioning and calculation of the dynamic heating and cooling capacity of Thermo Active Building Systems (TABS). 10. ISO :2012, Building environment design - Design, dimensioning, installation and control of the embedded radiant heating and cooling systems Part 5: Installation. 11. ISO :2012, Building environment design - Design, dimensioning, installation and control of the embedded radiant heating and cooling systems Part 6: Control. 12. ASHRAE Standard , Thermal Environmental Conditions for Human Occupancy. 13. ISO EN , Moderate thermal environments determination of the PMV and PPD indices and specification of the conditions for thermal comfort ASHRAE Handbook HVAC Systems and Equipment. 15. ISO EN , Ergonomics of the thermal environment- Instruments for measuring physical quantities. 16. Weitzmann, P., Pittarello, E., Olesen, B.W The cooling capacity of the thermo active building system combined with acoustic ceiling. Presented at Nordic Symposium on Building Physics. 17. Olesen, B.W Thermo active building systems using building mass to heat and cool. ASHRAE Journal 54(2): Advertisement formerly in this space. Advertisement formerly in this space. FEBRUARY 2015 ashrae.org ASHRAE JOURNAL 37

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - pcoolingandheating COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - Bjarne W. Olesen, Ph.D. D. F. Liedelt "Velta" Summary Due to intensive use of

More information

Radiant Floor Heating In Theory and Practice

Radiant Floor Heating In Theory and Practice The following article was published in ASHRAE Journal, July 02. Copyright 02 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA

More information

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE 3 213 2 2 UPONOR LIFE CYCLE COST COMPARISON OF TAB VS. OTHER HVAC Contents Introduction... 4 Base building... 5 System and tested

More information

Integrated Solar Radiant Systems

Integrated Solar Radiant Systems Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

RADIANT COOLING SYSTEMS PRINCIPLES OF RADIANT COOLING SYSTEMS INSTALLATION, DESIGN, CONTROLS, CAPACITIES

RADIANT COOLING SYSTEMS PRINCIPLES OF RADIANT COOLING SYSTEMS INSTALLATION, DESIGN, CONTROLS, CAPACITIES RADIANT COOLING SYSTEMS PRINCIPLES OF RADIANT COOLING SYSTEMS INSTALLATION, DESIGN, CONTROLS, CAPACITIES www.rehau.com Construction Automotive Industry INTRODUCTIONS PRESENTER Lance MacNevin - Manager,

More information

CEN/TC 156. pren 15251. Date: 2006-07-31 CEN/TC 156. Secretariat: BSI ICS: Descriptors:

CEN/TC 156. pren 15251. Date: 2006-07-31 CEN/TC 156. Secretariat: BSI ICS: Descriptors: CEN/TC 156 Date: 2006-07-31 pren 15251 CEN/TC 156 Secretariat: BSI Indoor environmental input parameters for design and assessment of energy performance of buildingsaddressing indoor air quality, thermal

More information

Saving Heating Costs In Warehouses

Saving Heating Costs In Warehouses 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 12, December 2005). This article may not

More information

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard

More information

Whole House Dehumidification for Occupant Comfort and Energy Savings

Whole House Dehumidification for Occupant Comfort and Energy Savings Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

We have been working in an ideal climate for thirty years.

We have been working in an ideal climate for thirty years. Underfloor cooling We have been working in an ideal climate for thirty years. A climate that has brought us to a position of leadership in Italy in the field of radiant heating and cooling. RDZ was the

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

Radiant Panels and Chilled Sails. www.price-hvac.com

Radiant Panels and Chilled Sails. www.price-hvac.com Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Software Development for Cooling Load Estimation by CLTD Method

Software Development for Cooling Load Estimation by CLTD Method IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department

More information

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS INTRODUCTION 1. There are no general EU regulations and standards for outdoor swimming pool heating. Local regulations in the member countries are covering most

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil

More information

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.

More information

FLORIDA SOLAR ENERGY CENTER

FLORIDA SOLAR ENERGY CENTER FLORIDA SOLAR ENERGY CENTER Creating Energy Independence Since 1975 Impact of Energy-Efficiency Parameters on Home Humidity Rob Vieira Florida Solar Energy Center A Research Institute of the University

More information

HDA -----------------------------------------------------------

HDA ----------------------------------------------------------- ----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS

More information

Chapter 2 PRESENT STATE OF KNOWLEDGE ABOUT RADIANT COOLING SYSTEMS

Chapter 2 PRESENT STATE OF KNOWLEDGE ABOUT RADIANT COOLING SYSTEMS Chapter 2 PRESENT STATE OF KNOWLEDGE ABOUT RADIANT COOLING SYSTEMS 2.1 All-Air Systems vs. Radiant Cooling Systems An air-conditioning system is designed to control indoor temperature and humidity, and

More information

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING Murray Milne, Research Professor Department of Architecture and Urban Design UCLA Los Angeles, CA 90095 milne@ucla.edu Tim Kohut, Project

More information

Adaptive strategies for office spaces in the UK climate

Adaptive strategies for office spaces in the UK climate International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to: PASSIVE Solar Design Solar Homes Catch the Sun Are you planning a new house? Discover how you can apply solar architecture principles to: keep your heating bills to a minimum enjoy the comfort of a warm

More information

School Performance Specifications. SPACES Engineering Technical Meeting 22 September 2015

School Performance Specifications. SPACES Engineering Technical Meeting 22 September 2015 School Performance Specifications SPACES Engineering Technical Meeting 22 September 2015 EFA Facilities Output Specification: Introduced in 2013 to promote: well-integrated and simple buildings that benefit

More information

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

SIMULATION OF RADIANT COOLING PERFORMANCE WITH SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE

More information

Simulation of hygroscopic materials in the HVAC system of an office building

Simulation of hygroscopic materials in the HVAC system of an office building Simulation of hygroscopic materials in the HVAC system of an office building IEA/ECBCS Annex 41 Porto Meeting Melanie Fauchoux, Carey Simonson and David Torvi Department of Mechanical Engineering, University

More information

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004

More information

Residential HVAC System Sizing

Residential HVAC System Sizing Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,

More information

Crawl space heat and moisture behaviour

Crawl space heat and moisture behaviour Crawl space heat and moisture behaviour Miimu Airaksinen, Dr., Technical Research Centre of Finland, VTT miimu.airaksinen@vtt.fi, www.vtt.fi KEYWORDS: crawl space, moisture, evaporation from ground, ground

More information

The calculus and simulation of underfloor heating systems

The calculus and simulation of underfloor heating systems The calculus and simulation of underfloor heating systems DORIN CRISTIAN NĂSTAC*, IOAN CĂLDARE**, IOAN GIURCA***, CORNEL MUNTEA*** * Building Services Engineering Department, Transilvania University of

More information

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper

More information

ASHRAE STANDARD. Thermal Environmental Conditions for Human Occupancy. BSR/ASHRAE Standard 55P -1992R. Proposed American National Standard

ASHRAE STANDARD. Thermal Environmental Conditions for Human Occupancy. BSR/ASHRAE Standard 55P -1992R. Proposed American National Standard BSR/ASHRAE Standard 55P -1992R This draft standard will be submitted to the American National Standards Institute Board of Standards Review (BSR) for approval. ASHRAE STANDARD Proposed American National

More information

Case Studies: Infrared Heating in Industrial Applications

Case Studies: Infrared Heating in Industrial Applications Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000

More information

Research Project F 2071. W. Richter. Manual of thermal comfort of Summer cooling mode

Research Project F 2071. W. Richter. Manual of thermal comfort of Summer cooling mode Research Project F 2071 W. Richter Manual of thermal comfort of Summer cooling mode Dortmund/Berlin/Dresden 2007 This publication is a summary of the final report of a project Development of a manual on

More information

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help?

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help? HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help? Proceedings of Healthy Buildings 94 Ben Bronsema, Consulting Engineer ONRI Ketel Consulting Engineers Ltd, DELFT

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

THE EFFECT OF ENERGY RECOVERY ON INDOOR CLIMATE, AIR QUALITY AND ENERGY CONSUMPTION USING COMPUTER SIMULATIONS

THE EFFECT OF ENERGY RECOVERY ON INDOOR CLIMATE, AIR QUALITY AND ENERGY CONSUMPTION USING COMPUTER SIMULATIONS THE EFFECT OF ENERGY RECOVERY ON INDOOR CLIMATE, AIR QUALITY AND ENERGY CONSUMPTION USING COMPUTER SIMULATIONS A Thesis Submitted to the College of Graduate Studies and Research in Partial Fulfillment

More information

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability 1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

More information

Comfort Conditioning & Indoor Air Quality

Comfort Conditioning & Indoor Air Quality This article was published in ASHRAE Journal, May 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.newellinstruments.com.

More information

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEFINITION OF VENTILATIVE COOLING VENTILATIVE COOLING IS APPLICATION (DISTRIBUTION IN TIME AND SPACE) OF VENTILATION AIR FLOW TO REDUCE COOLING LOADS IN

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences Yupeng Wang 1, and Hiroatsu Fukuda 2 1 Department of BCEE, Concordia University, Canada, Email: wangyupeng0628@gmail.com

More information

How a Ground Source Heat Pump Works for a School or College

How a Ground Source Heat Pump Works for a School or College How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Tsawwassen BC Arena Before & After installation of the Low-E ceiling

Tsawwassen BC Arena Before & After installation of the Low-E ceiling LOW EMISSIVITY CEILINGS Emissivity- Describes the ability of a certain material to radiate heat rather then absorb it. Materials that radiate 100% have an (EM) of 1.0, while materials that radiate no heat

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

Thermal Imaging for Home Inspectors

Thermal Imaging for Home Inspectors Thermal Imaging for Home Inspectors Structural member placement The gabled end of a cathedral ceiling. Note the studs and the ceiling joists with blocking. What is that glow in the upper right hand corner?

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

AIRCONDITIONING Cooling Loads Calculations

AIRCONDITIONING Cooling Loads Calculations Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

National Building Code of Canada 2010

National Building Code of Canada 2010 National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much?

SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much? SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much? The sun: friend of foe? Drawing by Le Corbusier ENGS 44 Sustainable Design Benoit Cushman-Roisin 14 April 2015

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

Essam E. Khalil khalile1@asme.org

Essam E. Khalil khalile1@asme.org AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets

More information

Thermal Environmental Conditions for Human Occupancy

Thermal Environmental Conditions for Human Occupancy ANSI/ASHRAE Standard 55-2004 (Supersedes ANSI/ASHRAE Standard 55-1992) Thermal Environmental Conditions for Human Occupancy Approved by the ASHRAE Standards Committee on January 24, 2004; by the ASHRAE

More information

How a Ground Source Heat Pump Works for Commercial Buildings

How a Ground Source Heat Pump Works for Commercial Buildings How a Ground Source Heat Pump Works for Commercial Buildings 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy of Climate Master 2 Why geothermal heat

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

CONDENSATION IN REFRIDGERATED BUILDINGS

CONDENSATION IN REFRIDGERATED BUILDINGS CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

BEST 3, Atlanta, April 2012 Grahame E. Maisey, P.E.

BEST 3, Atlanta, April 2012 Grahame E. Maisey, P.E. A Methodology to Develop a Sustainable, High Performance Building Envelope BEST 3, Atlanta, April 2012 Grahame E. Maisey, P.E. We re Going To Reveal New Sustainable Truths and Expose Old Bogus Truths We

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015

BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015 BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015 Thermos Bottle Buildings are now popular and practical. However, they have thermal

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions

Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions Climotion ensures a better climate. Better comfort and lower costs in all buildings. Bosch Energy and Building Solutions 2 Smart control Smart control 3 Savings have seldom felt so good. Comfort Sustainability

More information

OUTSTANDING CHARACTERISTICS OF TEKFOIL HI-PERFORMANCE REFLECTIVE INSULATION

OUTSTANDING CHARACTERISTICS OF TEKFOIL HI-PERFORMANCE REFLECTIVE INSULATION OUTSTANDING CHARACTERISTICS OF TEKFOIL HI-PERFORMANCE REFLECTIVE INSULATION Unaffected by ultraviolet rays Environmentally safe Nontoxic Nonallergenic Anti-static Stops air infiltration Better ventilation

More information

Smaller. Quieter. Smarter.

Smaller. Quieter. Smarter. Smaller. Quieter. Smarter. Product Guide Dehumidifiers Welcome to Aprilaire Aprilaire, Your Partners in Comfort offers a complete line of dehumidifiers designed to meet the ever increasing needs of today

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

Thermal destratification in buildings: The missing piece to the HVAC puzzle

Thermal destratification in buildings: The missing piece to the HVAC puzzle WHITE PAPER Thermal destratification in buildings: The missing piece to the HVAC puzzle January 2013 Thermal Destratification In Buildings: The missing piece to the HVAC puzzle 1. What is Thermal Destratification

More information

Heating and Ventilation

Heating and Ventilation Baltic Environmental Forum Latvia Antonijas iela 3-8 LV-1010 Riga, Latvia www.bef.lv Baltic Environmental Froum Deutschland e. V. Osterstraße 58 20259 Hamburg, Germany www. bef-de.org Heating and Ventilation

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

Air Conditioning, Comfort and Energy in India s Commercial Building Sector

Air Conditioning, Comfort and Energy in India s Commercial Building Sector Air Conditioning, Comfort and Energy in India s Commercial Building Sector THINK.CHANGE.DO Leena Thomas Richard dedear Rajan Rawal Ashok Lall PC Thomas University of Technology, Sydney Sydney University

More information

Heating Systems for Low Energy Buildings

Heating Systems for Low Energy Buildings Heating Systems for Low Energy Buildings Introduction...2 The design process...4 Energy efficiency...5 Heat Generation...7 i) Combined Heat and Power (CHP)...7 ii) Multiple Boiler Arrangements...7 iii)

More information