Power-factor testing of rotating machinery is another valuable test



Similar documents
Micalastic insulation for high voltage hydro generators

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

THE VALUE OF POWER FACTOR TESTING

Understanding Insulation Resistance Testing

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

AC-Synchronous Generator

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

DC MOTOR ANALYSIS & TROUBLESHOOTING

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

Basics of Electricity

Stator Winding Hipot (High Potential) Testing

Insulation resistance testing

ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

WIRE AND CABLE ENGINEERING GUIDE

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

An Overview of Lapp Insulator High Voltage Bushing Design

SECTION 13. Multipliers. Outline of Multiplier Design Process:

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

A Practical Guide to Dielectric Testing

C ole s quality Open Frame Instrument Rotary Switch provides low

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Unified requirements for systems with voltages above 1 kv up to 15 kv

Principles of Adjustable Frequency Drives

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Why Buy HVI VLF Products?

DIRECT CURRENT GENERATORS

Energy in Electrical Systems. Overview

Line Reactors and AC Drives

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

An equivalent circuit of a loop antenna.

WIRE AND CABLE ENGINEERING GUIDE

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC

Occupational Profile: Electrical & Electronics Engineering Technician

The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics

Insulation Resistance Testing of Low Voltage Cables in the Field

Three phase circuits

WINDING RESISTANCE TESTING

Power Plant Electrical Distribution Systems

Application Information

At Load Power Factor Correction Phase 2: Refrigerated Vending Machines

Typical values for a Kapton Polyimide tape wrapped sample, according to NEMA Specifications

Aircraft Electrical System

How To Understand And Understand The Theory Of Electricity

ELECTRICAL ENGINEERING Vol. III - Induction Motor and Self-Excited Induction Generator - Tze-Fun Chan

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Three-phase AC circuits

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

Inductors & Inductance. Electronic Components

Charger Output AC Ripple Voltage and the affect on VRLA batteries

R E C O M M E N D E D P R A C T I C E FOR THE REPAIR OF ROTATING ELECTRICAL APPARATUS

Transformer Bushings for GIS

COMPLIANCE WEST USA A Compliance Products USA, Inc. Company

Gulf Cable & Electrical Ind. Co.

Current and Temperature Ratings

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis

AC Electric Motors best practice

Lab 14: 3-phase alternator.

Ceramic Trimmer Capacitors

WCAP-CSGP Ceramic Capacitors

13 ELECTRIC MOTORS Basic Relations

Objectives. Capacitors 262 CHAPTER 5 ENERGY

EE301 Lesson 14 Reading: , , and

The Complete Guide to Electrical Insulation Testing A STITCH IN TIME 1

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

I. R. D. T INSTITUTE OF RESEARCH DEVELOPMENT AND TRAINING

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Fault location on power cables. Fault location on power cables

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.

APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS

MIT510/2, MIT520/2 and MIT1020/2

Polymer Termination. Mechanical Cracking 2. The reason for polymer termination. What is Polymer Termination? 3

Appendix B Audit Forms for PdM Program Assessment

NEMA Magnet Wire Thermal Class Ratings

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

ON-LINE PARTIAL DISCHARGE MEASUREMENTS ON TURBINE GENERATORS. EXPERIENCE WITH STATER SLOT AND BUS COUPLER MEASUREMENTS

Unit 33 Three-Phase Motors

Basic Nameplate Information

Metal-Oxide Varistors (MOVs) Surface Mount Multilayer Varistors (MLVs) > MLN Series. MLN SurgeArray TM Suppressor. Description

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT

Electrical Maintenance Workshop

CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR

This section applies to the design and installation of transformers.

4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152

Specifying a Variable Frequency Drive s

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

3mm Photodiode,T-1 PD204-6C/L3

EVANS ENTErprises, Inc.

EMI in Electric Vehicles

CATHODIC PROTECTION SYSTEM DESIGN

Transcription:

Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing information about the integrity of the insulation system. This test technique has been in existence for many years, and Doble has been maintaining a database of results since the late 1950s. The database has been updated as recently as this year. The test is effective in detecting insulation contamination, the quality of the semiconducting and stress gradient coatings, the amount of void content, partial discharge damage, insulation delamination, and the quality of the impregnation process. This article is a review of the test technique and the interpretation of results. Also included are several case studies. Theory Power-factor testing of rotating machinery is a nondestructive ac test performed off line at apparatus frequency. When a 60-hertz voltage is impressed across the stator insulation, the total current that flows is similar to that of any capacitor. The total current has two components: a relatively large capacitive current (i c ), which leads the voltage by 90, and a smaller resistive current (i r ) which is in phase with the voltage. The dielectric of this simulated capacitor is the insulation system which is embedded between two electrodes: the high-voltage copper conductors and the stator iron core. The power factor is the cosine of θ, the angle between the applied voltage and the total current. i r Ei r W Watts cosθ = = = = i t Ei t Ei t Volts x Amperes by Eileen Duarte Doble Power factor is a dimensionless quantity and, thus, can be compared with different volumes of insulation systems. It is a measure of the dielectric losses of the insulation and provides valuable information about the insulation quality. Power factor is performed per phase at incremental voltages, starting at a voltage below corona inception and continuing up to the line-to-ground voltage rating of the machine and possibly 25 percent over. Power-factor tipup is defined as the power factor measured at the line-to-ground voltage minus the low-voltage power factor (typically performed at 100 percent and 25 percent of the Summer 2004 1

Figure 1 Basic Dielectric Circuit Figure 2 Total Charging Current Figure 3 A coil with few voids may have a PF of 2% at rated voltage. However with many voids a power factor of 5% to 10% may be measured at rated voltage. line-to-ground voltage). Since all dry-type insulation systems contain voids, the power factor will increase with an increase in test voltage. The increases in power factor as a function of voltage are due to the ionization of the gas in the voids of the insulation system. An insulation system with excessive voids will have a higher power-factor tip-up (see figure 3). Excessive voids may be due to the aging of the paper tape or of the bonding material in the insulation system. Aging of these materials leads to a reduction of physical strength and, thus, the production of voids. Once ex- cessive voids are present, partial discharge will occur, which also damages the bonding materials. Degradation of the insulation system may occur internally or on the surface of the coil/bar due to loose coils within the slot, deterioration of the semiconductor grading paint, and/or inadequate coil spacing. Capacitance and total charging current are also measured and recorded as part of the Doble powerfactor test. These values provide important information about the physical condition of the insulation system. A change in capacitance may occur due to a change in the size, shape, or distance between the two conductors. As an insulation system cures or ages, the dielectric constant may change, causing a change in the measured capacitance and total charging current. Applications The power-factor test on stator windings is performed off line with either the rotor in or removed. The test may be performed in air or under sealed hydrogen at near-operating pressures. Hydrogen at pressures less than 15 pounds per square inch gauge (psig) has a lower breakdown level than air at atmospheric pressure. Water-cooled machines should be tested with the demineralized water flowing through the windings and when the conductivity of the water is less than 0.25 microsiemen per centimeter (micromho per centimeter). The dc losses associated with the water-cooling system must be subtracted from the ac losses using a specified test procedure. The test may be performed on low, medium, and high voltage machines. The initial test results may be compared with Doble s tabulated data and test results. Thereafter, test results should be compared with the previous results and the tabulated data. The stator windings must be isolated and the neutral separated so that each phase may be tested individually. Each phase is tested to ground and then to the adjacent phase. If the neutral cannot be separated, all phases should be tied together and tested to ground. Limitations The power-factor test must be performed with the unit off line and with the stator winding isolated. For large machines the test set must be used with a resonating inductor in order to achieve the recommended line-to-ground test voltage. The resonating inductor extends the total charging-current range of the powerfactor test set while minimizing the input current. On a completed stator, the measured power-factor and capacitance results are an average value of the phase under test. Therefore, it may be difficult to determine if a high power factor, tip-up, or a change in capacitance is due to an overall condition or an isolated coil or coil set. 2 NETA WORLD

Interpretation Power-factor analysis requires knowledge of both test circuits and the measured parameters. Each test mode involves a different portion of the insulation system. The phase-to-ground insulation test (grounded specimen test) involves mostly the coils/bars located within the slots. The interphase insulation test (ungrounded specimen test) primarily involves the endwinding insulation because the stator iron core shields the slot sections of the phases. The recorded and analyzed parameters are: Total charging current Watts, Power Factor Capacitance Power-factor tip-up or tip down. The power-factor and watts values provide information about the quality of the insulation. The power factor measured at low voltage, below corona-inception voltage, is an indication of the inherent dielectric losses of the insulation system and its general condition. An acceptable power factor assures that the insulation system was manufactured with low-loss materials, processed properly, and free of contaminants. The low-voltage power factor will also provide information about the moisture content and the degree of overall cleanliness and curing of the insulation. It is common to have an elevated low-voltage power factor on a newly rewound insulation system due to uncured materials. In our experience, the power factor returns to normal typically six months later. Also, poor contact of the semiconductive slot coating with the core can be detected by an elevated low-voltage power factor. The power-factor tip-up (or tip-down) is a calculated value, which is sensitive to the amount of void content within the insulation system. Thus, the power-factor tip-up reflects the quality of construction of the insulating system and the impregnation process. Power-factor tip-up will respond to excessive voids in the slot due to defective or deteriorated semiconductive slot coating. The continuity and condition of the stress-control coating is detectable by power-factor tip-up or tip-down. Often enough, the interphase test will exhibit a decreasing power-factor as the voltage is increased. This results in a power-factor tip-down and typically appears when the stress gradient paint or tape is applied on the windings as part of the insulation system. Power-factor tip-down is considered normal and should be compared with previous tests and the other two phases to monitor the condition of the stress gradient paint. Power-factor tip-up is also sensitive to delamination of the insulation due to thermal stresses and partial discharge damage. In low-loss specimens (less than 20 percent power factor), the total charging current is nearly equal to the capacitive current. As a result, when the measured capacitance changes, the total charging current will change proportionally. Therefore, total charging current and capacitance provide valuable information about mechanical or physical changes in the insulation system. A change in capacitance with increasing test voltage of five percent or more or when compared to a previous test may indicate deterioration of the semiconducting paint or tape used to ground the coils in the slots. Measured power factor, capacitance, and powerfactor tip-up should be compared with the phases and with previous test results. For insulation in good condition, the per-phase results should be similar. Case Study I: Power-Factor Slot Discharge Turbine generator: 13.8 kilovolts, 15.4 megavoltamperes, manufactured in 1985, epoxy-mica Power factor: Initially very high, improved some after repairs, normal after rewind Power-factor tip-up: Initially very high, normal after rewind Capacitance: Increase with test voltage of approximately eight percent before rewind Analysis: Severe slot discharge, deterioration of semiconducting coating and stress gradient paint, with overall contamination. Note: Machine rewound November, 1995. Figure 4 Insulation to Ground Power Factor Trend, Phase A Summer 2004 3

Figure 5 Interphase Insulation Power Factor and Tip-Up Trend, Phase A Case Study II: Power-Factor Insulation Delamination Induction motor: 4.16 kilovolts, 600 horsepower, manufactured circa 1980 Initial power factor: High Initial power-factor tip-up: High After-rewind power factor: Normal After-rewind power-factor tip-up: Normal Analysis: Overall winding deterioration and delamination of insulation due to thermal stress or poor impregnation. Figure 6 Power-Factor and Tip-Up Results before and after Repairs Figure 7 Insulation to Ground Power Factor Before and After Cleaning Case Study III: Power-Factor Effects of Maintenance Turbine generator: 13.8 kilovolts, 46.5 megawatts, manufactured 1972, epoxy-mica Percent power factor at two kilovolts before clean: Slightly high Percent power factor at two kilovolts after clean: Normal Percent tip-up before clean: Normal Percent tip-up after clean: Normal, but higher Percent power factor at two kilovolts tabulated: Less than 1.0 percent Percent tip-up tabulated: Less than 1.0 percent Analysis: Contaminated insulation References 1. G. A. Heuston and E. M. Duarte, Generator Stator Insulation Power Factors, Proceedings of the 2001 International Conference of Doble Clients, Sec 7-10. 2. G. W. Armstrong, Jr. and R. J. McGrath, Power Factors and Radio-Influence Voltages for Generator-Stator Insulation, a Progress Report, Proceedings of the 1974 International Conference of Doble Clients, Sec 7-901. 3. R. J. McGrath and F. J. Gryszkiewicz, Power Factors and Radio-Influence Voltages for Generator-Stator Insulation, a Progress Report, Proceedings of the 1990 International Conference of Doble Clients, Sec 7-6.1. 4. James E. Timperley, Variations in Stator Insulation Power Factor, Resistance and Capacitance Due to High Temperatures, Proceedings of the 2000 International Conference of Doble Clients. 5. E. H. Povey, Generator Testing, a Progress Report, Proceedings of the 1954 International Conference of Doble Clients, Sec 7-301. 6. Doble Engineering, Rotating Machinery Insulation-Test Guide, Section 6: Testing, Doble Engineering Company, Watertown, MA, 1985. 7. J. H. Diehl, A Doble Test Program Success Story: Nevada Power Company Sunrise Unit #1 Generator Rewind, Proceedings of the 1989 International Conference of Doble Clients, Sec. 7-6.1. 4 NETA WORLD

8. F. J. Gryszkiewicz, Discussion of the J. H. Diehl Paper, Proceedings of the 1989 International Conference of Doble Clients, Sec. 7-6.1A. Eileen M. Duarte received her BSEE from Northeastern University in Boston, Massachusetts in 1992. She worked for General Electric in the industrial and power services business for five years and was involved mostly with motor and generator repairs at several Apparatus Service Shops. She joined Doble Engineering Company in 1998 and is presently a Principal Engineer in the Client Service Department. She is a member of IEEE and is the Secretary of the Doble Rotating Machinery Committee. Summer 2004 5