HVAC Duct Construction. Bob Wasilewski Project Manager, Technical Resources SMACNA



Similar documents
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

Duct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated

HVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA

FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS

EFFICIENT DUCT SYSTEM DESIGN

4 Installation Requirements

FINAL December 2012 SECTION DUCTWORK

Duct Fabrication Specifications. Duct Construction SUBURBAN SHEET METAL LTD. Page 1 of 43. Mailing Address P.O. Box 739 Kennedale, TX 76060

FIRE DAMPER APPLICATION GUIDE

SECTION HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section

HOTCHKISS AIR SUPPLY Heating, Ventilating & Air Movement Equipment

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Air-side Systems: Air Duct Design

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers

HVAC Air Duct Leakage. November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA

Acoustical Design Guidelines for HVAC Systems in Schools

Exhaust Calculation Booklet

DUCT SYSTEMS CHAPTER 6

WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings

Design Calculation or Analysis Cover Sheet. Complete only applicable items M8C-VCTO B

CHAPTER 6 DUCT SYSTEMS

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

security products metric sizes Redefine your comfort zone.

INDEX. Chapter8. air master. Perforated Ceiling Diffusers

Duct Design. Presented by Dave Janquart

PART 1 GENERAL 1.1 SECTION INCLUDES

DRYER VENTING SPECIFICATIONS DRYER SAFETY

HVAC - How to Size and Design Ducts

ROOF TOP MOUNTED Air Handler Specification

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

Sheet Metal Products for the HVAC Industry

Quality Regulations for Profiles

ANSI/AHRI Standard 880 (I-P) with Addendum Standard for Performance Rating of Air Terminals

SECTION HVAC AIR DISTRIBUTION

CURTAIN TYPE FIRE DAMPERS

September 1, 2003 CONCRETE MANUAL CONCRETE PAVEMENT REHABILITATION

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..

SAM HOUSTON STATE UNIVERSITY

Services Enclosures and Protected Shafts - Maintaining Compartmentation

HYLINER AKS HDPE LINING

Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork

HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings

Incorporating V2.3. Product spec >>> > Series ECG - Egg Crate Grilles. > Series ECG45-45 Egg Crate Grilles

HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades

Fire Barrier Duct Wrap 15A

AIR CONDITIONING PRODUCTS COMPANY

HVAC Ducting - Principles and Fundamentals

Lindab Representative s Handbook

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS

AISI CHEMICAL COMPOSITION LIMITS: Nonresulphurized Carbon Steels

GUIDELINE ON THROUGH-PENETRATION FIRESTOPPING

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

plenum slot diffusers

This digital document created and presented by Richard Fleetwood. He is the. Civil Defense Now! ( websites.

vav retrofit terminals

AMPSEAL* Automotive Plug Connector and Header Assembly

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Basics of HVAC Cleaning

DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES

Below are detailed instructions for using the EMS load calculator.

ENHANCED LABORATORY HVAC SYSTEM

HVAC Vents & Diffusers

HVAC Calculations and Duct Sizing

TECHNICAL BULLETIN. Oil Canning in Metal Roof and Metal Wall Systems. What Is Oil Canning?

BODY OF KNOWLEDGE API-570 AUTHORIZED PIPING INSPECTOR CERTIFICATION EXAMINATION

Installation Instructions

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

1.2 Refrigerant Equipment. General

HVAC Control & Balancing Dampers Models VCD, MBD and RBD

Damper Selection and Sizing

ASTM A860/A860M-09 Standard Specification for Wrought High Strength. Ferritic Steel Butt Welding Fittings. 1. Scope :- 2. Reference Documents :-

Refrigeration Installation 101

INSTALLATION INSTRUCTIONS: Viewline 52 mm

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.

*** MAIN VERSION OF BOM ***

How to Measure HVAC System Airflow

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

Performance Rating of Room Fan- Coils

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

SECTION AIR INLETS AND OUTLETS

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

GrEAT PACIFIC ELBOW COMPANY PRODUC T C ATALOG

DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION

Noise in the Classroom

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

CONCRETE REPAIR GUIDELINES. Concrete repairs can be broken down into four basic types, plus special repairs and planing.

Copper and Copper Alloy Tube, Pipe and Fittings

Built to Last. Built for Beauty. Good. Solid. Logix. TM

Blast Proof Occupied Buildings

Blast Resistant Building BP Refinery Rotterdam

SMA Interface Mating Dimensions (Per MIL-STD-348)

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details

POWERS Controls No. 4 Pneumatic Damper Actuator

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT CHEVROLET/GMC VANS FOR

Transcription:

HVAC Duct Construction Bob Wasilewski Project Manager, Technical Resources SMACNA

HVAC Duct Construction Standards WHAT? WHY? HOW?

Today's Program 1 st 2 nd Edition HVAC-DCS Review Joints and Limitations Transverse Joints & Reinforcements Use of the Pressure Class Tables Tie Rod Addendum

Documents Preceding 2nd Edition HVAC-DCS Low Velocity Systems Duct Manual First Edition 1959 Second Edition 1963 Third Edition 1967 Low Velocity Duct Construction Standard 1969

Documents Preceding 2nd Edition HVAC-DCS Low Pressure Duct Construction Standard Fifth Edition 1976 High Velocity Duct Systems Manual First Edition 1965 High Velocity Duct Construction Standards Second Edition 1969

Documents Preceding 2nd Edition HVAC-DCS High Pressure Duct Construction Standards Third Edition 1975 Duct Liner Application Standard First Edition 1971 Second Edition 1975

Documents Preceding 2nd Edition HVAC-DCS Flexible Duct Installation Standards First Edition 1979 Second Edition 1980 HVAC Duct Construction Standards -- Metal and Flexible First Edition 1985

Major Changes from First Edition GENERAL Text edited to be more reader-friendly Reading aids added Static pressure only as the basis for duct construction classification -- velocity levels deleted (Table 1-1)

Major Changes from First Edition Chapter 7 revised to facilitate use for equivalent and comparable tests and ratings Model project specification added Reminders to designers to show all required fire, smoke, radiation and volume control dampers on contract drawings are accented

Major Changes from First Edition Boiler breeching omitted Volume damper construction is more specific Lead radiation shielding added Metrics are included Air terminal runouts and supports are revised

Major Changes from First Edition RECTANGULAR DUCT REVISIONS Negative pressure construction given for 4", 6", and 10" w.g. Six feet reinforcement schedules added Reinforcement schedules extended to 120" width

Major Changes from First Edition Tie rod alternatives expanded for both positive and negative pressures TDC and TDF joint systems included and rated as T-25a and T-25b joints T-24a joint added as a modification of T-24

Major Changes from First Edition Use of 26 gage added for 4", 6" and 10" pressures Trapeze hanger tables expanded to cover the 120" width range Duct liner pin schedule adjusted Infrequently used joints (T-4, 8, 17, 18, 19, 20 and 23) omitted

Major Changes from First Edition Round, Flexible and Oval Duct Revisions Duct pressure classes revised to be positive and negative at 2", 4" and 10" w.g. Crimped joint connection length changed from 1" to 2" Rectangular branch taps into round added for straight or 45 degree lead-in-entry

Major Changes from First Edition Type 1 reinforcement of oval duct now has an internal tie rod (based on ASHRAE test program) Maximum support spacing for round flexible duct and connector changed from 10 feet to 5 feet Additional riser support details are provided

DUCT SYSTEMS SIZINGS FITTINGS, ETC. FIRE/SMOKE PROTECTION CODE COMPLIANCE DUCT CONSTRUCTION CODE COMPLIANCE SMACNA HVAC-DCS 2 ND ED. 1995 INSPECTION CODE COMPLIANCE

DUCT SYSTEMS ENGINEER Design Considerations: CFM Static Pressure Duct Size Fitting Type Construction Pressure Class CONTRACTOR Construction Considerations: Panel Thickness (Gage) Pressure Class (as specified) Panel Width/Height Joint Type/Spacing Intermediate Reinforcement Type/Spacing

DEPENDENT VARIABLES

REGULAR DUCTS Maximum Deflection Joint and Reinf. 1/4" on 48" w. W/200 on 49"-120" Sheet: 3/8" on 12" Dn. 1/2" on 13"-18" 5/8"on 19"-24" 3/4" on 25"-84" 1" on 85"-120" Maximum Test Pressure Lab: Class Rating + 50% Field: Class Rating + 25% Tolerance: +7.5% Tolerance: +10%

Duct Systems Used for the movement of air in HVAC/Exhaust systems Ducts are classified based on maximum operating pressure 0.5" w.g. positive or negative 1.0" w.g. positive or negative 2.0" w.g. positive or negative

Duct Systems (Continued) Ducts are classified based on maximum operating pressure 3.0" w.g. positive or negative 4.0" w.g. positive or negative 6.0" w.g. positive or negative 10.0" w.g. positive or negative

TABLE 1-2 STANDARD DUCT SEALING REQUIREMENTS

EXAMPLE 1 Duct Size 24" x 24" Pressure Class 2" w.g. Sheet Stock Joints/Reinforcements 8 ft / 4 ft Standing S

EXAMPLE 2 Duct Size 42" x 24" Pressure Class 3" w.g. 5 ft Coil Line Joints/Reinforcements 5 ft / 2 ½ ft TDC or TDF

MIDPANEL TIE ROD (MPT) ½" w.g. - 6" w.g. 37" - 96" Duct Dimension Rectangular Duct

Mid Panel Tie Rod Addendum Joints All Tie Rods Threaded Rod or Tubing/Conduit with Threaded Insert Additional Application Tables, Qualifications and Reader Aids Included

FIGURE 1-3 TIE ROD ATTACHMENTS

FIGURE 1-4 TRANSVERSE (GIRTH) JOINTS

FIGURE 1-4 TRANSVERSE (GIRTH) JOINTS

FIGURE 1-4A SPECIAL JOINT PROFILES

FIGURE 1-5 LONGITUDINAL SEAMS RECTANGULAR DUCT

TABLE 1-24 UNREINFORCED DUCT (WALL THICKNESS)

TABLE 1-25 T-1 FLAT DRIVE ACCEPTED AS REINFORCEMENT

FIGURE 1-7 UNREINFORCED DUCT

FIGURE 1-8 CROSSBROKEN DUCT & BEADED DUCT

FIGURE 1-9 DUCT REINFORCED ON TWO SIDES

FIGURE 1-10 DUCT REINFORCED ON ALL SIDES

FIGURE 1-12 DUCT OVER 120" (3048 MM) WIDE

FIGURE 1-15 CORNER CLOSURES - FLANGES

FIGURE 2-22 DUCT LINER INTERRUPTION

TABLE 3-2A ROUND DUCT GAGE UNREINFORCED POSITIVE PRESSURE

TABLE 3-2B ROUND DUCT GAGE NEGATIVE PRESSURE

FIGURE 3-1 SEAMS ROUND DUCT AND FITTINGS

FIG. 3-2 TRANSVERSE JOINTS ROUND DUCT

FIGURE 3-6 FLAT OVAL DUCTS

FIGURE 3-9 FLEXIBLE DUCT SUPPORTS

FIGURE 3-10 FLEXIBLE DUCT SUPPORTS

TABLE 4-1 RECTANGULAR DUCT HANGERS MIN. SIZE

TABLE 4-2 MINIMUM HANGER SIZES FOR ROUND DUCT

FIGURE 4-4 LOWER HANGER ATTACHMENTS

Questions & Answers