THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012



Similar documents
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

CONSTANT CURRENT REGULATOR INDUPERM TYPE CCR 951. Standarddescription of CONSTANT CURRENT REGULATOR TYPE CCR 951.

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

SECTION DETECTION AND ALARM

Application/Connection Examples

Regards from the Team at Rheology Solutions.

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Remote Monitoring and REC 501 Control Unit Product Guide

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation.

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use:

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Quick Connect. quick - simple - efficient.

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

1.44 kw Programmable DC Power Supplies XLN Series

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

Wireless Gauge and Absolute Pressure Transmitters Series XYR 5000, Model WG5xx/WA5xx Specifications - Americas

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

Thyristor power units and Solid state contactors. TC2000 series. Two-phase control of a three-phase load or control of two single-phase loads

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

Process Alarm Solutions

38 Series - Relay interface modules A

TX2123 RS485 TO ETHERNET ADAPTOR

Applications. diris_826_a_1_gb_cat

Thyristor-controlled power supplies and battery chargers

Controller board and power supply for vivimat III systems

Positioner Versions. Remote feed-back. Local display, Electric / Hydraulic. Remote feed-back Electric / Hydraulic. Embedded Control Positioner

Multi-Range Programmable DC Power Supplies 9115 Series

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Multi-Range Programmable DC Power Supplies 9115 Series

EDI Distributor Control Interface Wiring and Setup Instructions

Instructions for copying HART DD files to 375/475 using Field Communicator Easy Upgrade Utility

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111


TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

NXL Series Inverters. HVAC Inverters made simple

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

A project to optimise quality and energy efficiency must include metering

DC1000 Series General Purpose UNIVERSAL DIGITAL CONTROLLERS

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

SMART SENSOR COLLECTION

GTEC transfer switch open transition

SD Series. SD Series Rectifiers. EPC Energy & Power Conversion

TMS TANK MANAGEMENT SYSTEM

E-STOP relays, safety gate monitors

Duct Humidity Transmitter

Electronic Control Devices The European Product Catalogue 2007

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

Series OMEGA WATTS POWER SUPPLY AC/DC SINGLE OR MULTIPLE OUTPUT. Flexible modular design. Programmable outputs** Power factor correction***

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Failure code manual. content

Technical Data. back-up time in minutes 100% load % load

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

Contents. Document information

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Ordering Part Numbers: Universal Signal Converter: USC-CVB Universal Signal Converter with a 4-20mA input and +/- 10V output: USC-CVB225-B10V

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Agilent 4338B Milliohm Meter

1/11 CO2 DOSAGE SYSTEMS. CO2 dosage system consists of following parts;

38 Series - Relay interface modules A

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Current and voltage measuring relays

SL Series AC and DC Electronic Loads

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

OZW30. Central Unit SYNERGYR

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Eaton s E-Series protective relay family

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

ZC-24DO CANopen I/O Module: 24 Digital Outputs

Electric Rotary Actuator - On/Off or programmable control actuator

Model: DC-A2IO Advanced HVAC Controller

Safety technique. Emergency stop module BO 5988 safemaster

TORKEL 820 Battery Load Unit

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

User manual Rev 1.3 Contents

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

Temperature & Humidity SMS Alert Controller

High voltage tester HA 1800 Table-top device

Waveguide Access Point WGA631. Product Guide

How to read this guide

Transcription:

Technical Information THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 GENERAL DESCRIPTION THYRISTORS T1-1PH is a full digital and universal Thyristor unit based on a very powerful dedicated micro configurable via serial communication port for all inputs, firing modes, control modes and loads types. Suitable to drive resistive, inductive, transformer and complex loads requiring current limit and power control mode. Frontal Key Pad standard to configure all the internal functions and parameters. Four Analog output configuirable. Six Digital input. Four realay output. Universal Input signal with automatic zero/span calibration. Universal Firing modes, customer configurable via Key Pad or communication port as Burst Firing and Phase Angle. Universal Feed back modes. Soft Start can be used in addition to Burst Firing and Phase Angle. Short circuit Thyristor and Heater Break Alarm. RS 485 port. Modbus protocol. Comply with EMC. IP20 Protection. 1

TECHNICAL SPECIFICATION Operating Temperature 0+40 C over this temperature see derating curve. Voltage Power supply 480V standard, 600V or 690V on request. Auxiliary Voltage Supply 90 265V; 20VA power consumption. Fan voltage supply: 230V ±15% as a standard and 110V on request. Analog Input 1 Main reference, 4 20mA, 0 10V, 10KPOT, RS485 port. Analog Input 2 Secondary reference, 0 10V, 10KPot. Analog Input 3 External Current Limit Set, via analog input 0-10V or KPot. Analog Ouput Digital Input Relay Output Universal Firing Soft Start Control Mode Heater Break Alarm Communication Thermal protection Four Analog output (0 20mA or 4 20mA) for retransmitted of, Voltage, Power and current. Six optoisalated digital intput (12/24Vdc), for START, STOP, ENABLE, CALIBRATION, RESET ALARM and EXTERNAL ALARM. Three configurable relay output and one critical alarm. One of these firing modes can be configured Burst Firing BF, Single Cycles SC, Soft Start + Burst Firing; Soft Start + Phase Angle S+PA; Delayed Triggering + Burst Firing DT + BF. Digital adjustable ramp rate. Voltage (V), Current Power (VxI) and External feedback. Circuit microprocessor based to diagnose partial or total load failure and short circuit on Thyristors. RS485 Port. Modbus communication protocol 9600 or 19200 bauds. Available on forced ventilated units. 0.8 0.6 0.4 0.2 Derating curve 2

HEATER BREAK ALARM HB ON FRONT CABINET BURST FIRING BF DELAYED TRIGGERING DT CD EASY CD-KP = FEW MINUTES TO SET AND CALIBRATE ALL THE UNITS PHASE ANGLE PA FIELD BUS MODULE POWER SCALING APPLICATIONS AND FOCUS ON: The Heather Break circuit diagnostic partial or total load failure. It reads load resistance with an internal voltage transducer and current transformer to calcolate the resitance value V/I. The Heather Break circuit is compensated for voltage fluctuation,infact a voltage variation has no influence on resistance value because V/I ratio remain constant. On this unit is possible to set the nominal resistance value and the alarm sensitivity. HB alarm in addition diagnostic the thyristor in short circuit. A normaly open contact gives the alarm condition and an indication of the alarm type appears on display. This firing is performed digitally within the thyristor unit at zero volts, producing no EMC interference. Analogue input is necessary for BF and the number of complete cycles must be specified for 50% power demand. This value can be between 1 and 255 complete cycles, determining the speed of firing. When 1 is specified, the firing mode becomes Single Cycle (SC). PA controls the power to the load by allowing the thyristor to conduct for part of the AC supply cycle only. The morepower required, the more the conduction angle is advanced until virtually the whole cycle is conducting for 100% power. The load power can be adjusted from 0 to 100% as a function of the analogue input signal, normally determined by a temperature controller or potentiometer, PA is normally used with inductive loads. Used to switch the primary coil of transformers when coupled with normal resistive loads (not cold resistance) on the secondary, DT prevents the inrush current when zero voltage (ON-OFF) is used to switch the primary. The thyristor unit switches OFF when the load voltage is negative and switches ON only when positive with a pre-set delay for the first half cycle. This is a memory support tool that can be used by mantenance personnel on shop floor. The user can copy the configuration of one unit and paste it into another.cd EASY is very simple with one push button to upload the configuration (Read and another to down load the stored configuration (Write) This tool can be used with our Remote service to mail the working configuration via internet. The CD-KP is designed mounted on front cabinet and to be connected with all cd automation s Thyristor units via RS485. On front unit is possible to read parameters, power, current, reference and alarms. One of these variables can be selected and retransmitted via an isolated output (4 20mA or 0 10V) On front unit is available a connector to comunicate with PC. In addition are available Local/Remote, up and down and function command. CD-RS Used to convert RS232 to RS422. TU-RS485-PDP Used to convert RS485 Modbus to Profibus DP. TU-RS485-ETH Used to convert RS485 Modbus to Ethernet. For more informations see "Field Bus Module". It's a scaling factor of the input command signal and limit the output of Thyristor unit. This parameter can be adjusted from 1 to 99% via RS485 or by the front of the unit If this parameter is setted at 50% and the input signal is 100% the output become 50% This feature is very useful to reduce the power when a zone has been oversized or when a temperature controller gives same reference to more unit along a furnace. Imagine 3 zones with left and right one close to the doar where in acontinuos furnace the material come into and flow out.the profile of temperature along furnace is higher in central zone because there is less dispersion but if we scale its input we can have a flat profile. Infrared lamp Autoclaves Fournaces Chemical Petrochemical Climatic chambers Pharmaceutical 3

WIRING CONNECTION THYRISTORS T1-1PH from 850A to 2700A THYRISTORS T1-1PH THYRISTORS LOAD TYPE LOAD TYPE NOTE Resistance and Infrared Lamps LOAD TYPE Variable Resistances Super Kanthal or Silicon Carbide Elements Transformers and Inductances (1) The user must provide for protection external electromagnetic circuit breaker or fuse isolator. (2) Use an appropriate external transformer to supply the electronic board (see the identification label). (3) The coil contactor, the relays and other inductive loads must be equipped with proper RC filter. (4) Before to give the Start command supply the input of auxiliary voltage. DIMENSION AND FIXING HOLES H H D W S14 1PH H 520 x W 262 x D 270-22,5kg. (850A) D W S18 1PH H 580 x W 263 x D 435-28kg. (1000A) S19 1PH H 780 x W 263 x D 435-39kg. (1400A/1500A) S20 1PH H 780 x W 263 x D 533-48kg. (2000/1850A) S21 1PH H 890 x W 263 x D 518-58kg. (2400/2700A) 4

OUTPUT FEATURES (POWER DEVICE) Current A Voltage range (V) Ripetitive peak reverse voltage (600V) (690V) Latching current (maeff) Max peak one cycle (10msec.) Leakage current (maeff) I2T value for fusing tp=10msec. Frequency range (Hz) Power loss I=Inom (W) Isolation Voltage Vac 850A 330 690V 1600 1800 1000 17800 15 1027000 47 70 3000 2500 1000A 330 600V 1600 N.A. 700 12500 300 781000 47 70 3300 2500 1400A 330 690V 1600 1800 700 24600 300 3026x1E3 47 70 4620 1700 1500A 330 600V 1600 N.A. 700 24600 300 3026x1E3 47 70 5625 1700 1850A 330 690V 1600 1800 700 36000 300 6480x1E3 47 70 6105 2500 2000A 330 600V 1800 N.A. 700 36000 300 6480x1E3 47 70 6600 2500 2400A 330 690V 1800 1800 700 60000 300 180000x1E3 47 70 8000 2500 2700A 330 600V 2200 N.A. 700 60000 300 180000x1E3 47 70 10125 2500 ORDERING CODES 1 2 3 4 5 6 7 7 8 9 10 11 12 13 14 15 16 THYRISTORS T1-1PH T 1 - Note 1 4, 5, 6 Description code 850A 1000A 1400A 1500A 1850A 2000A 2400A 2700A Current Numeric code 0 8 5 0 1 0 0 0 (2) 1 4 0 0 1 5 0 0 (2) 1 8 5 0 2 0 0 0 (2) 2 4 0 0 2 7 0 0 (2) 7 Max Voltage 480V 600V 690V 4 6 7 8 Aux. Voltage supply 110V 230V 1 2 9 Description code SSR 3:30V dc 0:10V 4:20 ma 10 K Pot RS485 Input Numeric code S V A K R 10 Firing Burst Firing BF B Soft Start + Burst Firing S+BF J Delayed Triggering + Burst Firing DT+BF D Phase Angle PA P Soft Start + Phase Angle S+PA E 11 Control Mode Open Loop Voltage Feed Back V Power Feed Back VxI Current Feed Back I External Feed Back 12 Option 4:20mA Retransmission 0:10V Retransmission 0 U W I E A (3) V (3) 13 Fan Voltage Fan Voltage equal to Aux. Voltage 3 14 \ Approvals CE EMC For European Market E 15 Manual None Italian Manual English Manual German Manual French Manual 0 1 2 3 4 16 Load type Resistive Load Transformer 8 9 LEGEND IF = Internal Fixed Fuse CT = Current Transformer HB = Heater Break Alarm Note (1): After 16th digit write current and voltage of load inside brackets Ex. (190A- 400V). This is to receive the Thyristor unit already tuned from Honeywell. Note (2): Rating not available at 690V. Note (3): In total are available 4 Analog Output. One dedicated to Control Mode and the other 3 dedicated to Current, Voltage etc. 5

SALES AND SERVICE For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below. ASIA PACIFIC EMEA NORTH AMERICA SOUTH AMERICA hfs-tac-support@honeywell.com Australia Honeywell Limited Phone: +(61) 7-3846 1255 Fax: +(61) 7-3840 6481 Toll Free: 1300-36-39-36 Toll Free Fax: 1300-36-04-70 China - PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826 Honeywell Process Solutions Phone: + 80012026455 or +44 (0)1202645583 Fax: +44 (0) 1344 655554 Email: (Sales) sc-cp-apps-salespa62@honeywell.com or hfs-tac-support@honeywell.com Honeywell Process Solutions Phone: 1-800-423-9883 or 1-800-343-0228 Email: (Sales) ask-ssc@honeywell.com or hfs-tac support@honeywell.com Honeywell do Brasil & Cia Phone: +(55-11) 7266-1900 Fax: +(55-11) 7266-1905 Email: (Sales) ask-ssc@honeywell.com or hfs-tac-support@honeywell.com Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033 South Korea Honeywell Korea Co Ltd. Phone: +(822) 799 6114 Fax: +(822) 792 9015 Specifications are subject to change without notice. For More Information Learn more about how Honeywell s THYRISTORS T1-1PH and how it can help improve plant performance. Visit our website www.honeywellprocess.com/ or contact your Honeywell account manager. Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix, Arizona 85027 Phone: 1-800-423-9883 or 1-800-343-0228 www.honeywellprocess.com/ 55-77-03-62 March 2012 2012 Honeywell International Inc. 6