Diesel Rotary UPS reliability and process availability



Similar documents
UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) don@tubbesing.com

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

Data centre experts. Advanced power protection for data centres

Power protection for data centers

Designed for uptime. Defining data center availability via a tier classification system

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

Designing Fault-Tolerant Power Infrastructure

Phase Modular Finally the benefits of Modular ups are for all

An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Strategic Data Centre Site Profiles Data Centre Co-Location London North

Calculating Total Power Requirements for Data Centers

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Wireless Networks and Power Quality

Data Center UPS Systems Why 1% Efficiency Matters

Piller Rental. Nothing protects quite like Piller. High performance containerized UPS systems.

Standardization and modularity as the foundation of data center UPS infrastructure

Power backup in data centers. Something going on. 24 I MTU Report 03/10

Reliability Block Diagram RBD

Performing Effective MTBF Comparisons for Data Center Infrastructure

The Real Cost of Manual Asset Management

Data center outages impact, causes, costs, and how to mitigate

Maximizing UPS Availability

Brochure. Electric generators to power the world

System Availability and Data Protection of Infortrend s ESVA Storage Solution

Galaxy VM. Three-phase power protection. schneider-electric.com

X-tier Data Facility. Prepared by X-tier SAE Corporation

DISTRIBUTED REDUNDANCY:

Isolated-Parallel UPS Configuration

The Different Types of UPS Systems

Private Clouds & Hosted IT Solutions

Westek Technology Snapshot and HA iscsi Replication Suite

Trinergy from 200 to 1600 kw. High Power Modular Scalable UPS With Three Dynamic Functioning Modes

Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment

Five Essential Components for Highly Reliable Data Centers

Strategic Data Centre Site Profiles. Data Centre Co-Location London East

Sovereign. The made to measure data centre

Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites

Onsite Support: 24/7/365 onsite team. Security: 24/7/365 onsite manned security and CCTV. Monitoring: 24/7/365 Environmental monitoring and management

Availability Digest. SAP on VMware High Availability Analysis. A Mathematical Approach. December 2012

A reliable and experienced supplier

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

ALWAYS ON GLOBALSWITCH.COM

International Standards for Data Centre Electrical Design. Developed from The Uptime Institute & TIA942 concepts

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup

Data Center Commissioning: What you need to know

DATA CENTER ASSESSMENT SERVICES

Eni Green Data Center - Specification

IT White Paper. N + 1 Become Too Many + 1?

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

WHEN UPTIME IS REALLY CRITICAL DISCOVER THE DIFFERENCE AT ENERGYST.COM

Qualitative Analysis of Power Distribution Configurations for Data Centers

Matthias Machowinski, Directing Analyst for Enterprise Networks and Video, Infonetics Research, 20152

As close to perfection. development and production. Modular data center

Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy

Microsoft s Open CloudServer

Building Reliable, Scalable AR System Solutions. High-Availability. White Paper

Applications for Infrared Thermography at Computer Centers

WORLD CLASS, GLOBALLY CERTIFIED, HIGH AVAILABILITY DATA CENTRE INTELLICENTRE 2 MACQUARIE PARK, SYDNEY

Solving Data Loss in Massive Storage Systems Jason Resch Cleversafe

LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.

The Different Types of UPS Systems

The Different Types of UPS Systems

Datacenter Hosting and Cloud Computing Services

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers

PERFORMANCE OF MPPT CHARGE CONTROLLERS A STATE OF THE ART ANALYSIS

N.K. Srivastava GM-R&M-Engg.Services NTPC- CC/Noida

A Quick Primer on Data Center Tier Classifications

LEED-certified COPT DC-6 Data Center s green design includes innovative backup power solutions from MTU Onsite Energy

Creating A Highly Available Database Solution

Value Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity

Alternative data center power

Colt Colocation Services Colt Technology Services Group Limited. All rights reserved.

Power Management of Cell Sites

Common mistakes in datacentre planning

Design & Build The Facility Operation Team

Comparing UPS System Design Configurations

4.0 UPS dedicated to ICT for unmatched energy savings

Global Case Studies in Highly Efficient Datacenters 2014

Data centres that deliver

Technical specifications. Containerized data centre NTR CDC 40f+

How Microsoft Designs its Cloud-Scale Servers

Colocation MIX

The Application of Circuit Breakers to Reduce Downtime in Datacentres

Reliability Modeling of Direct Current Power Feeding Systems for Green Data Center

Transcription:

Diesel Rotary UPS reliability and process availability Availability in datacenter UPS infrastructures compared Summary The typical characteristics of a DRUPS system are advantageous for the reliability and availability. In itself a DRUPS system is a simple concept, using a few components. This results in a higher unit MTBF figure than the more complex Static UPS systems. The Achilles heel of the Static UPS system is the standby Diesel generator set. But even leaving this component out of the calculation, DRUPS systems have a higher MTBF number due to the simple concept and low component count. End result is a higher process availability for the customer. Content 1. Introduction 2. MTBF figures, assumptions 3. Power system availability 4. Case study, Tier III datacenter 5. Conclusions White paper WP10-01.2 Date August 2013

1. Introduction This document describes an availability analysis comprising a system comparison between Diesel Rotary UPS configurations (DRUPS) and Static UPS configurations (SUPS). Availability is the measure that datacenter operators will be looking for as this will determine the probability that their equipment at any certain moment is working properly. In critical power supplies for datacenters, UPS systems play a dominant role. Commercial datacenters can for example be rated according to the Uptime Institute Tier levels 1. The power supplies in the datacenters are a part of these evaluations. End customers are mainly concerned about the uninterrupted support for their equipment. Using the Mean Time Between Failure (MTBF) combined with the Mean Time To Repair (MTTR) one can calculate the availability of the power supply. A UPS system must be capable of supplying the power, uninterrupted and for an indefinite period of time. The Uptime Institute Tier III and IV levels suggest the backup power system in the facilities as the prime power source, where the availability of the power grid is a cheap alternative, but cannot be counted on. A DRUPS system is capable of doing so. For a SUPS system, standby diesel generator sets must be used beside the UPS and batteries, to guarantee a continuous power supply in case the grid is not available for a longer period of time. Single UPS units will not have enough capacity to cope with the power capacity demands of a modern datacenter. Units are therefore placed in parallel. The number of units needed to cope with the demand is defined N. Dependant on the required redundancy, the UPS system is configured. The Tier level as described by the Uptime Institute can be used for that, but can also be used as point of departure to get the optimal balance between redundancy vs. CAPEX target and efficiency/maintainability vs. OPEX target. 1 www.uptimeinstitute.org 2

2. MTBF figures, assumptions MTBF figures, Static UPS (SUPS) We see a broad range of MTBF figures and MTTR quotes for SUPS systems in published literature. The one this paper uses as a basis for the calculations is the value quoted by the System Reliability Center (38.000 hours) 2. This institute quotes a large range, which is possible to achieve when putting single SUPS systems in parallel. We believe the lower value is most credible as this value comes very close to gathered data in 11 years of field use by Exxon 3, where, if battery failures are taken into account, the MTBF is just a little lower as mentioned (approximately 35.000 hours). Independent consultant company Uninteruptable Power Supply uses even a lower figure (20.000 hours) 4. Other listings of single UPS systems are found at Powerkinetics bulletin (31.000 hours) 5. Quotes of SUPS suppliers range from a staggering 2.000.000 hours (APC) 6 - although in this study battery failures are not taken into account - through 165.000 hours (Liebert) 7 - where only the hardware errors are taken into account - to 90.000 (Piller) 8 and 100.000 hours (Riello) 9. MTBF figures, Diesel Rotary UPS (DRUPS) The MTBF figure for a DRUPS system is 292.890 hours. This value is calculated by a third party consultant with a valued track record in UPS industry. This is for a single DRUPS unit without taking mains supply into account 10. Although there are not much field listings of other rotary UPS systems in literature most rotary system suppliers quote numbers in the same range. The MTTR is assumed to be around 6 to 8 hours, depending on the nature of the problem. When referred to the MTTR of SUPS systems, this is around 6 hours, although with line replaceable, hot swappable units the MTTR is claimed to go as low 30 minutes. This is very hard to support as the failures referred to are concerning the electronics and assume spare parts at site, where analysis of the failure will take up already a considerable amount of this time. This time needs to be included in the MTTR when it is to be used in availability calculations. Besides this the majority of failures will be of the battery components, of which the failure analysis will be even worse. Replacement takes considerable time as well. So although it is believed the MTTR of SUPS can be improved by hot swappable electronics, the final effect cannot lead to a factorial decrease. 2 System Reliability Center, Typical Equipment MTBF Values. 3 Mean Time Between Failure (MTBF) Data Analysis of UPS, Equipment at the Exxon Chemical Plant in Baton Rouge, Louisiana Solidstate Controls Incorporated. 4 Reliability of parallel redundant UPS, Uninterruptible power supplies, Whitepaper UPS 081-01-00. 5 Powerkinetics Bulletin 04 http://www.powerkinetics.com.my/bulletin.htm. 6 Performing Effective MTBF Comparisons for Data Center Infrastructure, APC white paper 12. 7 Field MTBF Numbers: What do they really mean? White paper Liebert 2001. 8 Beveiligde voedingsconcepten en varianten voor grote computer centra en industriële omgevingen. Piller Power Systems Gmbh. 9 Designing Resilience Into Secure Power Systems, Leo Craig, Sales Manager for Riello Galatrek Ltd. 10 Reliability Calculation for a Single Rotary UPS, Mr. H. Darrlemann of DBR Consult. 3

3. Power system availability Besides the IT equipment, also critical support systems need to be provided by uninterrupted or short interrupted power. (e.g. control, cooling and access). This will drive the power demand in medium and large sized datacenters in the range of many megawatts. A single UPS unit will not be able to provide this full capacity. Static UPS systems provide a typical capacity of 600-800 kva in the high ranges, where the backup diesel generator sets provide around 3000 kva in a large unit. Large DRUPS units typically are rated between 2.000 2.500 KVA. The formula above shows that the system availability is less than the single unit availability. In order to achieve better system availability for power supply systems in datacenters, redundant units are added. If we add k units more than the actual required N, the system still is capable of supporting the load, even if k units would be out of operation. The availability of a system that requires N units with k redundancy is defined: (N, k, system) = k i=0 ( N+k )P N+k-i i av (1- ) i In order to meet the power demand of modern datacenters one needs to parallel the single UPS units and combine the output power. Availability of a single unit is defined: Avail = MTBF MTBF + MTTR This can also be defined in terms of probability. Availability is the probability that the unit is working properly if probed at a random moment: Unit Avail = (unit) For a Tier IV datacenter infrastructure the mathematics are straight forward. The requirement for a Tier IV infrastructure is that two separate power supply lines are available to provide the power. The UPS system consists of two subsystems (A and B). If the both lines are laid out symmetrically the power system availability of subsystem A and B are equal (assumed for this review). Whether the system is a SUPS or DRUPS system does not affect the mathematics. So both technologies use the next formula: (1, 1, system) = 1 i=0 ( 2 )P 2-i i av (1- ) i If we would parallel N systems, all with their own availability the system availability is expressed by the following equation: (N, system) = If we assume that the unit availability is equal for each system, which reasonably can be assumed if the units are of one type: (N, system) = PN av N i=1, i or: =, unit N In Tier III datacenter infrastructures we often see a 2N battery system being backed up by N+1 diesel generator sets. The 2N system on the battery will improve the system availability as there are 2 parallel lines. Essentially one has a system consisting of two subsystems of which one subsystem is redundant. The power supply would not be secured if the backup diesel generator sets would not work. So the power system in fact is consisting of 2 subsystems that both need to work. This makes a system with N=2 (in which the systems have a different availability). 4

, system =, battery x, Genset In which: With:, battery =, battery, N 2, battery, N =, battery, unit N and:, Genset = (N, 1, system) = 1 i=0 ( N+1 )P N+1-i i av, unit, Genset (1-, unit, Genset ) i With a DRUPS system one can propose and install another configuration for a Tier III datacenter power infrastructure. An example of a Tier III certified site in the UK, London is used to define the availability formula of the DRUPS system. To comply with Tier III requirements the DRUPS design met the criterion of concurrent maintainability of the complete system. It used double output on each of the unit to feed the double distribution paths. For availability calculations it is equal to an N+2 configuration. And therefore the availability is expressed in the next formula: (N, 2, system) = 2 i=0 ( N+2 )P N+2-i i av, unit, Genset (1- ) i 5

4. Case study, Tier III datacenter As an example is reviewed a fictional, but realistic, Tier III datacenter case. The requirement for the critical load of our datacenter is a 15.000 kva, which would make a reasonable size datacenter. Required is a Tier III rating, the Static UPS configuration being a 2N battery and N+1 diesel generator sets and the DRUPS configuration a N+2. The next assumptions and input parameter are used: Assumptions SUPS Genset DRUPS Unit capacity (kva) 600 3.000 1.670 Total units needed (N) 25 5 9 Unit MBTF (hours) 38.000 14.000 292.890 MTTR (hours) 6 8 8 Availability DRUPS N 2N 2(N+1) N+1 N+2 Amount of units 9 18 20 10 11 Availability # of nines 3 7 14 7 11 Only 9 parallel units are needed to cope with the capacity requirement. The parallel lines of the 2N also bring the result up in a better range and this can be improved by adding more redundant units in each of the parallel input lines. SUPS configuration Tier III offers 4-nines availability, whereas Diesel Rotary UPS Tier III offers a far better availability of 11-nines. The formulas explained in chapter 3, lead to the following outcome. The availability in the number of nines for the SUPS system is limited to 4 (99.99%). The diesel generator sets bring the availability number down, but as they are a small amount and have sufficient redundancy, their influence on the total system availability is neglected. Availability SUPS N 2N 2(N+1) N+1 N+2 Amount of units 25 50 52 26 27 Availability # of nines 2 4 10 5 7 The main factor is that 25 parallel battery units are needed to cope with the capacity requirement. All units need to work in order to have enough capacity. The parallel lines of the 2N bring the result up in a better range. One can improve this by adding more redundant units in the each of the parallel input lines. Adding 1 unit in each line 2(N+1), will bring the availability to 5 nines. This will increase the availability of the battery system to 10 nines. The DRUPS system with its N+2 configuration reaches a 10 nines availability. 6

5. Conclusions The physical characteristics of a DRUPS system are advantageous for the reliability and availability. In itself a DRUPS system is a simple concept using a few components. This results in a higher unit MTBF figure than the more complex Static UPS systems. The Achilles heel of the Static UPS system is the diesel generator set configuration, which according to many standards needs to be available as they are considered to be the prime power supply. With low unit availability figures diesel generator sets make the SUPS systems have a low availability compared to DRUPS technology. One can argue that the diesel generator sets are only necessary when the power fails for a longer time and take the utility into account. Even taking this to the extreme and just comparing the battery part of the SUPS with the DRUPS system, result in a higher availability of DRUPS. This is caused by the unit MTBF of the single Static UPS system being lower than of the single DRUPS system. Even when the MTFB figures of the battery systems would improve, the lower output capacity will require many battery backed SUPS systems to be paralleled, which decreases the total system availability. Overall this white paper shows that the prime function of a UPS system (availability) is best secured by simple technology and a high unit output capacity of Diesel Rotary UPS modules. 7

Other white papers available at hitec-ups.com How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. For contact details please visit www.hitec-ups.com 2013 Hitec Power Protection. All rights reserved. This publication or parts of this publication may not be used, reproduced, photocopied, transmitted, or stored in any system, without the prior written permission of Hitec Power Protection, the copyright owner.