Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage



Similar documents
Introduction. Harmonics and IEEE 519 Page 1 of 19

Product Data Bulletin

Power System Harmonics

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

The design and performance of Static Var Compensators for particle accelerators

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Power Quality Standards for Electric Service

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

A Comparison Between Theoretically Calculated and Pratically Generated Electrical Powers of Wind Turbines: A Case Study in Belen Wind farm, Turkey

Electricity Meter in the age of Photovoltaic

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Make your electric distribution network safe

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: [633] [Choudhary, 3(12): December, 2014] ISSN:

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants

Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations

Harmonic Distortion and Variable Frequency Drives

Nuclear Power Plant Electrical Power Supply System Requirements

POWER QUALITY ISSUES IN A STAND-ALONE MICROGRID BASED ON RENEWABLE ENERGY

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

21 st Century Facilities

How To Improve Power Quality

Three phase circuits

Simulation of Cable Overloading Problem on a University Distribution System

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Survey of Harmonics Measurements in Electrical Distribution Systems

APPLICATION OF IEEE STD HARMONIC LIMITS

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Facilities. Facility Power Monitoring: Or, Where Did All the Electrons Go? Technology & Development Program. Permanent and Temporary Metering

Interfacing Renewable Energy Sources to the AC Grid by a CMLI with Voltage Regulation under Low THD

Harmonics in your electrical system

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Analysis of AC-DC Converter Based on Power Factor and THD

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Power Quality for Information Technology System

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

On-site Measurement of Load and No-load Losses of GSU Transformer

Modeling and Simulation of a Large Chipper Drive

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

The Grid Interconnection of Renewable Energy at Distribution Level with the Features of High Power-Quality Improvement

RIELLO ELETTRONICA. Master HP

TECHNICAL INTERCONNECTION REQUIREMENTS FOR DISTRIBUTED GENERATION. Micro Generation & Small Generation, 3-phase, less than 30 kw

7. Reactive energy compensation

Power Factor The Basics

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

How To Improve Power Quality

Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor

Data center power dynamics within the settings of regional power grid

High Intensify Interleaved Converter for Renewable Energy Resources

Wind Turbine Operation in Power Systems and Grid Connection Requirements

Test & Data Management Software

Context: significant penetration of DG = increased risks for system security

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Scholars Research Library

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Power Quality in Isolated Systems, Requirements and Examples Analysis.

A Design of DC/DC Converter of Photovoltaic Generation System for Streetcars

Survey of Harmonics Measurements in Electrical Distribution Systems

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Electrical Energy Measurements for Rome LV Customers by Distributed Web-Server Instruments

Contents. Preface. xiii. Part I 1

Renewable Energy Grid Integration

INTERFACES FOR RENEWABLE ENERGY SOURCES WITH ELECTRIC POWER SYSTEMS

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Transcription:

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage Mustafa SEKKELI 1,*, Süleyman EROL 2 1 Sutcu Imam University, Faculty of Engineering, Electrical and Electronics Depart., K. Maras, Turkey 2 Directorate general of GASKI, GAZİANTEP,Turkey. msekkeli@ksu.edu.tr, erolsuleyman2000@hotmail.com *Corresponding author: Address: Kahramanmaras Sutcu Imam University, Dept. of Electrical and Electronics Engineering, Kahramanmaras, Turkey, E-mail address: mustafasekkeli@hotmail.com, Phone: +90344 280 1633 Abstract Power Quality (PQ) related issues are of the most concern nowadays. The widespread use of electronic equipment, such as information technology, power electronics applications, programmable logic controllers (PLC), led to a complete change of electric loads nature. These loads are simultaneously the major causers power quality problems. Due to their non-linearity, all these loads cause disturbances in the voltage waveform. This paper deals with the measurement, analysis and evaluation of the power quality parameters in a water pumping station with a medium-voltage level. Power quality parameters such as voltage, current, active power and harmonics are measured, analyzed and evaluated taking into consideration IEEE 519-1992 standards. Keywords: Power Quality, Harmonic, Medium Voltage 1. Introduction Power quality (PQ) has received a great deal of attention recently, since the increased use of power electronic devices such as converters in adjustable speed drives etc. Such devices are non-linear loads which draw nonlinear currents from the power supply. This causes distortion in the voltage and current wave form at the network [1-3].Although there are many parameters affecting on power quality, harmonics are one of the major power quality problems in power systems. These harmonics result in some problems such as malfunctions in sensitive equipment, increased heating in the conductors and motors [4-10]. Harmonics can be described as the sum of several highfrequency sinusoidal signal components. Given the importance of power quality, harmonics analysis and evaluation have been much more studied by researchers recently [11-13]. There are power quality standards that define the maximum allowable limit of distortion in voltage and current waveforms of the power supply. Many standards, guidelines and recommendations including IEEE standard 519-1992 and IEC 61000 series of standards have come into effect in this regard [1, 14]. Also, some indices like Total Harmonic Distortion (THD) and Total Demand Distortion (TDD), used respectively for voltage and current harmonics [1, 8]. In this study, an investigation is carried out to measure and evaluate the power quality in a pump station spplied by medium voltage level. This paper is organized as follows. Section 2 describes the basic knowledge of harmonic and formulations; Section 3 presents brief technical properties of installed power plant; Section 4 establishes an evaluation power quality data; finally, conclusions of overall study are presented in Section 5 2. Basic knowledge of the harmonic and indices Power systems are designed to supply and operate with pure sinusoidal voltage and current waveforms. In reality, small deviations from ideal supply conditions are generally experienced. The actual waveform is composed of a number of sine waves of different frequencies, including one at the power frequency, referred to as the fundamental component and harmonics. The term harmonic", refers to any one of the above mentioned Doi: 10.5505/apjes.2014.91300

42 sinusoidal components, the frequency of which is a multiple of that of the fundamental. The amplitude of a harmonic is generally a few percent of that of the fundamental [1-4]. Fig.1. shows a typical real, fundamental and harmonic current waveform in power systems. Figure 1.Typical distorted current waveform in electric power systems. Harmonic indices have been developed to assess the service quality of a power system with respect to the harmonic distortion levels. These indices are measures of the effective value of a waveform and can be applied to both the current and the voltage [5-7]. The IEEE-519 document has set limits on the level of allowable harmonics [14]. Several indices are available for harmonic analysis; however, the two most commonly used are the total harmonic distortion (THD) and the total demand distortion (TDD). Mathematical formulations of (THD) and (TDD) for voltage and current are given in equations (1), (2) and (3) respectively [1,4,14]: THD V h2 V 1 V 2 h 2 Ih h2 (1) THDI (2) I1 Where V1 and I1 are the RMS value of the fundamental, and Vh and Ih are the RMS value of the h-order harmonic component. Total Demand Distortion (TDD): Is the total harmonic current distortion defined by the ratio of the RMS value of the sum of the individual harmonic amplitudes to the maximum or rated demand load current IL as shown in the following expression: TDD I 2 Ih h2 I L (3) 3. Technical properties of power plant Drinking water is pumped to the city by means of power plant under study. There is one piece induction motor which is the rated power f 1000 kw in the plant. Nominal operating voltage of the motor is 10 kv. Motor is supplied by one power transformer which is rated power of 5000 kva. İndividual compensatin system is performed in the plant. Total power of capacitor connected parallel to the network is 450 kvar. Short technical specifications of the motor, transformer and capacitor are given the Table 1.

43 Table 1. Technical specifications of the motor, transformer and capacitor. Transformer Unit Secondary Voltage (kv) 10 Rating (kva) 5000 Motors Operation Voltage (kv) 10 Rating (kw) 100 Capacitors Voltage (kv) 10 Rating (kvar) 450 4. Results and discussion In this study, power quality investigation has been performed in a plant supplied by medium voltage level. Voltage, current, active power and harmonics have been analyzed and evaluated based on IEEE 519-1992 standart [14]. All Power quality parameters are measured and recorded while motor is loaded within nomial value and all capacitors are connected to network for fully compensation. Measurement was carried out by using AR5 type portable power analyzer. Voltage and current transformer already installed in the plant are used for this measurement. The measurement results are given and analized below in summary. Fig.2. shows the waveform of the three phase voltage measured from the network. As shown in the fig.2, waveform of the voltage is not pure sinusoidal form but it has some distortions. Figure 2. Voltage variations of three phases at grid. The single phase waveform of the voltage and current are also given in the Fig.3. Maximum and minimum of the fundamental voltage rms value has been changed between 8500-8400 volt while current varies between 76620-75420 milliampere.

44 Figure 3. Single phase waveform of the voltage and current. Fig.4. and 5 Shows the waveform of the voltage and current during motor start up respectively. As can be seen from the fig, sudden change in voltage and current is observed during starting up the motor. It is called transient and disappears after a short period of time. Motors should be started up with the help of soft tart techniques in order to avoid any damage on the motor. Additionally, waveform of the active power measured from the motor is given in fig.6 Figure 4. Voltage change of the motor during start up. Figure 5. Current change of the motor during start up.

45 Figure 6. Avtive power change of the motor during start up Total harmonic distortion (THD) value of the voltage and current obtained from the network buses are shown in the fig.2. It can be seen that the fig.2, maximum value of the voltage THD is 3,1% at bus while the maximum value of the current THD is 5,5% at bus. Table 2 and 3 shows the total distortion limits (THD) of voltage and current according to IEEE Std. 519-1992 respectively [14]. Considering the voltage and current THD, current value is high compared with the allowed standart values while voltage value is acceptable limit. These values should be lowered using a proper filtering system. Fig.7. Shows the individual harmonic spectrum of voltage and current measured from power plant. There are 5th and 7th harmonics order for voltage spectrum while current harmonics have 5th,7th and 13th. According to IEEE std. 519-1992, voltage harmonics order is within the acceptaple level while 7th harmonic order exceeds the allowable limit. Figure 7. Indivudial harmonic spectrum of voltage and current at power plant.

46 Table 2. Voltage distortion limits for general distribution system. Voltage Distortion Limits Bus Voltage at PCC Individual Voltage Total Voltage Distortion THD (%) Distortion THD (%) 69 kv and below 3.0 5.0 69.001 kv through 161 kv 1.5 2.5 161.001 kv and above 1.0 1.5 Table 3. Current distortion limits for general distribution system at medium and high voltage. Current Distortion Limits for General Distribution Systems (120 V Through 69 kv) Maximum Harmonic Current Distortion in Percent of IL Individual Harmonic Order (Odd Harmonics) Isc/Il <11 11<h<17 17<h<23 23<h<35 35<h TDD <20* 4.0 2.0 1.5 0.6 0.3 5.0 20<50 7.0 3.5 2.5 1.0 0.5 8.0 50<100 10.0 4.5 4.0 1.5 0.7 12.0 100<1000 12.0 5.5 5.0 2.0 1.0 15.0 >1000 15.0 7.0 6.0 2.5 1.4 20.0 5. Conclusions In this paper, a power quality evaluation of the power plant supplied by medium voltage level under maximum loading condition is presented. Harmonics and power quality events such as voltage, current, active power have been measured, analyzed and evaluated based on IEEE 519-1992 standards. The investigations show that total harmonic distortion of current measured from the plant has slightly exceeded the limit while the voltage and other parameters are mainly good. A proper filter should be designed for harmonic elimination. After applying filters, harmonic distortions will be reduced considerably and that their maximum values are within the maximum allowable limits. Acknowledgements Authors would like to thanks GASKİ power plant, it s manager and staff for their helps, collaboration and supports in our study. References [1] C. Sankaran, Power Quality, Crc press, New York, (2002). [2] B. Ebrahim, F.K. Mohammad, Sensitive load voltage compensation against voltage sags/swells and harmonics in the grid voltage and limit downstream fault currents using DVR, Electric Power Systems Research 83, 80-90 (2012). [3] M.M. Ertay, H.T. Duru, Harmonic analysis and passive power filter design for a medium voltage power system according to IEEE standards, Energy Education Science And Technology Part A 29(2), 1253-1262 (2012). [4] M. Sekkeli, Investigation of Power Quality Impact on the Textile Factories, Electronic Journal of Textile Technologies 3(3), 1-11 (2009). [5] M. Şekkeli, A.S. Yılmaz, Bir taş kırma tesisinde güç kalitesi seviyesinin ölçümü ve değerlendirilmesi, Pamukkale Üniversitesi Mühendislik Bilimleri Dergisi 15(3), 317-323 (2009). [6] M. Sekkeli, N. Tarkan, Development of a novel method for optimal use of a newly designed reactive power control relay, International Journal of Electrical Power & Energy Systems 44, 736-742 (2013). [7] K.J. Sachin, S.N. Singh, Harmonics estimation in emerging power system: Key issues and challenges, Electric Power Systems Research 81, 1754-1766 (2011). [8] N. Thai, L. Yuan, Power quality disturbance classification utilizing S-transform and binary feature matrix method, Electric Power Systems Research 79, 569-575 (2009). [9] R. Sanae, N. Éloi, X. Jianhong, S. Pierre, Performance evaluation of harmonics detection methods applied to harmonics compensation in presence of common power quality problems, Mathematics and Computers in Simulation 63, 363-375 (2003). [10] Z. Ming, L. Kaicheng, H. Yisheng, A real-time classification method of power quality disturb-

47 ances, Electric Power Systems Research 81, 660-666 (2011). [11] C. Kocatepe, A. Inan, O. Arikan, R. Yumurtaci, B. Kekezoglu, M. Baysal, A. Bozkurt, Y. Akkaya, Power quality assessment of gridconnected wind farms considering regulations in Turkey, Renewable & Sustainable Energy Reviews 13, 2553-2561 (2009). [12] F.C. Victor, L.A. Patricia, Hybrid Power Filter to Enhance Power Quality in a Medium-Voltage Distribution Network, IEEE Transactions on Industrial Electronics 5(8), 2885-2893 (2009). [13] A.P. Stavros, S. Fritz, Power-Quality Measurements in an Autonomous Island Grid With High Wind Penetration, IEEE Transactions on Power Delivery 21(1), 218-224 (2006). [14] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Standard 519-1992, USA, (1992).