HAIL EFFECTS ON AIR-CONDITIONER PERFORMANCE



Similar documents
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

SECTION HEAT PUMPS

The Development of a Frost-Less Heat Pump

Air-Conditioning Buying Guide

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

Creating Efficient HVAC Systems

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Energy Efficiency. Energy Efficient Home Cooling:

ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments.

Why Daikin? 2015 Houston, Texas USA

Glossary of Heating, Ventilation and Air Conditioning Terms

Dehumidification Frequently Asked Questions

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

HVAC Efficiency Definitions

1116, Suenaga, Takatsu-ku, Kawasaki , Japan

Heating, Ventilation & Air Conditioning Equipment

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Evaporative Cooling for Residential and Light-Commercial

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Introduction. Motor Types

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO

HVAC Basic Science - System Capacity

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

Development and testing of a multi-type air conditioner without using AC inverters

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Hot Dry Climate Air Conditioner (HDAC) Combined Field Test Report

Performance Rating of Room Fan- Coils

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Cooling Off While Utilities Heat Up in the Rockies

Schedule 3(A) Room Air Conditioners

Todd M. Rossi, Ph.D. President

Laboratory Performance Testing of Residential Window Mounted Air Conditioners

How To Buy A Lennox Power System

ECO-AIR AIR CONDITIONING

Get the FACTS about SEER and Deliver Better Customer Value

SASO 2663 :2014 ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS

Heating & Cooling Efficiency

CoolTeg Plus Chilled Water (CW) version: AC-TCW

How To Design A Building In New Delhi

How Ground/Water Source Heat Pumps Work

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests

Characteristics of Evaporators

Measured Energy and Peak Demand Reduction from High Efficiency Air Conditioner Replacement

york air-conditioning products Residential & VRF News 2015

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

Pioneer in sustainability

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Heating, Ventilation & Air Conditioning Equipment

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

Residential Duct Systems for New and Retrofit Homes

Air Conditioning 101. STN Presentation AC101

SECTION AIR CONDITIONING UNIT

Understanding Heating Seasonal Performance Factors for Heat Pumps

Performance 17 Two-Stage Air Conditioner with Puron Refrigerant

Lower Energy Costs with Rooftop Air-Conditioning Package Units

How To Improve Energy Efficiency Through Raising Inlet Temperatures

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings

The Different Types of Air Conditioning Equipment for IT Environments

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs

Innovent LASER Packaged Fresh Air Conditioning Units

Air Conditioner Cooling Capacity Test AS/NZS :1998

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

GCS16 GCS20 WARNING CAUTION

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

Strategy Guideline: HVAC Equipment Sizing

HVAC Systems: Overview

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: Uptime Racks:

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps

Residential HVAC System Sizing

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

DX14SA AIR CONDITIONER ENERGY-EFFICIENT UP TO 15 SEER SINGLE SPEED COMFORT FOR LIFE

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Preliminary Final Proposal

ARMSTRONG AIR HEAT PUMPS

Using Time-of-Day Scheduling To Save Energy

Your Guide to Buying an Energy-Efficient Central Air Conditioner

RPV - RP - RA air handling units

Environmental Data Center Management and Monitoring

Element D Services Heating, Ventilating, and Air Conditioning

Chilled Water HVAC Systems

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE

3/29/2012 INTRODUCTION HVAC BASICS

Transcription:

Proceedings of IMECE 2007 2007 ASME International Mechanical Engineering Congress and Eposition November 11-15, 2007, Seattle, Washington, United States IMECE2007-41518 HAIL EFFECTS ON AIR-CONDITIONER PERFORMANCE Matthew J. Sitzmann Haag Engineering, Co. 2455 McIver Lane Carrollton, Teas 75006 U.S.A. msitzmann@haagengineering.com Frank K. Lu Aerodynamics Research Center, Mechanical and Aerospace Engineering Department, University of Teas at Arlington Arlington, Teas 76019 U.S.A. franklu@uta.edu Steve R. Smith Haag Engineering, Co. 2455 McIver Lane Carrollton, Teas 75006 U.S.A. ssmith@haagengineering.com ABSTRACT Eperiments demonstrated the effects on air-conditioner system performance resulting from dents in fins of their condenser coils and the etent to which conventional fin repair methods restore performance. Two different, commercially available, split-system, residential-type air-conditioners were tested. Flattening substantial areas of the fins caused a reduction in capacity and efficiency of the cooling systems tested. Performance first dropped appreciably when 60% of the fin areas were pressed flat. Incremental increases in total percentages of areas flattened beyond the first reduction in performance resulted in incremental decreases in capacity and efficiency. Specifically, with 60% of the fin area flattened on one condenser, system capacity decreased 4%; system SEER (efficiency), 9%. With 100% of the fin area flattened, system capacity decreased 27%; system SEER, 34%. Combing dents from the fins after the etreme case where all fins were flattened restored capacity to within 1% of the undented condition and SEER to within 6% of the undented efficiency. Similar results were obtained for the second condenser tested. INTRODUCTION The performance of residential and commercial airconditioners has a large influence on electrical energy consumption in the United States. In 2004, households in the U.S. used 216.8 billion kwh of electricity for air-conditioning, accounting for 6.4 percent of all electricity consumed by residences [1]. Commercial buildings in 2004 consumed an additional 169.9 billion kwh of electricity for air-conditioning. In 2001, 80.8 million households within the U.S. were airconditioned [2]. In 2003, 3.6 million commercial buildings were air-conditioned [3]. Most of those were in the southwest, south Atlantic, Midwest, and middle Atlantic states [2,3]. 1 Copyright 2007 by ASME

The number of air-conditioners found in any locale can be attributed to two primary factors: population and climate. The influence of climate is measured by the number of cooling degree days per year. Unrelated to air-conditioning, but very much governed by weather, is the occurrence of hail. Much of the continental United States eperiences hail. Areas east of the Rocky Mountains, particularly southwestern and midwestern states are especially prone. It is in those areas that warm moist air from the Gulf of Meico collides with cold air from the north, creating conditions that favor hail. Figure 1 is a map of the United States depicting locations of all reports of hail ¾ inch (19.1 mm) in diameter and larger from 1981 to 1990 [4]. Included on that same map is a breakdown by geographical region of the numbers of residences and commercial buildings with air-conditioning. From the map it is readily apparent that hail-prone regions have many airconditioned buildings. Hail damage to crops, roofing, automobiles, and aircraft is well documented. The subject of this paper is hail damage to air-conditioning systems. Hail physically affects airconditioning systems by denting their condenser coil fins. Typically, condenser coil assemblies comprise punched and pressed aluminum fins fitted onto copper coils. Fin spacings vary; assemblies commonly have between 8 and 20 fins per inch (3.1 and 7.9 fins per centimeter). The thin cross sections of fins serve well to conduct heat from the refrigerant in the coils and transfer it to air passing by them. But these fins are easily bent. Impacts by even small hailstones fold the fins over. Figure 2 is a photograph of an air-conditioner with hail-dented fins. Figure 1. Locations of hailstorms with ¾ inch (19.1 mm) and larger hail from 1981 to 1990 [4]. Overlaid on the hail map is the number of residences and commercial buildings with air-conditioning by region [2,3]. + Hail (3/4 in. +) Residences w/ac (millions) Commercial Bldgs w/ac (100 thousands) 2 Copyright 2007 by ASME

Figure 2. Condenser coil fins of a rooftop air conditioner that were dented by hail. The goal of this study is to determine the effects dents have on air-conditioner performance and to what etent conventional fin repair methods restore performance. TEST DESCRIPTION Tests were performed to determine the capacity, energy efficiency ratio (EER), and seasonal energy efficiency ratio (SEER) of two separate air-conditioners as increasingly larger portions of their condenser coil fins were dented. All tests were conducted according to ARI 210/240 standards [5,6]. In all cases, the Indoor Enthalpy Method was used for reporting performance. The Outdoor Enthalpy Method was used as a check of the accuracy of the Indoor Enthalpy Method. Duct traverses with pitot tubes mounted in accordance with ANSI/ASHRAE 41.1-2000 [7] measured airflow. A complete air-conditioning system was constructed using an outdoor condenser, an indoor air handler, and copper tubing to connect the two. The condenser and the air handler were mounted in separate rooms (psychrometric chambers), and auiliary equipment controlled the environments of both rooms. A duct attached to the air handler discharge captured the airflow leaving it. Pressure, temperature, and relative humidity sensors measured properties of air entering the air handler, leaving the air handler, and entering the condenser. Pitot tubes with differential pressure sensors measured the airflow rate, and a power analyzer measured electricity consumption. Change in enthalpy of the air across the air handler and the airflow rate combined to give the cooling capacity of the systems [6,8,9,10]. Dividing the cooling capacities by electricity consumption produced the efficiencies [5,6]. Air-conditioner capacities were measured with the indoor chamber held at 80 F (26.7 C), 51% relative humidity, and the outdoor chamber temperature held at 95 F (35 C). Energy efficiency ratio (EER) was measured under those same conditions. Data for calculating the seasonal energy efficiency ratio (SEER) was measured with the indoor temperature at 80 F (26.7 C), the indoor relative humidity at 51%, and the outdoor temperature at 82 F (27.8 C) (all environmental conditions listed are nominal). In addition to the parameters required by ARI 210/240, pressure of refrigerant leaving the condenser and temperatures at multiple locations on the T1 RH1 Air Handler T2 RH2 Pv2a Pv2b Pv2c 80 F 51 %RH Ps2 Pbar Indoor Chamber Figure 3. Schematic of test setup for measuring the performance of an air-conditioning system using the Indoor Enthalpy Method. Temperature Sensor, Air Temperature Sensor, Refrigerant Relative Humidity Sensor Diff. Pressure Sensor (in. w.g.) Diff. Pressure Sensor (psig.) Power Meter Air Sampler Static Pressure Manifold Pitot Tube Barometer T3 RH3 Pliquid Condenser 95 F/82 F Outdoor Chamber 3 Copyright 2007 by ASME

evaporator and condenser coils were monitored throughout the tests. Figure 3 is a schematic of the test setup for the Indoor Enthalpy Method. Additional ducts, instrumentation, and a fan were added to the condenser outlet for usage in the Outdoor Enthalpy Method. Figures 4 and 5 are photographs of the laboratory setups. Air-Conditioning Equipment Two commercially available condensers with different manufactures were tested. Each condenser tested had a rated capacity of 30,000 Btu/h (8.8 kw) nominal and was coupled with a same-sized air handler. Manufacturer-recommended charges of R-22 refrigerant were used. Denting Strategy A wooden dowel with a hemispherical head on one end, ½- inch (12.7 mm) radius, was used to dent the fins. Welded wire with a 1-inch (25.4 mm) mesh stretched over the front of the condensers provided a grid for locating the dents. Each square of the welded wire grid was assigned a letter and a number. A random number generator selected the pattern in which the fins were to be dented. Dents were formed by manually pressing the denting tool (denter) against the fins. The denter was pressed inward until it flattened fins against the coil. Regions of fins affected by pressing the denter inward were elliptical in shape. The fins were flattened completely in a circular portion of the affected area. Figure 6 is a photograph of a typical dent. The elliptical affected area and circular flattened area are marked for clarity. On unit 1, flattened areas for each dent averaged 0.40 in. 2 (258 mm 2 ). On unit 2, flattened areas for each dent averaged 0.46 in. 2 (297 mm 2 ). The denter was utilized until ultimately every square in the guiding grid had been dented. To facilitate greater flattened areas, entire sections of the fins were folded over and flattened by hand. Figure 4. Indoor chamber with air handler, duct, flow measuring device, and instruments. Flattened Area Affected Area Figure 6. Typical dent in condenser coil fins. The affected area is elliptical in shape (yellow ellipse). The fins are flattened completely within the center of the affected area (red circle), where the denter contacted the fins directly. Repair Method To reverse the effects of denting, conventional fin combs were passed through the condenser coils to straighten the fins. Figure 5. Outdoor chamber with condenser, duct, flow measuring device, fan, and instruments. 4 Copyright 2007 by ASME

Test Protocol As built, steel louvers surrounded the condenser coils of both units tested. The units were tested initially with their louvers, then the louvers were removed to epose the coils and the units tested again. Net, dents were made randomly in the aluminum coil fins. Successive tests were performed with increasingly greater numbers of dents until every square of the wire grid had been dented. With every grid square dented, 41% to 45% of the fin areas were flattened. The remainder of the fin area was deformed but not flat or unaffected altogether. To increase the flattened fin area beyond the denter s capability, entire columns of fins were folded over mechanically so that no gaps remained between fins in those areas. Columns of flattened fins were added so that 60%, 80%, and 100% flattening resulted. The 100% flattened condition eliminated nearly all airflow through the condenser. Tests measured capacities and efficiencies of the assemblies for each condition. Finally, the fins were combed and the performances measured again. Figure 7 is a photograph of the denter and the welded wire grid. Figure 8 shows several dented conditions for which tests were run. A) 3% Flat. B) 12% Flat. C) 16% Flat D) 24% Flat. E) 41% Flat. F) 60% Flat. Figure 7. Denter and wire grid. Inset is the rounded head of the denter. G) 100%Flat. H) Combed. Figure 8. Dented coil fin conditions. 5 Copyright 2007 by ASME

FINDINGS AND DISCUSSION Denting air-conditioner fins in discrete circular regions throughout the coils had little to no effect on the capacities of the units, even with 41% of the fin areas completely flattened. Beyond the discrete dents, folding columns of fins so that 60% of the condenser areas were flattened caused the capacities to drop 4%. Flattening all of the fins, thereby eliminating nearly all airflow across the condensers, reduced the tested unit capacities 23% and 27%. Incremental increases in percentage of area dented caused incremental increases in power consumed by the systems. With all of the fins flattened, power consumption increased from the undented condition 15% for unit 1 and 19% for unit 2. With the entire coil surface covered with discrete dents (the 41% flat condition), the power consumption of one air-conditioner increased 5% and the other increased 3%. Denting the fins caused reductions in air-conditioner efficiency. The SEER of both units was reduced 34% in the etreme condition of the coil fins flattened completely. With discrete dents on the entire coil surface (the 41% flattened condition), the SEER of one unit dropped 5% and the SEER of the other unit dropped 2%. With the fins completely flattened, EER decreased 35 and 36%. In the 41% flattened condition, EER decreased 3 and 6%. Combing dents from the fins after the etreme cases where all fins were flattened completely restored capacities to within 1 and 4% of the undented capacities and SEER s to within 4 and 6% of the undented efficiencies. Figures 9 through 12 depict the capacity, EER, SEER, and power consumption for both condenser units tested. Test conditions included the as-shipped construction (with louvers on), eposed coils with a wide range of dents (with louvers off), and eposed coils after combing. 1.10 Combed 1.00 Capacity (Normalized) 0.90 Unit #1 With Louvers (as shipped) 0.80 Unit #2 0.70 0% 20% 40% 60% 80% 100% Percentage of Fin Area Flattened Figure 9. Effects of Fin Dents on System Capacity. 1.10 With Louvers (as shipped) 1.00 Efficiency, EER (Normalized) 0.90 0.80 Unit #1 Unit #2 Combed 0.70 0.60 0% 20% 40% 60% 80% 100% Percentage of Fin Area Flattened Figure 10. Effects of Fin Dents on Energy Efficiency Ratio (EER). 6 Copyright 2007 by ASME

1.10 1.00 With Louvers (as shipped) Efficiency, SEER (Normalized) 0.90 0.80 0.70 Unit #1 Unit #2 Combed 0.60 0% 20% 40% 60% 80% 100% Percentage of Fin Area Flattened Figure 11. Effects of Fin Dents on Seasonal Energy Efficiency Ratio (SEER). 1.20 Power Consumption (Normalized) 1.15 1.10 1.05 1.00 Unit #1 Unit #2 Combed With Louvers (as shipped) 0.95 0% 20% 40% 60% 80% 100% Percentage of Fin Area Flattened Figure 12. Effects of Fin Dents on Power Consumption. 7 Copyright 2007 by ASME

CONCLUSIONS Eperiments were conducted to determine the effects on air-conditioner system performance caused by denting condenser coil fins and the etent to which conventional fin repair methods restore performance. Two separate condensers were tested. With discrete dents spread over the entire surface of the units (41% of the fin area flattened), there were little to no decreases in capacity, 2 and 5% decreases in SEER, and 3 and 6% decreases in EER. In the etreme cases where all the fins were flattened completely, one unit lost 23% of its capacity while the other lost 27% of its capacity. The EER dropped 35% for one unit and 36% for the other. The SEER of each unit decreased 34%. Combing dents from the fins after the etreme cases where all fins were flattened completely restored the systems to within 1 and 4% of their undented capacities and to within 4 and 6% of their undented efficiencies. ACKNOWLEDGMENTS We would like to thank the University of Teas at Arlington and Haag Engineering for their financial and technical support. Special thanks go to Albert Ortiz for his programming epertise. REFERENCES [1] U.S. Department of Energy. 2006. 2006 Buildings Energy Data Book. Washington D.C.: Office of Energy Efficiency and Renewable Energy. [2] Energy Information Administration. 2001 Residential Energy Consumption Survey: Housing Characteristics Tables. http://www.eia.doe.gov/emeu/recs. [3] Energy Information Administration. 2003 Commercial Buildings Energy Consumption Survey: Building Characteristics Tables, Revised June 2006. http://www.eia.doe.gov/emeu/cbecs. [4] National Climatic Data Center. Hail Events Map- ESRI ArcEplorer 1.1. http://cdo.ncdc.noaa.gov/climaps/hail4614.pdf. [5] U.S. Department of Energy. 10 CFR Part 430, Appendi M to Subpart B, Uniform Test Method for Measuring the Energy Consumption of Central Air- Conditioners and Heat Pumps. http://ecfr.gpoaccess.gov/cgi/t/tet/tetid?c=ecfr&tpl=/ecfrbrowse/title10/10cfr430_main_02.tpl [6] Air-Conditioning & Refrigeration Institute. 2006. Performance Rating of Unitary Air-Conditioning and Air- Source Heat Pump Equipment, ARI Standard 210/240. Arlington, Virginia: ARI. [7] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 1992. Standard Methods for Laboratory Airflow Measurement, ANSI/ASHRAE Standard 41.2-1987 (RA 92). Atlanta, Georgia: ASHRAE. [8] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 2005. Methods of Testing for Rating Electricity Driven Unitary Air-Conditioning and Heat Pump Equipment, ANSI/ASHRAE Standard 37-2005. Atlanta, Georgia: ASHRAE. [9] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 2006. Standard Methods for Measurement of Moist Air Properties, ANSI/ASHRAE Standard 41.6-1994 (RA 2006). Atlanta, Georgia: ASHRAE. [10] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 2005. 2005 ASHRAE Handbook Fundamentals, I-P Edition. Atlanta, Georgia: ASHRAE. [11] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 2006. Standard Method for Temperature Measurement, ANSI/ASHRAE Standard 41.1-1986 (RA 2006). Atlanta, Georgia: ASHRAE. 8 Copyright 2007 by ASME