Manufactured Home Inspection Checklist
|
|
|
- Barrie Bradley
- 10 years ago
- Views:
Transcription
1 Where building safety research leads to real-world solutions. Manufactured Home Inspection Checklist Nearly eight percent of the U.S. population lives in a manufactured home, according to the U.S. Census Bureau, and many of those homes were built before wind standards were improved in The Insurance Institute for Business & Home Safety (IBHS) developed this checklist to help residents gauge how vulnerable their home might be to wind damage, based on where it s located, how well it s anchored, and what type of foundation was used. SAFETY PRECAUTIONS Never try to ride out a hurricane or tornado inside a manufactured home. Even manufactured homes with tiedowns overturn in these storms because they have light frames and offer winds a large surface area to push against. Their exteriors are also vulnerable to high winds and wind-borne debris. From 2006 to 2011, 31 percent of the 823 people killed in tornadoes in the U.S. died while in or fleeing from mobile homes, according to the National Oceanic and Atmospheric Administration. The National Severe Storm Center has found that occupants of such dwellings are 10 to 20 times more likely to be killed in tornadoes than those in conventional homes. If you re considering buying a new manufactured home, pay close attention to the year of construction. Purchase the latest model with the highest HUD Wind Zone Rating you can afford. ABOUT HUD WIND ZONE RATINGS I, II AND III If your home was built before June 1976, then there were no universal standards in place and your home is likely quite vulnerable to damage in a severe windstorm or hurricane. Between June 1976 and July 1994 manufactured housing was built to a single HUD standard regardless of where it was to be sited. While these homes (especially the double-wide units) typically perform better in high wind events than the pre-1976 homes, they are not nearly as wind resistant as the HUD Wind Zone II and Wind Zone III homes built after July Since July 1994, each newly constructed manufactured home has been required to comply with the Manufactured Home Construction and Safety Standards, commonly called the HUD Map courtesy U.S. Department of Housing and Urban Development Code. The HUD Code stipulates the home shall be designed and constructed to conform to one of three wind load zones. The appropriate wind zone used in design is dependent upon where the home will be initially installed. Homes designed and constructed to HUD Wind Zone I cannot be installed in a higher wind zone. HUD Wind Zone I = 70 mph basic wind speed HUD Wind Zone II = 100 mph basic wind speed HUD Wind Zone III = 110 mph basic wind speed If you are purchasing a new manufactured home, have it installed on a permanent foundation. If a permanent foundation is not feasible, the latest anchorage recommendations for HUD Wind Zone III should be used for maximum resistance against uplift and overturning forces. If you own one of the older homes or a HUD Wind Zone I home, the structure of the home is vulnerable to damage in a severe wind event and strengthening of that structure is difficult to accomplish. However, the following checklist may help you better assess the level of vulnerability that exists and the actions listed below may help to reduce the overall vulnerability of the home and will hopefully improve the chances that the home will still be there when you return after the event. The following is a list of items to inspect with regards to site characteristics, foundation requirements, and anchoring requirements for an existing manufactured home.
2 2 SITE CHARACTERISTICS: 1. Are there trees that are in close proximity or hang over the home that can potentially cause damage during a high wind event? Trees that are in close proximity or hang over the home can fall or branches can break off the tree during a high wind event. Trees should be pruned to reduce the risk of damage or possibly removed to eliminate the danger of tree fall. Of particular concern are pine trees, 12-inches or more in diameter, that are tall enough to fall across the home. 2. Are there power lines directly over or near the home that can pose a threat to the home during a high wind event? Power lines are located in a public right of way; therefore if a manufactured home is installed under a power line, it was likely sited in the incorrect location. During a high wind event, power lines may be pushed laterally, causing slack in the power line, knocked down by debris or failed poles and towers. You may be in danger if the power line comes in contact with the home. 3. Is there a gas tank outside of the home that is not properly tied down to a concrete foundation? If there is a gas tank outside the home, it should be supported by a concrete foundation with anchor bolts embedded into the foundation at all four legs. Anchor bolts should not be severely rusted or corroded. 4. Is your home located in a park with older homes or homes with additions, roof replacements and carports? Pre-HUD standard homes (typically single wide homes built before 1976) are very vulnerable to damage, and destruction in severe windstorms. Manufactured homes built between 1976 and 1994 or post 1994 wind zone I homes are also vulnerable to damage and destruction in severe windstorms. Carports and additions frequently fail in severe winds as do roof structures added over top of the original roof on older homes. Failures of these structures can generate a tremendous amount of windborne debris that can damage your home. 5. Does your home have one or more extra rooms, a carport, and/or a storage room that has been added by someone other than the original manufacturer? Carports and additions are frequently designed to lower wind load standards than the newer high wind rated homes. The manufactured housing industry generally requires that additions be freestanding (not attached to the manufactured home) unless it is sold as a kit designed for that home. It is not uncommon, however, for engineers to certify that the home is capable of supporting an attached carport or addition. This paves the way for aftermarket carports and additions, many of which are designed to lower standards. IBHS recommends that you have any carport, porch or addition checked to evaluate its strength and anchorage. A starting point would be to contact the manufacturer of your home and see if they can recommend someone in the area who in familiar with proper wind resistant construction details for your type of addition or carport. Improving the anchorage of the addition or carport, improving the lateral bracing of the structure, adding more fasteners to the roof panels and possibly replacing or adding more support members are typical ways of reinforcing an existing carport of addition. If you want to add a carport or addition, IBHS recommends that you purchase one with the highest wind rating (design wind speed) you can afford and that it is freestanding or attached in a manner that is appropriate for the home you own. CONDITIONS OF EXTERIOR SURFACES: 6. Are there loose or missing exterior trim or panels? Loose trim and paneling at the exterior surface of the home can become a source of wind borne debris during a high wind event. Additionally, if exterior trim or paneling is missing, the building envelope is not fully protected from water damage inside the home. 7. Are there loose or missing flashing around the perimeter exterior wall openings and/or roof edges? Flashing is a thin impervious material consisting of sheet metal, plastic, rubber, etc. that can be found at intersections and terminations of roofing systems and other exterior
3 surfaces. It is used to prevent water from penetrating the building envelope (roof and walls). Flashing is most commonly found at roof valleys, chimneys, roof penetrations, eaves, skylights roof-to-wall intersections, and around exterior wall penetrations such as windows and doors. Loose or missing flashing allows water to penetrate the building envelope and can potentially cause water damage to the structure and interior finishes. Additionally, loose flashing can become a source of wind borne debris during a high wind event. FOUNDATION AND SUPPORT STRUCTURES: Estimates suggest that more than 95 percent of manufactured housing units are never moved from their initial site. Consequently, it is prudent to install the home using the most permanent foundation system that you can afford. A permanent concrete foundation or reinforced concrete masonry stem wall on a poured footing will minimize the movement of the home in a high wind event. Shallow earth screws, that are commonly used to anchor manufactured housing units, have frequently exhibited significant lateral movement (4 to 12 inches or more) before the design capacity is developed, if it is in fact ever developed. IBHS recommends that you install your home on a permanent reinforced concrete or reinforced masonry foundation. If that is not possible, consider pouring a concrete slab under the home that encompasses the heads of the anchors or at least a concrete perimeter footer that encompasses the heads of the anchors. For an existing installation, access underneath the manufactured home is required to properly inspect the manufactured home s foundation and support structure. A flashlight, gloves, knee pads, jumpsuit, moth crystals, and a snake and/or rodent repelling substance are useful recommended equipment to have before inspecting underneath any home. Additionally, inspectors should know what Brown Recluse and Black Widow spiders look like, since it is possible to encounter these spiders during an inspection. FRAMING 8. Are the I-beams bent or rusted? Bent or rusted I-beams indicate that the weight of the manufactured home may not be properly supported. If the I-beams show signs of serious deflection, the masonry piers supporting the home may not be properly spaced to support the home on the soil conditions present at the site. Sticking doors and windows and valleys or humps in the fl oor are also signs within the home that an I-beam may be severely bent. 9. Is the wood floor framing damaged or rotted? A damaged floor framing system is a sign of possible structural failure. Since the wood floor framing is covered by a floor covering on the top and a moisture barrier underneath the home, it may be difficult to inspect. Potential damage may show up as soft spots on the floor. If you are concerned that your wood floor framing may be damaged or rotted, contact the manufacturer of your home and ask for a recommendation of someone to conduct an inspection of your floor system. A rotted floor framing system indicates moisture intrusion into the home. Check plumbing and water using devices like toilets, hot water heaters and washing machines to ensure they are not leaking. Have the rotted framing members replaced and make sure that measures (caulking, moisture barriers, etc.) are taken to prevent future moisture intrusion. PIERS 10. Are the masonry piers cracked, chipped, or otherwise damaged? Large cracks, chips, or damage to the masonry piers may reduce the structural support of the manufactured home. If several of the home s piers are severely damaged, it is recommended that you have a certified installer evaluate the integrity of the foundation pier system. 11. Are the masonry piers in contact with the steel frame? Masonry piers are used to support the weight of the manufactured home. Those piers that are not in contact with the frame are not contributing to the support of the home and can cause excessive defl ection in the beams, which can ultimately lead to structural damage. Contact a certified installer to correct any loose or non-supporting piers. 12. Are the masonry holes in blocks used in the piers facing upward or sideways? Upward Sideway Masonry block is designed to support more weight if the holes are facing in the upward direction. Additionally, if holes are facing sideways, they provide a potential home for snakes and rodents. 3
4 13. Is the cap on the masonry piers wood or concrete? Wood Concrete Concrete caps can support more weight than a wood cap and are not subject to rot and termite infestation and are therefore the IBHS recommended cap for a masonry pier. 14. Is the cap on the masonry piers cracked, rotted, or otherwise damaged? If the cap on the masonry pier is cracked, rotted or otherwise damaged, it cannot effectively support the intended weight it was designed to support. Cracked, rotted or damaged pier caps should be replaced. Contact a certifi ed installer to replace any cracked rotted or damaged pier caps. 15. Are wooden wedges present between the pier cap and the steel frame? Wooden wedges are often used to fi ll a gap that may exist between the pier cap and the structural I-beam. This is widely accepted by the industry as an approved method for leveling and supporting a manufactured home. In a high wind event, vibration and movement of the home can cause the wedges to become loose. IBHS recommends that you consider replacing the wedges with a concrete cap. PERIMETER BLOCKING: 16. Is there perimeter blocking located underneath large wall openings such as sliding glass doors and windows greater than 4 in length? Perimeter blocking is usually composed of structural wood members underneath the exterior of the home that are used for additional support at large wall openings, such as sliding glass doors and window openings greater than 4ʼ. If perimeter blocking is not present, window and door openings may defl ect causing the windows and doors to stick in the frame. If windows or doors are sticking in the frame and you suspect that it is caused by excessive deflection around the openings, contact the manufacturer or a certified installer to review the installation and blocking. ANCHOR REQUIREMENTS: Anchors and straps are widely used to secure the home to the ground. A variety of systems are used to anchor manufactured homes. The following checklist is intended to help you perform an initial assessment of your anchorage system. You may fi nd three or more types of anchors. Sidewall anchors are located along the two long sides of the home, endwall anchors are located along the short sides of the home, and centerline anchors are located underneath the marriage walls of double- and triple-wide manufactured homes. Some new installations include braces that anchor the piers to the home. Each manufacturer develops an installation guide that describes acceptable anchorage systems for a particular home based on expected wind risks. Start by checking the latest guides from your manufacturer or the state regulatory body. Try to determine how well your anchoring system matches the latest recommendations for high wind installations for your type of home. 17. What type of anchor attachment is used? Metal Strapping Cable Wires Metal strapping is the preferred method of anchor attachment for manufactured homes. Typically, the strapping should be galvanized steel 1-1/4 inches wide and inches thick. 18. In general, how many straps are attached to the anchor? None 1-2 In high wind areas, two straps are typically used to properly attach the anchor to the frame. One strap should extend vertically from the anchor to the exterior sidewall, and the other strap should wrap around the steel frame I-beam and connect to the anchor attachment point at an angle of approximately 45-degrees. The number of anchor straps required on each side and the actual angles are dependent on many factors including the length of the home, the type of soil at the site, the expected capacity of the anchor in that soil, and the design wind speed at the site where the home is installed. In high wind areas, older installations typically had straps at 8 to 10-foot spacing along the length of the home while many of the newer installations in the same areas have straps at 4 to 5-foot spacing. If the anchor straps for your home are installed with excessive space between consecutive straps (greater than 5 ) or if you have questions about the installation, contact a certified installer, to determine whether the straps will provide enough resistance during a high wind event. 4
5 19. How are the diagonal straps attached to the frame? Hood with no wrap attachment Wrapped around frame Wrap with cable clamp (cable wires only) Anchor to anchor wrap The anchor straps should fully wrap around the frame (I-beam) of the manufactured home. If straps are not wrapped completely around the frame members, the strap could disengage during a high wind event and the home could be moved from its foundations. 20. In general, what is the angle of the strap? < 45 ~ 45 > 45 In most cases, the angle of the diagonal anchor strap should be approximately 45-degrees to provide the best anchorage to resist horizontal and vertical forces. If anchor straps are not at this angle and your home is not installed on a sloping site, the anchors might not be in the correct location. If you have questions about the installation, have a certified installer evaluate your installation and if necessary relocated the anchors. 21. In general, are stabilizer plates used with the anchors? Stabilizer plates are attached to the anchors or driven next to the anchor on the side facing the interior of the home and are used to improve the resistance of the anchor heads to lateral movement. At least one manufacturer builds anchors with plates attached to a sleeve that fi ts around the anchor stem. They can be effective during a high wind event in reducing the amount of lateral movement of the anchoring system and consequently the home. Stabilizer plates may be located underground and it is therefore necessary to closely inspect the anchors for stabilizer plates. 22. In general, what is the positioning of the anchor heads relative to the ground surface? Flush with ground Part of the rod extends above ground surface Bent or angled away from home Anchors should be installed flush with the ground to provide the best resistance to lateral forces during high wind events. Those anchors that are not flush with the ground should be re-installed so that the head is flush with the ground surface. Anchors that are bent, should be replaced with new anchors. If a strong tug on each of the anchors or straps pulls any of the anchors out of the ground or moves the head a noticeable amount, then they will probably pull out or move too much during a severe windstorm as well. A longer anchor with a large stabilizer plate may have to be installed and/ or the anchor moved to a different location. A certified or licensed installer should be retained to evaluate and repair the anchorage system. 23. Are any of the straps loose or noticeably sagging? Loose or noticeably sagging anchor straps are not providing enough tension to properly anchor the home during a high wind event. If the strap can be shaken with little effort, it is too loose and it is recommended that straps be tightened to meet the manufacturer s recommendations. In colder regions it is necessary to check straps more often due to freezing and thawing which can loosen straps. 24. Are any of the bolts in the anchors loose, corroded, or otherwise severely rusted? Anchor bolts are used to secure the anchor straps to the anchor. Anchor bolts will most likely show some signs of rust; however severely rusted or corroded anchor bolts can reduce the strength of the anchor attachment and should be replaced with new anchor bolts. Additionally, any loose bolts should be tightened. 25. Are any of the anchor straps spliced? It is recommended that spliced anchor straps not be used as they may have reduced resistance to forces experienced during a high wind event. If yes, how many crimp seals are used to splice the straps? 1 (Single) 2 (Double) Crimp seals are used to connect the two ends of a splice together. There are two types of crimp seals, a single crimp seal and a double crimp seal. If a splice is encountered, two crimp seals are recommended to provide the most anchor strap strength. If you identify anchorage issues as a result of this inspection and want to ensure that you maximize the anchorage resistance for high winds, have a certified or licensed installer review your installation and compare it with the latest high wind recommendations. Further, if you have the resources, IBHS recommends that you 5
6 consider installing your home on a permanent reinforced concrete or reinforced masonry foundation. If that is not possible, add anchors to bring the installation up to the latest high wind anchorage recommendations and consider pouring a concrete slab under the home that encompasses the heads of the anchors or at least a concrete perimeter footer that encompasses the heads of the anchors. The footer or pad should encompass the tops of the anchors as this will help reduce movement of the anchor head and provide a much more stable anchorage. In addition, the footer or pad can provide a much more substantial support for the bottom of skirting around the base of the home. IBHS is a non-profit applied research and communications organization dedicated to reducing property losses due to natural and man-made disasters by building stronger, more resilient communities. Insurance Institute for Business & Home Safety 4775 East Fowler Ave. Tampa, FL (813) DisasterSafety.org
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
Protecting Your Home From Hurricane Wind Damage
T H E W I N D Protecting Your Home From Hurricane Wind Damage During a hurricane, homes may be damaged or destroyed by high winds and high waves. Debris can break windows and doors, allowing high winds
For the purposes of this Part, the following words shall have the following meanings:
LOUISIANA REVISED STATUTES TITLE 51. TRADE AND COMMERCE CHAPTER 2. PARTICULAR GOODS PART XIV-B. MINIMUM STANDARDS FOR INSTALLATION OF MANUFACTURED HOMES Current through all 2010 Regular Session Acts 912.21.
Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open
Add Strength and Water Resistance When Repairing Your Walls Any home repair or remodeling work you do presents an opportunity to make your home fare better in the next storm. Whether you are just replacing
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
Designed and Engineered to Perform
History EARTH CONTACT PRODUCTS, L.L.C., is a family owned company, based in Olathe, Kansas. This company was built upon Don May s U.S. Patented fourth-generation Steel Piering System that has led to the
Protecting Your Home from Wind Damage
Protecting Your Home from Wind Damage During severe thunderstorms or hurricanes, homes may be damaged or destroyed by high winds. Debris flying through the air can break windows and doors, allowing high
Uniform Construction Code (UCC) Manufactured Homes. Modular Homes. Building Permit Application Package
Uniform Construction Code (UCC) Manufactured Homes (Single-Wide, Double-Wide) Modular Homes Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
Protecting YOUR NEW HOME FROM Wind Damage
Protecting YOUR NEW HOME FROM Wind Damage Blueprint for Safety... A Blueprint for Life When severe weather threatens, protecting life and property automatically becomes top priority for millions of Florida
6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
Basement & Foundation Damage
Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.
Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering
Structural Failures Cost Lives and Time
Structural Failures Cost Lives and Time Recent failures of storage bins, silos and other structures highlight the need to increase awareness of hazards associated with these structures. Since 2010, one
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
FLAT ROOF CARPORT RECOMMENDED INSTRUCTION MANUAL
FLAT ROOF CARPORT RECOMMENDED INSTRUCTION MANUAL Table of Contents Introduction... 2 Components... 3 Step 1 Marking out the Perimeter of the Carport... 3 Step 2a Footing Set-Out for Concrete Block Pad
March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202
Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request
How To Repair A House
Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
International Greenhouse Company
Greenhouse Foundation Design As with any building, a good solid foundation is crucial for the long term durability and functionality of your greenhouse. A weak foundation will cause your greenhouse to
Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
Guidelines for Earthquake Bracing of Residential Water Heaters
Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)
Inspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
Guidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.
Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION
Common Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
What is Seismic Retrofitting?
What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes
Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION
SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.
Structural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
SECTION 3 ONM & J STRUCTURAL ANALYSIS
Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
The minimum reinforcement for the stem wall is the placement of:
PolySteel creates an ideal insulated stem wall for concrete slabs that can make this part of your project easier and faster, in addition to making your finished project more energy-efficient. Figures 3.20
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
Elevating Your House. Introduction CHAPTER 5
CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
Pre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
PANELIZED HOME INSTALLATION GUIDELINE
PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product
HOME INSPECTION CHECKLIST
CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards
Patio Covers / Carports
Patio Covers / Carports Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed
MANUFACTURED HOME INSTALLATION FOR PERMANENT FOUNDATIONS (TRANSVERSE FLOORS) (SUPPLEMENT TO MANUFACTURED HOME INSTALLATION MANUAL)
MANUFACTURED HOME INSTALLATION FOR PERMANENT FOUNDATIONS (TRANSVERSE FLOORS) (SUPPLEMENT TO MANUFACTURED HOME INSTALLATION MANUAL) NOTE: THIS MANUAL IS INTENDED TO INSTRUCT AND TO ASSIST ALREADY QUALIFIED
OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION
OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION Table of Contents Executive Summary... 1 Introduction... 1 Installing
PROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
During severe flood events, such as those
Recommended Practice for Home Heating Oil Tank Flood Resistance During severe flood events, such as those occurring from Hurricane Irene and Super- Storm Sandy, many coastal and low elevation inland areas
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
STANDARD OPEN PATIO COVER
STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for minimizing water intrusion through roof vent systems
Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996
CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed
MANUFACTURED HOUSING USED AS DWELLINGS
MANUFACTURED HOUSING USED AS DWELLINGS SECTION AE101 SCOPE AE101.1 General. These provisions shall be applicable only to a manufactured home used as a single dwelling unit and shall apply to the following:
Superform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
Status of Building Codes in New Jersey and New York: The Future of Resilience in a Post-Sandy Environment
Status of Building Codes in New Jersey and New York: The Future of Resilience in a Post-Sandy Environment Sandy devastated properties in several states, but primarily in New York and New Jersey. Now, as
symptoms of a faulty foundation
symptoms of a faulty foundation How does drought impact your home's foundation? For many Texas families, their home becomes the single largest investment and also the family fortune. The home's foundation
Guide to Safe Building Practices
Guide to Safe Building Practices Guide to Safe Building Practices This is a guide for tradesmen, builders and contractors to help them build, repair and retrofit buildings and particularly roofs, with
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
Ver. 2. Guide to. Inspecting Residential Brick Veneer
Ver. 2 Guide to Inspecting Residential Brick Veneer 1. A guide created by industry professionals. The knowledgeable staff at MASONPRO together with technical support from the Masonry Institute of Michigan
STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA
STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael
Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training
Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline
How to secure your property after a disaster
How to secure your property after a disaster The Red Guide to Recovery HOuse secured properly Board-Up of Windows, Doors and Roof Hole. Lot secured with Perimeter Fencing. Fires, floods, tornadoes, hurricanes,
Chapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
PART E SPECIFICATIONS
PART E SPECIFICATIONS Page 1 of 5 PART E - SPECIFICATIONS GENERAL E1. APPLICABLE SPECIFICATIONS, STANDARD DETAILS AND DRAWINGS E1.1 The City of Winnipeg Works and Operations Division Standard Construction
Uncovered Decks & Porches
Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed
EZ-48-3AB-125-35 Weather Station Mounting Tripod and Mast
EZ-48-3AB-125-35 Weather Station Mounting Tripod and Mast EZ-125-35M 35 Mast Extension (Optional) EZ-125-SK Stake Kit (Optional) EZ-46-3 Tar Pad Kit (Optional) EZ-GWA Guy Wire Kit (Optional) Ambient Weather
www.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
CITY OF SELMA, TEXAS Inspection Checklist: Commercial
Rev Y71004 The Permits and Inspections Department welcomes you to the City of Selma. The following information is provided to you as guidance through the inspection process. The City of Selma provides
TechPractices: Home Front Homes:
TechPractices: Home Front Homes: PATH's Technologies in Practice are large scale housing projects throughout the U.S. where innovative technologies are being installed and used. Information is presented
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Mobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
WorkSafe Guidance Document FALL PROTECTION IN RESIDENTIAL CONSTRUCTION
WorkSafe Guidance Document FALL PROTECTION IN RESIDENTIAL CONSTRUCTION WorkSafe Guidance Document Fall Protection in Residential Construction Table of Contents Executive Summary... 1 Introduction... 1
Finegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
Lighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: [email protected] Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting
Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting for School Buildings in Japan 8 January 2009 Koichi Shinpo Director, Educational Facilities Research Center National
CONSTRUCTION DETAILS & LOAD DESIGN CHARTS
Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
Basement Window Installation Guide Hopper and Sliding
Basement Window Installation Guide Hopper and Sliding americancraftsmanwindows.com Project Requirements: Installation must comply with all applicable building codes. Existing window frame, wall and weatherresistant
HfHMD uses LP SmartSide siding and trim.
HfHMD uses LP SmartSide siding and trim. These products are: More durable than cement fiber board. Much more volunteer-friendly to install. When installed correctly, have a 5/50- year pro-rated warranty.
Home Warranty Inspection Report
Scope of the Inspection 1111 Sample Dr. home warranty inspection 2/30/2006 Home Warranty Inspection Report 1111 Sample Dr., Detroit, MI 48223 Inspection Date: February 30, 2006 Client: Alfred E. Neumann
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
A Solid Foundation Solution for Homeowners. from. Our products are made with 90% Recycled Material Down. Right. Solid. GREEN.
A Solid Foundation Solution for Homeowners from Our products are made with 90% Recycled Material Down. Right. Solid. GREEN. Stop the damaging effects of foundation settling... Sinking foundations, cracked
PDmB, Inc. Definitions
Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or
INSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW
Vinyl Windows and Doors Manufactured by Pella Corporation INSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW Lea las instrucciones en español en el reverso.
HomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above
Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.
TM TM Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. SM The Leading Edge. 10 One Major Causes of foundation settlement or more conditions may
Rehab Inspection Report Page 1
Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
FLAT ROOF BOX SPAN CARPORTS
AGS/NC/03 FLAT ROOF BOX SPAN CARPORTS Thank you for choosing this quality product. We strongly recommend that you read these instructions thoroughly. Please take your time and do not rush the erection
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
Chapter 3 FOUNDATIONS AND FOUNDATION WALLS
Chapter 3 FOUNDATIONS AND FOUNDATION WALLS This chapter discusses foundations and foundation walls constructed using the two most common foundation materials concrete and masonry. Although the IRC permits
DRAFT TERMITE PROTECTION IN BUILDINGS
DRAFT TERMITE PROTECTION IN BUILDINGS Protection of homes and businesses from termites in Florida requires the combined efforts of builders, pest management professionals, and building inspectors. The
INSTALLATION. General. Important Note. Design. Transport
General The roof trusses you are about to install have been manufactured to precise engineering standards. To ensure that the trusses perform as designed, it is essential that they be handled, erected
Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022
M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0
Structural Foundation System
Structural Foundation System SLABTEK, a technological advancement in foundation designs for residential and lightweight commercial structures SlabTek is a patent allowed process for concrete foundations