STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA

Size: px
Start display at page:

Download "STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA"

Transcription

1 STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box College Avenue, Building MS-3 Kentfield, California November 3, 2005 Degenkolb Job Number A SUITE 450 Degenkolb Engineers Frank H. Ogawa Plaza Oakland, California phone fax

2 TABLE OF CONTENTS 1.2 Structural Assessment Executive Summary Introduction Building Description Structural and Non-Structural Assessment (Deficiencies) Recommendations Figures Photographs Appendix NOVEMBER 2005 BOLINAS MARINE STATION

3 1.2 STRUCTURAL ASSESSMENT Executive Summary An evaluation of the 5 structures (Laboratory, House, Water Storage Tank, Storage Shed and Dock) at the Bolinas Marine Station was performed by Degenkolb Engineers to identify seismic deficiencies, or weak links, of the structural and non-structural systems at the Life-Safety Performance Level as defined in ASCE 31: Seismic Evaluation of Existing Buildings. The Laboratory and the House are light framed wood construction and were originally constructed in 1914 followed by a remodel in 1964 and the construction of the reinforced concrete water storage tank. The construction of the shed is not formally documented but is of similar construction and vintage to Laboratory and House. The dock was upgraded in 1994 and consists of wood framing supported on multiple timber piers wrapped with polyethylene. Per the Geologic Hazard Assessment performed by Fugro West Inc., the site is located within the State of California Special Studies Zones for the San Andreas Fault and is located within 1080 feet of a splay of this fault. Therefore, the site is potentially subject to very high ground accelerations and potential surface fault rupture. Collapse of the structures is likely in the event that surface rupture occurs within the site. Behind the site is a very steep slope that is potentially unstable. Due to the proximity of the site to the Bolinas Lagoon, there is also the potential for liquefaction. For more detailed information refer to the Fugro West Inc. report entitled Preliminary Focused Geologic Hazard Assessment Marine Biology Laboratory. Our structural evaluation of the Laboratory, House and Storage Shed revealed that the buildings do not meet the Life-Safety Performance Objective. Strengthening of these structures is required to meet this objective. Recommended strengthening measures for the Lab include providing a new plywood roof diaphragm and positive connections between the existing wood posts and girders. Strengthening measures for the House include replacement of the roof and floor sheathing with new plywood, strengthening of the shear walls with new exterior plywood, adding hold downs at the ends of shear walls, and anchoring the brick chimneys to the roof and floors. Strengthening measures for the Storage Shed include replacing the existing sheathing on the north wall with plywood and providing holdowns connecting the walls to the foundation along the north wall. Our evaluation of the Water Storage Tank and the Dock confirmed that these structures meet the Life- Safety Performance Objective. For the Water Storage Tank, we noted that reinforcement of the tank walls is corroding due to water intrusion into the concrete and that the wood roof of the tank is rotting due to prolonged weather exposure. We recommend filling the existing cracks in the walls of the Water Storage Tank and replacing the tank roof to arrest further deterioration. Our site observations also indicated structural damage related to prolonged maintenance of the structures. There is observed water damage of the timber sheathing and framing in the House and water damage is suspected in the Laboratory. We recommend replacement of the damaged structural elements. There are also some life-safety concerns regarding the non-structural components of the building including anchorage of bookcases, containment of hazardous materials, and bracing of mechanical equipment. 1

4 1.2.2 Introduction This report presents the findings of building structural assessments per ASCE 31: Seismic Evaluation of Existing Buildings. Aspects of building performance that are considered include structural, non-structural, and foundation/geologic hazard issues. Lifelines such as water, electrical, gas and waste, etc., beyond the perimeter of the building are not considered. The ASCE 31 evaluation process is 3-tiered with a choice of 2 performance objectives: life-safety and immediate occupancy. The targeted performance objective for the College of Marin is Life-Safety. A Tier 1 evaluation is considered a preliminary phase with the purpose of screening out buildings that are compliant and quickly identifying buildings with potential seismic deficiencies. A Tier 2 evaluation is an analysis of the building that addresses the potential seismic deficiencies identified in Tier 1 screening. A Tier 3 evaluation is a detailed and complete analysis of the building. A Tier 3 evaluation is excluded from this assessment. The scope of work for the building assessments included the following tasks: 1. Reviewing available original construction documents. 2. Making site visits to of each of the buildings. The intent of the site visits was to confirm that the available drawings properly identify the extent of the building, to observe whether significant building modifications have occurred, and to observe the non-structural system bracing and anchorage. 3. Performing the required calculations as required by ASCE Preparing a report summarizing our findings including conceptual level retrofit sketches for seismically deficient buildings that are identified for a Tier 2 level assessment. Supporting documentation including a list of drawings reviewed, ASCE31 checklists, and structural calculations are included in the Appendix Building Description The Bolinas Marine Station is located along the Bolinas Lagoon at 72 Wharf Road in Bolinas, California. The Marine Station consists 5 structures including the Laboratory, the House, the Storage Shed, the Water Storage Tank, and the Dock. A site plan is shown in Figure 1. Per the Geologic Hazard Assessment performed by Fugro West Inc., the site is located within the State of California Special Studies Zones for the San Andreas Fault and is within 1080 feet from the 1906 trace. Therefore, the site is potentially subject to very high ground accelerations and potential surface fault rupture. Laboratory Building name: Bolinas Marine Laboratory Year constructed: Originally 1914, Remodeled 1964 Plan configuration: Rectangular 23 x 39 Number of stories: ASCE 31 Building type: 1 story W2 Wood Frames, Commercial and Industrial 2

5 Structural systems: See Figure 2 Roof Framing: Floor Framing: Foundation System: Lateral System: 1x straight sheathing over 2x6 roof rafters at 16 o.c supported by wood bearing walls 2x6 16 o.c. over wood sleepers Unknown, continuous footing at perimeter and spread footings at interior posts assumed. Diagonal sheathed wood shear walls Non-structural systems bracing/anchorage: Cladding: Ceilings: Lighting: Piping/Ductwork: Building contents: Hazardous materials: Cement asbestos tiles Glued on hard ceiling boards/tiles Ductwork not visible to view. Water distribution line for lab sinks braced in transverse direction only Tall bookcases, could not discern anchorage/bracing. Unknown. Bookcases house many glass containers with unknown chemicals. House Building name: Bolinas Marine House Year constructed: Originally 1914, Remodeled 1964 Plan configuration: Rectangular 23 x 39 Number of stories: ASCE 31 Building type: 1 story W2 Wood Frames, Commercial and Industrial Structural systems: See Figure 3 Roof Framing: 1x straight sheathing over 2x8 roof rafters at 16 o.c supported by wood bearing walls 2 nd Floor Framing: 1x diagonal sheathing over 2x10 16 o.c. over bearing walls Ground Floor Framing: 1x diagonal sheathing over 2x10 16 o.c. over bearing walls or girders supported by wood posts Foundation System: Unknown, continuous footing at perimeter and spread footings at interior posts assumed. Lateral System: 1x diagonal sheathing on wood stud walls 3

6 Non-structural systems bracing/anchorage:. Cladding: Masonry chimneys: Ceilings: Lighting: Piping/Ductwork: Fire sprinklers: Mechanical/Electrical Equipment: Building contents: Hazardous materials: Cement asbestos tiles 2 brick chimneys. No connection to floors or roof visible nor indicated on drawings retrofit details not implemented. Chimneys below the attic level are enclosed in plaster walls. Glued on hard ceiling tiles Surface mounted. Ductwork and piping, if any, not visible to view. Present, heads visible, distribution lines concealed by hard ceiling Wall mounted electric heaters Tall bookcases, not an braced to walls. Unknown, but not likely. Water Storage Tank Building name: Water Storage Tank Year constructed: 1964 Plan configuration: Number of stories: ASCE 31 Building type: Circular, 13 ft. diameter 1 story C2A Concrete Shear Wall Buildings with Flexible Diaphragms Structural systems: See Figure 4. Roof Framing: Foundation System: Lateral System: 2x8 tongue and groove planking spanning to radial 3x8 timber beams supported on 8 circular concrete wall 8 reinforced concrete slab. 8 concrete shear walls Non-structural systems bracing/anchorage: N/A Storage Shed Building name: Storage Shed, See Photo 7 Year constructed: Unknown Plan configuration: Rectangular with approximate dimensions of 11 ft x 23-6 Number of stories: Building type: 1 story Concrete shear wall 4

7 Structural systems: Roof Framing: Foundation System: Lateral System: Gable roof 2x framing with 2x collars ties supported by bearing stud walls Slab on grade, foundation unknown Straight sheathing on roof, diagonal sheathing on walls Non-structural systems bracing/anchorage: Cladding: Ceilings: Lighting: Mechanical/Electrical Equipment: Building contents: Hazardous materials: Cement asbestos tiles Plywood boards mounted to underside of collar ties. Exposed light bulbs. Wall mounted heater. Miscellaneous storage, tools, equipment etc. Unknown, but likely. Store of multiple glass containers with unknown chemicals and metal and plastic containers with flammable liquids. Dock Building name: Dock Year constructed: Original construction date unknown, Structural repairs 1994 Plan configuration: Rectangular 22 x 20 Structural systems: See Figures 5 & 6. Framing: Foundation System: Lateral System: 3x timbers flat over 4x12 pressure treated beams Timber piers wrapped in polyethylene Timber piers Non-structural systems bracing/anchorage:.n/a Structural and Non-Structural Assessment (Deficiencies): Laboratory The straight-sheathed roof diaphragm is not adequate for seismic loads. Water damage is evident at several locations through the ceiling indicating possible deterioration of the wood framing. No positive connection between the timber girders and the columns has been provided which could result in a loss of gravity support during an earthquake. The water pipe suspended from the ceiling has no longitudinal bracing, see Photo 3. House The straight-sheathed roof diaphragm is not adequate for seismic loads. The diagonal sheathed floor diaphragm is not adequate for seismic loads. The diagonal sheathed shear walls are not adequate for seismic loads. The shear walls are not adequately connected through the floor to resist overturning forces. 5

8 Water damage to the roof sheathing and framing is evident at several locations in the attic, see Photo 2. The brick masonry chimney is not reinforced or adequately braced at floor and roof levels for seismic loads, see Photo 1. Some of the bookcases are not braced to the wall and pose falling hazards. Water Storage Tank The concrete tank walls are showing rust stains indicative of corroding rebar. See Photo 4. There is cracking of the tank walls which allows for water intrusion into the concrete and accelerates corrosion of rebar, see Photo 5. The wood roof framing shows signs of deterioration including dry rot and mold, see Photo 6. Storage Shed The narrow shear walls on the north side of the shear are not adequate for seismic loads. The wall mounted heater is not braced for seismic loads. Hazardous and/or flammable materials are improperly stored and could topple over in an earthquake. Dock There are no structural deficiencies for the dock. Site Features The retaining wall at the rear of the house is showing signs of distress and has rotated out of plumb. A propane tank located near the storage tank is not anchored to the concrete pad. Numerous water pipes are interconnected between the buildings, see Photo Recommendations Laboratory Remove the existing straight roof sheathing and replace with new plywood sheathing, see Figure 7. Perform invasive testing to determine the extent of the water damage. Replace framing with signs of dry rot. Provide straps at the girder to column connections, see Figure 8. While bracing of the water pipe is not a life-safety concern, we recommend bracing the pipe in the longitudinal direction to reduce potential damage in an earthquake, see Figure 8. House Remove the existing straight roof sheathing and replace with new plywood sheathing, see Figures 10 & 11. Remove the diagonal straight floor sheathing and replace with new plywood sheathing, see Figures 9 & 11. Replace the existing diagonal sheathing with new plywood at the upper story walls, see Figures 10 & 11. Replace the existing diagonal sheathing with new plywood sheathing and replace the framing receiving edge nailing with 3x members at the lower story walls, see Figures 9 & 11. Provide hold-downs to the foundation and across the 2 nd floor at the ends of all shear walls, see Figures 9, 10 & 11. 6

9 Brace the brick chimney to the roof and floors. If the chimney is no longer operable and not desired by the District, remove the chimney and infill the floor and roof openings. Replace any members with significant water damage. Brace all bookcases. Water Storage Tank Fill any cracks greater than 0.1mm with epoxy. Apply a concrete sealer to the perimeter of the exterior and interior of the tank. This will halt the corrosion of the rebar in the tank walls. In addition, the tank shall be monitored for further cracking or spalling of concrete. If either occurs, we recommend replacement of the tank. Locally remove the existing roof to provide access for inspection of the inside of the tank. Condition of the inside of the tank is unknown. Replace roof framing with significant water damage. Storage Shed Replace the existing diagonal sheathing at the north wall with new plywood. Provide hold-downs at the ends of the shearwall segments on the north elevation. Provide containment of hazardous and/or flammable materials. Provide seismic bracing for the wall-mounted heater. Dock Inspect the dock regularly and perform periodic maintenance. Site Geotechnical engineer to make repair recommendations for the failing retaining walls. Provide anchorage for the propane tank to the existing slab. Though bracing of the water pipes is not a life-safety concern, we recommend the addition of bracing and flexible connections to limit damage that could result from pipe breakage. 7

10 1.2.6 Figures Figure 1 Bolinas Site Plan 8

11 Figure 2 Laboratory Framing Plans and Section 9

12 Figure 3 House Framing Plans & Section 10

13 Figure 4 Water Storage Tank Plans & Sections 11

14

15

16 Figure 7 Laboratory Retrofit Concept - Roof Plan 14

17 Figure 8 Laboratory Retrofit Concept - Ceiling Plan 15

18 Figure 9 House Retrofit Concept - Ground Floor Plan 16

19 Figure 10 House Retrofit Concept - Second Floor Plan 17

20 Figure 11 House Retrofit Concept - Section 18

21 1.2.7 Photographs Photo 1 Bolinas Marine House Brick Chimneys Photo 2 Bolinas Marine House Water Damage at Roof Photo 3 Bolinas Marine Laboratory Plumbing Distribution Line Photo 4 Bolinas Marine Water Storage Tank Elevation (Evidence of Corrosion) Photo 5 Bolinas Marine Water Storage Tank Damage to Tank Wall Photo 6 Bolinas Marine Water Storage Tank Deterioration of Wood Roof 19

22 1.2.7 Photographs (continued) Photo 7 Bolinas Marine Storage Shed West Elevation Photo 8 Bolinas Marine Storage Shed Interior Photo 9 Bolinas Marine Storage Shed Hazardous Materials Photo 10 Bolinas Marine Laboratory Interconnecting Utilities 20

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael

More information

Expected Performance Rating System

Expected Performance Rating System Expected Performance Rating System In researching seismic rating systems to determine how to best classify the facilities within the Portland Public School system, we searched out what was used by other

More information

What is Seismic Retrofitting?

What is Seismic Retrofitting? What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes

More information

SECTION 7 Engineered Buildings Field Investigation

SECTION 7 Engineered Buildings Field Investigation SECTION 7 Engineered Buildings Field Investigation Types of Data to Be Collected and Recorded A field investigator looking at engineered buildings is expected to assess the type of damage to buildings.

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

STANDARD OPEN PATIO COVER

STANDARD OPEN PATIO COVER STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist

More information

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline

More information

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022 M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

Photos showing the change in condition from 2006 to 2012 are located in Appendix A.

Photos showing the change in condition from 2006 to 2012 are located in Appendix A. January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives

More information

Photo 2. View showing flour mill, machine shed, veranda and saw mill + storage shed.

Photo 2. View showing flour mill, machine shed, veranda and saw mill + storage shed. May 7,2015 KSANDER & ASSOCIATES CONSULTING PROFESSIONAL ENGINEERS 130 HUINTER STREET, UNIT 103, PETERBOROUGH, ONTARIO K9H2K8 TELEPHONE (705) 743-9221 FAX 743-0904 Ontario Region Conservation Authority

More information

EARTHQUAKE DESIGN OF BUILDINGS

EARTHQUAKE DESIGN OF BUILDINGS GAP.2.0.9 A Publication of Global Asset Protection Services LLC EARTHQUAKE DESIGN OF BUILDINGS INTRODUCTION Buildings in many areas of the world are susceptible to damage from moderate to severe earthquakes.

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

Structural Failures Cost Lives and Time

Structural Failures Cost Lives and Time Structural Failures Cost Lives and Time Recent failures of storage bins, silos and other structures highlight the need to increase awareness of hazards associated with these structures. Since 2010, one

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

Critical Facility Round Table

Critical Facility Round Table Critical Facility Round Table October 16, 2003 San Francisco Seismic Risk for Data Centers David Bonneville Senior Principal Degenkolb Engineers San Francisco, California Presentation Outline Seismic Risk

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

Coos Bay Public Library

Coos Bay Public Library Coos Bay Public Library Structural Assessment 525 Anderson Avenue, Coos Bay, OR February 21, 2014 Prepared for: Randy Dixon 500 Central Avenue Coos Bay, OR 97420 Tel: 541.269.1181 Fax: 541.269.8916 Prepared

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No. Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering

More information

Slavic Village Building Condition Review

Slavic Village Building Condition Review Slavic Village Building Condition Review Slavic Village Development May 8, 2015 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

Chapter. Restoration of Damaged Structures

Chapter. Restoration of Damaged Structures 5 Chapter Restoration of Damaged Structures Bringing back a damaged structure to its pre-earthquake state and original strength is called restoration. This is the first step of building rehabilitation.

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We

More information

Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting

Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting for School Buildings in Japan 8 January 2009 Koichi Shinpo Director, Educational Facilities Research Center National

More information

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,

More information

Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open

Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open Add Strength and Water Resistance When Repairing Your Walls Any home repair or remodeling work you do presents an opportunity to make your home fare better in the next storm. Whether you are just replacing

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are: When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory

More information

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 Structural Inspection Report Client: CSArch Architecture Engineering Construction Management 19 Front Street, Newburgh,

More information

TYPICAL PATIO COVERS 111

TYPICAL PATIO COVERS 111 City of Laguna Niguel Building Division 30111 Crown Valley Pkwy Laguna Niguel, CA 92677 (949) 362-4360 FAX 362-4369 www.cityoflagunaniguel.org TYPICAL PATIO COVERS 111 PLEASE NOTE: This information Bulletin

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

MEMORANDUM. General: Foundation:

MEMORANDUM. General: Foundation: MEMORANDUM State of Alaska Department of Transportation and Public Facilities Central Region - Division of Construction and Operations Public Facilities Branch TO: Jennifer Murrel DATE: August 19, 2010

More information

17,280 square feet Overview:

17,280 square feet Overview: CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

Elevating Your House. Introduction CHAPTER 5

Elevating Your House. Introduction CHAPTER 5 CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,

More information

Engineers, Civil Structural Survey

Engineers, Civil Structural Survey Engineers, Civil Structural Survey 317 STREET 0 6 3 6 0 886-1966 886-9165 FAX. September 1 1 Mr. Alan Bergren City Manager City of Norwich Broadway, Floor Norwich, 06360 Re: Limited Structural Condition

More information

Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT

Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT Property Inspection 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT March 2013 This document has been prepared for the benefit of Clint Marston. No liability is accepted by this company

More information

Structural Seismic Retrofits For Hawaii Single Family Residences With Post and Pier Foundations

Structural Seismic Retrofits For Hawaii Single Family Residences With Post and Pier Foundations Structural Seismic Retrofits For Hawaii Single Family Residences With Post and Pier Foundations Volume I Results of Study, Structural Analysis and Retrofit Strategies Prepared for FEMA Hazard Mitigation

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Patio Covers / Carports

Patio Covers / Carports Patio Covers / Carports Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

Building Foundation and Structure

Building Foundation and Structure Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original

More information

Architectural Condition Survey

Architectural Condition Survey Architectural Condition Survey Santa Fe Railroad / AMTRAK Depot, Lawrence. Kansas for the City of Lawrence, 2002 Survey: (student) PI: William Carswell, Associate Dean, School of Architecture, University

More information

Building Construction. Lightweight construction. Conventional Construction

Building Construction. Lightweight construction. Conventional Construction Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.

More information

Estimated Cost of Repair

Estimated Cost of Repair 1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:

More information

SECTION 8 Industrial Facilities Field Investigation

SECTION 8 Industrial Facilities Field Investigation SECTION 8 Industrial Facilities Field Investigation Types of Data to Be Collected and Recorded Warehouses, manufacturing facilities, energy-producing facilities, and factories should be inspected for performance

More information

Basement & Foundation Damage

Basement & Foundation Damage Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

STRUCTURAL ASSESSMENT

STRUCTURAL ASSESSMENT STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

ISO Types 1-6: Construction Code Descriptions

ISO Types 1-6: Construction Code Descriptions ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with

More information

CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST

CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

SINGLE-FAMILY EARTHQUAKE (SEISMIC) RETROFITS

SINGLE-FAMILY EARTHQUAKE (SEISMIC) RETROFITS CITY OF BEAVERTON Community Development Department Building Division 12725 SW Millikan Way / PO Box 4755, Beaverton, OR 97076 Phone: (503) 526-2493 Fax: (503) 526-2550 General Information (503) 526-2222

More information

inimi ing damage and repair osts to manufa tured omes during an eart ua e

inimi ing damage and repair osts to manufa tured omes during an eart ua e inimi ing damage and repair osts to manufa tured omes during an eart ua e Prepared for T e Department of Housing and Urban Development Offi e of Poli y Development and eesear by t e National Conferen e

More information

Article 5: Building Regulations

Article 5: Building Regulations Article 5: Building Regulations Division 37: Additional Building Regulations for Archaic Materials and Methods of Construction (Added Additional Building Regulations for Archaic Materials and Methods of

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

Prestige Home Inspection LLC

Prestige Home Inspection LLC Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012

More information

HomeSpec REPORT SUMMARY

HomeSpec REPORT SUMMARY HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above

More information

PETERSONS WATERFRONT CONDOMINIUMS

PETERSONS WATERFRONT CONDOMINIUMS CONSULT DESIGN CONSTRUCT PETERSONS WATERFRONT CONDOMINIUMS 103 Park Street Chelan, Washington Findings Summary Report Prepared for: Petersons Waterfront Condominium Association March 21, 2014 J2 Project

More information

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)

More information

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

School Construction Authority Architecture & Engineering

School Construction Authority Architecture & Engineering SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following

More information

Structural Assessment Report

Structural Assessment Report Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive

More information

Custom 30 x 20-8 Garage Plan Plan #g233 By SDS-CAD Specialized Design Systems

Custom 30 x 20-8 Garage Plan Plan #g233 By SDS-CAD Specialized Design Systems P O Box 34 Mendon, Utah Custom 30 x 20-8 Garage Plan Plan #g233 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical Section

More information

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for: A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.

More information

Repair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY

Repair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY Repair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY Purpose and Intended Audience The August 24, 2014 South Napa Earthquake has again served as a reminder that

More information

Earthquakes and Data Centers

Earthquakes and Data Centers 7x24 Exchange Fall Symposium September 11, 2013 Hilton Bellevue Andrew W. Taylor, Ph.D., S.E., FACI Earthquake Hazards 2 September 11, 2013 1 Cascadia Earthquake Sources Figure Credit: Craig Weaver, Pacific

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

Simpson Engineering A state licensed engineering firm F-1607

Simpson Engineering A state licensed engineering firm F-1607 Simpson Engineering A state licensed engineering firm F-1607 4126 Allencrest 13901 Midway Lane, Dallas, Road, Texas Ste.102-136 75244 Telephone: 214-351-1637 Dallas, - Fax: TX 214-351-1639 75244-4388 Telephone:

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering

More information

RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS

RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS Johnson County Building Officials Association January 2008 Residential Foundation Guideline Foundation designs for one-and two-family dwellings may use

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section

More information

Chapter. Earthquake Damage: Types, Process, Categories

Chapter. Earthquake Damage: Types, Process, Categories 3 Chapter Earthquake Damage: Types, Process, Categories Earthquakes leave behind a trail of damage and destruction. People s lives are affected by the loss of loved ones, destruction of property, economic

More information

Pre-Drywall Inspection Report

Pre-Drywall Inspection Report SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion

More information

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction

More information

I NI NP R Inspected Items

I NI NP R Inspected Items 6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and

More information

OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION

OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION OSHA GUIDANCE DOCUMENT FALL PROTECTION IN RESIDENTIAL CONSTRUCTION Table of Contents Executive Summary... 1 Introduction... 1 Installing

More information

ASHULIA APPARELS LTD. Client Summary Report

ASHULIA APPARELS LTD. Client Summary Report Revision : Issue 1 Date: 18 March 2014 ASHULIA APPARELS LTD Samad Mansion, Sec # 6, Block # kha, Road No# 1, Plot #14, Shenpara Parbata, Mirpur, Dhaka (23.8065N,90.3683E) 4th March 2014 Client Summary

More information

Solar Water Heating and Solar Electric Generators Installed on One or Two Family Dwellings

Solar Water Heating and Solar Electric Generators Installed on One or Two Family Dwellings Solar Water Heating and Solar Electric Generators Installed on Category: Residential Construction Revised: [Paul L. Scarlett], Director Responsible Bureau Section: Development Services Center 1900 SW Fourth

More information

HomeGuard. Incorporated. Home Inspection Report. 3030 Park Estates Way, San Jose. Ordered by: Inspected by:

HomeGuard. Incorporated. Home Inspection Report. 3030 Park Estates Way, San Jose. Ordered by: Inspected by: HomeGuard Incorporated Home Inspection Report 3030 Park Estates Way, San Jose Ordered by: Heidi Catalan Referral Realty 2028 Scott Boulevard #A Santa Clara, CA 95054 Inspected by: Perry Knowlton June 30,

More information

Water Damage & Repair

Water Damage & Repair Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below

More information

General Earthquake Damage Inspection Checklist

General Earthquake Damage Inspection Checklist A. GENERAL INFORMATION 1. Street Address of Property: City: State: Zip: 2. Property Owner s Name: 3. Date of inspection: 4. Inspector s Name: B. BUILDING SITE INSPECTION 5. Utility Service Safety: IMPORTANT

More information

Post and Beam Construction

Post and Beam Construction Post and Beam Construction A Presentation By the Canadian Wood Council Canadian Conseil Wood canadien Council du bois Early settlers introduced the concept of post and beam construction in North America

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

Development Services City of Lawrence, KS

Development Services City of Lawrence, KS Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.

More information