1 Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119

2 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution, and cable sprawl with a minimum of heartache and expense. Whether the data center mess is created over years of mismanagement or whether the cable-choked data center is inherited, solutions for both quick fixes and longer term evolutionary changes exist. This paper outlines several innovative approaches for dealing with the symptoms of chaos and for eliminating the root causes of disorder. 2

3 Introduction In many data centers, the symptoms of chaos are readily apparent. A cursory tour of an unplanned data center exhibits numerous undesirable symptoms such as missing floor tiles, masses of disorganized cabling, and rudimentary spot cooling. Fortunately, solutions can be deployed and processes can be instituted that either force revolutionary change or that encourage an evolutionary migration to an orderly data center. Figure 1 Establishment of order through modular deployment of zones Benefit: Organized zone separate from existing chaos Taking Control: Tools and Methods to Resolve An IT manager faced with the symptoms of chaos can resolve the issues by taking charge of two areas: physical infrastructure deployment and change management behaviors. Hardware innovations which allow the easy deployment of self-contained zones of racks, and software developments which enable rational physical infrastructure change management are two keys for an affordable and non disruptive data center face lift. Imaginative physical infrastructure deployments Since data centers are evolving to scalable modular rack-based solutions, a cure can be applied to the chaos problem. By deploying a rack-based system that includes the UPS power, electrical distribution, monitoring, cable routing and air flow solutions, an integrated approach can be easily adopted, at reasonable cost. 3

4 Racks have evolved to accommodate higher density IT equipment. Selecting a standard rack size is an important first step. For information regarding rack selection criteria, please see APC White Paper #72, Five Basic Steps for Efficient Space Organization within High Density Enclosures. A new row of racks can be set up as a self contained zone that resides on the data center floor but which operates independent of the existing infrastructure (see Figure 1). These organized zones can proliferate as the existing chaotic infrastructure begins to phase out, either rack by rack or row by row. By leveraging the opportunity to install integrated rack systems, chaotic growth can be transitioned to controlled growth as the new equipment phases out the old. Alteration of change management behaviors Change control is a systematic way for the IT manager to control his or her destiny. Traditional IT change control is characterized by a formal request to initiate a change in the IT environment, followed by a formal review of the suggested change, followed by an analysis of the predicted outcome, and formulation of a back-out plan if the change does not work out as planned. Frequently overlooked in this methodology, however, is the power of the change control process to direct the evolution of both the IT and physical infrastructure. After all, a failure in the IT infrastructure impacts one application or system, while a failure in the physical Infrastructure (power, cooling) can potentially impact all applications and systems. Figure 2 Screen from APC Capacity and Change Manager tools 4

5 By adopting an automated change control process (see Figure 2), an IT manager can positively influence how the data center evolves from a systems perspective. By including the facility or physical infrastructure side of the data center environment, the IT manager can also steer the evolution of the data center away from one that breeds organizational chaos. Robust vendor management is also an important tool for avoiding chaos. The trend towards the outsourcing of facilities and systems to third parties has blurred the issue of accountability for quality of performance. An IT manager seeking to evolve from a chaotic situation should insist on strict adherence to standard data center practices, including a change control process, as part of any contract for services outside of the direct chain of command. Only by having all data center personnel operating under the same standards of performance can the evolution from chaos to order occur. Figure 3 Wire management in back of the rack Multiple colored cables with no labeling Consistent cable color Difficult to locate cable destinations Ties help organize cables Random wiring configuration Benefit: Reduction in human error Right side cable orientation The Cause of The primary cause of chaos is unplanned, uncontrolled growth. As the business introduces new processes to help drive the growth, IT responds by building and supporting new applications. IT equipment is rolled into the data center to support the applications and new systems are deployed in a hectic deadline driven environment. New servers and applications can be obtained and pressed into service within days. However, the installation of the accompanying physical infrastructure (raised floor, cable, racks, cooling, UPS, PDUs) can take months. Under the pressure of time, equipment is often installed with no regard to the long term implications to the data center integrity and reliability. 5

6 The chaotic environment is compounded by turnover in IT staff and supplier personnel. This turnover cuts short any institutional learning that may develop over time and thereby prevents the fostering of order and organization. In the end, a typical response is to keep adding servers and accompanying communications and power cables rather than to institute an orderly replacement or reuse process. Figure 4 Overhead cabling provides a way out of the plenum mess If a legacy cable problem is at the root of the chaos in the data center, and that the cable problem is below the raised floor, then the obvious solution is to install overhead cable and power distribution systems to 6

7 support the IT equipment see Figure 4. As the new equipment is powered and cabled from overhead, the under floor cable and power can be abandoned in place until it can be removed safely with minimal risk. The Effects of Poor air distribution Poor air distribution can cause servers and related IT equipment to overheat. IT server equipment typically requires an air flow of cubic feet per minute. This rate of air flow will remove enough heat to raise the exhaust air temperature by F ( C). If this heat transfer does not take place, the device may shut down, fail prematurely, or corrupt the data being processed. Figure 5 Installation of blanking panels Gaps wreak havoc on air flow New equipment addition would require unplugging of some existing wires Tool-less installation and removal of blanking panels Barrier to unwanted hot air Benefit: Higher efficiency, lower electrical bills Poor power system capacity management Electrical distribution circuits have defined capabilities that limit the amount of load that can be placed on them before the circuit protector (fuse or circuit breaker) opens. Uncontrolled circuit assignment can lead to downtime when circuit limitations are exceeded. Downtime can also occur when conditioned power sources, such as UPS systems, are not well managed and maintained. The automated capacity management system (see Figure 2) can automatically distribute and track single and three-phase equipment power draw, ensuring that all three phases on the power system carry a balanced load. In addition, the system maps the power path and illustrates the physical system relationships and dependencies. 7

8 Disrupted communications Poor planning can constrain telecommunications when the cabling system, patch panels and device interconnects reach capacity limits. As cable technologies evolve over time, the avenues or paths the cables take to link systems to one another become saturated with abandoned legacy cable. This can have a profound impact when fiber optic telecommunication cables are mixed with copper cables in a random fashion. Fiber is easy to break, and the quantity of data riding through is large, magnifying the impact if a cable problem occurs. The inability to address cable issues without impacting the data center operation is the primary reason why chaos is allowed to proliferate. IT managers are loath to remove dead or unused cables if the potential impact is downtime or a break in communications. Figure 6 Migration to contained close-coupled cooling Recirculation of warm air Cold air distribution Uneven air distribution Scalable cooling (variable speed fans) Tripping hazard Intelligent temperature monitoring Benefit: Accommodation of high density racks Quick Fixes to Eliminate Numerous actions can be taken to begin the process of establishing order in the data center: Organize power and data cables in a standard manner (see APC White Paper #72, Five Basic Steps for Efficient Space Organization within High Density Enclosures for details) (Figure 4) Label power cables identifying both specific cable origin on one end and load targeted at the other end Assign specific power cables to specific loads and document cable assignments Remove poor grade power strips and deploy vertical PDUs in back of racks to distribute power that can be monitored Replace damaged or missing ceiling tiles this will improve the efficiency of the air flow 8

9 Audit locations of perforated raised floor tiles. Remove damaged tiles and replace any that are in cold aisles. Seal any cable cut outs in floor tiles that support cables coming through the raised floor (Figure 7) Eliminate fans and supplementary air conditioned units and install row-based air conditioning to address hot spots (Figure 6) Remove all packaging materials, spare parts, unused equipment that are present from the data center floor Install blanking panels so that open gaps in racks which disrupt air flow patterns are eliminated. These gaps complicate hot air removal (Figure 5) Figure 7 Sealing of open floor cutouts Removed tiles allow mixing of cold and hot air leading to decrease In cooling efficiency Brush strip prevents cold air escaping and increases air pressure under the raised floor Wires in under floor plenum obstruct proper airflow Benefit: Efficient cold air distribution Leverage Evolution as a Long Term Solution As data centers continue to evolve over time, an opportunity exists for leveraging the changes to breed order instead of chaos. An IT manager faced with a legacy mess, inherited or created must recognize that the bad situation developed over time. Fortunately, the same forces that lead to the creation of the chaos also offer a way out. As business requirements drive new solutions and generations of equipment, they offer the opportunity to migrate to a more stable, reliable environment. By exercising control going forward in the selection of data center infrastructure methodologies and equipment that support the mission critical environment, an IT manager can resolve the legacy chaos through the natural equipment replacement and upgrade process. 9

10 Conclusion An IT professional faced with the challenge of managing a chaotic data center now has some available options for solving the problem. Many of today s technologies provide integrated rack-based data center solutions for power, air, cable routing, and management that allow for a migration from a chaotic to a managed data center with minimal risk of downtime. The key is to leverage the natural evolution of IT systems and communication platforms. A paradigm shift may be required that relegates the traditional raised floor environment to obsolete status, but this is easily done with today s technologies. The IT manager must standardize behavioral methodologies by instituting a change control system that accounts for both the IT infrastructure and the physical infrastructure. Only through the effective use of these tools and methods can order evolve from chaos. About the Author: Dennis Bouley is a Strategic Research Analyst at APC s Data Center Science Center, in West Kingston, RI. He holds a Bachelor s degree in Journalism and French from the University of Rhode Island and a Certificat Annuel from the Sorbonne in Paris, France. Over the last 20 years (10 with IBM and 10 with APC) he has interviewed data center professionals regarding their data center IT and physical infrastructure environments. 10

Creating Order from Chaos in Data Centers and Server Rooms

Creating Order from Chaos in Data Centers and Server Rooms Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Strategies for Deploying Blade Servers in Existing Data Centers

Strategies for Deploying Blade Servers in Existing Data Centers Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling

More information

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Essential Rack System Requirements for Next Generation Data Centers

Essential Rack System Requirements for Next Generation Data Centers Essential Rack System Requirements for Next Generation Data Centers White Paper #7 Revision 2 Executive Summary Effective mission critical installations must address the known problems and challenges relating

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

Thermal Optimisation in the Data Centre

Thermal Optimisation in the Data Centre Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal

More information

OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers

OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging

More information

Essential NCPI Management Requirements for Next Generation Data Centers

Essential NCPI Management Requirements for Next Generation Data Centers Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Re-examining the Suitability of the Raised Floor for Data Center Applications

Re-examining the Suitability of the Raised Floor for Data Center Applications Re-examining the Suitability of the Raised Floor for Data Center Applications By Neil Rasmussen White Paper #19 Revision 1 Executive Summary The circumstances that gave rise to the development and use

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

EMC PERSPECTIVE Managing Energy Efficiency in the Data Center

EMC PERSPECTIVE Managing Energy Efficiency in the Data Center EMC PERSPECTIVE Managing Energy Efficiency in the Data Center A tactical approach can deliver immediate problem resolution plus long-term savings and efficiencies Managing Energy Efficiency in the Data

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129 Executive Summary Significant improvements in efficiency, power density, power monitoring,

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

ADC-APC Integrated Cisco Data Center Solutions

ADC-APC Integrated Cisco Data Center Solutions Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design Considerations Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design: Overall Expectations Need: Prime vs. Redundant vs. Mirrored

More information

Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC

Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC About us Data centre consulting World-class products Expert national team Mike Hassaballa, Applications

More information

Smart Data Center Solutions

Smart Data Center Solutions Smart Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing,

More information

An Introduction to Cold Aisle Containment Systems in the Data Centre

An Introduction to Cold Aisle Containment Systems in the Data Centre An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems

More information

Data Center Solutions

Data Center Solutions Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing, deploying

More information

Cabinets 101: Configuring A Network Or Server Cabinet

Cabinets 101: Configuring A Network Or Server Cabinet Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms By Neil Rasmussen White Paper #49 Executive Summary Avoidable mistakes that are routinely made when installing cooling

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability

Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability Colocation and Cloud Hosting Solutions Build a strong and efficient physical infrastructure that delivers service reliability and profitability 2 Dependability and Deployment Speed that Improves Your Bottom

More information

WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption

WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption WHITE PAPER Creating the Green Data Center Simple Measures to Reduce Energy Consumption Introduction Energy Awareness Driving Decisions in the DataCenter The continued thirst for energy is a recurring

More information

Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth

Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Integrated Cabinet Solutions For Business-Critical Continuity Why Proper Cable Management Is So Important Your rack

More information

Policy Title-Aquia Data Center Operational Policy & Procedure. Policy ID - TSD-ADC001. Version - Version: 1.0. Supersedes Version 1.

Policy Title-Aquia Data Center Operational Policy & Procedure. Policy ID - TSD-ADC001. Version - Version: 1.0. Supersedes Version 1. Policy Title-Aquia Data Center Operational Policy & Procedure Policy ID - TSD-ADC001 Version - Version: 1.0 Supersedes Version 1.0 Review Date One (1) year from effective date. Policy & Procedure - Provides

More information

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

Essential Cooling System Requirements for Next Generation Data Centers

Essential Cooling System Requirements for Next Generation Data Centers Essential Cooling System Requirements for Next Generation Data Centers White Paper #5 Revision 3 Executive Summary Effective mission critical installations must address the known problems and challenges

More information

Layer Zero. for the data center

Layer Zero. for the data center Layer Zero for the data center Preparefor the Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,

More information

Classification of Data Center Operations Technology (OT) Management Tools

Classification of Data Center Operations Technology (OT) Management Tools Classification of Data Center Operations Technology (OT) Management Tools White Paper 104 Revision 0 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Cabinet V800 V800 CABINETS

Cabinet V800 V800 CABINETS V800 Cabinet Siemon s V800 cabinets provide a robust, cost-effective enclosure solution that provides valuable Zero-U space on each side of the equipment rails for cable management, PDU mounting or connectivity

More information

Convergence of Complexity

Convergence of Complexity Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December

More information

THE KEY TO DATA CENTRE INFRASTRUCTURE

THE KEY TO DATA CENTRE INFRASTRUCTURE ENCLOSURES, RACKS & CABINETS THE KEY TO DATA CENTRE INFRASTRUCTURE PAGE 52 www.insidenetworksme.com JULY 15 Jonathan Duncan, Data Centre and Integrated Solutions Director, Schneider Electric, outlines

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

Data Center Cabling Design Trends

Data Center Cabling Design Trends Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:

More information

Energy-efficient & scalable data center infrastructure design

Energy-efficient & scalable data center infrastructure design Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

Airflow Management Solutions

Airflow Management Solutions Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment

More information

// GREEN IT / DATA CENTRE BUILD GREEN

// GREEN IT / DATA CENTRE BUILD GREEN BUILD GREEN BUILDING A COMPLETELY GREEN DATA CENTRE IS A FANTASTIC WAY FOR COMPANIES TO DRAMATICALLY SHRINK THEIR ENERGY COSTS AND IMPROVE THEIR GREEN CREDENTIALS // 28 / NETWORK MIDDLE EAST / AUGUST 2013

More information

DATA CENTER SOLUTIONS GUIDE

DATA CENTER SOLUTIONS GUIDE DATA CENTER SOLUTIONS GUIDE designed to be better. Power Cabinets Racks Pathways Aisle Containment Connectivity and Cabling RACKS AND CABINETS Legrand s cabinets and racks, designed for all your network

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Server Room Thermal Assessment

Server Room Thermal Assessment PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...

More information

Customized Server Cabinets

Customized Server Cabinets GOING GREEN WITH CUSTOMIZABLE CABINETS AND RACKS Designed to provide industry leading airflow, CyrusOne s cabinets and rack solutions promote optimal cooling and contribute to reduced power consumption.

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Microsoft Technology Center: Philadelphia

Microsoft Technology Center: Philadelphia A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

Raised Floor Data Centers Prepared for the Future

Raised Floor Data Centers Prepared for the Future Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The

More information

Virtual Data Centre Design A blueprint for success

Virtual Data Centre Design A blueprint for success Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

THE GREEN DATA CENTER

THE GREEN DATA CENTER GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access

More information

abstract about the GREEn GRiD

abstract about the GREEn GRiD Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

IMPACT OF VIRTUALIZATION ON DATA CENTER PHYSICAL INFRASTRUCTURE

IMPACT OF VIRTUALIZATION ON DATA CENTER PHYSICAL INFRASTRUCTURE WHITE PAPER #27 IMPACT OF VIRTUALIZATION ON DATA CENTER PHYSICAL INFRASTRUCTURE EDITOR: DENNIS BOULEY, APC BY SCHNEIDER ELECTRIC PAGE 2 EXECUTIVE SUMMARY Data center virtualization, which includes storage,

More information

Data Centers and Mission Critical Facilities Operations Procedures

Data Centers and Mission Critical Facilities Operations Procedures Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)

More information

2014 Best Practices. The EU Code of Conduct on Data Centres

2014 Best Practices. The EU Code of Conduct on Data Centres 2014 Best Practices The EU Code of Conduct on Data Centres 1 Document Information 1.1 Version History Version 1 Description Version Updates Date 5.0.1 2014 Review draft Comments from 2013 stakeholders

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

HP Data Center Services

HP Data Center Services HP Data Center Services HP Technology Services - Per Event Services Technical data Enterprise-class data center facility infrastructures need to support both current IT objectives and new equipment and

More information

DATA CENTER SOLUTIONS

DATA CENTER SOLUTIONS DATA CENTER SOLUTIONS Nobody Makes Better Data Center Equipment Maximize availability, manageability and efficiency with cost-effective solutions from a dependable partner. Provide reliable, efficient

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Small Data / Telecommunications Room on Slab Floor

Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure

More information

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center White Paper October 2012 Optimizing the SAN Fiber Optic Physical Layer in Your Data Center Deploying a structured cabling system for the SAN provides measurable results and long term value, whether you

More information

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are

More information

Racks & Enclosures. Deliver. Design. Define. Three simple words that clearly describe how we approach a Data Center project.

Racks & Enclosures. Deliver. Design. Define. Three simple words that clearly describe how we approach a Data Center project. Three simple words that clearly describe how we approach a Data Center project. Eclipse Racks & Enclosures DELIVERING THE RIGHT INFRASTRUCTURE FOR YOUR MISSION-CRITICAL NEEDS SERVER RACKS & NETWORKING

More information

Classification of Data Center Infrastructure Management (DCIM) Tools

Classification of Data Center Infrastructure Management (DCIM) Tools Classification of Infrastructure Management (DCIM) Tools White Paper 104 Revision 3 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying infrastructure

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information