DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER
|
|
|
- Reginald Lucas
- 10 years ago
- Views:
Transcription
1 DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER
2 EXECUTIVE SUMMARY Data center racks were once viewed as simple platforms in which to neatly stack equipment. As data center densities have increased, however, data center racks have come to play a vital role in the availability, reliability and flexibility of the IT infrastructure. The right rack enclosure can also reduce data center operational costs by preserving valuable floor space, optimizing cooling and increasing the efficiency of IT staff. Four factors have altered the landscape for data center rack selection: Increasing weight loads Offsite integration processes Multivendor IT environments Increased cooling costs Organizations need data center racks that can hold heavier loads and maintain their structural integrity when shipped fully loaded with equipment. Racks should also provide the flexibility to accommodate equipment from multiple vendors with varying locations for cabling and power distribution. High-density data centers further demand racks that provide maximum usable space, minimal air mixing, adequate clearances for airflow, and easy access for troubleshooting and reconfiguration of equipment. Although data center racks come in standard sizes, not all products deliver these capabilities. This whitepaper will discuss some of the key considerations in choosing racks for today s data center environment. It will then examine some of the characteristics that make DAMAC s Fastrack a superior choice to meet those requirements now and in the future. 2
3 A DAMAC WHITEPAPER STRENGTH AND STRUCTURAL INTEGRITY Organizations are demanding that their data centers deliver 24x7 availability, top performance and ever-increasing storage capacity. As a result, the physical data center infrastructure is under mounting pressure to support growing server and storage densities. Studies indicate that the average power density per rack will reach 12kW in 2014 double the average 6kW power density per rack in Equipment is also getting heavier due to increased data storage requirements and the cooling demands of next-generation processors. Five years ago, data center racks needed to hold about 2,000 pounds. Today, weight loads of 3,000 pounds or more are not uncommon. At the same time, many organizations are turning to offsite integration processes to minimize the disruption associated with installing, configuring and integrating equipment within the data center environment. System integrators rack and stack equipment in fully configured units for delivery to the customer s site. The structural integrity of the data center rack becomes even more critical in this scenario. The rack must not only hold the weight of the equipment when stationary but withstand the stresses of shipment. The transportation stresses mimic a seismic event that exerts force on both the x and y axes of the racks structural members. The typical data center rack is made of formed or folded sheet metal, a construction that provides vertical but not horizontal strength. Furthermore, most manufacturers save time, labor and material by using stitch welding rather than a continuous seam weld. As a result, weight loads must be limited to about 2,000 pounds for the rack to arrive with its original structural integrity. Otherwise these racks tend to become deflected when shipped fully populated with equipment. Poor-quality racks may buckle, damaging valuable equipment. But even if the rack appears undamaged when it is uncrated and moved into the data center, IT personnel often find it difficult to remove equipment from the rack for servicing. The deflection of the rack alters the distance between the rails such that the mounting area no longer follows Electronic Industries Alliance (EIA) specifications. THE DAMAC DIFFERENCE DAMAC s Fastrack is constructed of tubular steel, which lends itself to horizontal as well as vertical strength. In addition, each seam and joint is fully welded, eliminating the inherent failure points associated with stitch welding. 3
4 Fastrack can hold 3,500 pounds of equipment when stationary, enabling it to facilitate growing weight loads. More importantly, it will maintain the EIA specification within the mounting area when shipped fully populated with up to 3,000 pounds of equipment. Fastrack also features larger casters than competitive products. This provides greater floor clearance, making it easier to load and unload the rack from a shipping crate and move a fully populated rack on both flat and angled surfaces. A fully welded, seismic floor mounting plate is built into the base of the rack. The floor mounting anchor points and levelers are set outside of the equipment mounting area for easy accessibility when the rack is fully populated. Grounding provisions are included in the frame to tie the rack into the facility central ground. EASE OF USE AND FLEXIBILITY Data center racks have become taller, wider and deeper to accommodate increasing equipment densities. The most popular racks are 42U, 45U or 48U high, 24 inches or 30 inches wide and 42 inches or 48 inches deep. However, these industry-standard specifications do not indicate how much usable space is available inside the rack. This is an important consideration given that IT managers are building up cabinets in order to maximize valuable data center space. Any industry-standard rack will support the mounting of 19-inch equipment, but may not provide the capacity for growing cabling and power distribution requirements. Because space is at a premium in racks constructed from sheet metal, organizations often purchase larger cabinets to ensure that cables and power distribution units (PDUs) don not block access to equipment. While the value of orderly cabling may be worth the investment in a larger rack and associated floor space, a rack that can support cable management within a smaller footprint delivers a greater ROI. The dynamic nature of today s data centers also demands slide in, slide out component mounting and streamlined cable management. IT staff efficiency is another important factor.time savings equates to reduced costs as well as a more efficient and flexible environment. Single-piece panels held on by screws make it difficult to work on equipment in traditional racks. Poor cable and PDU management limits the flexibility, accessibility and ease of use of many cabinets. 4
5 A DAMAC WHITEPAPER THE DAMAC DIFFERENCE Because tubular steel is less bulky than sheet metal, Fastrack provides 20 percent more usable space than competitive products and thus more room for cabling and power distribution equipment. The top panel, side panels and doors are easily removed, making it easy to work on a fully populated rack. Side panels are recessed into the cabinet frame with slam latches for locking. This adds no width to the overall rack footprint and allows for zero clearance coupling between cabinets. The top panel has multiple cable pass-through ports to facilitate routing cables above the cabinet. Fastrack features a rear coffin section an industry first dedicated to PDU mounting and cabling. It recesses into the tubular steel frame of the cabinet, allowing easy access to the rear of the equipment. It is not necessary to unplug power strips or disconnect cables to service equipment from the back side. The coffin section includes standard PDU mounting provisions on both sides, making Fastrack field-configurable to the specific requirements of the equipment. There are multiple provisions to accommodate all popular PDU manufacturers, including ServerTech, Geist, Raritan and APC. The rear coffin section also includes a vertical cable manager with routing fingers set at each rackmount unit location to maintain the proper bend radius of the data cables. The cable manager can also be installed on the left or right side to meet the cable dressing requirements of the equipment. A locking cover ensures that cables do not drift out of position when the cabinet is shipped. COOLING EFFICIENCY High-density data centers demand effective thermal management. Because high temperatures and humidity can lead to equipment failure, proper cooling plays a key role in maximizing system availability and longevity. Most equipment is designed to draw chilled air in through the front and exhaust hot air through the back. As a result, industry best practices call for racks to be arranged with cabinet fronts facing each other (the cold aisle) and cabinet backs facing each 5
6 other (the hot aisle). This hot-aisle/cold-aisle configuration prevents hot exhaust air expelled from the back of one rack to be drawn into equipment across the aisle. Traditional racks often require airflow management accessories to make them compatible with hot-aisle/cold-aisle arrangements. Blanking panels and vertical airflow baffles must be added to prevent short cycling and ensure that hot exhaust air is not drawn back into the cool aisle. However, add-on equipment cannot provide the optimized airflow needed to support high-performance equipment in a high-density data center environment. Due to the increased heat load of next-generation servers, equipment manufacturers increasingly call for clearances of 6 to 11 inches to ensure proper airflow. It is important to select a data center rack with sufficient capacity and cabling management for unobstructed airflow through equipment. Cooling is one of the largest expenses in any data center, making cooling efficiency one of the most important considerations when selecting a data center rack. Airflow efficiency within the rack can lower operational costs dramatically by reducing the amount of chilled air that must be circulated. A rack that is built to enhance the facilities cooling system will reduce chilled air volumes even further. As a result, an investment in cabinets with advanced cooling features can pay big dividends. THE DAMAC DIFFERENCE DAMAC s energy-efficient cabinets are hot-aisle/cold-aisle ready and exceed active equipment airflow requirements. In addition, a built-in front perimeter air dam eliminates air mixing when the mounting rails are kept in the preset factory position. Air does not leak above, below or along the sides of equipment, helping to ensure that equipment is optimally cooled. The rear coffin section of the Fastrack cabinet further increases cooling efficiency by ensuring that cabling and PDUs do not block exhaust air from exiting the rear of the cabinet. The fully perforated mesh door also provides airflow of 82 percent or more. Customers are typically able to raise the temperature in their data centers a minimum of two degrees because of the high airflow design of Fastrack. This set point can be further increased if Fastrack is installed along with the DAMAC aisle containment system, which doubles or quadruples cooling efficiency by physically separating the hot and cold aisles. 6
7 A DAMAC WHITEPAPER CONCLUSION In terms of cost, the data center rack is relatively insignificant compared to value of the equipment it houses and the cost of the labor to configure and integrate that equipment. Nevertheless, it is a strategic component that must be carefully selected with today s data center challenges in mind. The right rack will provide the structural integrity, flexibility and cooling support needed in a high-performance, high-density data center environment. It will also enable offsite integration processes, arriving in perfect condition when shipped fully loaded with preconfigured, pre-integrated equipment. DAMAC s Fastrack has the strength to support growing equipment weight loads within the data center and in transit, along with superior ease of use and airflow optimization. It provides the features needed in today s dynamic multivendor data center environments, delivering reduced operational costs, increased efficiency and investment protection. 7
8 Industry Circle La Mirada, CA (877)
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
Secure your IT equipment with confidence... secure with NetClosure
Secure your IT equipment with confidence... secure with NetClosure SERVER CABINETS NetClosure s REM Series Server Cabinet is the ultimate solution designed and engineered for demanding data center environments.
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812.
1 Compaq 10000 Series Racks The 10000 series racks are a family of 1000mm deep racks which are available in 22U, 36U, 42U and 47U 600mm widths. Compaq 10000 Series Racks provides a common, integrated platform
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
Rack Installation Instructions
Rack Installation Instructions Guidelines This publication provides information about how to install your server into a standard rack cabinet using the rail kit shipped with your server. If you no longer
Customized Server Cabinets
GOING GREEN WITH CUSTOMIZABLE CABINETS AND RACKS Designed to provide industry leading airflow, CyrusOne s cabinets and rack solutions promote optimal cooling and contribute to reduced power consumption.
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
ADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
Racks & Enclosures. Deliver. Design. Define. Three simple words that clearly describe how we approach a Data Center project.
Three simple words that clearly describe how we approach a Data Center project. Eclipse Racks & Enclosures DELIVERING THE RIGHT INFRASTRUCTURE FOR YOUR MISSION-CRITICAL NEEDS SERVER RACKS & NETWORKING
Introducing an innovative team devoted to providing unparalleled customer service and support for ISPs, ASPs and Hosting applications.
Introducing an innovative team devoted to providing unparalleled customer service and support for ISPs, ASPs and Hosting applications. The partner you can rely on - APW's Internet Business Solutions Team
Layer Zero. for the data center
Layer Zero for the data center Preparefor the Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,
Access Server Rack Cabinet Compatibility Guide
Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800
SERVER ROOM CABINET INSTALLATION CONCEPTS
SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the
Rack Systems Solutions
Rack Systems Solutions Designed to simplify cable management and improve power distribution Engineered by APC by Schneider Electric for Dell, NetShelter S is the next-generation rack enclosure solution
Key Considerations for Selecting Server Cabinets for Seismic Areas
Key Considerations for Selecting Server Cabinets for Seismic Areas Protect Up to 1500 of Critical Network Equipment without Sacrificing Flexibility Planning a data center in a seismically active area requires
How To Build A T7 Rack For Information Technology
THE NEXT GENERATION RACK FOR INFORMATION TECHNOLOGY THE RACK CABINET FOR INFORMATION TECHNOLOGY T7, THE HI-TECH HEART OF THE BLADESHELTER SYSTEM The real answer to the requirements of: Safety Versatility
Compaq Rack Options and Accessories. Monitors and Keyboards
1 Compaq Rack Options and Accessories Compaq offers a wide variety of rack options and accessories that help you to complete your 9000 and 10000 series racks. Monitors and Keyboards TFT5600RKM United States
Vantage Enclosure Systems
Vantage Enclosure Systems Custom-configured solutions to store your mission-critical hardware IT Co-location Managed Server Facility WEB HOSTING communications ISP E-business Vantage Enclosures Vantage
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Rack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre
IT infrastructure Efficiency-boosting solutions nextlevel for data centre 2 Rittal IT infrastructure The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind,
Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
NAISSUS THERMAL MANAGEMENT SOLUTIONS
NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP WATER COOLING SYSTEM NTMS30 30kW SYSTEM Cool the servers, not the room! NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
How To Fit A Dll 2420 And 4220 Rack Enclosure
DELL BEST PRACTICES GUIDE FOR RACK ENCLOSURES A Dell Technical White Paper PE2420 & PE4220 By Danny Alvarado Dell Data Center Infrastructure THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
Cabinet & Enclosure Systems
Cabinet & Enclosure Systems Optimize. Store. Secure. CPI Cabinets Optimize. Store. Secure. The cabinet platform on which your enterprise is built is just as critical as the equipment it stores. Utilizing
DELTA3-1. Delta 3 Data Centre Rack Solution
DELTA3-1 Delta 3 Data Centre Rack Solution Contents Building on more than 50 years of British design and innovation, Cooper B-Line introduces Delta 3 ( Delta cubed ). Designed to offer M.O.R.E. to customers
Installation. Basic Rack Power Distribution Unit for Blade Servers
Installation Basic Rack Power Distribution Unit for Blade Servers Contents Preliminary Information...................1 Features............................. 1 Receiving inspection................... 1
DATA CENTER SOLUTIONS GUIDE
DATA CENTER SOLUTIONS GUIDE designed to be better. Power Cabinets Racks Pathways Aisle Containment Connectivity and Cabling RACKS AND CABINETS Legrand s cabinets and racks, designed for all your network
AU-110 racking guide NBXPN: 023
AU-110 racking guide NBXPN: 023 1. Overview NIMBOXX AU-110 Rack Installation This guide provides setup instructions for installing your NIMBOXX AU-110 in a rack. Following these steps in the order given
F-SERIES TERAFRAME HD CABINET SYSTEM
P R O D U C T D ATA S H E E T F-SERIES TERAFRAME HD CABINET SYSTEM K E Y F E AT U R E S Safely transports up to 3,000 lb (1360 kg) of electronic equipment from a factory integration site direct to a customer
DCF Optimized Rack System Selection Guide
DCF Optimized Rack System Selection Guide DCF Optimized Rack System: Optimized Design, Optimized Delivery, Optimized Value A Rack System Designed to Meet The Challenges Your Data Center Faces Today Your
Cabinet Overview Frame Material & Construction. Shelves Fan Options Cable Trays Blank Panels Brush Cable Entry
i Q S E R I E S S P E C I F I C A T I O N S P a g e s 2-5 Cabinet Overview Frame Material & Construction Quality Assurance Freestanding Specifications i Q S E R I E S B A S I C C A B I N E T F R A M E
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Knürr DCM. Knürr DCM. 19 Server Rack System 19 Heavy Duty Rack 1.2 to 1.9 1.1
Knürr DCM 19 Server Rack System 19 Heavy Duty Rack 1.2 to 1.9 1.1 Knürr DCM conquers the world Standardization in the data center begins with the Knürr DCM! The Knürr DCM is the modular building block
Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks
Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks 19-inch Industry Standard Rack Systems The trend to consolidation as a result of virtualization and optimization
Storage Solutions. Maximize Storage & Optimize Space
Storage Solutions Maximize Storage & Optimize Space Your Files Are Important With the cost and availability of office space at a premium, space utilization is key. An end-tab color-coded filing system
Powerware Enclosure Solutions Product Focus
Powerware Enclosure Solutions Product Focus Powerware Enclosures IT availability and reliability are critical corporate issues in today s demanding, mission-critical environments. For this reason, it is
Rack Basics: Everything You Need to Know Before You Equip Your Data Center
W H I T E P A P E R Rack Basics: Everything You Need to Know Before You Equip Your Data Center Executive Summary When you re designing a data center, server room or network closet, deciding which racks
Cabinet V800 V800 CABINETS
V800 Cabinet Siemon s V800 cabinets provide a robust, cost-effective enclosure solution that provides valuable Zero-U space on each side of the equipment rails for cable management, PDU mounting or connectivity
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Integrated Cabinet Solutions For Business-Critical Continuity Why Proper Cable Management Is So Important Your rack
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
DCF Optimized Rack System
Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that
Layer Zero. for the data center
Layer Zero for the data center PREPAREFOR THE Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Thermal Optimisation in the Data Centre
Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal
Organizing and Managing Equipment Rooms
Organizing and Managing Equipment Rooms How you organize and maintain your equipment room can be just as important as maintaining the operating systems on the boxes themselves. Although many companies
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
DATA CENTER SOLUTIONS
DATA CENTER SOLUTIONS Nobody Makes Better Data Center Equipment Maximize availability, manageability and efficiency with cost-effective solutions from a dependable partner. Provide reliable, efficient
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
Spec Sheet. Cisco R42610 Rack CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, 95134 REV A.6 DECEMBER 9, 2014 WWW.CISCO.
Spec Sheet CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, 95134 REV A.6 DECEMBER 9, 2014 WWW.CISCO.COM Overview................................................ 3 Rack Certifications
Energy-efficient & scalable data center infrastructure design
Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Rack installation instructions
Rack installation instructions Review the documentation that comes with the rack cabinet for safety and cabling information. Before you install the server in a rack cabinet, review the following guidelines:
Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n
Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction How To Preserve Your Servers And Prevent Overheating Your high-performance, multiprocessor servers are working hard, computing tons
Knürr Miracel. Knürr Miracel. 19 Network and Server Rack Platform 1.12 to 1.22 1.11
Knürr Miracel 19 Network and Server Rack Platform 1.12 to 1.22 1.11 19" Server Rack: Knürr Miracel Strong points 1.13 Knürr Miracel ASP ASP/Server Rack 1.16 Knürr Miracel Server Rack 1.18 Knürr Miracel
Free-Stand Cabinets PROLINE Network Switch Cabinets
763.422.2588 Spec-00525 M763.422.2661 Free-Stand Cabinets PROLINE Network s Free-Stand Cabinets PROLINE Network s PROLINE Network INDUSTRY STANDARDS EIA 310-D APPLICATION PROLINE Network Switch cabinet
How To Buy Anixter Data Center
Products. Technology. Services. Delivered Globally. DATA CENTER SOLUTIONS: MULTI-TENANT, SERVICE PROVIDER, CLOUD THE ANIXTER DIFFERENCE Anixter has the knowledge and products to make your multi-tenant
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
Rack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances
This set of instructions applies to racking and rail kit installation for 6XX and above. The Rack Mounting Instructions section below provides information on installing the SC825 chassis into a rack unit
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
Rack Blanking Panels To Fill or Not to Fill
Rack Blanking Panels To Fill or Not to Fill A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss Joyce F. Ruff Learn more at Dell.com/PowerEdge/Rack THIS WHITE PAPER IS FOR INFORMATIONAL
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Airflow Management Solutions
Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment
Data Center Racks. Vantage S2. Enclosure System. Switch N to Eaton.
Data Center Racks Vantage S2 Enclosure System Switch N to Eaton. The Lean Data Center Data center managers are constantly moving, adding and changing IT equipment and electrical circuits all while trying
ADC Structured Cabling Solutions
ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution
DIGITUS Network & Server Cabinets. UNIQUE Series
DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door
(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Driving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
vantage S2 enclosure system
vantage S2 enclosure system The Lean Data Center The days when the data center was a static environment performing batch processing have turned into a 24/7 virtual operation focused on real time processing
19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.
19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Rack Cabinets. Rack Configuration. 19 inch
Rack Cabinets Rack Configuration 19 inch 19 RACK COMPONENTS FEATURES Hallam Manufacturing s range of 19 inch racks and cabinets for today s data/communications installations are designed and manufactured
A QUICK AND EASY GUIDE TO SETTING UP THE DELL POWEREDGE C8000
A QUICK AND EASY GUIDE TO SETTING UP THE DELL POWEREDGE C8000 A Principled Technologies setup guide commissioned by Dell Inc. TABLE OF CONTENTS Table of contents... 2 Introduction... 3 Dell 42U rack...3
Server Chassis and Triplet Hardware v1.0
Server Chassis and Triplet Hardware v1.0 Author: Steve Furuta, Mechanical Designer 1 Scope This document describes the technical specifications for the custom chassis used in Open Compute Project servers
42U/45U 28" Wide Rack Installation & Service Guide
42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part
UPDATEUPDATEUPDATE. Converting the tower chassis to a rack-mount chassis. A - M5 13 8 To mount outer member to rack
UPDATEUPDATEUPDATE Converting the tower chassis to a rack-mount chassis Rail overview Converting your Server to Rack-Mount The rail kit includes the following: Two rail units Five packages of screws (labeled
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels