DC INVERTER MULTI-SYSTEM AIR CONDITIONER

Size: px
Start display at page:

Download "DC INVERTER MULTI-SYSTEM AIR CONDITIONER"

Transcription

1 TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH AEMI0AH Product Code No ( 9 ) 70 0 ( 9 ) ( 9 7) 70 0 ( 9 ) AEMI0AH AEMIAHB AEMIAH < Applicable Indoor Units > AEMI0AH all mounted type AMIAHL AMI7AHL AMIAHL AIAHL AIAHL NOTE For details about the combination, refer to "Unit Combination Table" in the Appendix of this manual. RoHS This product does not contain any hazardous substances prohibited by the RoHS Directive. ARNING You are requested to use RoHS compliant parts for maintenance or repair. You are requested to use lead-free solder. F-GAS REGULATION (EC) No / 00 Do not vent R0A into atmosphere : R0A is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global arming Potential (GP) = 97. REFERENCE NO. SM7007

2 Important! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which can ARNING result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can CAUTION result in personal injury or product or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS ARNING hen iring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO IRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur. hen Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. hen Installing In a Ceiling or all Make sure the ceiling/wall is strong enough to hold the unit s weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High inds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. hen Connecting Refrigerant Tubing Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run. hen Servicing Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Others CAUTION Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.

3 Table of Contents APPLICABLE INDOOR UNITS... Page. OPERATING RANGE.... SPECIFICATIONS -. Unit Specifications Major Component Specifications Other Component Specifications DIMENSIONAL DATA.... REFRIGERANT FLO DIAGRAM -. Refrigerant Flow Diagram PERFORMANCE DATA -. Temperature Charts.... ELECTRICAL DATA -. Electric iring Diagrams FUNCTIONS 7-. Explanation of Functions Protective Functions.... TROUBLESHOOTING -. Precautions before Performing Inspection or Repair Trouble Diagnosis by Error Monitor Lamps Checking the Outdoor System Trouble Diagnosis of Each Part Trouble Diagnosis of Fan Motor REFRIGERANT R0A: SPECIAL PRECAUTIONS HEN SERVICING UNIT 9-. Characteristics of New Refrigerant R0A Checklist before Servicing Tools Specifically for R0A Tubing Installation Procedures In Case of Compressor Malfunction In Case Refrigerant is Leaking Charging Additional Refrigerant Retro-Fitting Existing Systems

4 Page APPENDIX A INSTALLATION INSTRUCTIONS... A- APPENDIX B UNIT COMBINATION TABLES... A-

5 APPLICABLE INDOOR UNITS Multi-Outdoor Unit Indoor Unit AMIAHL AMI7AHL AMIAHL AIAHL AIAHL -Room AEMI0AH YES YES YES NO NO -Room -Room AEMIAHB YES YES YES YES NO AEMIAH YES YES YES YES YES -Room AEMI0AH YES YES YES YES YES NOTE. The table lists the wall-mounted type of indoor units as representative models.. For details on the applicable indoor units other than the wall-mounted type, refer to the catalog.

6 . OPERATING RANGE Cooling Heating Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum Minimum Maximum Minimum C D.B. / C.B. 9 C D.B. / C.B. 7 C D.B. C D.B. C D.B. 9 C D.B. C D.B. / C.B. _ D.B. / - C.B.

7 . SPECIFICATIONS -. Unit Specifications Outdoor Unit AEMI0AH Indoor Unit AMI7AHL Type Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units Power Source Voltage Rating k -Room Multi Outdoor Unit. 0 to 0V Single-Phase 0Hz 0V Performance Capacity Air Circulation (High) k BTU/h m /h.0,00 Cooling (.0 to.0 ) (,00 to 7,00 ),900.,00 Heating (. to. ) ( 7,00 to,00 ),900 Electrical Rating Cooling Available Voltage Range V 9 to Running Amperes Power Input A. 9 Power Factor % 9 E.E.R. /. C.O.P. / - Compressor Locked Rotor Amperes A. Heating Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment kg DC Twin Rotary (Inverter) R0A /.7 Refrigerant Control Electric Expansion Valve Operation Sound Hi db-a 7 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit m 0 Refrigerant Narrow tube mm (in.). (/") Tube Diameter ide tube mm (in.) 9. (/") Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping mm mm kg kg m DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AMI7AHL units Outdoor Unit : AEMI0AH unit. Rating conditions are: Cooling : Indoor air temp. 7 C D.B. / 9 C.B. Heating : Indoor air temp. 0 C D.B. Outdoor air temp. C D.B. / C.B. Outdoor air temp. 7 C D.B. / C.B. 7

8 Outdoor Unit AEMIAHB Indoor Unit AMI7AHL + AIAHL Type Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units Power Source Voltage Rating k -Room Multi Outdoor Unit. 0 to 0V Single-Phase 0Hz 0V Performance Capacity Air Circulation (High) k BTU/h m /h. 9,00 Cooling (. to. ) ( 7,00 to,00 ),900 7.,900 Heating (. to. ) (,00 to,700 ),900 Electrical Rating Cooling Available Voltage Range V 9 to Running Amperes Power Input A 7.,9 Power Factor % 9 E.E.R. /.0 C.O.P. / - Compressor Locked Rotor Amperes A. Heating 7.70, Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment kg DC Twin Rotary (Inverter) R0A /. Refrigerant Control Electric Expansion Valve Operation Sound Hi db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit m Refrigerant Narrow tube mm (in.). (/") Tube Diameter ide tube mm (in.) 9. (/") Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping mm mm kg kg m , DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AMI7AHL unit + AIAHL unit Outdoor Unit : AEMIAHB unit. Rating conditions are: Cooling : Indoor air temp. 7 C D.B. / 9 C.B. Heating : Indoor air temp. 0 C D.B. Outdoor air temp. C D.B. / C.B. Outdoor air temp. 7 C D.B. / C.B.

9 Outdoor Unit AEMIAH Indoor Unit AMI7AHL Type Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units Power Source Voltage Rating k -Room Multi Outdoor Unit. 0 to 0V Single-Phase 0Hz 0V Performance Capacity Air Circulation (High) k BTU/h m /h.,00 Cooling (.9 to. ) ( 9,900 to 7,00 ),900. 9,00 Heating (. to 9.0 ) (,00 to 0,700 ),900 Electrical Rating Cooling Available Voltage Range V 9 to Running Amperes Power Input A.7,000 Power Factor % 9 E.E.R. /.0 C.O.P. / - Compressor Locked Rotor Amperes A. Heating.7, Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment kg DC Twin Rotary (Inverter) R0A /. Refrigerant Control Electric Expansion Valve Operation Sound Hi db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit m Refrigerant Narrow tube mm (in.). (/") Tube Diameter ide tube mm (in.) 9. (/") +.7 (/") Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping mm mm kg kg m , DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AMI7AHL units Outdoor Unit : AEMIAH unit. Rating conditions are: Cooling : Indoor air temp. 7 C D.B. / 9 C.B. Heating : Indoor air temp. 0 C D.B. Outdoor air temp. C D.B. / C.B. Outdoor air temp. 7 C D.B. / C.B. 9

10 Outdoor Unit AEMI0AH Indoor Unit AMI7AHL Type Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units Power Source Voltage Rating k -Room Multi Outdoor Unit.7 0 to 0V Single-Phase 0Hz 0V Performance Capacity Air Circulation (High) k BTU/h m /h.0 7,00 Cooling (.9 to 9. ) ( 9,900 to,00 ),070 9.,00 Heating (. to 9. ) (,00 to,00 ),070 Electrical Rating Cooling Available Voltage Range V 9 to Running Amperes Power Input A 7.,7 Power Factor % 99 E.E.R. /. C.O.P. / - Compressor Locked Rotor Amperes A 7.0 Heating.9, Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi, Me, Lo) Compressor Refrigerant / Amount charged at shipment kg DC Twin Rotary (Inverter) R0A /. Refrigerant Control Electric Expansion Valve Operation Sound Hi db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit m 0 Refrigerant Narrow tube mm (in.). (/") Tube Diameter ide tube mm (in.) 9. (/") +.7 (/") Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping mm mm kg kg m ,09, DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AMI7AHL units Outdoor Unit : AEMI0AH unit. Rating conditions are: Cooling : Indoor air temp. 7 C D.B. / 9 C.B. Heating : Indoor air temp. 0 C D.B. Outdoor air temp. C D.B. / C.B. Outdoor air temp. 7 C D.B. / C.B. 0

11 -. Major Component Specifications --. Outdoor Unit Outdoor Unit AEMI0AH Control PCB Part No. Controls Control Circuit Fuse CB-CMRVEH Microprocessor 0V A Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Coil Resistance (Ambient Temp. 0 C) cc Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Run Capacitor Crankcase Heater DC Twin Rotary (Hermetic) C-RVN9H0M /,000 FV0S... 0 R - S : 0. S - T : 0. T - R : 0. Yes Yes Yes CS-7L Operation Temp. Open : C, Close : 9 C Micro F - VAC - - Fan Type Q'ty... Dia. mm Propeller... D0 Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 0 C) Safety Device Type Over-Current Protection Run Capacitor Ohm Micro F VAC DC Motor DAJ-J7-CR / : : : 77. Internal Controller Yes - - Heat Exchanger Coil Coil Rows Fin Pitch mm Face Area m External Finish Aluminum Plate Fin / Copper Tube 0. Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

12 Outdoor Unit AEMIAHB Control PCB Part No. Controls Control Circuit Fuse CB-CMRV9EH Microprocessor 0V A Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Coil Resistance (Ambient Temp. 0 C) Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Run Capacitor Crankcase Heater DC Twin Rotary (Hermetic) KD0XAB /,700 cc FV0S Ohm U - V : 0.70 V - : U : 0.7 Yes Yes Yes CS-7LN Operation Temp. Open : C, Close : 00 C Micro F - VAC - 0V Fan Type Q'ty... Dia. mm Propeller... D0 Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 0 C) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Ohm Micro F VAC DC Motor SIC-7F-D / Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fin Pitch mm Aluminum Plate Fin / Copper Tube. Face Area 0.9 m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

13 Outdoor Unit AEMIAH Control PCB Part No. Controls Control Circuit Fuse CB-CMRVEH Microprocessor 0V A Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Coil Resistance (Ambient Temp. 0 C) Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Run Capacitor Crankcase Heater DC Twin Rotary (Hermetic) KD0XAB /,700 cc FV0S Ohm U - V : 0.70 V - : U : 0.7 Yes Yes Yes CS-7LN Operation Temp. Open : C, Close : 00 C Micro F - VAC - 0V Fan Type Q'ty... Dia. mm Propeller... D0 Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 0 C) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Ohm Micro F VAC DC Motor SIC-7F-D / Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fin Pitch mm Aluminum Plate Fin / Copper Tube. Face Area 0.9 m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

14 Outdoor Unit AEMI0AH Control PCB Part No. Controls Control Circuit Fuse CB-CMRVEH Microprocessor 0V A Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Coil Resistance (Ambient Temp. 0 C) Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Run Capacitor Crankcase Heater DC Twin Rotary (Hermetic) JD0XAB /,000 cc FV0S...,00 Ohm U - V : 0. V - : 0. - U : 0. Yes Yes Yes CS-7LN Operation Temp. Open : C, Close : 00 C Micro F - VAC - 0V Fan Type Q'ty... Dia. mm Propeller... D0 Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 0 C) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Ohm Micro F VAC DC Motor SIC-7F-D / Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fin Pitch mm Aluminum Plate Fin / Copper Tube. Face Area 0.7 m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

15 -. Other Component Specifications Sensor Name Model No. of sensor Quantity of Sensor AEMI0AH AEMIAHB AEMIAH AEMI0AH Outdoor air temp sensor TKS9B Outdoor heat exchanger sensor TKS9B A / AN sensor TKS9B / / / / B / BN sensor TKS9B / / / / C / CN sensor TKS9B 0 0 / / D / DN sensor TKS9B 0 0 / / 0 Resistance (k ohm) Temperature ( C) Sensor Name Model No. of sensor Quantity of Sensor AEMI0AH AEMIAHB AEMIAH AEMI0AH Compressor temp sensor TKS9B Resistance (k ohm) Temperature ( C)

16 . DIMENSIONAL DATA Outdoor Unit AEMI0AH 0 -ID: -ID:. 9 0 ID: Narrow tube service valve dia.. (/") ide tube service valve dia.9. (/") Unit: mm

17 Outdoor Unit AEMIAHB 0 9 ID: -ID:. 0 9 Narrow tube service valve dia.. (/") 900 ide tube service valve dia.9. (/") Unit: mm 7

18 Outdoor Unit AEMIAH 0 9 ID: -ID:. 0 9 ide tube service valve dia..70 (/") Narrow tube service valve dia.. (/") 900 ide tube service valve dia.9. (/") Unit: mm

19 Outdoor Unit AEMI0AH 0 9 ID: -ID:. 0 9 ide tube service valve dia..70 (/") Narrow tube service valve dia.. (/") 900 ide tube service valve dia.9. (/") Unit: mm 9

20 . REFRIGERANT FLO DIAGRAM -. Refrigerant Flow Diagram Outdoor Unit AEMI0AH Indoor unit Outdoor unit ide tube O.D.9.mm O.D.9.mm Service valve on wide tube B A Muffler Sub accumulator Main accumulator Compressor -way valve Defrost valve for hot gas bypass S Heat exchanger Narrow tube O.D..mm O.D..mm Service valve on narrow tube BN AN Strainer Electric expansion valve M M Capillary tube for split flow Cooling cycle Heating cycle Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. mm. Thickness: Min. mm Insulation Thickness: Min. mm CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube 0

21 Outdoor Unit AEMIAHB Indoor unit Outdoor unit ide tube O.D.9.mm O.D.9.mm Service valve on wide tube B A Header Sub accumulator Main accumulator Compressor -way valve Defrost valve for hot gas bypass S Heat exchanger Narrow tube O.D..mm O.D..mm Service valve on narrow tube BN AN Strainer Electric expansion valve M M Header Cooling cycle Heating cycle Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. mm. Thickness: Min. mm Insulation Thickness: Min. mm CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube

22 Outdoor Unit AEMIAH Indoor unit Outdoor unit ide tube O.D.9.mm O.D.9.mm O.D.9.mm O.D..7mm Service valve on wide tube D C B A Header -way valve Sub accumulator Main accumulator Compressor Narrow tube O.D..mm O.D..mm O.D..mm O.D..mm Service valve on narrow tube DN CN BN AN Strainer Electric expansion valve M M M M Header Defrost valve for hot gas bypass S Heat exchanger Cooling cycle Heating cycle Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. mm. Thickness: Min. mm Insulation Thickness: Min. mm CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube

23 Outdoor Unit AEMI0AH Indoor unit Outdoor unit ide tube O.D.9.mm O.D.9.mm O.D..7mm O.D..7mm Service valve on wide tube D C B A Header -way valve Sub accumulator Main accumulator Compressor Narrow tube O.D..mm O.D..mm O.D..mm O.D..mm Service valve on narrow tube DN CN BN AN Strainer Electric expansion valve M M M M Header Defrost valve for hot gas bypass S Heat exchanger Cooling cycle Heating cycle Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. mm. Thickness: Min. mm Insulation Thickness: Min. mm CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube

24 . PERFORMANCE DATA -. Temperature Charts --. Temperature Charts (AEMI0AH) Outdoor Unit AEMI0AH Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.). (.) Lo fan Hi fan Indoor air temp.0 C 7 C C.0 (0.). 0 0 (.) () Operating current performance chart () Operating current performance chart High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.).0 (0.) Indoor air temp. C 0 C 7 C Lo fan Hi fan Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

25 Outdoor Unit AEMI0AH Indoor Unit AMI7AHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.). (.).0 (0.) Lo fan Hi fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C.0 (0.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan 7 Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

26 Outdoor Unit AEMI0AH Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.).0 (0.) 0. (.) Lo fan Hi fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G).0 (0.). (.7).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Operating current (A) Lo fan Hi fan Indoor air temp.0 C 7 C C Operating current (A) 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

27 --. Temperature Charts (AEMIAHB) Outdoor Unit AEMIAHB Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.). (.).0 (0.) Lo fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C.0 (0.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan HH fan Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan HH fan Indoor air temp.0 C 7 C C Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary. 7

28 Outdoor Unit AEMIAHB Indoor Unit AMI7AHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.). (.).0 (0.) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C.0 (0.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan HH fan Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

29 Outdoor Unit AEMIAHB Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.).0 (0.) 0.9 (9.) Lo fan Hi fan Indoor air temp.0 C 7 C C 0 0 HH fan () Operating current performance chart () Operating current performance chart High pressure at wide tube service valve MPaG (kgf/cm G).0 (0.). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C 0 Operating current (A) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Operating current (A) 9 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) C Indoor air temp. C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary. 9

30 Outdoor Unit AEMIAHB Indoor Unit AIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.).0 (0.) 0.9 (9.) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G).0 (0.). (.7).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan HH fan Operating current (A) 7 Indoor air temp.0 C 7 C C Operating current (A) 0 9 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary. 0

31 --. Temperature Charts (AEMIAH) Outdoor Unit AEMIAH Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.). (.).0 (0.) Lo fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C.0 (0.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan HH fan Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan HH fan Indoor air temp.0 C 7 C C Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

32 Outdoor Unit AEMIAH Indoor Unit AMI7AHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.). (.).0 (0.) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C.0 (0.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan HH fan Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

33 Outdoor Unit AEMIAH Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.).0 (0.) 0.9 (9.) Lo fan Hi fan Indoor air temp.0 C 7 C C 0 0 HH fan () Operating current performance chart () Operating current performance chart High pressure at wide tube service valve MPaG (kgf/cm G).0 (0.). (.7).0 (0.). (.) Indoor air temp. C 0 C 7 C 0 Operating current (A) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Operating current (A) 9 7 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart 0 Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) C Indoor air temp. C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

34 Outdoor Unit AEMIAH Indoor Unit AIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.).0 (0.) 0.9 (9.) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G).0 (0.). (.7).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan HH fan Operating current (A) 7 Indoor air temp.0 C 7 C C Operating current (A) 0 9 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

35 Outdoor Unit AEMIAH Indoor Unit AIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.). (.).0 (0.) 0.9 (9.) Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G).0 (0.). (.7).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Operating current (A) 9 7 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Operating current (A) 0 Indoor air temp. C 0 C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Indoor air temp.0 C 7 C C HH fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

36 --. Temperature Charts (AEMI0AH) Outdoor Unit AEMI0AH Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.).0 (0.) 0. (.) 0. (.) Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.).0 (0.) 0 C Indoor air temp. C 7 C. (.) () Operating current performance chart () Operating current performance chart Lo fan Hi fan Hi fan HH fan 9 Operating current (A) Indoor air temp.0 C 7 C C Operating current (A) 7 0 C Indoor air temp. C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

37 Outdoor Unit AEMI0AH Indoor Unit AMI7AHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.).0 (0.) 0. (.) 0. (.) Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.).0 (0.) 0 C Indoor air temp. C 7 C. (.) () Operating current performance chart () Operating current performance chart Operating current (A) Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C Operating current (A) 7 0 C Indoor air temp. C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 Indoor discharge air temperature ( C) 0 0 C Indoor air temp. C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary. 7

38 Outdoor Unit AEMI0AH Indoor Unit AMIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.).0 (0.) 0. (.) 0. (.) Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Operating current (A) Lo fan Hi fan Hi fan HH fan 7 C Indoor air temp.0 C C Operating current (A) C 0 C Indoor air air temp. C temp. C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Hi fan Hi fan HH fan Indoor air temp.0 C 7 C C 0 0 Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary.

39 Outdoor Unit AEMI0AH Indoor Unit AIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.).0 (0.) 0. (.) 0. (.) Lo fan Indoor air temp.0 C 7 C C Hi fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Operating current (A) 9 7 Lo fan 7 C Indoor air temp.0 C C Hi fan Operating current (A) 0 C 0 C Indoor Indoor air temp. C temp. C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Indoor air temp.0 C 7 C C 0 0 Hi fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary. 9

40 Outdoor Unit AEMI0AH Indoor Unit AIAHL Cooling Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) Heating Characteristics (RH : %, Indoor fan speed : High fan) (0V, 0Hz) () Low pressure performance chart () High pressure performance chart Low pressure at wide tube service valve MPaG (kgf/cm G). (.).0 (0.) 0. (.) 0. (.) Lo fan Indoor air temp.0 C 7 C C Hi fan 0 0 High pressure at wide tube service valve MPaG (kgf/cm G). (.7).0 (0.). (.).0 (0.) Indoor air temp. C 0 C 7 C. (.) () Operating current performance chart () Operating current performance chart Operating current (A) 0 9 Lo fan 7 C Indoor air temp.0 C C Hi fan Operating current (A) 0 C 0 C Indoor Indoor air temp. C temp. C 7 C () Indoor discharge air performance chart () Indoor discharge air performance chart Indoor discharge air temperature ( C) 0 0 Lo fan Indoor air temp.0 C 7 C C 0 0 Hi fan Indoor discharge air temperature ( C) Indoor air temp. C 0 C 7 C NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of 7. m. If the tubing length is different, the performance chart will vary. 0

41 . ELECTRICAL DATA -. Electric iring Diagrams Outdoor Unit AEMI0AH ARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. CONTROLLER REACTANCE COMPRESSOR THERMISTOR (P) CONNECTOR COIL THERMISTOR OUTDOOR THERMISTOR (7P) CONNECTOR (P) CONNECTOR ORG ORG GRY GRY N L POER SUPPLY B INDDOR UNIT A INDDOR UNIT TO INDDOR UNIT (P) CONNECTOR (P) CONNECTOR COIL/OUTDOOR COMP MV0 MAGNETIC COIL TERMINAL PLATE 7 GND A-TH (P) CONNECTOR A THERMISTOR AN THERMISTOR (P) CONNECTOR B THERMISTOR BN THERMISTOR COIL DEFROST VALVE DEF B-TH DEF DEF0 MV0 (P) CONNECTOR (P) CONNECTOR COIL AY VALVE RV RV RV0 MAGNETIC COIL L L E- E- (P) CONNECTOR ORG ORG GRY GRY CN0 DCFM 7 7 FAN MOTOR MV MV (P) CONNECTOR GRN/ GRN/ GRN/ (OLR) OVERLOAD RELAY OLR0 OLR U V COMPRESSOR MOTOR CM C S R GRN/ (PNK) FERRITE CORE (P)CONNECTOR (PNK) 7 FM E ACIN A ACIN SI-A SI-B REACTANCE FA

42 Outdoor Unit AEMIAHB ARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. ORG GRY N L POER SUPPLY B INDDOR UNIT A INDDOR UNIT TO INDDOR UNIT REACTANCE CONTROLLER HEATER CRANKCASE (P) CONNECTOR MV0 MAGNETIC COIL REACTANCE TERMINAL PLATE 7 GND ORG BRN ORG BRN 7 7 (P) CONNECTOR FERRITE CORE S/U C/ FM R/V CM FAN MOTOR COMPRESSOR MOTOR FERRITE CORE COMPRESSOR THERMISTOR (PNK) (PNK) COIL/OUTDOOR COMP COIL THERMISTOR OUTDOOR THERMISTOR A THERMISTOR AN THERMISTOR B THERMISTOR BN THERMISTOR (P) CONNECTOR (P) CONNECTOR COIL DEFROST VALVE COIL AY VALVE DEF RV (P) CONNECTOR A-TH B-TH DEF DEF0 RV RV0 L L E- E- CN0 DCFM MV 7 MV0 ORG GRY (P) CONNECTOR GRN/ GRN/ GRN/ (OLR) OVERLOAD RELAY OLR0 OLR U V HEATER HEATER0 GRN/ MV MAGNETIC COIL ACIN E A ACIN SI-A SI-B FA

43 Outdoor Unit AEMIAH ARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. (P) CONNECTOR OVERLOAD RELAY (OLR) CONTROLLER REACTANCE COMPRESSOR THERMISTOR COIL THERMISTOR OUTDOOR THERMISTOR COIL/OUTDOOR COMP A-TH COIL DEFROST VALVE DEF A THERMISTOR AN THERMISTOR B THERMISTOR BN THERMISTOR (P) CONNECTOR (P) CONNECTOR B-TH DEF DEF0 COIL AY VALVE RV (P) CONNECTOR GRN/ GRN/ GRN/ OLR0 OLR U V E A GND A INDDOR UNIT B INDDOR UNIT C INDDOR UNIT 7 9 D INDDOR UNIT N L POER SUPPLY TO INDDOR UNIT BRN GRY ACIN ACIN SI-A SI-B REACTANCE FERRITE CORE 0 GND R/V (PNK) (P) CONNECTOR FERRITE CORE (PNK) S/U CM C/ GRN/ COMPRESSOR MOTOR (P) CONNECTOR CRANKCASE HEATER RV RV0 HEATER HEATER0 L L E- E- SICOM MV MV0 ORG GRY ORG GRY ORG GRY C-TH MV MV MAGNETIC COIL MV SI-D SI-C MAGNETIC COIL MAGNETIC COIL MV MAGNETIC COIL ORG GRY ORG BRN ORG BRN CN0 DCFM FM FAN MOTOR 7 KS 7 KS 7 CN0 CN0 D-TH KS0 CN0 SICOM MV MV0 D THERMISTOR DN THERMISTOR C THERMISTOR CN THERMISTOR TERMINAL PLATE FA

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH SAP-CMRV9EH SAP-CMRV9EH SAP-CMRVEH SAP-CMRVEH FILE NO. Destination: Europe Northern Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.6k.6k

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO. TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402 TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EHDS + SAP-CRV96EHDS SAP-KRV126EHDS + SAP-CRV126EHDS FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EHDS

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV9AEH + SAP-CRV9AEH SAP-KRV12AEH + SAP-CRV12AEH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV9AEH SAP-KRV12AEH Product

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS1NB41 & CZ18BT1U + CUKS1NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EH + SAP-CRV96EH SAP-KRV126EH + SAP-CRV126EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EH SAP-KRV126EH

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV93EH + SAP-CRV93EH SAP-KRV123EH + SAP-CRV123EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No.

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE

CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................

More information

MULTI SPLIT SYSTEM AIR CONDITIONER

MULTI SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL AER534QC Dual System Kit :DKR8585C (Option) MULTI SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AER534QC 387007146 Model No. Product Code No. DKR8585C 387025905 Outdoor

More information

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET (PART NO. 97474700) For authorized service personnel only. This installation instruction sheet describes how to install the outdoor unit only.

More information

Technical service manual

Technical service manual GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

Technical service manual 2009

Technical service manual 2009 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work. Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------

More information

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit Troubleshooting 13. Troubleshooting Indoor unit s LED indication of Corona DC inverter unit MCAC-HTSM-2007-11 E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P5 EEPROM error outdoor communication error Zero-crossing examination

More information

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for

More information

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060 4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE

More information

Install Guide CT101. Caution. Caution

Install Guide CT101. Caution. Caution Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

Air Conditioning System

Air Conditioning System Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,

More information

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

ROOM AIR CONDITIONER INSTALLATION MANUAL

ROOM AIR CONDITIONER INSTALLATION MANUAL ROOM AIR CONDITIONER INSTALLATION MANUAL ( Split Type) Please read this installation manual completely before installing the product When the power cord is damaged, replacement work shall be performed

More information

CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING

CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING Order No: PAPAMY1207094CE Indoor Unit CS-CE9NKE CS-CE12NKE Outdoor Unit CU-CE9NKE CU-CE12NKE WARNING This service information is designed for experienced repair technicians only and is not designed for

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Quest 105, Dry155, and 205 Dual

Quest 105, Dry155, and 205 Dual Quest 105, Dry155, and 205 Dual Read and Save These Instructions This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully.

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact: 7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca

More information

AIR CONDITIONER OUTDOOR UNIT

AIR CONDITIONER OUTDOOR UNIT AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.

More information

ALL IN ONE. Heat Pump Water Heater

ALL IN ONE. Heat Pump Water Heater ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit. www.airtradecentre.com CONTENTS A. IMPORTANT REMARKS ------------------------------------------------------------------------------------------------

More information

9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE

9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE 9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 6 3. Dimension... 9 3.1 Indoor

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

Meaco 30L and Meaco 40L dehumidifier instruction manual

Meaco 30L and Meaco 40L dehumidifier instruction manual Meaco 30L and Meaco 40L dehumidifier instruction manual Please read this instruction manual before using the dehumidifier and keep safe for future reference SAFETY INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

INSTALLATION & OPERATION MANUAL MODULAR AIR COOLED CHILLER

INSTALLATION & OPERATION MANUAL MODULAR AIR COOLED CHILLER INSTALLATION & OPERATION MANUAL MODULAR AIR COOLED CHILLER Model: MAC160/210A CONTENTS MAC00912-A4 Part No.: M08019301021 1. Features page2 2. Nomenclature page3 3. Specifications page5 4. Performance

More information

LG Floor Standing Type Air Conditioner INSTALLATION MANUAL

LG Floor Standing Type Air Conditioner INSTALLATION MANUAL website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG Floor Standing Type Air Conditioner INSTALLATION MANUAL LG IMPORTANT Please read this installation manual completely before

More information

Air Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315

Air Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315 RECORD THIS INFORMATION FOR FUTURE REFERENCE: Number Serial Number ADB Number ADB Serial Number Date Purchased USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 CANADA Dometic

More information

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4. AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice

More information

Heat Pump Water Heater IOM Manual

Heat Pump Water Heater IOM Manual Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump

More information

TYPE. MODEL B3200 Roof-Top Air Conditioner used with Mechanical Air Distribution Box INSTALLATION & OPERATING INSTRUCTIONS. 3253.332 Air Conditioner

TYPE. MODEL B3200 Roof-Top Air Conditioner used with Mechanical Air Distribution Box INSTALLATION & OPERATING INSTRUCTIONS. 3253.332 Air Conditioner Type 5. Installation and Operating Instructions RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number Serial Number Date Purchased MODEL B00 Roof-Top Air Conditioner used with Mechanical Air

More information

Ceiling Mount Air Handler Manual

Ceiling Mount Air Handler Manual www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty

More information

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience

More information

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Please read this instruction sheet completely before installing the product. When the power cord is damaged, replacement work should be

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

LOBOY 16 AIR CONDITIONERS

LOBOY 16 AIR CONDITIONERS INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

How To Measure Temperature On A Thermostat

How To Measure Temperature On A Thermostat Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information