DC INVERTER SPLIT SYSTEM AIR CONDITIONER
|
|
|
- Abigayle Little
- 10 years ago
- Views:
Transcription
1 TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U) Product Code No. Body (Panel) ( ) ( ) Outdoor Model No. Product Code No. CUKE1NK CUKE18NKU Indoor Unit Outdoor Unit Body Panel CSKE1NB41 (Body) & CZ18BT1U (Panel) CSKE18NB4UW (Body) & CZ18BT1U (Panel) CUKE1NK1 Remote Controller CUKE18NKU Wired Remote Controller (Option) REFERENCE NO. SM700880
2 SAFETY PRECAUTIONS Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them. The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the " Warning" table. However, even precautionary items identified as " Caution" also have the potential for serious consequences if not performed correctly. Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them. Symbol Indication : This symbol indicates items to which we need to pay attention. In this triangle, a definite precautionary item is described. : This symbol indicates the item to be prohibited. In or close to this circle, a prohibited item is described. : This symbol indicates the items requiring special attention or instruction. In or close to this circle, a prohibited item is described. After doing repair work, perform a test run to confirm that there are no abnormalities. At the same time, explain the precautions in use to the user. Warning Before performing an overhaul, disconnect the power plug or power cable from the unit. Performing the work with the power supplied to the unit, may cause an electric shock. When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed, do not touch the charging section. Doing so may cause an electric shock. Prohibit For the stepup capacitor attached to the electric section, perform the repair work after sufficiently discharging it. Insufficient capacitor discharge may cause an electric shock. Do not perform repair work on the electric sections with wet hands. Doing so may cause an electric shock. Do not start or stop the air conditioner by means of connecting or disconnecting the power plug. Doing so may cause an electric shock or fire. When conducting repair work only use components included in the parts list for the corresponding unit and perform the work with the appropriate tools. Incorrect or poor repair work may cause an electric shock or fire. Never modify the unit. Doing so may cause an electric shock or fire. Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring regulation and make sure to use the exclusive circuit. Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire. Prohibit Prohibit Prohibit Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration. Failure to do so may cause an electric shock, overheating or fire. Make sure that there is no dust on or slack in the power plug and insert fully into the socket. Dust or incomplete connections may cause an electric shock or fire. Do not damage or process the power cord, as it may cause an electric shock or fire. Prohibit For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate. Poorly fixed wiring may cause a heat or fire. After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely. Incomplete attachment of the terminal cover may cause overheating or fire.
3 Warning If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite. Prohibit If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated. Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle. If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle, which may cause a unit breakdown." When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in a wellventilated place after sufficiently recovering the refrigerant gas. Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury. Prohibit When the work is to be performed in a high place (About meters or more), make sure to wear a safety helmet, gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall. When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit. Insufficient strength of the installation location and incomplete installation work may cause an injury due to the unit falling. When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children. If a child swallows a battery, make sure that the child gets immediate medical attention. Caution Do not wash the air conditioner with water, as this may cause an electric shock or fire. Prohibit For the repair work in places with high humidity or moisture, make sure to ground the unit. Failure to do so may cause an electric shock. Confirm that the component attachment position, wiring condition, soldering condition and connector connection are normal. If not, it may cause overheating or fire. Confirm that the temperature around the compressor is not too high, and then perform the repair work. Failure to do so may cause a burn. Perform welding work in a place with good ventilation. If the work is performed in a poorly ventilated area, it might cause a lack of oxygen. If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it. Failure to do so may cause an injury due to the unit falling. When the cleaning is to be performed, make sure to turn off the power and pull out the plug. Touching the fan that is rotating at high speed may result in an injury. When the indoor unit is to be removed, do not place it on an incline. Doing so may cause wet furniture because water left inside may trickle down. Prohibit Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger. Prohibit After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more. Any insulation error may cause an electric shock. After repairs, make sure to check the drainage of the indoor unit. Inappropriate drainage may cause wet furniture and floors due to water leakage. 3
4 Table of Contents SAFETY PRECAUTIONS... Page TABLE OF CONTENTS 1. OPERATING RANGE SPECIFICATIONS 1. Unit Specifications.... Major Component Specifications Other Component Specifications DIMENSIONAL DATA REFRIGERANT FLOW DIAGRAM 41. Refrigerant Flow Diagram PERFORMANCE DATA 51. Temperature Charts Cooling Capacity Cooling Capacity (Low Ambient) Heating Capacity ELECTRICAL DATA 61. Electrical Characteristics 6. Electric Wiring Diagrams 7. MAINTENANCE 71. Address Setting of the Remote Control Unit Disconnecting and Connecting Positive Connector for Outdoor Unit Disassembly Procedure FUNCTIONS 81. Operation Functions 8. Protective Functions TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 91. Precautions before Performing Inspection or Repair Method of SelfDiagnostics Checking the Indoor and Outdoor Units Trouble Diagnosis of Fan Motor Noise Malfunction and Electromagnetic Interference
5 Page 10. CHECKING ELECTRICAL COMPONENTS 101. Measurement of Insulation Resistance Checking Continuity of Fuse on PCB Ass'y REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 111. Characteristics of New Refrigerant R410A Checklist before Servicing Tools Specifically for R410A Tubing Installation Procedures In Case of Compressor Malfunction In Case Refrigerant is Leaking Charging Additional Refrigerant RetroFitting Existing Systems... APPENDIX A Operating Instructions... (CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU) APPENDIX B INSTALLATION INSTRUCTIONS... (CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU) A1 A APPENDIX C Operating Instructions (CZRD515U)... A3 APPENDIX D INSTALLATION INSTRUCTIONS (CZRD515U)... A4 5
6 1. OPERATING RANGE Cooling Heating Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum Minimum Maximum Minimum 95 F DB / 71 F WB 67 F DB / 57 F WB 80 F DB / 67 F WB DB / WB 115 F DB 0 F DB 75 F DB / 65 F WB DB / 0 F WB 6
7 . SPECIFICATIONS 1. Unit Specifications 11. Performance Electrical Rating Features Voltage Rating Indoor Unit Outdoor Unit CSKE1NB41 & CZ18BT1U CUKE1NK1 115V SinglePhase 60Hz Total Capacity BTU/h kw 11, Cooling ( 3,000 to 11,900 ) ( 0.9 to 3.5 ) 13, Heating ( 3,000 to 13,600 ) ( 0.9 to 4.0 ) Sensible Capacity Latent Capacity BTU/h BTU/h 7,00 4,700 Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) 35(399) / 06(350) / 194(330) 68(455) / 47(40) / 4(381) Moisture Removal (High) Pints/h 4.6 Available Voltage Range V 104 to 16 Running Amperes Power Input A W 1.6 1,60 (.5 to 1.6 ) ( 50 to 1,60 ) ,460 (.5 to 14.6 ) ( 50 to 1,460 ) Power Factor % EER BTU/h/W 9.44 COP W/W.74 SEER BTU/Wh 16 HSPF BTU/Wh 8.5 Compressor Locked Rotor Amperes A 0 Fuse or Circuit Breaker Capacity A 0 Controls / Temperature Control Microprocessor / I.C. Thermister Control Unit Wireless Remote Control Unit Timer 4Hour ON or OFF Timer, 1Hour OFF Timer Fan Speeds Indoor / Outdoor Auto and 3 steps / Auto (Hi, Me, Lo) Airflow Direction (Indoor) Horizontal Air Filter Compressor Vertical Auto Washable, AntiMold DC Rotary (Inverter) Refrigerant / Amount charged at shipment Ibs (g) R410A /.43 (1,100) Refrigerant Control Electric Expansion Valve Operation Sound Indoor : Hi/Me/Lo Outdoor : Hi dba dba 34 / 3 / / 34 / 3 49 Refrigerant Tubing Connections Flare Type Max. allowable tubing length at shipment ft (m) 5 (7.5) Refrigerant Narrow tube inch (mm) 1/4 (6.35) Tube Diameter Wide tube inch (mm) 3/8 (9.5) Wired Remote Controller (Option) CZRD515U 7
8 Indoor Unit Outdoor Unit CSKE1NB41 & CZ18BT1U CUKE1NK1 Dimensions & Weight (Indoor Unit) Unit Dimensions Package Dimensions Weight Shipping Volume Weight Shipping Volume Height Width Depth Height Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Width inch (mm) 413/16 (630) Depth inch (mm) 81/8 (714) Net Shipping Ib. (kg) Ib. (kg) 41.3 (18.7) 35.3 (16) 41.9 (19) cu.ft (m 3 ) 4.59 (0.13) Height Width Depth Height Width Depth Net Shipping Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB Individual Unit Indoor Unit Body (CSKE1NB41 & CZ18BT1U) (CSKE1NB41) inch (mm) 15/16 (313) 115/3 (83) Panel (CZ18BT1U) 19/16 (40) inch (mm) 419/3 (65) 5/8 (575) 419/3 (65) inch (mm) 419/3 (65) 5/8 (575) 419/3 (65) inch (mm) 1113/3 (90) 41/8 (105) 63/16 (665) 611/16 (678) 6.0 (.7) 7.7 (3.5) 1.65 (0.04) Outdoor Unit (CUKE1NK1) inch (mm) 19/16 (548) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m 3 ) 811/3 (70) 107/16 (65) 315/3 (596) 343/3 (866) 141/ (368) 77. (35.0) 83.8 (38.0) 6.35 (0.18) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Heating: Indoor air temperature 70 F DB Outdoor air temperature 47 F DB / 43 F WB 8
9 1. Performance Electrical Rating Features Voltage Rating Indoor Unit Outdoor Unit CSKE18NB4UW & CZ18BT1U CUKE18NKU 30V SinglePhase 60Hz < 30V > Total Capacity BTU/h kw 17, Cooling ( 4,000 to 17,500 ) ( 1. to 5.15 ) 0, Heating ( 4,400 to 0,400 ) ( 1.3 to 6.0 ) Sensible Capacity Latent Capacity BTU/h BTU/h 10,600 6,900 Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) 341(579) / 94(500) / 53(430) 383(651) / 34(551) / 65(450) Moisture Removal (High) Pints/h 4.89 Available Voltage Range V 187 to 53 Running Amperes Power Input A W 8.3 1,860 ( 1. to 8.3 ) ( 50 to 1,860 ) 10.5,340 ( 1.3 to 10.5 ) ( 70 to,340 ) Power Factor % EER BTU/h/W 9.41 COP W/W.56 SEER BTU/Wh 16 HSPF BTU/Wh 8.5 Compressor Locked Rotor Amperes A 17.5 Fuse or Circuit Breaker Capacity A 15 Controls / Temperature Control Microprocessor / I.C. Thermister Control Unit Wireless Remote Control Unit Timer 4Hour ON or OFF Timer, 1Hour OFF Timer Fan Speeds Indoor / Outdoor Auto and 3 steps / Auto (Hi, Me, Lo) Airflow Direction (Indoor) Horizontal Air Filter Compressor Vertical Auto Washable, AntiMold DC Twin Rotary (Inverter) Refrigerant / Amount charged at shipment Ibs (g) R410A /.87 (1,300) Refrigerant Control Electric Expansion Valve Operation Sound Indoor : Hi/Me/Lo Outdoor : Hi dba dba 44 / 40 / / 40 / 36 5 Refrigerant Tubing Connections Flare Type Max. allowable tubing length at shipment ft (m) 5 (7.5) Refrigerant Narrow tube inch (mm) 1/4 (6.35) Tube Diameter Wide tube inch (mm) 1/ (1.7) Wired Remote Controller (Option) CZRD515U 9
10 Indoor Unit Outdoor Unit Weight Shipping Volume CSKE18NB4UW & CZ18BT1U CUKE18NKU Dimensions & Weight (Indoor Unit) Unit Dimensions Package Dimensions Height Width Depth Height Width Depth Net Shipping inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m 3 ) Indoor Unit (CSKE18NB4UW & CZ18BT1U) 15/16 (313) 419/3 (65) 419/3 (65) 41.3 (18.7) Body (CSKE18NB4UW) 115/3 (83) < 30V > Individual Unit Panel (CZ18BT1U) 19/16 (40) 5/8 (575) 419/3 (65) 5/8 (575) 1113/3 (90) 419/3 (65) 41/8 (105) 413/16 (630) 63/16 (665) 81/8 (714) 611/16 (678) 35.3 (16) 6.0 (.7) 41.9 (19) 7.7 (3.5) 4.59 (0.13) 1.65 (0.04) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Shipping Volume Height Width Depth Height Width Depth Net Shipping Outdoor Unit (CUKE18NKU) inch (mm) 63/8 (670) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m 3 ) Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB 341/3 (880) 117/3 (85) 87/3 (733) 397/3 (1,01) 149/3 (379) 97.0 (44.0) (48.0) 9.88 (0.8) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Heating: Indoor air temperature 70 F DB Outdoor air temperature 47 F DB / 43 F WB 10
11 13. Performance Electrical Rating Features Indoor Unit Outdoor Unit Voltage Rating CSKE18NB4UW & CZ18BT1U CUKE18NKU 08V SinglePhase 60Hz < 08V > Total Capacity BTU/h kw 17, Cooling ( 4,000 to 17,500 ) ( 1. to 5.15 ) 0, Heating ( 4,400 to 0,400 ) ( 1.3 to 6.0 ) Sensible Capacity Latent Capacity BTU/h BTU/h 10,600 6,900 Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) 341(579) / 94(500) / 53(430) 383(651) / 34(551) / 65(450) Moisture Removal (High) Pints/h 4.89 Available Voltage Range V 187 to 53 Running Amperes Power Input A W 9.1 1,860 ( 1. to 9.1 ) ( 50 to 1,860 ) 11.5,340 ( 1.3 to 11.5 ) ( 70 to,340 ) Power Factor % EER BTU/h/W 9.41 COP W/W.56 SEER BTU/Wh 16 HSPF BTU/Wh 8.5 Compressor Locked Rotor Amperes A 17.5 Fuse or Circuit Breaker Capacity A 15 Controls / Temperature Control Microprocessor / I.C. Thermister Control Unit Wireless Remote Control Unit Timer 4Hour ON or OFF Timer, 1Hour OFF Timer Fan Speeds Indoor / Outdoor Auto and 3 steps / Auto (Hi, Me, Lo) Airflow Direction (Indoor) Horizontal Air Filter Compressor Vertical Auto Washable, AntiMold DC Twin Rotary (Inverter) Refrigerant / Amount charged at shipment Ibs (g) R410A /.87 (1,300) Refrigerant Control Electric Expansion Valve Operation Sound Indoor : Hi/Me/Lo Outdoor : Hi dba dba 44 / 40 / / 40 / 36 5 Refrigerant Tubing Connections Flare Type Max. allowable tubing length at shipment ft (m) 5 (7.5) Refrigerant Narrow tube inch (mm) 1/4 (6.35) Tube Diameter Wide tube inch (mm) 1/ (1.7) Wired Remote Controller (Option) CZRD515U 11
12 Indoor Unit Outdoor Unit Weight Shipping Volume CSKE18NB4UW & CZ18BT1U CUKE18NKU Dimensions & Weight (Indoor Unit) Unit Dimensions Package Dimensions Height Width Depth Height Width Depth Net Shipping inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m 3 ) Indoor Unit (CZKE18NB4UW & CZ18BT1U) 15/16 (313) 419/3 (65) 419/3 (65) 41.3 (18.7) Body (CSKE18NB4UW) 115/3 (83) < 08V > Individual Unit Panel (CZ18BT1U) 19/16 (40) 5/8 (575) 419/3 (65) 5/8 (575) 1113/3 (90) 419/3 (65) 41/8 (105) 413/16 (630) 63/16 (665) 81/8 (714) 611/16 (678) 35.3 (16) 6.0 (.7) 41.9 (19) 7.7 (3.5) 4.59 (0.13) 1.65 (0.04) Dimensions & Weight (Outdoor Unit) Unit Dimensions Package Dimensions Weight Shipping Volume Height Width Depth Height Width Depth Net Shipping Outdoor Unit (CUKE18NKU) inch (mm) 63/8 (670) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m 3 ) Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB 341/3 (880) 117/3 (85) 87/3 (733) 397/3 (1,01) 149/3 (379) 97.0 (44.0) (48.0) 9.88 (0.8) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Heating: Indoor air temperature 70 F DB Outdoor air temperature 47 F DB / 43 F WB 1
13 . Major Component Specifications 1. Indoor Unit Indoor Unit (Body) CSKE1NB41 Control PCB Part No. Controls Control Circuit Fuse CBCSKE1NB4U Microprocessor 50V 3A Fan Type Q'ty... Dia. and Length inch (mm) Turbo 1... D15/8 / L53/4 (D3/L147) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool / Heat) Rating Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over Current Protection Over Heat Protection Run Capacitor Voltage / Nominal Output Ohm Micro F VAC DC Motor SIC6FWD / 50 DC160V / 3W Internal Controller Yes Yes Drain Pump Model... Q'ty Rating Voltage, Hz Input Coil Resistance (Ambient Temp. 68 F (0 C)) Safty Device Type Open Heat Exchanger Coil Coil Rows Fins per inch Face Area W Ohm F ( C) ft (m ) PLD1115ST AC115V, 60Hz / 10% Thermal Fuse 93 (145) Aluminum Plate Fin / Copper Tube (0.73) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Indoor Unit (Panel) CZ18BT1U Flap Motor Type Model... Q'ty Rating Coil Resistance (Ambient Temp. 77 F (5 C)) Ohm Stepping Motor MPZN1V... DC 1V Each Pair of Terminal : 380 +/ 7% DATA SUBJECT TO CHANGE WITHOUT NOTICE. 13
14 Indoor Unit (Body) CSKE18NB4UW Control PCB Part No. Controls Control Circuit Fuse CBCSKE18NB4U Microprocessor 50V 3A Fan Type Q'ty... Dia. and Length inch (mm) Turbo 1... D15/8 / L53/4 (D3/L147) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool / Heat) Rating Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over Current Protection Over Heat Protection Run Capacitor Voltage / Nominal Output Ohm Micro F VAC DC Motor SIC6FVD / 70 DC340V / 0W Thermal Fuse Yes Yes Drain Pump Model... Q'ty Rating Coil Resistance (Ambient Temp. 68 F (0 C)) Safty Device Type Open Heat Exchanger Coil Coil Rows Fins per inch Face Area Voltage, Hz Input W Ohm F ( C) ft (m ) PLD130ST AC08 to 40V, 60Hz / 10% Thermal Fuse 93 (145) Aluminum Plate Fin / Copper Tube (0.73) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Indoor Unit (Panel) CZ18BT1U Flap Motor Type Model... Q'ty Rating Coil Resistance (Ambient Temp. 77 F (5 C)) Ohm Stepping Motor MP4ZN1V... DC 1V Each Pair of Terminal : 380 +/ 7% DATA SUBJECT TO CHANGE WITHOUT NOTICE. 14
15 . Outdoor Unit Outdoor Unit CUKE1NK1 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cutoff control) Compressor Discharge Temp. Control Operation cutoff control in abnormal ambient Temp. Run Capacitor Overload Relay Crankcase Heater Model Operation Temp. Micro F VAC CBCUKE1NK1 Microprocessor 15V 5A DC Rotary (Hermetic) G4C090LU1ER / 900W FV50S (30) U V : 0.81 V W : 0.81 W U : 0.81 Yes Yes Yes CS7L115 Open : 39 F (115 C), Close : 03 F (95 C) 115V 0W Fan Type Q'ty... Dia. inch (mm) Propeller 1... D153/4 (D400) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool / Heat) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over Current Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC67FVF / RED WHT : 77.5 WHT BLU : 77.5 BLU RED : 77.5 Internal Controller Yes Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 18.1 Face Area ft (m ) 3.95 (0.367) External Finish Acrylic bakedon enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 15
16 Outdoor Unit CUKE18NKU Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cutoff control) Compressor Discharge Temp. Control Operation cutoff control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CBCUKE18NKU Microprocessor 50V 5A DC Twin Rotary (Hermetic) C6RVN93H0M / 1,050W FV50S (350) R S : 0.48 S T : 0.48 T R : 0.48 Yes Yes Yes CS7L115 Open : 39 F (115 C), Close : 03 F (95 C) Fan Type Q'ty... Dia. inch (mm) Propeller 1... D1617/3 (D40) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool / Heat) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over Current Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC67FVF / RED WHT : 77.5 WHT BLU : 77.5 BLU RED : 77.5 Internal Controller Yes Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 1. Face Area ft (m ) 5.49 (0.510) External Finish Acrylic bakedon enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 16
17 3. Other Component Specifications Indoor Unit CSKE1NB41 & CZ18BT1U CSKE18NB4UW & CZ18BT1U Outdoor Unit CUKE1NK1 CUKE18NKU Indoor air temp sensor (Model:KTEC35S98) Indoor heat exchanger sensor (Model:PTM51HS3) Compressor temp sensor (CUKE1NK1... Model:DTNTKS74Y TH) (CUKE18NKU... Model:DTNTKS93B) Resistance (k ohm) (10) (15) (0) (5) (30) (35) (40) Temperature F ( C) Resistance (k ohm) (0) (10) (0) (30) (40) (50) (60) (70) (80) (90) Temperature F ( C) Outdoor air temp sensor (CUKE1NK1... Model:DTNTKS69B) (CUKE18NKU... Model:TKS95B) Outdoor heat exchanger sensor (CUKE1NK1... Model:DTNTKS74Y TH1) (CUKE18NKU... Model:TKS9B) 40 Resistance (k ohm) (0)(15)(10) (5) (0) (5) (10) (15) (0) Temperature F ( C) 17
18 3. DIMENSIONAL DATA Indoor Unit CSKE1NB41 & CZ18BT1U CSKE18NB4UW & CZ18BT1U 13/16 (30) 3/3 5/8 (575) 65/16 611/16 419/3 15/3 15/3 815/3 115/3 (83) 5/8 (575) Less than 31/3 Less than 31/3 11/3 (534) Suspension bolt pitch /3 (65) 143/3 (358) 5 35/8 17/8 135/3 (334) 17/16 419/3 (65) 11/3 (534) Suspension bolt pitch 35/8 (600) Ceiling opening dimensions 711/16 13/ /8 (600) Ceiling opening dimensions Center of panel A View 49/3 8 1/3 31/ Air intake Discharge outlet Refrigerant tubing (liquid tube) dia. 1/4" (flared) Refrigerant tubing (gas tube) dia. 1/" (flared) Drain tube connection port VP0 (outer dia. 1") Power supply port Suspension bolt hole (4 1/" x 11/8" hole) Fresh air intake duct connection port (dia. 37/8") 3/3 5/3 A The length of the suspension bolts should be selected so that there is a gap of 13/16" or the ceiling (1/3" or more below the lower surface of the main unit), as shown in the figure at right. If the suspension bolts is too long, it will contact the ceiling panel and the unit cannot be installed. 73/3 3/4 19/3 59/16 17/3 13/3 Unit : inch (mm) 18
19 Outdoor Unit CUKE1NK1 13/16 319/3 1013/16 15/3 ID:3/3 4ID:15/16 49/3 5/3 319/3 107/16 (65) 1113/3 17/16 811/3 (70) 1/8 Wide tube service valve dia.3/8" (9.5) Narrow tube service valve dia.1/4" (6.35) 19/16 (548) 5/8 63/3 Unit : inch (mm) ( ) 19
20 Outdoor Unit CUKE18NKU 315/16 511/3 13/8 1117/3 ID:3/3 4ID:15/16 15/3 341/3(880) Wide tube service valve dia.1/" (1.70) Narrow tube service valve dia.1/4" (6.35) 3/3 43/8 5/3 617/3 63/8(670) 117/3(85) 17/3 135/3 17/3 113/16 3/3 53/3 13/3 Unit : inch (mm) ( ) 0
21 4. REFRIGERANT FLOW DIAGRAM 41. Refrigerant Flow Diagram Indoor Unit CSKE1NB41 & CZ18BT1U Outdoor Unit CUKE1NK1 Indoor unit Outdoor unit Wide tube O.D. 3/8" (9.5 mm) Wide tube service valve Muffler Accumulator High pressure switch H.P. Compressor 4way valve Heat exchanger Strainer Heat exchanger Narrow tube O.D. 1/4" (6.35 mm) Narrow tube service valve Strainer Muffler Electric expansion valve M Capillary tube for split flow Cooling cycle (Defrosting cycle) Heating cycle 1
22 Indoor Unit CSKE18NB4UW & CZ18BT1U Outdoor Unit CUKE18NKU Indoor unit Outdoor unit Wide tube O.D. 1/" (1.7mm) Wide tube service valve Muffler Accumulator High pressure switch H.P. Compressor 4way valve Strainer Heat exchanger Heat exchanger Narrow tube O.D. 1/4" (6.35 mm) Narrow tube service valve Strainer Electric expansion valve M Capillary tube for split flow Cooling cycle (Defrosting cycle) Heating cycle
23 5. PERFORMANCE DATA 51. Temperature Charts Indoor Unit CSKE1NB41 & CZ18BT1U Outdoor Unit CUKE1NK1 Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 115V) (1) Low pressure performance chart Low pressure at wide tube service valve psig(mpag) 131 (0.9) 10 (0.7) () Operating current performance chart 73 (0.5) 77 (5) 15 Lo Fan Hi Fan (30) (35) Outdoor inlet air DB temp. F( C) Lo Fan Indoor Air Temp.86 F (30 C) Hi Fan 80 F (7 C) 80 F (7 C) 75 F (4 C) 75 F (4 C) 104 (40) Operating current (A) F (7 C) 80 F (7 C) Indoor Air Temp.86 F (30 C) 75 F (4 C) 75 F (4 C) (3) Indoor discharge air performance chart Indoor discharge air temperature F( C) (0) 59 (15) 50 (10) 41 (5) 77 (5) 3 (0) 77 (5) (30) (35) Outdoor inlet air DB temp. F( C) Lo Fan Hi Fan Indoor Air Temp.86 F (30 C) 80 F (7 C) 80 F (7 C) 75 F (4 C) 75 F (4 C) (30) (35) Outdoor inlet air DB temp. F( C) 104 (40) 104 (40) NOTE Check each performance value in testrun mode. Electrical performance values represent a combined indoor/outdoor value. 3
24 Indoor Unit CSKE1NB41 & CZ18BT1U Outdoor Unit CUKE1NK1 Heating Characteristics (RH : 85%, Indoor fan speed : High fan) (60Hz, 115V) (1) High pressure performance chart High pressure at wide tube service valve psig(mpag) Operating current (A) 508 (3.5) 435 (3.0) 363 (.5) 90 (.0) 18 (1.5) 3 (5) () Operating current performance chart Indoor Air Temp.73 F (3 C) 70 F (1 C) 63 F (17 C) 3 (0) 41 (5) 50 (10) 59 (15) 68 (0) Outdoor inlet air DB temp. F( C) Indoor Air Temp.73 F (3 C) 70 F (1 C) 63 F (17 C) 77 (5) 1 Indoor discharge air temperature F( C) 11 3 (5) (3) Indoor discharge air performance chart 131 (55) 1 (50) 113 (45) 104 (40) 95 (35) 86 (30) 77 (5) 68 (0) 3 (5) 3 (0) 41 (5) 50 (10) 59 (15) 68 (0) Outdoor inlet air DB temp. F( C) Indoor Air Temp.73 F (3 C) 70 F (1 C) 63 F (17 C) 3 (0) 41 (5) 50 (10) 59 (15) 68 (0) Outdoor inlet air DB temp. F( C) 77 (5) 77 (5) NOTE Check each performance value in testrun mode. Electrical performance values represent a combined indoor/outdoor value. Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "8. Protective Functions Overload prevention during heating.") 4
25 Indoor Unit CSKE18NB4UW & CZ18BT1U Outdoor Unit CUKE18NKU Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 30V) (1) Low pressure performance chart Low pressure at wide tube service valve psig(mpag) () Operating current performance chart Operating current (A) 131 (0.9) 10 (0.7) 73 (0.5) 77 (5) Lo Fan Hi Fan (30) (35) Outdoor inlet air DB temp. F( C) Lo Fan Indoor Air Temp.86 F (30 C) Hi Fan 80 F (7 C) 80 F (7 C) 75 F (4 C) 75 F (4 C) 80 F (7 C) 80 F (7 C) Indoor Air Temp.86 F (30 C) Indoor Air Temp.86 F (30 C) 75 F (4 C) 75 F (4 C) 104 (40) (3) Indoor discharge air performance chart Indoor discharge air temperature F( C) 5 68 (0) 59 (15) 50 (10) 41 (5) 77 (5) 3 (0) 77 (5) (30) (35) Outdoor inlet air DB temp. F( C) Lo Fan Hi Fan Indoor Air Temp.86 F (30 C) Indoor Air Temp.86 F (30 C) 80 F (7 C) 80 F (7 C) 75 F (4 C) 75 F (4 C) (30) (35) Outdoor inlet air DB temp. F( C) 104 (40) 104 (40) NOTE Check each performance value in testrun mode. Electrical performance values represent a combined indoor/outdoor value. 5
26 Indoor Unit CSKE18NB4UW & CZ18BT1U Outdoor Unit CUKE18NKU Heating Characteristics (RH : 85%, Indoor fan speed : High fan) (60Hz, 30V) (1) High pressure performance chart High pressure at wide tube service valve psig(mpag) Operating current (A) 508 (3.5) 435 (3.0) 363 (.5) 90 (.0) 18 (1.5) 3 (5) () Operating current performance chart Indoor Air Temp.73 F (3 C) 70 F (1 C) 63 F (17 C) 3 (0) 41 (5) 50 (10) 59 (15) 68 (0) Outdoor inlet air DB temp. F( C) Indoor Air Temp.73 F (3 C) 70 F (1 C) 63 F (17 C) 77 (5) Indoor discharge air temperature F( C) 131 (55) 1 (50) 113 (45) 104 (40) 95 (35) 86 (30) 77 (5) 6 3 (5) (3) Indoor discharge air performance chart 68 (0) 3 (5) 3 (0) 41 (5) 50 (10) 59 (15) 68 (0) Outdoor inlet air DB temp. F( C) Indoor Air Temp.73 F (3 C) 70 F (1 C) 63 F (17 C) 3 (0) 41 (5) 50 (10) 59 (15) 68 (0) Outdoor inlet air DB temp. F( C) 77 (5) 77 (5) NOTE Check each performance value in testrun mode. Electrical performance values represent a combined indoor/outdoor value. Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "8. Protective Functions Overload prevention during heating.") 6
27 5. Cooling Capacity Indoor Unit : CSKE1NB41 & CZ18BT1U Outdoor Unit : CUKE1NK1 Power Supply : 115V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: 11,900 BTU/h AIR FLOW RATE: 35 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (18.3) (3.9) (9.4) (35.0) (40.6) (46.1) TC 8,350 8,570 8,800 8,930 9,10 7,830 CI (.) SHC 6,340 6,430 6,570 6,610 6,800 6, (4.4) SHC 7,10 7,300 7,440 7,480 7,660 6,930 (15.0) 80 (6.7) SHC 8,10 8,10 8,350 8,400 8,530 7, (8.9) SHC 8,350 8,570 8,800 8,930 9,10 7, (31.1) SHC 8,350 8,570 8,800 8,930 9,10 7,830 TC 1,30 1,030 11,790 11,580 10,580 7,950 CI (.) SHC 7,070 6,930 6,840 6,700 6,00 4, (4.4) SHC 7,940 7,800 7,710 7,570 7,070 5,840 (17.) 80 (6.7) SHC 8,850 8,70 8,580 8,490 7,980 6, (8.9) SHC 9,70 9,590 9,450 9,360 8,850 7,60 88 (31.1) SHC 10,590 10,450 10,360 10,30 9,70 7,950 TC 1,460 1,90 1,070 # 11,900 10,700 8,040 CI (.) SHC 5,790 5,700 5,610 5,50 4,970 3, (4.4) SHC 6,660 6,570 6,480 6,380 5,880 4,740 (19.4) 80 (6.7) SHC 7,570 7,480 7,390 7,300 6,750 5, (8.9) SHC 8,440 8,350 8,60 8,170 7,60 6,50 88 (31.1) SHC 9,310 9,0 9,130 9,040 8,490 7,390 TC 1,640 1,490 1,300 1,170 10,770 8,100 CI (.) SHC 4,460 4,40 4,330 4,80 3,690, (4.4) SHC 5,330 5,90 5,00 5,150 4,560 3,550 (1.7) 80 (6.7) SHC 6,50 6,00 6,110 6,060 5,470 4, (8.9) SHC 7,10 7,070 6,980 6,930 6,340 5, (31.1) SHC 7,980 7,940 7,850 7,800 7,10 6,00 TC 1,730 1,610 1,450 1,370 10,780 8, (4.4) SHC 4,050 4,010 3,960 3,90 3,370,450 (3.9) 80 (6.7) SHC 4,970 4,90 4,880 4,830 4,80 3, (8.9) SHC 5,840 5,790 5,740 5,700 5,150 4,40 88 (31.1) SHC 6,700 6,660 6,610 6,570 6,00 5,100 NOTE TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (6.7 C) DB / 67 F (19.4 C) WB : Outdoor Ambient Temp. 95 F (35 C) DB. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. 3. Above data represents the value when the operation frequency of a compressor is fixed. 7
28 Indoor Unit : CSKE18NB4UW & CZ18BT1U Outdoor Unit : CUKE18NKU Power Supply : 30V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: 17,500 BTU/h AIR FLOW RATE: 341 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (18.3) (3.9) (9.4) (35.0) (40.6) (46.1) TC 1,60 1,550 1,830 13,060 13,460 9,50 CI (.) SHC 9,140 9,70 9,400 9,540 9,740 7, (4.4) SHC 10,330 10,470 10,600 10,730 10,930 9,010 (15.0) 80 (6.7) SHC 11,590 11,70 11,860 11,990 1,190 9,50 84 (8.9) SHC 1,60 1,550 1,830 13,060 13,380 9,50 88 (31.1) SHC 1,60 1,550 1,830 13,060 13,460 9,50 TC 18,110 17,790 17,400 17,000 14,080 9,650 CI (.) SHC 10,400 10,00 10,000 9,800 8,340 6, (4.4) SHC 11,590 11,390 11,190 11,000 9,540 7,480 (17.) 80 (6.7) SHC 1,850 1,650 1,450 1,60 10,800 8, (8.9) SHC 14,040 13,850 13,650 13,450 11,990 9, (31.1) SHC 15,40 15,110 14,840 14,640 13,180 9,650 TC 18,510 18,0 17,860 # 17,500 14,0 9,750 CI (.) SHC 8,680 8,480 8,340 8,140 6,60 4, (4.4) SHC 9,870 9,740 9,540 9,340 7,880 6,00 (19.4) 80 (6.7) SHC 11,130 10,930 10,800 10,600 9,070 7,80 84 (8.9) SHC 1,30 1,190 11,990 11,790 10,330 8, (31.1) SHC 13,510 13,380 13,180 1,980 11,530 9,670 TC 18,80 18,570 18,60 17,940 14,90 9,810 CI (.) SHC 6,750 6,690 6,550 6,40 4,900 3, (4.4) SHC 7,950 7,880 7,750 7,610 6,090 4,430 (1.7) 80 (6.7) SHC 9,10 9,140 9,010 8,870 7,350 5, (8.9) SHC 10,470 10,330 10,00 10,070 8,540 6, (31.1) SHC 11,660 11,530 11,390 11,60 9,740 8,080 TC 19,010 18,800 18,530 18,60 14,80 9,810 CI (4.4) SHC 6,160 6,090 5,960 5,890 4,430,970 (3.9) 80 (6.7) SHC 7,40 7,350 7,0 7,150 5,690 4,30 84 (8.9) SHC 8,610 8,540 8,410 8,340 6,890 5, (31.1) SHC 9,800 9,740 9,670 9,540 8,080 6,60 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE 1. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (6.7 C) DB / 67 F (19.4 C) WB : Outdoor Ambient Temp. 95 F (35 C) DB. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. 3. Above data represents the value when the operation frequency of a compressor is fixed. 8
29 53. Cooling Capacity (Low Ambient) Indoor Unit : CSKE1NB41 & CZ18BT1U Outdoor Unit : CUKE1NK1 Power Supply : 115V Single Phase 60Hz < Cooling Capacity (Low Ambient) > RATING CAPACITY: 11,900 BTU/h AIR FLOW RATE: 35 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (17.8) (15.0) (9.4) (3.9) (1.7) (7.) (1.8) TC 9,530 9,550 9,560 9,590 9,600 9,590 9,570 CI (.) SHC 6,930 6,930 6,980 8,580 6,980 6,980 6, (4.4) SHC 7,800 7,800 7,850 9,450 7,850 7,850 7,850 (15.0) 80 (6.7) SHC 8,70 8,70 8,70 9,590 8,760 8,760 8, (8.9) SHC 9,530 9,550 9,560 9,590 9,600 9,590 9, (31.1) SHC 9,530 9,550 9,560 9,590 9,600 9,590 9,570 TC 9,440 9,460 9,530 9,590 9,650 9,660 9,670 CI (.) SHC 5,650 5,650 5,700 8,580 5,740 5,740 5, (4.4) SHC 6,50 6,50 6,570 9,450 6,610 6,610 6,660 (17.) 80 (6.7) SHC 7,440 7,440 7,480 9,590 7,530 7,530 7, (8.9) SHC 8,300 8,300 8,350 9,590 8,400 8,400 8, (31.1) SHC 9,170 9,170 9,0 9,590 9,70 9,70 9,70 TC 9,50 9,90 9,410 9,530 9,60 9,670 9,70 CI (.) SHC 4,370 4,370 4,40 8,580 4,510 4,560 4, (4.4) SHC 5,40 5,40 5,90 9,450 5,380 5,40 5,40 (19.4) 80 (6.7) SHC 6,160 6,160 6,00 9,530 6,90 6,340 6, (8.9) SHC 7,00 7,00 7,070 9,530 7,160 7,10 7,10 88 (31.1) SHC 7,890 7,890 7,940 9,530 8,030 8,080 8,080 TC 8,950 9,010 9,10 9,380 9,50 9,610 9,710 CI (.) SHC 3,000 3,050 3,090 8,580 3,30 3,80 3, (4.4) SHC 3,870 3,90 3,960 9,380 4,100 4,140 4,140 (1.7) 80 (6.7) SHC 4,780 4,830 4,880 9,380 5,010 5,060 5, (8.9) SHC 5,650 5,700 5,740 9,380 5,880 5,930 5, (31.1) SHC 6,50 6,570 6,610 9,380 6,750 6,800 6,800 TC 8,590 8,650 8,930 9,160 9,360 9,480 9,60 CI (4.4) SHC,590,640,730 9,160,860,910,960 (3.9) 80 (6.7) SHC 3,500 3,550 3,640 9,160 3,780 3,80 3, (8.9) SHC 4,370 4,40 4,510 9,160 4,650 4,690 4, (31.1) SHC 5,40 5,90 5,380 9,160 5,50 5,560 5,610 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. NOTE Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 9
30 Indoor Unit : CSKE18NB4UW & CZ18BT1U Outdoor Unit : CUKE18NKU Power Supply : 30V Single Phase 60Hz < Cooling Capacity (Low Ambient) > RATING CAPACITY: 17,500 BTU/h AIR FLOW RATE: 341 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (17.8) (15.0) (9.4) (3.9) (1.7) (7.) (1.8) TC 13,400 13,430 13,440 13,470 13,500 13,50 13,510 CI (.) SHC 9,740 9,740 9,740 11,860 9,740 9,800 9, (4.4) SHC 10,930 10,930 10,930 13,050 11,000 11,000 11,000 (15.0) 80 (6.7) SHC 1,190 1,190 1,190 13,470 1,190 1,60 1, (8.9) SHC 13,380 13,380 13,380 13,470 13,380 13,450 13, (31.1) SHC 13,400 13,430 13,440 13,470 13,500 13,50 13,510 TC 13,60 13,300 13,370 13,480 13,560 13,640 13,670 CI (.) SHC 7,950 7,950 7,950 11,860 8,080 8,080 8, (4.4) SHC 9,140 9,140 9,10 13,050 9,70 9,70 9,340 (17.) 80 (6.7) SHC 10,400 10,400 10,400 13,480 10,530 10,530 10, (8.9) SHC 11,590 11,590 11,590 13,480 11,70 11,70 11, (31.1) SHC 1,790 1,790 1,850 13,480 1,90 1,980 1,980 TC 1,980 13,040 13,170 13,380 13,530 13,670 13,760 CI (.) SHC 6,090 6,160 6,0 11,860 6,360 6,40 6, (4.4) SHC 7,80 7,350 7,40 13,050 7,550 7,610 7,680 (19.4) 80 (6.7) SHC 8,540 8,610 8,680 13,380 8,810 8,870 8, (8.9) SHC 9,740 9,800 9,870 13,380 10,000 10,070 10, (31.1) SHC 11,000 11,000 11,060 13,380 11,190 11,60 11,330 TC 1,550 1,630 1,830 13,160 13,390 13,600 13,750 CI (.) SHC 4,30 4,30 4,370 11,860 4,570 4,630 4, (4.4) SHC 5,430 5,490 5,560 13,050 5,760 5,80 5,890 (1.7) 80 (6.7) SHC 6,690 6,690 6,80 13,160 7,00 7,080 7, (8.9) SHC 7,880 7,950 8,010 13,160 8,10 8,80 8, (31.1) SHC 9,070 9,140 9,10 13,160 9,400 9,470 9,540 TC 1,010 1,110 1,380 1,850 13,150 13,440 13,650 CI (4.4) SHC 3,640 3,700 3,770 1,850 4,030 4,170 4,30 (3.9) 80 (6.7) SHC 4,900 4,960 5,030 1,850 5,90 5,360 5, (8.9) SHC 6,090 6,160 6,0 1,850 6,490 6,60 6, (31.1) SHC 7,80 7,350 7,40 1,850 7,680 7,810 7,880 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) 1. NOTE Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 30
31 54. Heating Capacity Indoor Unit : CSKE1NB41 & CZ18BT1U Outdoor Unit : CUKE1NK1 Power Supply : 115V Single Phase 60Hz < Heating Capacity > RATING CAPACITY: 13,600 BTU/h AIR FLOW RATE: 68 CFM OUTDOOR INDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB (15.6) (18.3) (1.1) (3.9) (6.7) 0 (17.8) TH 7,510 7,540 7,560 7,580 7,590 CI (16.1) TH 7,760 7,790 7,810 7,830 7,840 CI (13.3) TH 8,350 8,380 8,410 8,40 8,440 CI (10.6) TH 8,980 9,000 9,030 9,050 9,060 CI (7.8) TH 9,660 9,690 9,70 9,730 9,750 CI (5.0) TH 10,390 10,40 10,440 10,460 10,470 CI (.) TH 11,150 11,180 11,00 11,10 11,0 CI (0.6) TH 11,930 11,960 11,980 1,000 11,740 CI (3.3) TH 1,70 1,750 1,770 1,780 11,740 CI (6.1) TH 13,560 13,580 # 13,600 13,010 11,740 CI (8.9) TH 14,40 14,440 14,10 13,010 11,740 CI (11.7) TH 15,90 15,00 14,00 13,010 11,740 CI (14.4) TH 15,990 15,080 14,40 13,010 11,740 CI (17.) TH 16,000 15,070 14,0 13,010 11,740 CI (18.3) TH 15,980 15,050 14,190 13,010 11,740 CI TH : Total Heating Capacity (BTU/h) NOTE 1. Rating conditions (#) : Indoor Unit Entering Air Temp. 70 F (1.1 C) DB : Outdoor Ambient Temp. 47 F (8.3 C) DB / 43 F (6.1 C) WB. Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air Prevention Protection during heating operation into account. For this reason, the value may vary from the actual heating characteristics. 3. Above data represents the value when the operation frequency of a compressor is fixed. 31
32 Indoor Unit : CSKE18NB4UW & CZ18BT1U Outdoor Unit : CUKE18NKU Power Supply : 30V Single Phase 60Hz < Heating Capacity > RATING CAPACITY: 0,400 BTU/h AIR FLOW RATE: 383 CFM OUTDOOR INDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB (15.6) (18.3) (1.1) (3.9) (6.7) 0 (17.8) TH 11,350 11,400 11,440 11,480 11,510 CI (16.1) TH 11,70 11,770 11,80 11,850 11,890 CI (13.3) TH 1,600 1,650 1,700 1,750 1,780 CI (10.6) TH 13,50 13,580 13,630 13,670 13,710 CI (7.8) TH 14,540 14,600 14,650 14,700 14,730 CI (5.0) TH 15,610 15,670 15,730 15,770 15,810 CI (.) TH 16,730 16,800 16,850 16,890 16,770 CI (0.6) TH 17,900 17,960 18,010 18,060 16,770 CI (3.3) TH 19,050 19,10 19,170 18,590 16,770 CI (6.1) TH 0,90 0,350 # 0,400 18,590 16,770 CI (8.9) TH 1,550 1,610 0,410 18,590 16,770 CI (11.7) TH,830,30 0,410 18,590 16,770 CI (14.4) TH 3,990,30 0,410 18,590 16,770 CI (17.) TH 3,990,30 0,410 18,590 16,770 CI (18.3) TH 3,990,30 0,410 18,590 16,770 CI TH : Total Heating Capacity (BTU/h) NOTE 1. Rating conditions (#) : Indoor Unit Entering Air Temp. 70 F (1.1 C) DB : Outdoor Ambient Temp. 47 F (8.3 C) DB / 43 F (6.1 C) WB. Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air Prevention Protection during heating operation into account. For this reason, the value may vary from the actual heating characteristics. 3. Above data represents the value when the operation frequency of a compressor is fixed. 3
33 6. ELECTRICAL DATA 61. Electrical Characteristics Indoor Unit CSKE1NB41 & CZ18BT1U Outdoor Unit CUKE1NK1 Cooling Performance at Rating conditions Running amp. A 0.1 Power input W 18 Rating conditions: Indoor air temperature: 80 F (6.7 C) DB / 67 F (19.4 C) WB Outdoor air temperature: 95 F (35 C) DB Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor + Compressor 115V Singlephase 60Hz , ,60 Heating Performance at Rating conditions Running amp. A 0.5 Power input W 0 Rating conditions: Indoor air temperature 70 F (1.1 C) DB Outdoor air temperature 47 F (8.3 C) DB / 43 F (6.1 C) WB Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor + Compressor 115V Singlephase 60Hz , ,460 33
34 Indoor Unit CZKE18NB4U & CZ18BT1U Outdoor Unit CUKE18NKU (1) Voltage:30V Cooling Indoor Unit Fan Motor Performance at Rating conditions Running amp. A 0.15 Power input W Outdoor Unit Fan Motor + Compressor 30V Singlephase 60Hz ,838 < 30V > Complete Unit 8.3 1,860 Rating conditions: Indoor air temperature: 80 F (6.7 C) DB / 67 F (19.4 C) WB Outdoor air temperature: 95 F (35 C) DB Heating Indoor Unit Fan Motor Performance at Rating conditions Running amp. Power input A W Rating conditions: Indoor air temperature 70 F (1.1 C) DB Outdoor air temperature 47 F (8.3 C) DB / 43 F (6.1 C) WB Outdoor Unit Fan Motor + Compressor 30V Singlephase 60Hz 10.31,313 Complete Unit 10.5,340 () Voltage:08V Cooling Indoor Unit Fan Motor Performance at Rating conditions Running amp. Power input A W 0.16 Rating conditions: Indoor air temperature: 80 F (6.7 C) DB / 67 F (19.4 C) WB Outdoor air temperature: 95 F (35 C) DB Outdoor Unit Fan Motor + Compressor 08V Singlephase 60Hz ,838 < 08V > Complete Unit 9.1 1,860 Heating Indoor Unit Fan Motor Performance at Rating conditions Running amp. Power input A W 0. 7 Rating conditions: Indoor air temperature 70 F (1.1 C) DB Outdoor air temperature 47 F (8.3 C) DB / 43 F (6.1 C) WB Outdoor Unit Fan Motor + Compressor 08V Singlephase 60Hz 11.3,313 Complete Unit 11.5,340 34
35 6. Electric Wiring Diagrams Indoor Unit CSKE1NB41 & CZ18BT1U CSKE18NB4UW & CZ18BT1U FLOAT SWITCH TO OUTDOOR UNIT GND 1 3 TERMINAL BASE FAN MOTOR FM DCM 6P (BLU) 6P (WHT) DRAIN PUMP DP DP 3P (BLU) 3P (RED) PWM/POW 7P (RED) PWM/POW 7P (RED) RC 4P (WHT) SERIAL P (WHT) SERIAL P (WHT) GRN BOX BOX IND LAMP ASSY FLAP (W) IND 7P (WHT) FLAP 5P (WHT) CONTROLLER CONTROLLER FS 3P (RED) ROOM P (YEL) COIL1 P (RED) 8FA RED BLK WHT YEL BLU YEL/(RED) YEL/(RED) FERRITE CORE AC1 AC SI BRN RED ORG YEL PNK BLU VLT BLK WHT RED GRN/YEL WHT BLK GRN BRN RED ORG YEL PNK BLU VLT BLK BLK RED WHT THERMISTOR ROOM COIL1 1 1 FLAP (R) BLK ORG BLU BRN WHT BLK ORG BLU BRN WHT BLK WHT BRN BLU ORG BLK BLK BLK BLK 35
36 Outdoor Unit CUKE1NK1 8FA
37 Outdoor Unit CUKE18NKU REACTANCE WHT PCONNECTOR (WHT) WHT 1 1 WHT WHT GRN GRN GRN 6 5 BLK POWER RELAY BLK 1 4 3PCONNECTOR (WHT) RED(PINK) RED(PINK) WHT WHT BLU BLU S R T CM w w w FERRITE CORE COMPRESSOR THERMISTOR COMPRESSOR MOTOR U V W * ELEC SYSTEM ASSY w w COMP ATH COIL/OUTDOOR BLK BLK L1 L E E1 BLK BLK OUT DOOR THERMISTOR OVERLOAD RELAY (OLR) YEL YEL COIL THERMISTOR CONTROLLER 7PCONNECTOR (WHT) DCFM WHT WHT BLK BLK RED BLU RED BLU YEL FM YEL FAN MOTOR WHT WHT 5A MV ORG RED GRY 1 1 w MV0 WHT YEL 5 5 w MAGNETIC COIL w ACIN1 w ACIN w SIA w RV0 RV1 w w BLK BLK 1 1 RED RED RV COIL 1 1 PCONNECTOR (RED) E PCONNECTOR(WHT) 4WAY VALVE BLK WHT RED WHT WHT WHT FERRITE CORE BLK WHT TERMINAL PLATE GND GND N L POWER SUPPLY TO INDOOR UNIT HIGH PRESSURE SWITCH 1 1 BLK BLK PCONNECTOR (BLK) 8FA
38 7. MAINTENANCE 71. Address Setting of the Remote Controller The address can be set in order to prevent interference between remote controllers when two indoor units are installed near each other. The address is normally set to "A." To set a different address, it is necessary to change the address on the second remote controller. NOTE Once changed, you cannot restore the original address setting of the air conditioner. Tab Fig. 1 (1) Switch on the power source. () Break the addresssetting tab marked "A" on the second remote controller to change the address (Fig. 1). When the tab is removed, the address is automatically set to B (Fig. ). (3) Press and hold the remote controller HIGH POWER button and 1 HR TIMER button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release HIGH POWER and 1 HR. TIMER buttons, "op1" (test run) appears, blinking in the remote controller clock display area. (4) Each time the 1 HR TIMER button is pressed, the display changes as shown below. Press this button times to change the display to "op7" (address setting). (Fig. 3) Test run mode Selfdiagnostic mode Address setting mode HIGH POWER button Fig. ON/OFF operation button 1HR. TIMER button ACL button (5) "op7" has now been selected for address setting. (6) Press the ON/OFF operation button on the remote controller. (Fig. 3) Check that the "beep" signal received sound is heard from the second indoor unit (approximately 5 times). The sound you hear is the signal that the remote controller address has been changed. (7) Finally press the remote controller ACL (reset) button to cancel the blinking "op7" display. (Fig. 3) Changing of the second remote controller address is now completed. 38 Fig. 3 ACL (Reset) button
39 7. Disconnecting and Connecting Positive Connector for Outdoor Unit One of the two types of connectors illustrated at left is used. Their basic structure is the same for each. How to Disconnect Pull the cover upward Hold the resin connector cover, and pull the connector off. You cannot disconnect the connector by pulling the wire since it is locked inside. Always hold the cover to disconnect. (See illustration at left.) For the connector without the resin cover, push the lock in the direction of "" while pulling it off. How to Connect In order to connect, hold the resin cover of the connector and push it in. Confirm the click sound for the inside lock. When the cover is pulled upward, the lock is released with the sequence of 1 and. 39
40 73. Disassembly Procedure WARNING To avoid electrical shock hazard, be sure to disconnect power before attempting to disassemble the unit. When a footstool, etc. is used for disassembling the indoor unit, be careful not to fall down. If you fall down, you might be injured seriously Remove the air intake grill. (1) Slide the latches each to the corresponding arrow direction. (Fig. 1 and Fig. ) Open downward the air intake grill located on the latch side. () Undo the air intake grill drop preventive hook. (Fig. 3) Undo the hinges for the grill and remove the air intake grill. Latch Hinge Latch Hook Air intake grill Hinge Fig.1 Fig. Fig Disconnect the connectors in the control box. (1) Remove the screws and remove the control box cover. (Fig. 4) () Disconnect the connectors CN04 (FLAP 5P), CN1 (RC 4P) and CN13 (IND 7P). (Fig. 5) CN04 Control PCboard CN13 CN1 Screw Control box cover Fig.4 Fig.5 40
41 733. Remove the ceiling panel. (1) Open the clamp (4 locations) and remove the lead wires from the clamps. (Fig. 6) () Remove the 4 screws fixing the corner cover (at 3 locations) and indicator cover (at 1 location). (Fig. 6) (3) Press the center 1 of the cover and remove the cover with the section pulled down. (Fig. 7) (4) Remove the strap (3 locations) from the hook on the ceiling panel. (Fig. 8) NOTE There is no strap on the indicator cover. (5) Remove the bolt (4 locations) with a washer and remove the ceiling panel. (Fig. 9) Indicator cover Screw Clamp Corner cover Lead wire Pull down section. Cover Clamp Center 1 Corner cover Screw Fig.6 Corner cover Fig.7 Bolt Strap Remove the strap from the hook. Bolt Fig.8 Fig.9 41
42 734. Remove the indoor air temperature sensor. (1) Disconnect the connector CN08 (ROOM P) in the control box and remove the indoor air temperature sensor. (Fig. 10) Indoor air temperature sensor CN08 Fig Remove the power box and control box. (1) Remove a screw and remove the terminal cover. (Fig. 11) () Remove the screws and remove the power box cover. (Fig. 11) (3) Disconnect the power lines (No. 1 and No. ) / signal line (No. 3) and ground cable from the terminals in the power box. (Fig. 1) Terminal cover Screw Screw Power box cover Fig.11 Terminal 1 3 Ground cable Power lines / Signal line Fig.1 4
43 (4) Disconnect the connector CN07 (DP P) in the power box. (Fig. 13) Remove a screw and disconnect the ground cable. (Fig. 13) (5) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 14) (6) Remove the 4 screws and remove the power box. (Fig. 14) (7) Disconnect the connectors CN06 (FS 3P) and CN09 (COIL1 P) in the control box. (Fig. 15) (8) Remove the screws and remove the control box. (Fig. 15) Screw Ground cable 1 3 Fig.13 CN07 Screw Screw Screw Fig.14 CN03 Screw CN09 Screw Screw Fig.15 CN06 43
44 NOTE For the removal of the following components, perform any work after removing the indoor unit (main body) from the ceiling. Main body lower section Heat exchanger sensor Drain pump Float switch Turbo fan Fan motor Heat exchanger 1. Perform the work after draining the water to prevent the water leakage from the drain pan. Put a bucket, etc., under the drain cap and remove the drain cap to drain the water. (Fig. 16). Refer to the installation instructions for recovery of refrigerant or removal of the power cable or tubing Remove the main body lower section. (1) Remove the 4 screws. (Fig. 16) () Remove the screws. (Fig. 17) (3) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 18) (4) Lift the main body lower section and remove it from the main body upper section. Screw Screw Drain cap Main body lower section Main body lower section Screw Screw Fig.16 Main body lower section Main body upper section Screw CN03 Fig.17 Fig.18 44
45 737. Remove the heat exchanger sensor. (1) Remove the heat exchanger sensor from the sensor holder. (Fig. 19) Heat exchanger sensor Holder Fig Remove the drain pump and float switch. (1) Remove the screws (Fig. 0) () Loosen the clamp and disconnect the drain hose from the drain pump. (Fig. 0) (3) Remove the drain pump from the main body upper section. (Fig. 0) (4) Remove a nut and remove the float switch. (Fig. 1) Drain pump Screw Float switch Nut Drain hose Clamp Fig.0 Fig.1 45
46 739. Remove the turbo fan and fan motor. (1) Remove a nut and remove the turbo fan. (Fig. ) () Remove the screws and 3 nuts, and remove the fan motor. (Fig. 3) Turbo fan Nut Screw Nut Fan motor Fig. Fig Remove the heat exchanger. (1) Remove the 3 screws. (Fig. 4) () Remove the 3 screws. (Fig. 5) (3) Remove the heat exchanger from the main body upper section with the heat exchanger lifted. Heat exchanger Screw Screw Main body upper section Screw Fig.4 Fig.5 46
47 8. FUNCTIONS 81. Operation Functions Emergency operation Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used. To operate the system, press the OPERATION button, which is also used as the receiver, below the unit display. Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation. COOL HEAT STOP (GREEN) (RED) (Lamp Off) The set temperature is 4 F( C) below the detected room temperature in the case of cooling operation, and 4 F( C) above the room temperature in the case of heating operation. The flap and fan speed settings are AUTO. AUTO cooling/heating operation Selecting the operation mode When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to Cooling or Heating mode. Room temp. Set temp. COOL Room temp. Set temp. HEAT As shown by the example in the figure below, with AUTO cooling/heating operation, the mode changes between Heating and Cooling mode according to changes in the relationship between the current room temperature and the set temperature. Example Example of operation in AUTO mode with the set room temperature at 74 F(3 C). Room temp. Set temp. 74 Zone A Zone B Zone C Zone C SENSOR DRY During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment. SENSOR DRY operation DRY operation is as shown in the figure below. Load DRY A The compressor operation frequency varies. The indoor fan operates with 1/f fluctuation. DRY B The compressor operates at a low operating frequency. The indoor fan operates with 1/f fluctuation. Monitor Conditions are monitored at all times when the room temperature is below 59 F(15 C). Monitoring operation takes place when the room temperature is below 59 F(15 C), or more than 5 F(3 C) below the set temperature. When the monitoring range is entered, the compressor stops, and the indoor fan operates with 1/f fluctuation. PAM COOL zone A zone B zone control In order to further improve inverter performance, control is switched between PWM control at low operation speeds, and PAM control at high operation speeds, making the most effective use of power. Zone B Zone A More than 1 hour Within 1 hour Compressor ON OFF ON OFF ON Operation mode Cooling Heating Cooling 47
48 HIGH POWER This function acts to raise the power but keeps the AC system in the same operating mode. This function is set with the HIGH POWER button on the remote controller. (It can be set regardless of the temperature and fan speed settings.) HIGH POWER operation from remote controller The unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above "High." Frequency MAX NIGHT SETBACK When NIGHT SETBACK operation is set, the temperature and fan speed settings will be adjusted automatically to allow comfortable sleep. When NIGHT SETBACK operation is set, " mark" appears on the remote controller. The main unit display lamp also becomes dimmer. COOL and DRY modes When the night setback mode is selected, the air conditioner automatically raises the temperature setting F(1 C) when 30 minutes have passed after the selection was made, and then another F(1 C) after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed min. 5 min. Time Setting temperature F(1 C) F(1 C) NOTE When HIGH POWER operation ends, the unit operates at low Hz for 5 minutes, regardless of the thermostat OFF conditions. When in DRY mode, operation is in the cooling zone. Lamp colors OPERATION lamp OPERATION lamp TIMER lamp HIGH POWER lamp Start HEAT operation DRY operation COOL operation FAN operation DEFROSTING operation End Red Orange Green Green Red and Orange alternately Green Green Green Press the NIGHT SETBACK button 30 min. 30 min. Time HEAT mode When the night setback mode is selected, the air conditioner automatically lowers the temperature setting 4 F( C) when 30 minutes have passed after the selection was made, and then another 4 F( C) after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle heating is needed. Setting temperature Press the NIGHT SETBACK button 4 F( C) 4 F( C) 30 min. 30 min. Time Timer backup Operation stops if there are no operator controls for 5 hours or longer after unit operation switched from OFF to ON by use of ON timer operation. 48
49 8. Protective Functions Overload prevention during heating During HEAT operation, the temperature of the indoor heat exchanger is used to control the frequency and lessen the load on the compressor before the protective device is activated. Indoor heat exchanger temperature F( C) Approx. 17 (53) a. Area: Automatic capacity control b. When Point A has been exceeded, the operation frequency is reduced by a certain proportion. c. Area: Frequency increase is prohibited. d. At Point B and below, overload prevention is ended and control is the same as in the a area. Freeze prevention During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below. 1. Freezeprevention operation is engaged when the temperature of the indoor heat exchanger is below 43 F(6 C).. Restart after freezeprevention operation occurs when the temperature of the indoor heat exchanger reaches 46 F(8 C) or above. Indoor heat exchanger temperature F( C) Approx. 117 (47) 46 (8) 43 (6) 36 () * A A Indoor heat exchanger A. Control start B. Control end a b c d a b c d a. Area: Automatic capacity control b. When the temperature drops below Point A, the operation frequency is reduced by a certain proportion. c. Area: Frequency increase is prohibited. d. When the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the a area. * When the temperature drops to below 36 F( C) (continuously for minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off. B B C Coldair prevention during heating During heating, the fan speed is set to "LL" (very low) or stopped. As the temperature of the indoor heat exchanger rises, the fan speed is changed to the set speed. High LL Stopped NOTE At stability of operation 77 (5) 86 (30) Indoor heat exchanger temperature F( C) Set fan speed At start of operation Approx. 104 (40) The fan speed is forcibly changed to "LL" beginning 30 seconds after the thermostat turns OFF. At stability of operation refers to operation when the room temperature has approached the set temperature. When HEAT operation starts, the indoor fan is stopped until the temperature of the indoor heat exchanger reaches 68 F(0 C) or higher, or until the room temperature reaches 59 F(15 C) or higher. Compressor discharge temperature control This function controls the operation frequency to prevent the compressor discharge temperature from rising more than a specified temperature. Compressor discharge temperature F( C) Approx. 14 (101) Approx. 01 (94) A a b c d a. Area: Automatic capacity control. b. When the temperature rises above Point A, the operation frequency is reduced at a specified rate. c. Area: Further frequency increase is prohibited. d. When the temperature falls below Point B, prevention of a rise in frequency is released and the air conditioner operates as in a area. B * The compressor will stop if the temperature of the compressor discharge exceeds 48 F(10 C) due to shortage of gas or other reason. 49
50 Defrost detection and release ReverseCycle Defrosting Outdoor fan ON 4way valve ON Defrosting Sequence Heating operation Frost sensing Defrost detection occurs in either of the following cases: The temperature of the heat exchanger remains at or below the L1 line for 3 minutes after the start of HEAT operation. The temperature of the heat exchanger remains at or below the L line for 10 minutes after the start of HEAT operation. Outdoor heat exchanger temp. 0 Ambient temp. CT (Peak current cutoff control) This function prevents the circuit breaker or fuse from operating to open the circuit. This function works when electrical current has increased due to an increase in the cooling / heating load, or to a decrease in the power supply voltage. In these cases, operation frequency is reduced or operation is interrupted automatically to control the electrical current for operation. When the cause of the increase in electrical current is rectified, the system will resume operation in the original mode. <CSKE1NB41> (A) Cooling Dry Heating Peak current cutoff trips.5 Hz down <CSKE18NB4UW> Cooling Dry Heating Peak current cutoff trips 17.5 Hz down NOTE Electrical current setting for COOL operation is used during DEFROST operation. (A) L L1 Frosting area Reversecycle defrosting operation Compressor 1 minute after it is stopped, compressor is ON. Outdoor fan OFF Indoor fan OFF 4way valve OFF Operation lamp Repeatedly switches between red and orange illumination. Releasing of defrosting Outdoor heating exchanger temp. is over 68 F(0 C). Defrosting operation lasts 1 minutes (maximum). minutes after it is stopped, compressor is ON. 4way valve is ON. Outdoor fan is ON. NOTE If the air conditioner is turned off during the defrosting cycle, it will continue defrosting and turn itself off after defrosting is completed. 50
51 9. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 91. Precautions before Performing Inspection or Repair After checking the selfdiagnostics monitor, turn the power OFF before starting inspection or repair. Highcapacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF. If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller. 9. Method of SelfDiagnostics Follow the procedure below to perform detailed trouble diagnostics. NOTE < Clock display > Test run mode Selfdiagnostics mode 1: If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board, or a ROM socket insertion problem, or the ROM has not been installed. : The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics. PROCEDURE After turning on power to the air conditioner, use the remote controller and follow the steps below to execute selfdiagnostics. Step 1: Press and hold the remote controller HIGH POWER button and 1 HR TIMER button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release HIGH POWER and 1 HR TIMER buttons, "op1" (test run) appears, blinking in the remote controller clock display area. Step : Next, press the 1 HR TIMER button once to change the display from "op1" to "op3" (selfdiagnostics). (The display continues to blink.) Step 3: Finally press the ON/OFF button to engage selfdiagnostics mode. The selfdiagnostics function utilizes the 3 indicator lamps on the main unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to report the existence of sensor trouble or a protective operation. (The lamps blink or remain ON for 5 seconds, then turn OFF for seconds.) Selfdiagnostics is completed when the buzzer sounds 3 short beeps. A maximum of 3 selfdiagnostics reports are displayed, for 5 seconds each, beginning with the most recent report. Following this display the lamps turn OFF. In order to view the selfdiagnostics results again, press the ON/OFF button again. The 3 lamps remain OFF if no trouble has occurred. <IMPORTANT> After selfdiagnostics is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate if this is not done. HIGH POWER button ON/OFF operation button 1HR. TIMER button ACL (Reset) button 51
52 (1) Selfdiagnostics Lamps INDOOR UNIT OPERATION button OPERATION lamp TIMER lamp HIGH POWER lamp REMOTE CONTROL receiver Since the indications cover various units, the corresponding parts listed below may not be present in some models. INDICATION ON INDOOR UNIT... OFF... BLINKING... ON OPERATION TIMER HIGH POWER CODE DIAGNOSIS CONTENTS POSSIBLE MALFUNCTION S01 S0 S04 S05 S06 ROOM TEMP. SENSOR TROUBLE I/D HEAT EXCHANGER TEMP. SENSOR TROUBLE COMPRESSOR TEMP. SENSOR TROUBLE O/D HEAT EXCHANGER TEMP. SENSOR TROUBLE O/D AIR TEMP. SENSOR TROUBLE (1) OPEN OR SHORT CIRCUIT IN SENSOR () POOR CONTACT AT CONNECTOR OR OPEN CIRCUIT AT TERMINAL PRESSFIT LOCATION. (3) I/D PCB FAILURE (I/D = INDOOR) (1) OPEN OR SHORT CIRCUIT IN SENSOR () POOR CONTACT AT CONNECTOR OR OPEN CIRCUIT AT TERMINAL PRESSFIT LOCATION (3) O/D PCB FAILURE (O/D = OUTDOOR) S07 O/D CURRENT SENSOR ERROR O/D PCB FAILURE E01 E0 E03 E04 E05 E06 E07 E08 I/DO/D COMMUNICATION TROUBLE (SERIAL COMMUNICATION TROUBLE) HIC CIRCUIT TROUBLE POWER TR CIRCUIT TROUBLE O/D UNIT EXTERNAL ROM (1) EXTERNAL ROM DATA FAILURE () O/D PCB FAILURE TROUBLE (1) INSTANTANEOUS POWER STOPPAGE () HIC OR POWER TR FAILURE CURRENT PEAK CUT (3) O/D PCB FAILURE PAM CIRCUIT TROUBLE ACTIVE CIRCUIT TROUBLE COMPRESSOR DISCHARGE TEMP. OVERHEATING PREVENTION I/D FAN OPERATION TROUBLE 4WAY VALVE SWITCHING TROUBLE ZEROCROSS TROUBLE (1) MISWIRING () AC POWER FAILURE (3) BLOWN FUSE (4) POWER RELAY FAILURE (5) I/D OR O/D PCB FAILURE (6) O/D FAN MOTOR FAILURE (7) REACTOR FAILURE (8) HIGHPRESSURE SW FAILURE (9) OLR FAILURE (10) MAGNETIC COIL FAILURE (1) HIC OR POWER TR FAILURE () O/D FAN NOT OPERATING (3) INSTANTANEOUS POWER STOPPAGE (4) SERVICE VALVE NOT OPENED (5) O/D FAN BLOCKED (6) CONTINUOUS OVERLOAD OPERATION (7) COMPRESSOR FAILURE (8) O/D PCB FAILURE (1) O/D PCB FAILURE () O/D POWER VOLTAGE TROUBLE (1) ELECTRIC EXPANSION VALVE FAILURE () CHOKED CAPILLARY TUBE (3) INSUFFICIENT GAS (4) CONTINUOUS OVERLOAD OPERATION (5) O/D FAN NOT OPERATING (6) O/D PCB FAILURE (1) FAN MOTOR FAILURE () CONNECTOR CONTACT FAILURE (3) I/D PCB FAILURE (1) 4WAY VALVE FAILURE (HEAT PUMP MODEL ONLY) () O/D PCB FAILURE E09 E10 E11 E1 GASLOSS PREVENTION DC COMPRESSOR DRIVE CIRCUIT TROUBLE O/D DC FAN OPERATION TROUBLE O/D SYSTEM COMM FAILURE, OLR OPERATION, O/D POWER OPEN PHASE, O/D FREEZING (1) SERVICE VALVE NOT OPENED () INSUFFICIENT GAS (1) OPEN PHASE () O/D PCB FAILURE (1) FAN MOTOR FAILURE () CONNECTOR CONTACT FAILURE (3) O/D PCB FAILURE (1) MISWIRING () BLOWN FUSE (3) POWER RELAY FAILURE (4) O/D PCB FAILURE (5) COMPRESSOR FAILURE E13 FREEZINGPREVENTION OPERATION (1) I/D FAN SYSTEM TROUBLE () INSUFFICIENT GAS (3) OPERATION AT LOW TEMPERATURE TIMER LAMP BLINKING (3 SEC. INTERVAL) FLOAT SWICTH (FS) IS ACTIVED. (1) DRAIN PUMP FAILURE () FS FAILURE (3) CHOKED DRAIN HOSE
53 () If the selfdiagnostics function fails to operate Check the indoor unit. Is the fuse blown? Normal Replace the controller. No indicators illuminate and the indoor fan does not rotate. Check the power voltage. Blown Replace the circuit board or the fuse. 93. Checking the Indoor and Outdoor Units (1) Checking the indoor unit No. Control () Checking the outdoor unit Check items (unit operation) 1 Use the remote controller to operate the unit in "TEST run" mode. To determine whether the mode is currently in "TEST run" mode, check the 3 indicator lamps on the unit. If all 3 are blinking, the current mode is "TEST run." The rated voltage must be present between interunit wirings 1 and. Connect a 5 k ohm resistor between interunit wirings and 3. When the voltage at both ends is measured, approximately 1 to 15V DC must be output and the multimeter pointer must bounce once every 8 seconds. Or instead of measuring the voltage, you can insert an LED jig and check that the LED flickers once every 8 seconds. No. If there are no problems with the above, then check the outdoor unit. For the "Test run" procedure, refer to the Appendix B "Installation Instructions". Control Check items (unit operation) 1 Apply the rated voltage between outdoor The control panel LED (red) must illuminate. unit terminals L and N. Shortcircuit the outdoor unit COM terminal The compressor, fan motor and 4way valve must all turn on. to the TRUN terminal. If there are no problems with the above, then check the indoor unit. Using the TEST/TRUN terminals TRUN : Test run (compressor and fan motor turn ON). TEST/MV : Compresses time to 1/60th (accelerates operation by 60 times faster than normal). TEST/TRUN terminals (TEST)/MV TRUN COM 53
54 (3) Serial Communication Error Identification Procedure If the lamps on the main body show the following conditions after the completion of selfdiagnostics, a communication error between the indoor unit and outdoor unit might be considered. In such a case, identify the breakdown section by using the following procedure. NOTE Refer to "Method of SelfDiagnostics" for the selfdiagnostics procedure. Lamp Operation Timer High Power : Off Condition E01 : Blinking : Illuminated E1 < Before the Operation > For terminal strip short circuit work or interunit wiring removal, turn off the power to WARNING avoid an electric shock. Release the terminal strip short circuit after the completion of selfdiagnostics. CAUTION Do not perform the shortcircuit work between any other terminals except for specified ones on the specified terminal strip. If such work is performed between the incorrect terminals, the unit might be broken. < Convenient Tool for ShortCircuit Work ( for example ) > Alligator Clip Cable Alligator Clip < Check Items before Troubleshooting Serial Communication Start > After confirming that the following errors do not exist, start the "Troubleshooting Serial Communication" in "Condition: E01 and E1". 1. Mis wiring (interunit cable, etc.). AC power failure 3. Blown fuse 4. Power Relay failure 5. Outdoor Fan Motor failure (defective insulation, etc.) 6. Reactor failure (defective insulation, etc.) 7. HighPressure Switch failure 8. Overload Relay failure 9. Magnetic Coil failure (defective insulation, shortcircuit, etc.) 10. Compressor failure (defective insulation, etc.) (31) Condition: E01 Troubleshooting Serial Communication V + Outdoor Unit Power Outdoor Unit Power 1 3 Indoor Unit Fig. 1 Indoor Unit V + Fig. Is the voltage of about DC1V or more given between the terminals and 3 on the outdoor unit terminal strip (Serial Communication Line)? (Fig. 1) No 1. Turn OFF the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.. Disconnect the cable from the terminal 3 on the indoor unit terminal strip. (Fig. ) 3. Turn ON the power. Yes A ( Continued to the next page A. ) B ( Continued to the next page B. ) 54
55 ( Continued from the previous page A. ) A ( Continued from the previous page B. ) B Yes Is the voltage of about DCV to 4V given between the terminals and 3 on the indoor unit terminal strip (Serial Communication Line)? (Fig. ) No Defect or connection error in the interunit cable Defect in the indoor unit P.C. board 1. Turn OFF the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.. Shortcircuit between the terminals and 3 on the outdoor unit terminal strip. (Fig. 3) 1. Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.. Perform the selfdiagnosis five seconds after the operation start. Outdoor Unit Indoor Unit Fig. 3 Power What is the latest selfdiagnosis result? Condition: E1 Defect in the outdoor unit P.C. board. Condition: E01 1. Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.. Remove the shortcircuit between the terminals and 3 on the outdoor unit terminal strip. 3. Disconnect the cable from the terminal 3 on the indoor unit terminal strip. (Fig. 4) Shortcircuit between the terminals and 3 on the indoor unit terminal board. (Fig. 5) Indoor Unit Fig. 4 Outdoor Unit Power Indoor Unit Fig. 5 Outdoor Unit Power 1. Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.. Perform the selfdiagnosis five seconds after the operation start. What is the latest selfdiagnosis result? Condition: E1 Defect or connection error in the interunit cable Condition: E01 Defect in the indoor unit P.C. board 55
56 (3) Condition: E1 Troubleshooting Serial Communication Outdoor Unit Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.. Disconnect the cable from the terminal 3 on the Outdoor unit terminal strip. (Fig. 6) 1. Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.. Perform the selfdiagnosis five seconds after the operation start. 1 3 Indoor Unit Fig. 6 Power What is the latest selfdiagnosis result? Condition: E01 Defect in the outdoor unit P.C. board Condition: E1 1. Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.. Disconnect the cable from the terminal 3 on the indoor unit terminal strip. (Fig. 7) 1. Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.. Perform the selfdiagnosis five seconds after the operation start Indoor Unit Fig. 7 Outdoor Unit Power What is the latest selfdiagnosis result? Condition: E01 Defect in the interunit cable Condition: E1 Defect in the indoor unit P.C. board 56
57 94. Trouble Diagnosis of Fan Motor 941. Indoor Fan Motor This indoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. To perform diagnosis, operate the unit in cooling mode with indoor fan speed "High". Next, make sure that the indoor unit receive the signals from the remote controller when the ON/OFF operation button is pressed. Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors. (B) When performing voltage measurement at the indoor controller connector for (3) in the table below, the DC motor will trip and voltage output will stop approximately 1 minute after operation is started. For this reason, to measure the voltage again, turn OFF the unit once using the remote controller, and then start the air conditioner again. [Trouble symptom 1] The fan does not stop when the unit stops. Indoor unit controller trouble. [Trouble symptom ] The fan motor does not rotate when the unit is operating. (Diagnostic procedure) * Disconnect the motor connectors and measure the voltage at the DC motor connectors on the indoor unit controller (3 locations). Measurement location (1) VmGnd: Between pin 1 and pin 3 () VccGnd: Between pin 4 and pin 3 (3) VsGnd: Between pin 5 and pin 3 Normal value CSKE1NB41 CSKE18NB4UW DC 130V to 195V DC 80V to 340V DC 15V +/ 10% Fluctuation between DC 1.8V to 5.7V (Diagnostic results) All of the above measured values are normal. Fan motor trouble (Replace the motor.) Any one of the above measured values is not normal. Indoor unit controller trouble (Replace the controller.) (Reference) DC motor connector pin arrangement Pin 1: Vm (red) Pin : Not used Pin 3: Gnd (black) Pin 4: Vcc (white) Pin 5: Vs (yellow) Pin 6: PG (blue) [Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the indoor unit operates. (There is trouble in the system that provides feedback of motor rotation speed from the motor to the indoor unit controller.) [Trouble symptom 4] Fan motor rotation speed does not change during indoor unit operation. [Trouble symptom 5] Fan motor rotation speed varies excessively during indoor unit operation. (Remedy for symptom 3 to 5) It is not possible to identify whether the trouble is indoor unit controller trouble or motor trouble. Therefore, first replace the indoor unit controller, then (if necessary) replace the DC motor. 57
58 94. Outdoor Fan Motor This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. Perform the trouble diagnosis by Test Run mode described on Installation Instructions. Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors. (B) When performing voltage measurement at the outdoor controller connector for (3) in the table below, the DC motor will trip and voltage output will stop approximately 10 seconds after operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor unit power, then, measure the voltage in Test Run mode. [Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble [Trouble symptom ] The fan motor does not rotate when the outdoor unit is operating. (Diagnostic procedure) * Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor unit controller (3 locations). Measurement location (1) VsGnd: Between pin 1 and pin 4 () VccGnd: Between pin 5 and pin 4 (3) VspGnd: Between pin 7 and pin 4 Normal value DC 110V or more DC 14V or more After fluctuating 4 times between DC 1.0 to 4.3V (1 sec. ON) and DC 0 V (1 sec. OFF), the DC motor trips. (Diagnostic results) All of the above measured values are normal. Fan motor trouble (Replace the motor.) Any one of the above measured values is not normal. Outdoor unit controller trouble (Replace the controller.) (Reference) DC motor connector pin arrangement Pin 1: Vs (white) Pin : Not used Pin 3: Not used Pin 4: Gnd (black) Pin 5: Vcc (red) Pin 6: FG (blue) Pin 7: Vsp (yellow) [Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor unit operates. (There is trouble in the system that provides feedback of motor rotation speed from the motor to the outdoor unit controller.) [Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation. [Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation. (Remedy for symptom 3 to 5) It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble. Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor. 58
59 95. Noise Malfunction and Electromagnetic Interference An inverter A/C operates using pulse signal control and high frequencies. Therefore, it is susceptible to the effects of external noise, and is likely to cause electromagnetic interference with nearby wireless devices. A noise filter is installed for ordinary use, preventing these problems. However, depending on the installation conditions, these effects may still occur. Please pay attention to the points listed below. (1) Noise malfunction This refers to the application of highfrequency noise to the signal wires, resulting in abnormal signal pulses and malfunction. Locations most susceptible to noise 1. Locations near broadcast stations where there are strong electromagnetic waves. Locations near amateur radio (short wave) stations 3. Locations near electronic sewing machines and arcwelding machines Trouble Either of the following trouble may occur. 1. The unit may stop suddenly during operation.. Indicator lamps may flicker. Correction (The fundamental concept is to make the system less susceptible to noise.) Insulate for noise or distance from the noise source. 1. Use shielded wires.. Move unit away from the noise source. () Electromagnetic interference This refers to noise generated by highspeed switching of the microcomputer and compressor. This noise radiates through space and returns to the electric wiring, affecting any wireless devices (televisions, radios, etc.) located nearby. Locations most susceptible to noise 1. A television or radio is located near the A/C and A/C wiring.. The antenna cable for a television or radio is located close to the A/C and A/C wiring. 3. Locations where television and radio signals are weak. Trouble 1. Noise appears in the television picture, or the picture is distorted.. Static occurs in the radio sound. Correction 1. Select a separate power source.. Keep the A/C and A/C wiring at least 1 meter away from wireless devices and antenna cables. 3. Change the wireless device's antenna to a highsensitivity antenna. 4. Change the antenna cable to a BS coaxial cable. 5. Use a noise filter (for the wireless device). 6. Use a signal booster. 59
60 10. CHECKING ELECTRICAL COMPONENTS 101. Measurement of Insulation Resistance The insulation is in good condition if the resistance exceeds 1M ohm. Clip Ground wire Power Supply Cord Clamp the grounding wire of power cord with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the two power wires. (Fig. 1) Then also measure the resistance between the grounding and other power terminals. (Fig. 1) 101. Indoor Unit Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate. (Fig. ) Note that the ground line terminal should be skipped for the check Outdoor Unit Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate. (Fig. ) Probe Copper tube or metallic part Clip Fig. 1 Terminal plate Fig. Insulation tester Insulation tester Probe Probe Measurement of Insulation Resistance for Electrical Parts Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 3 and 4) NOTE Refer to Electric Wiring Diagram. If the probe cannot enter the poles because the hole is too narrow then use a probe with a thinner pin. Clip Copper tube or metallic part Metallic part Insulation tester Fig. 3 Probe From fan motor, compressor and other parts Clip Fig. 4 Insulation tester 60
61 10. Checking Continuity of Fuse on PCB Ass'y Fuse Remove the PCB Ass'y from the electrical component box. Then pull out the fuse from the PCB Ass'y. (Fig. 5) Check for continuity using a multimeter as shown in Fig. 6. PCB Ass'y Fig. 5 Fuse Fig. 6 61
62 11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 111. Characteristics of New Refrigerant R410A What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudononazeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R Components (mixing proportions) HFC3 (50%) / HFC15 (50%) Characteristics Less toxic, more chemically stable refrigerant The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase). When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state. Thus, always charge the refrigerant while it is in liquid phase. CAUTION Ethertype oil is used for compressor oil for R410Atype units, which is different from the mineral oil used for R. Thus more attention to moisture prevention and faster replacement work compared with conventional models are required. 6
63 11. Checklist before Servicing Use a clutchtype flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of extrusion) by using the flare spacer. Diameter of tube D Dia.1/4" (6.35 mm) Dia.3/8" (9.5 mm) Dia.1/" (1.7 mm) Dia.5/8" (15.88 mm) Specification A Flare tool for R410A Conventional flare tool (for R) 0 to " 0.047" (0 to 0.5 mm) (1. mm) Size of flare D D Spacer A A Flare tool for R410A Conventional flare tool (R) Tubing precautions Refrigerant R410A is more easily affected by dust or moisture compared with R, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation. Never use 0.076" (0.7 mm)thick copper tubing or tubing which is less than " (0.8 mm) in thickness, since air conditioners with R410A are subject to higher pressure than those using R and R407C. No addition of compressor oil for R410A No additional charge of compressor oil is permitted. No use of refrigerant other than R410A Never use a refrigerant other than R410A. If refrigerant R410A is exposed to fire Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure to provide ample ventilation during installation work. Caution in case of R410A leak Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, immediately provide thorough ventilation. 63
64 113. Tools Specifically for R410A For servicing, use the following tools for R410A Tool Distinction Tools specifically for R410A Tools which can be commonly used for R, R407C, and R410A Tool Name Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with antireverse flow (*1) (Solenoid valveinstalled type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*)...can be used if the following adapter is attached. Vacuum pump adapter (reverseflow prevention adapter) (*3). (Solenoid valveinstalled adapter attached to a conventional vacuum pump.) Electronic scale for charging refrigerant Flare tool Bender Torque wrench Cutter, reamer Welding tool, nitrogen gas cylinder CAUTION The above tools specifically for R410A must not be used for R and R407C. Doing so will cause malfunction of the unit. For the above vacuum pump (*1, *) and vacuum pump adapter (*3), those for Rtype units can be used for R410Atype. However, they must be used exclusively for R410A and never alternately with R and R407C. To prevent other refrigerants (R, R407C) from being mistakenly charged to this unit, shape and external diameter of the service port screw has been altered. <External diameter of service port> R410A : 5/16" R, R407C : 1/4" 114. Tubing Installation Procedures When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing. The following is the HAB oil generally used: Esso: ZERICE S3 NOTE For details on tubing installation procedures, refer to the installation manuals attached to the indoor unit and outdoor unit. 64
65 115. In Case of Compressor Malfunction CAUTION Should the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "113. Tools Specifically for R410A." Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R410A. Do not reuse the recovered refrigerant, since it will contain impurities. () Replacing Compressor Soon after removing seals of both discharge and suction tubes of the new compressor, replace it quickly. (3) Checking for sealing Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas. (4) Evacuation Use a solenoid valveinstalled vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back. The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly. When using a vacuum pump with exhaust air volume more than cu.ft./min. and ultimate vacuum pressure rate of 50 micron Hg. (1) Recover refrigerant OK () Replace compressor OK (3) Check for sealing OK (4) Evacuation OK (5) Recharge Standard time for evacuation Length of tubing Evacuation time Less than 33 ft. (10 m) More than 10 minutes More than 33 ft. (10 m) More than 15 minutes 65
66 (5) Recharging Be sure to charge the specified amount of refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate. When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation. CAUTION Never charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor. When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 0% of the fullycharged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if the amount in the charging cylinder is less than 0%. Also, charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit. Configuration and characteristics of cylinders Liquid Valve Single valve Charge liquid refrigerant with cylinder in upsidedown position. Fig. 1 Valve Example: In case of charging refrigerant to a unit requiring 1.68 lb. (0.76 Kg) using a capacity of a lb. (10 Kg) cylinder, the minimum necessary amount for the cylinder is: = 6.08 lb. ( =.76 Kg) For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer. If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder. Prepare an evacuated charging cylinder beforehand. Charging cylinder Liquid Single valve (with siphon tube) Charge with cylinder in normal position. Fig. NO! CAUTION To prevent the composition of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant. (Fig. 3) Open Liquid Refrigerant cylinder Do not use the refrigerant if the amount in the charging cylinder is less than 0%. Fig. 3 66
67 116. In Case Refrigerant is Leaking CAUTION Never attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points. () Recovering refrigerant Never release the gas to the atmosphere; recover residual refrigerant using the refrigerant recovery unit for R410A, instead. Do not reuse the recovered refrigerant because its composition will have been altered. (3) Welding leaking points Confirm again that no residual refrigerant exists in the unit before starting welding. Weld securely using flux and wax for R410A. Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen (N) in the refrigerant circuit of the unit. Leave ends of tubes open during welding. (4) Checking for sealing Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas. (1) Detect leaks OK () Recover refrigerant OK (3) Weld leaking points OK (4) Check for sealing OK (5) Evacuation Use a solenoid valveinstalled vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back. The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly. When using a vacuum pump with exhaust air volume more than cu.ft./min. and ultimate vacuum pressure rate of 50 micron Hg. Standard time for evacuation (5) Evacuation (6) Recharge OK Length of tubing Evacuation time Less than 33 ft. (10 m) More than 10 minutes More than 33 ft. (10 m) More than 15 minutes (6) Recharging Recharge unit in the same manner explained on the previous page "(5) Recharging." 67
68 117. Charging Additional Refrigerant When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. CAUTION Never charge additional refrigerant if refrigerant is leaking from the unit. Follow instructions given in "116. In Case Refrigerant is Leaking" and completely carry out repairs. Only then should you recharge the refrigerant RetroFitting Existing Systems Use of Existing Units Never use new refrigerant R410A for existing units which use R. This will cause the air conditioner to operate improperly and may result in a hazardous condition Use of Existing Tubing If replacing an older unit that used refrigerant R with a R410A unit, do not use its existing tubing. Instead, completely new tubing must be used. 68
69
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKS1NB41 & CZ18BT1U + CUKS1NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU
TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.
TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EHDS + SAP-CRV96EHDS SAP-KRV126EHDS + SAP-CRV126EHDS FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EHDS
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL SAP-KRV9AEH + SAP-CRV9AEH SAP-KRV12AEH + SAP-CRV12AEH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV9AEH SAP-KRV12AEH Product
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV93EH + SAP-CRV93EH SAP-KRV123EH + SAP-CRV123EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No.
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EH + SAP-CRV96EH SAP-KRV126EH + SAP-CRV126EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EH SAP-KRV126EH
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
Appendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH SAP-CMRV9EH SAP-CMRV9EH SAP-CMRVEH SAP-CMRVEH FILE NO. Destination: Europe Northern Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.6k.6k
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2
SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-
Air Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor
SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT
SiUS041111. Service Manual. Inverter Pair Wall Mounted Type K-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump
Service Manual Inverter Pair Wall Mounted Type K-Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair Wall Mounted Type K-Series Cooling Only Indoor Unit FTXN09KEVJU
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
SiBE12-625. D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump
SiBE12-625 D-Series / E-Series [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump SUPER MULTI NX D-Series / E-Series Cooling Only Indoor Unit FTKS20D3VMW FTKS20CAVMB FDKS25CAVMB
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
SiUS091133. Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump
Service Manual Inverter Pair FTXS-L Series FDXS-L Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair FTXS-L Series FDXS-L Series Cooling Only Indoor Unit FTXS30LVJU
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL
USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA
USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your
CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE
Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE
Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Split Type Room Air Conditioner. KSWM units
OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.
CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING
Order No: PAPAMY1207094CE Indoor Unit CS-CE9NKE CS-CE12NKE Outdoor Unit CU-CE9NKE CU-CE12NKE WARNING This service information is designed for experienced repair technicians only and is not designed for
Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV
Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................
OPTIONAL SLENDER REMOTE CONTROL
DAIKIN ROOM AIR CONDITIONER Operation Manual OPTIONAL SLENDER REMOTE CONTROL BRC944A2B READ BEFORE OPERATION Safety Precautions...2 Names of Functions of Parts...4 Preparation before Operation...5 OPERATION
Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0
Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view
Instruction manual for Firstline FCS12000CH
Instruction manual for Firstline FCS12000CH Contents Introduction... 2 Safety Awareness... 3 Safety Awareness... 4 Name of Parts... 5 Name of Parts... 6 Remote Controller Preparation... 7 Operation of
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
Operating Instructions Air Conditioner
F566272 Operating Instructions Air Conditioner CS-C18FFH CS-C28FFH CU-C18FFH CU-C28FFH ENGLISH Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner * Shows U1 type Model No. Indoor Units Type Indoor Unit Type 26 36 42 Remarks U1 4-Way Cassette S-26PU1U6 S-36PU1U6 S-42PU1U6 with Wired Remote Controller:
DESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LECA AS G09LECA AS G12LECA AS G14LECA OUTDOOR AO G07LEC AO G09LEC AO G12LEC AO G14LEC 1. INDOOR UNIT : AS G07LECA AS G09LECA AS
OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex
OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
SERVICE Manual AIR CONDITIONER AWH090ZE0K. 1. Precautions. 2. Product Specifications. 3. Installation and Operating Instructions
ROOM AIR CONDITIONER AWH090ZE0K SERVICE Manual AIR CONDITIONER CONTENTS 1. Precautions 2. Product Specifications 3. Installation and Operating Instructions 4. Disassembly and Reassembly 5. Troubleshooting
REGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
FAN SPEED AIR SWING SET CANCEL FAN AIR SWING SET CANCEL WARNING
AUT O HE AT COOL DRY AUT O HE AT COOL DRY FAN SP E ED FAN SPEED AC AC AIR SWING SE T CHE CK CLOCK RE SE T AIR SWING SE T CHE CK CLOCK RE SE T FAN SPEED AIR SWING RC RC Order No: PAPAMY32039CE (YE9/2QKE)
Technical service manual 2009
MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features
Use and Care Manual. Model CPA12KH AIR CONDITIONER
Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage
SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL
SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL Thank you for choosing our Air Conditioner. Please read this OWNER'S MANUAL carefully prior to use and keep it for further reference. CONTENTS Contents
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
Operating Instructions Air Conditioner
P07-T10130 Operating Instructions Air Conditioner Indoor Unit CS-F24DD1E5 CS-F28DD1E5 CS-F34DD1E5 CS-F43DD1E5 CS-F50DD1E5 Outdoor Unit Inverter Model (HBE5 Series) CU-YL24HBE5 CU-YL28HBE5 CU-YL34HBE5 CU-YL43HBE5
USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB98-29565A(1) ENGLISH ESPAÑOL
USER S MANUAL Duct Type Series MH MH FEEA Series FUEA Series ENGLISH ESPAÑOL PORTUGUÊS E HNIKA DEUTSCH ITALIANO FRANÇAIS Free Joint Multi Air Conditioner (Cooling and Heating) E S F I P D G DB98-29565A(1)
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
Technical Service Manual. Version One
[Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:
How To Power A Car With A Fan And A Fan (Power)
SPLIT TYPE ROO AIR CONDITIONER CEILING WALL TYPE INVERTER Indoor unit AWYZLBC AWYZLBC AWYZLBC AWYZLBC Outdoor unit AOYZLBC AOYZLBL AOYZLBC AOYZLBL CONTENTS SPECIFICATIONS................... OUTLINE AND
OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump
R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully
AIR CONDITIONER (SPLIT TYPE)
OWNER S MANUAL AIR CONDITIONER (SPLIT TYPE) For general public use ENGLISH EN Indoor Unit RAS-07PKVP-E RAS-10PKVP-E RAS-13PKVP-E RAS-16PKVP-E RAS-18PKVP-E RAS-07PKVP-ND RAS-10PKVP-ND RAS-13PKVP-ND RAS-16PKVP-ND
NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
Quest 105, Dry155, and 205 Dual
Quest 105, Dry155, and 205 Dual Read and Save These Instructions This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully.
Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC
Portable Evaporative Air Cooler OWNER S MANUAL Read and save these instructions before use Model: CL30XC Power rating: 250 Watts Voltage rating: 230 Volt, 50Hz Made in P.R.C. QUICK START GUIDE Fill with
SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03
Domestic Air Conditioner SERVICE MANUAL Model HW-05LN03 Feature Anti-mold filter Mechanical control Easy clean filters Slide chassis 4-way airflow direction 2 cool settings, 2 fan settings Serial Number:
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
HEATER, AIR CONDITIONING AND VENTILATION
55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
To suit Daikin FDY "F" Series and FD "F" Series. (and other models incorporating BRC1B62/52 Remote Controller)
OPERATION MANUAL Split System Ducted Air Conditioner To suit Daikin FDY "F" Series and FD "F" Series AIR CONDITIONER A hr o C (and other models incorporating BRC1B62/52 Remote Controller) Dear Owner, Thank
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
DESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LKC AS A12LKC OUTDOOR AO R09LKC AO R12LKC 1.INDOOR UNIT : AS A09LKC AS A12LKC DTR_AS039E_01 2010.02.24 1. INDOOR UNIT CONTENTS 1.
PORTABLE AIR CONDITIONER
VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner
DC INVERTER (WALL TYPE) INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT RAS-18FH6 RAC-18YH6. 1 PHASE, 50 Hz, 220-230V
SERVICE MANUAL TECHNICAL INFORMATION AW NO. 0024E RAS-18FH6 RAC-18YH6 RAS-25FH6 RAC-25YH6 REFER TO THE FOUNDATION MANUAL FOR SERVICE PERSONNEL ONLY CONTENTS SPECIFICATIONS -------------------------------------------------------------------
