1 Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Energy Implications of Economizer Use in California Data Centers Author: Shehabi, Arman Publication Date: Permalink: Abstract: In the US, data center operations currently account for about 61 billion kwh/y of electricity consumption, which is more than 1.5percent of total demand. Data center energy consumption is rising rapidly, having doubled in the last five years. A substantial portion of data-center energy use is dedicated to removing the heat generated by the computer equipment. Data-center cooling load might be met with substantially reduced energy consumption with the use of air-side economizers. This energy saving measure, however, has been shown to expose servers to an order-ofmagnitude increase in indoor particle concentrations with an unquantified increase in the risk of equipment failure. An alternative energy saving option is the use of water-side economizers, which do not affect the indoor particle concentration but require additional mechanical equipment and tend to be less beneficial in high humidity areas. Published research has only presented qualitative benefits of economizer use, providing industry with inadequate information on which to base their design decisions. Energy savings depend on local climate and the specific buildingdesign characteristics. In this paper, based on building energy models, we report energy savings for air-side and water-side economizer use in data centers in several climate zones in California. Results show that in terms of energy savings, air-side economizers consistently outperform waterside economizers, though the performance difference varies by location. Model results also show that conventional humidity restrictions must by relaxed or removed to gain the energy benefits of air-side economizers. Copyright Information: All rights reserved unless otherwise indicated. Contact the author or original publisher for any necessary permissions. escholarship is not the copyright owner for deposited works. Learn more at escholarship provides open access, scholarly publishing services to the University of California and delivers a dynamic research platform to scholars worldwide.
2 Energy Implications of Economizer Use in California Data Centers Arman Shehabi 1, Srirupa Ganguly 2,*, Kim Traber 3, Hillary Price 3 Arpad Horvath 1, William W Nazaroff 1, Ashok J Gadgil 2, 1 Department of Civil and Environmental Engineering, University of California, Berkeley, CA Indoor Environment Department, Lawrence Berkeley National Laboratory, Berkeley, CA Rumsey Engineers, Oakland, CA * Author to whom correspondence should be addressed [email protected] Abstract In the US, data center operations currently account for about 61 billion kwh/y of electricity consumption, which is more than 1.5% of total demand. Data center energy consumption is rising rapidly, having doubled in the last five years. A substantial portion of datacenter energy use is dedicated to removing the heat generated by the computer equipment. Datacenter cooling load might be met with substantially reduced energy consumption with the use of air-side economizers. This energy saving measure, however, has been shown to expose servers to an order-of-magnitude increase in indoor particle concentrations with an unquantified increase in the risk of equipment failure. An alternative energy saving option is the use of water-side economizers, which do not affect the indoor particle concentration but require additional mechanical equipment and tend to be less beneficial in high humidity areas. Published research has only presented qualitative benefits of economizer use, providing industry with inadequate information on which to base their design decisions. Energy savings depend on local climate and the specific building-design characteristics. In this paper, based on building energy models, we report energy savings for air-side and water-side economizer use in data centers in several climate zones in California. Results show that in terms of energy savings, air-side economizers consistently outperform water-side economizers, though the performance difference varies by location. Model results also show that conventional humidity restrictions must by relaxed or removed to gain the energy benefits of air-side economizers. Introduction Data centers are computing facilities that house the electronic equipment used for data processing, networking and storage. Rapid growth in computational demand emerging from various sectors of the economy is causing strong rates of increase in servers and IT-related hardware (IDC 7). Server performance has doubled every two years since 1999, leading to increasingly higher densities of heat dissipation within data centers (Belady 7). A substantial proportion of energy consumption in data centers is dedicated to the cooling load associated with electronic power dissipation (Tschudi et al. 3). A recent study estimates that US data centers account for 61 billion kwh or 1.5% of the nation s annual electricity consumption (US DOE 7a). This corresponds to an electricity bill of approximately $4.5 billion in 6 (EPA 7). The environmental impact is substantial because 70% of the electricity in US is generated in power plants that burn fossil fuel (EIA 7). Improved data center cooling technologies have the potential to provide significant energy savings. Cost savings and environmental benefits might also accrue.
3 A typical data center consists of rows of tall (2 m) cabinets or racks in which the servers, data storage and networking equipment are vertically arrayed. The cooling of data-center equipment is accomplished using computer room air conditioners (CRACs), which supply cold air to a raised-floor plenum beneath the racks. The CRAC system air handler is placed on the data center floor while chilled water in transported from compressor-based chillers to the CRAC cooling coils. More efficient cooling systems employ low outside air temperatures to reduce chiller load. Cooling towers that use ambient air to directly cool or precool the chilled water are known as water-side or fluid-side economizers. This type of system has been claimed to cut cooling-energy costs by as much as 70% (ASHRAE HVAC Fundamentals Handbook 5) during economizer operation. Based on local weather data in San Jose, water-side economizers can be used for more than one-third of the year (PG&E 6). An alternate data center arrangement uses air-handling units (AHU) and an air-side economizer. Such systems directly provide outdoor air for cooling whenever the temperature of outside air is lower than the setpoint for return-air temperature in the data center. In San Francisco s cool climate, outside air could contribute to some level of air-side cooling for nearly all hours of the year (Syska Hennessy 7). The use of air-side economizers brings with it an associated concern about contamination including moisture from humidity that may possibly threaten equipment reliability. Deliquescent sulfate, nitrate and chloride salts, in a humid environment (> 40% relative humidity) can cause corrosion, accumulate and become conductive, and may lead to electrical short-circuiting (Rice et al. 1981; Sinclair et al. 1990; Litvak et al. 0). In this paper, the energy implications of a data center using a CRAC system will be compared with alternative cooling systems using air-side or water-side economizers for five different California climate zones. The modeling results and discussion focus on understanding the energy implications for both type of economizers and their effectiveness in different climate zones. The equipment reliability concerns associated with air-side economizers are acknowledged to be important, but addressing it is beyond the scope of the present paper. Methods Data center design scenarios Energy-use simulations were performed for three different data center HVAC design scenarios (Figure 1). The baseline case considers a data center using conventional computer room air conditioning (CRAC) units. In this scenario, CRAC units are placed directly on the computer room floor. Air enters the top of a CRAC unit, passes across the cooling coils, and is then discharged to the underfloor plenum. Perforations in the floor tiles in front of the server racks allow the cool air to exit from the plenum into the data-center room. Fans within the computer servers draw the conditioned air upward and through the servers to remove equipmentgenerated heat. After exiting the backside of the server housing, the warm air rises and is transported to the intake of a CRAC unit. Most air circulation in the baseline scenario is internal to the data center. A small amount of air is supplied through a rooftop AHU to positively pressurize the room and to supply outside air for occupants. Cooling is provided by a watercooled chiller plant. Refrigerant in the chillers is used to cool water through heat exchangers at the evaporator. The chilled water is then piped to the CRAC units on the data center floor. Waste heat from the chiller refrigerant is removed by water through heat exchangers in the condenser. Condenser water is piped from the cooling towers, which cools the water through interaction with the outside air. This baseline design is common to most mid- to large-size data
4 centers (Tschudi et al. 3; Rumsey 5; Syska Hennessy 7). The water-side economizer (WSE) scenario assumes a CRAC unit layout similar to that of the baseline case, except that additional heat exchangers are installed between the condenser water in the cooling towers and the chilled water supplied to the CRAC units. Under appropriate weather conditions, the cooling towers can cool the condenser water enough to cool the chilled water in the CRAC units directly, without operating the chiller plant. The CRAC units and chiller plant are assumed to be the same as in the baseline scenario. The air-side economizer scenario (ASE) requires a different type of air delivery than typically found in a data center with conventional CRAC units. AHUs are placed outside of the data center room, commonly on the rooftop, and air is then sent to and from the computer racks through ducts. A ducted air delivery system creates greater air resistance than a conventional CRAC unit layout, though this system better prevents cold and warm air from unintentionally mixing within the data center. When the outside air temperature is equal to or below the temperature of the air supplied to cool the server, the AHU can directly draw outside air into the data center and exhaust all of the return air after it has passed across the computer servers. The movement of % outside air through the system can require more fan energy than the baseline case, as the economizer design requires more ducting, which increases air resistance through the system. However, during this % outside air mode the cooling is provided without operating the chiller, chilled water pumps, condenser water pumps, or the cooling tower fans. Outside air is also provided instead of recirculated air whenever the outside air temperature is greater than the supply air temperature but lower than that of the return air. Under this condition the chiller must operate, but the cooling required of the chiller is less than in a case with complete recirculation. Energy modeling protocol For each design scenario, the model calculations assume a 30,000 ft 2 (2800 m 2 ) data center with an internal heat density of approximately 80 W/ft 2 (0.86 kw/m 2 ; 2.4 MW total) This size and power density are characteristic of data centers evaluated in previous studies (Shehabi et al. 8; Greenberg et al. 6; Tschudi et al. 3). The size of data centers varies greatly; 30,000 ft 2 is within the largest industry size classification, which is responsible for most servers in the US (IDC 7). Power density in data centers is rapidly increasing (Uptime Institute 0) and a power density of 80 W/ft 2 is currently considered to be of low- to mid-range (Rumsey 8). Basic properties of the modeled data center for all three scenarios are summarized in Table 1. Energy demand is calculated as the sum of the loads generated by servers, chiller use, fan operation, transformer and uninterruptible power supply (UPS) losses, and building lighting. The chiller encompasses coolant compressor, chilled water pumps, condensing water pumps, humidification pumps, and cooling-tower fans. Energy demand for servers, UPS, and lighting are constant, unaffected by the different design scenarios, but are included to determine total building-energy use. The base case and WSE scenarios assume conventional humidity restrictions recommend by ASHRAE (ASHRAE 5). The ASE scenario assumes no humidity restriction, which is an adjustment required to gain ASE benefits as is typical in ASE implementation (Rumsey 8). Air-side economizers also require a different air distribution design and the fan parameters associated with each design scenario are listed in Table 2. The
5 properties of other pumps and fans throughout the HVAC system remain constant for all three scenarios. Values are from previous data-center energy analyses (Rumsey 8; Rumsey 5). The energy modeling approach used in this study applies a previously used protocol (Rumsey 8; Rumsery 5) and is based on a combination of fundamental HVAC sizing equations that apply equipment size and efficiencies observed through professional experience. Building energy modeling is typically performed using energy models such as DOE-2, which simultaneously models heat sources and losses within the building and through the building envelope. However, models such as DOE-2 are not designed to incorporate some of the HVAC characteristics unique to data centers. Also, data centers have floor-area-weighted power densities that are 15- times higher than those of typical commercial buildings (Greenberg et al. 6). This allows accurate modeling of data-center energy use to focus exclusively on internal heat load and the thermal properties of outdoor air entering the building. This is the approach taken in this study, as heat generated from data center occupants and heat transfer through the building envelope are negligible relative to the heat produced by servers. The building envelope may influence the cooling load in low-density data centers housed in older buildings that have minimal insulation. Evaluating this building type is worthy of exploration, but the required analysis is more complex and outside the scope of the present paper. Both air-side and water-side economizers are designed to allow the chiller to shut down or reduce chiller energy load under appropriate weather conditions. Less overall energy is required for operation when the chiller load is reduced, but chiller efficiency is compromised. Changes in chiller efficiency used in this analysis are shown in Figure 2, representing a watercooled centrifugal chiller with a capacity > 300 tons and condenser water temperature of 80 F. A chilled water temperature of 45 F, which is standard practice for data center operation, is used in the base case and ASE scenario. The WSE scenario uses a chilled water temperature of 52 F, which is common when using water-side economizers. This increases needed airflow rates but allows greater use of the water-side economizers. The curves are based on the DOE2.1E software model and apply coefficients specified in the Nonresidential Alternative Calculation Method (ACM) Approval Manual for the 5 Building Energy Efficiency Standards for Residential and Nonresidential Buildings (CEC 5). Annual data center energy use is evaluated for each of the three configuration scenarios assuming that a data center building is located in each of the five cities shown in Figure 3. Weather conditions at each city are based on hourly DOE2.1E weather data for California climate zones (CEC 5). Results and Discussion Results from each scenario modeled are presented in Table 3 as a performance ratio which equals the ratio of total building energy divided by the energy required to operate the computer servers. Lower value of the performance ratio implies better energy utilization of the HVAC system. The performance ratio for the base case is 1.55 and, as expected, is the same for all the cities analyzed, since the operation of this design is practically independent of outdoor weather conditions. The base case performance ratio is better than the current stock of data centers in the US (EPA 7; Koomey 7) because the base case represents newer data centers with water-cooled chillers, which are more efficient than the air-cooled chillers and direct expansion (DX) cooling systems found in older data centers.
6 The performance ratios for the ASE and WSE scenarios show air-side economizers consistently provide savings relative to the base case, though the difference in savings between the two scenarios varies. It is important the note that even small changes in the performance ratio results in significant savings, given the large amount of energy used in data centers. For example, reducing the performance ratio at the model data center in San Jose from 1.55 to 1.44 represents a savings of about 1.9 million kwh/y, which corresponds to a cost savings of more than $130,000/y (assuming $0.07/kWh). Figure 4 shows the disaggregation of the cooling systems annual energy use, normalized by floor area, for each modeled data center by location and design scenario. The annual energy use dedicated to the servers, USP, and lighting is 584, 95, and 9 kwh/ft 2, respectively. These energy values are independent of the climate and HVAC design in scenario and not included in the graphs in Figure 4. Economizer use is typically controlled by combination of outside air temperature, humidity, and enthalpy; however results shown in Figure 4 are for economizer use controlled by outside air temperature only. Results show that the ASE scenario provides the greatest savings in San Francisco while Fresno provides the least ASE savings. Sacramento benefited the most from the WSE scenario while minimal savings were realized in Los Angeles and San Francisco. The San Francisco WSE scenario, where significant gains would be expected because of the cool climate, is hindered by chiller part-load inefficiencies. The relatively higher moisture content in the San Francisco air increases the latent cooling load in the model and causes the chiller plant to reach the capacity limit of the first chiller more often, activating a second chiller. The second chiller shares the cooling load equally with the first, resulting in a transition from one chiller at a high load factor (efficient operation) to two chillers at slightly above half the load factor (less efficient operation). The results from the WSE scenario in San Francisco emphasize the need for engineers to model the hour-by-hour load, rather than just the peak load, and to size chillers such that all active chillers at any moment will be running near their most efficient operating point. Figure 5 shows that removing the humidity restrictions commonly applied to data centers is necessary to gain ASE energy savings. As the relative humidity (RH) ranged is narrowed, energy use from the fans begins to sharply increase, surpassing the equivalent baseline energy in most of the cities. Humidity levels are often restricted in data centers to minimize potential server reliability issues. ASHRAE s guidelines released in 5 for data centers provide a recommend RH range between 40-55% and an allowable range between 20-80% (ASHRAE 5). There is minimal cost in applying the more conservative ASHRAE RH restrictions in conventional data center design, such as the baseline in this study shown in Figure 5. The influence of humidity on server performance, however, is poorly documented and the need for humidity restrictions is increasingly being questioned (Fontecchio 7). The energy saving difference between adhering to ASHRAE s recommend RH range versus the allowable RH range is substantial, and warrants further investigation. Conclusion Employing the energy-saving measures evaluated in this paper would require a shift in conventional data center design and operation. Various operational concerns must be addressed before widespread adoption of these technologies could be expected in data-center buildings. This paper contributes to the informed implementation of air-side and water-side economizers by assessing the energy benefits of adopting these efficiency improvements. Air-side economizers
7 are shown to consistently outperform water-side economizers in California, though the difference in performance varies by the climate conditions of the locations evaluated. Furthermore, the models show that conventional humidity restrictions must by relaxed or removed to substantially realize the energy benefits of air-side economizers. As the data center economy continues to rapidly grow, energy efficiency will continue to emerge as an important financial and environmental concern. The results presented here contribute to our understanding of different design implications and should assist decision makers in the implementation of energy-efficient data centers. Acknowledgments We thank Rumsey Engineers for their assistance in running energy models and data center operators that helped determine conventional HVAC parameters. This project was funded by Pacific Gas & Electric and by the University of California Energy Institute, California Studies Grant Program. Some of this work was performed at LBNL under the U.S. Department of Energy Contract No. DE-AC02-05CH References [ASHRAE] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc 5. Design Considerations for Data and Communications Equipment Centers. Atlanta, GA. [ASHRAE] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 6. Liquid Cooling guidelines for Datcom Equipment Centers. ASHRAE Datacom Series, Atlanta, GA [ASHRAE] American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 5. ASHRAE HVAC Fundamental Handbook. Atlanta, GA Belady, C. 7. In the Data Center, Power and Cooling Costs More than the IT Equipment it Supports." Electronics Cooling Magazine. February 7. [CEC] California Energy Commission (CEC) 5. Nonresidential Compliance Manual For California's 5 Energy Efficiency Standards. [EIA] Energy Information Administration 7. International Energy Outlook, Energy Information Administration (EIA). May 7. [EPA] Environmental Protection Agency 7. Report to Congress on Server and Data Center Energy Efficiency. August 2. Fontecchio, M. 7. Data center humidity levels source of debate. SearchDataCenter.com June 18. Greenberg, S., Mills, E., Tschudi, W., Rumsey, P., Myatt, B. 6. Best practices for data centers: Results from benchmarking 22 data centers. Proceedings of the 6 ACEEE
8 Summer Study on Energy Efficiency in Buildings. Asilomar, CA. [IDC] International Data Corporation 7. IDC s Worlwide Installed Base Forecast, Framingham, MA Koomey, J. 7. Estimating total power consumption by servers in the U.S. and the world. Oakland, CA: Analytics Press. Litvak, A., Gadgil, A.J., Fisk, W.J. 0. Hygroscopic fine mode particle deposition on electronic circuits and resulting degradation of circuit performance: an experimental study. Indoor Air 10: [PG&E] Pacific Gas and Electric 6. High Performance Data Centers. A Design Guidelines Sourcebook. January. Rice, D. W., Cappell, R. J., Kinsolving, W., Laskowski, J. J Indoor corrosion of metal. Journal of Electrochemical Society 128: Rumsey Engineers. 8 Network Appliance: Building 02 Datacenter. Pacific Gas and Electric Non-Residential New Construction Incentive Program. January. Rumsey Engineers. 5 Network Appliance Building 11 Datacenter. Pacific Gas and Electric Industrial Savings by Design Program. June. Sinclair, J.D., Psota-Kelty, L.A., Weschler, C.J., Shields, H.C Deposition of Airborne Sulfate, Nitrate, and Chloride salts as It Relates to Corrosion in Electronics. Journal of the Electrochemical Society 137:44 Shehabi, A., Horvath, A., Tschudi, W., Gadgil, A., Nazaroff, W. 8. Particulate Matter in Data Centers. Atmospheric Environment, draft submission, October. Syska Hennessy Group 7. The Use of Outside Air Economizers In Data Center Environments. White paper 7. Tschudi, W.F., Xu, T.T., Sartor, D. A., Stein, J. 3. High Performance Data Centers: A Research Roadmap. Lawrence Berkeley National Laboratory. Berkeley, CA Uptime Institute 0. Heat Density Trends in Data Processing, Computer Systems, and Telecommunications Equipment. Santa Fe, NM. [US DOE 7a] United States Department of Energy 7a. Annual Energy Outlook 7, with Projections to Washington, DC
9 Table 1: Data Center Characteristics Common to All Design Scenarios Data Center Parameters Floor Area 30,000 ft 2 UPS Waste Heat 326 kw Data Center Lights 30 kw Total Rack Load 0 kw Total Internal Load 2,356 kw Average Internal Load Density 79 W/ft 2 Minimum Ventilation 4,500 ft 3 /min Supply Air Temperature 55 F Return Air Drybulb Setpoint 72 F Chiller Capacity 1750 kw Number of Chillers 3 Table 2: Data Center Fan Properties Fan System Parameters Baseline and WSE ASE MUAH Exhaust CRACs Supply Relief Total Air Flow (cfm) 4,500 4, , , ,758 Fan Motor Size, Nominal (hp) Number of Fans Fan Efficiency 53.3% 44.0% 55.6% 63.8% 67.5% Fan Drive Efficiency 95% 95% 95% 95% 95% Fan Motor Efficiency 89.6% 86.2% 90.1% 92.5% 93.2% VFD Efficiency n/a n/a n/a 98% 98% Total Static Pressure Drop (in w.g.) Table 3: Ratio of Total Building Energy to Computer Server Energy San Jose San Francisco Sacramento Fresno Los Angeles Baseline Air-side Economizer Water-side Economizer
10 Figure 1: Schematic of Data Center Cooling Design Scenarios cooling tower cold air warm air AHU outside air cold water warm water condensing water water-side economizer (not in basecase) heat exchanger CRAC condenser chiller evaporator chilled water cooling tower condensing water air-side economizer condenser chiller evaporator chilled water AHU Air and water flow schematic for the basecase and water-side economizer scenarios (above). Air and water flow schematic for the air-side economizer scenario (below).
11 Figure 2: Assumed Part Load Performance of Data Center Chillers 11.1 C 6.7 C Part load efficiencies for a water-cooled centrifugal chiller with a capacity >300 tons and an condenser water temperature of 26.7 C (CEC, 5)) Figure 3: Evaluated Climate Zone Locations Sacramento San Francisco San Jose Fresno Los Angeles
12 Figure 4: Disaggregated Energy Use (Climate Dependent Values Only) Transformer Losses Fans Chiller San Jose baseline air-side water-side economizer scenarios San Francisco baseline air-side water-side Sacramento baseline air-side water-side economizer scenarios economizer scenarios Fresno baseline air-side water-side Los Angeles baseline air-side water-side economizer scenarios economizer scenarios
13 Figure 5: Chiller and Fan Energy Resulting from Humidity Restrictions baseline scenario air-side economizer water-side economizer % 90% San Jose 20%- 80% 30%- 70% 40%- 55% humitidy restrictions (RH) % San Francisco 90% 20%- 80% 30%- 70% 40%- 55% % Sacramento 90% 20%- 80% 30%- 70% 40%- 55% humitidy restrictions (RH) humitidy restrictions (RH) % 90% Frenso 20%- 80% 30%- 70% 40%- 55% % Los Angeles 90% 20%- 80% 30%- 70% 40%- 55% humitidy restrictions (RH) humitidy restrictions (RH)
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
Guide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
SIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Data Center RD&D at EPRI
Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Tim Facius Baltimore Aircoil
Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
Energy Efficiency Baselines for DATA CENTERS. Statewide Customized New Construction and Customized Retrofit Incentive Programs.
Energy Efficiency Baselines for DATA CENTERS Statewide Customized New Construction and Customized Retrofit Incentive Programs March 1, 2013* Revision 1 (Rectifier Efficiency Added) Written By: Integral
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Flexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
USE OF AIR SIDE ECONOMIZER FOR DATA CENTER THERMAL MANAGEMENT. A Thesis Presented to The Academic Faculty. Anubhav Kumar
USE OF AIR SIDE ECONOMIZER FOR DATA CENTER THERMAL MANAGEMENT A Thesis Presented to The Academic Faculty By Anubhav Kumar In Partial Fulfillment of the Requirements for the Masters Degree in the School
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected]
Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected] Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
The Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
Improving Data Center Efficiency with Rack or Row Cooling Devices:
Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
CRITICAL COOLING FOR DATA CENTERS
IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice
Datacenter Efficiency Program
Datacenter Efficiency Program Yuming Qiu, CLEAResult Anna Stieve, CLEAResult Michael Stachowiak, CLEAResult Abstract Worldwide, datacenter energy consumption is skyrocketing and datacenter energy efficiency
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL
Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Article Mechanical Engineering July 2011 Vol.56 No.20: 2185 2190 doi: 10.1007/s11434-011-4500-5 SPECIAL TOPICS: Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products. Richard Lord
Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products Richard Lord Overview and Agenda My goal today is to give you quick an overview of the current status of HVAC products
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Data Center Environments
Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Variable Refrigerant Flow Systems
The following article was published in ASHRAE Journal, April 2007. Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Thermal Mass Availability for Cooling Data Centers during Power Shutdown
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
By Donald Fisher, P.Eng., Associate Member ASHRAE
By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can