Air-Conditioning of Parked Aircraft by Ground- Based Equipment
|
|
|
- Griffin Bruce
- 10 years ago
- Views:
Transcription
1 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Air-Conditioning of Parked Aircraft by Ground- Based Equipment Evgenia Sikorski Offenburg University Follow this and additional works at: Sikorski, Evgenia, "Air-Conditioning of Parked Aircraft by Ground-Based Equipment" (2010). International Refrigeration and Air Conditioning Conference. Paper This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at Herrick/Events/orderlit.html
2 Air-Conditioning of Parked Aircraft by Ground-Based Equipment Evgenia SIKORSKI 2309, Page 1 Offenburg University, Mechanical and Process Engineering, Offenburg, Germany Phone: +49-(0) , Fax: +49-(0) , [email protected] ABSTRACT Pre-conditioned air systems (PCA) represent the art of air-conditioning parked aircraft by a ground-based system, bringing outside filtered, cooled or heated air into the plane. The present report mainly addresses central PCA systems. A description of special requirements, calculation of the overall cooling demand profile, and an explanation on the chilled water (brine) system design are given hereinafter for the central PCA system installed at the New Athens International Airport. The particularities of air handling units (AHU) for PCA are explained and relevant technical data given. 1. INTRODUCTION Every aircraft whether in the air, on the runway, or on the ground needs air-conditioning and 400 Hz power supply. This paper addresses the air-conditioning issues only. Naturally, air-conditioning of aircraft in motion can be done only by means of onboard equipment an auxiliary power unit (APU). When parked, though, the means of supply depend on whether the aircraft stays in operation (during passenger boarding, disembarking, cleaning, etc.) or is out of operation (e.g. when it is parked for an overnight stay). The latter case is of little interest since no air-conditioning is required, except for some heating in northern climate countries to prevent freezing. When in operation, a plane needs lots of outside air for the people on board (17 m³/h per person for normal operation and 5 m³/h per person for emergency operation). Mostly, it needs cooled outside air. Without any air being supplied to the cabin, the cabin temperature would rise up to 50 C within some 15 minutes (whereby the outside air temperature is of minor significance). After 5 minutes, the high CO 2 concentration and possible shortage of oxygen make the cabin air almost unbreathable. The method conventionally used to supply air-conditioning to parked aircraft is by letting the APU continue to run. APUs, however, involve high levels of noxious emissions and fuel gas odors (e.g. 550 l/h of fuel are required for B ) and cause a noise level of some 80 db(a) at the airfield apron while their efficiency is between 10 and 12 %. Pre-conditioned air systems represent the alternative method by using ground-based equipment. The electrically driven PCA systems do not require any fuel, their noise level is 70 db(a), and their efficiency is up to 50 % (for central systems in terms of primary energy use). The noise level of 70 db(a) at the airfield apron instead of 80 db(a) corresponds to a 10-fold noise level reduction! Two PCA versions are common: Point-of-use systems (mainly in US and Far East) and central systems (in Europe). Point-of-use system means a suitable air handling unit and pertinent air delivery equipment being mounted on a truck. Central PCA systems consist of several AHUs and air delivery equipment being installed on passenger-
3 2309, Page 2 boarding bridges (one AHU for each bridge), one or two chillers, usually ice storage units, distribution piping, and controls. Planes are parked either at a terminal or on a remote position. For remote positions, Point-of-use systems are the obvious choice. At terminals, both PCA versions can be used. Which version is used at terminals is mainly determined by ownership conditions at the airport. In the US and Far East, modular airports are common; airlines own the gates and are entitled to install on their, mostly few, gates any additional equipment. In Europe, airports are built as functionally rigid areas; airlines merely lease gates, decisions on gate equipment rest with the Airport Authorities. When PCA is to supply many or all gates at an airport, central systems are by far more energy-efficient than Pointof-use systems. Hybrid plants (central basic supply system with decentralized equipment for peak load demand) are also possible. This paper mainly addresses central PCA systems. In this report, an explanation of the main issues regarding central PCA systems are given for the central PCA system installed at the New Athens International Airport. 2. CENTRAL PCA PLANT FOR THE ATHENS AIRPORT 2.1 General The New Athens International Airport shall handle 15 million passengers yearly and 75,000 passengers at a Typical Peak Day. The selected PCA concept for the Athens Airport is a central cooling supply concept. Two terminals are served: the Main Terminal (14 gates) and the Satellite Building (10 gates). Both buildings are served from one central cooling system. The PCA plant room is located in the Main Terminal. Connection between the Main Terminal and Satellite is by way of an underground link. Design conditions: Summer ambient design temperature: 35 C dry bulb / 35% r. h. Winter ambient design temperature: -1 C Aircraft cabin temperature: 24 C in summer, 21 C in winter 2.2 Contact Position Occupancy Aircraft contact parking interchangeability is realized as specified in the Master Plan. There are three different scenarios of aircraft types to be accommodated at each gate: maximum (B , B , A 320, MD 11), minimum (MD 80 only), and simultaneous (B , A 320, MD 11). Simultaneous occupancy is the worst-case occupancy under consideration of all restrictions on neighboring positions. Gate equipment mostly AHUs is designed on maximum position occupancy. There are three major types of aircraft: Jumbo, Wide and Narrow Body. However, distinction is made between two types of AHU only: AHU for Jumbo and AHU for Wide/Narrow Body aircraft. As a result, 11 aircraft positions are equipped with AHUs for Jumbos, the other 13 positions with AHUs for Wide/Narrow Body aircraft. For typical gate equipment refer to Figure 1. It is imperative that the central equipment design is defined by simultaneous position occupancy. 2.3 AHU Airflow and Cooling Capacity The aircraft internal cooling load comprises four major components, which ratios are nearly equal for all types of aircraft. Considering the Athens design conditions and maximum occupation (seating load factor of 1.0 as determined in the Master Plan for non-scheduled flights), these are: cabin wall conduction (23 %), solar load on windows (11 %), electrical load of lighting and equipment originated by 400 Hz connection (22 %), and passengers and crew (44 %).
4 2309, Page 3 The individual cooling load and cooling capacity for all five types of aircraft mentioned under Aircraft contact parking interchangeability as calculated for the Athens environment considers a maximum seating factor of 95 % as listed in the Forecast Timetable. The calculations show that cooling load is approx. 30 % of the cooling capacity for all aircraft types; the cooling capacity varies between max. 96 % (from 13:00 to 15:00) and min. 76 % (from 3:00 to 5:00). The cooling capacity of the pre-conditioned air when delivered to the aircraft is a function of airflow, outlet air temperature, and heat gain in the delivery path. The AHU outlet temperature is set to -5 C at design ambient temperature in summer, requiring the brine supply temperature to be -7 C. The required airflow is calculated under consideration of the heat gain in a standard air hose for normal passenger-boarding bridges. The maximum required airflow is about 200 kg/min for Jumbo and 40 kg/min for MD80 aircraft. Due to the heat gain in the delivery path, the air temperature at the aircraft adapter rises from -5 C to -0.3 C for B or 4.2 C for MD80 aircraft. The maximum AHU cooling capacity for Jumbo and Wide/Narrow Body positions is 217 kw and 121 kw, respectively. With 11 Jumbo and 13 Wide/Narrow Body positions at the airport, the installed gate equipment capacity (all AHU cooling capacities) totals up to 3,960 kw. For a Point-of-use PCA system refrigerating machines of exactly this capacity (at maximum contact position occupancy) would have to be installed. For central systems, the simultaneous position occupancy is decisive; hence the capacity to be installed is reduced to about 3,500 kw (diversity factor of 88 %). Diversity factors have a direct effect on the central system investment costs. They also demonstrate the benefits achieved when comparing the calculations for any previous design step. In the end, a chiller capacity of merely 1,240 kw (see below) is sufficient (overall diversity factor 1,240 kw / 3,960 kw = 31 %), justifying the calculation and analysis efforts involved. 2.4 Overall Cooling Load Profile The overall cooling load profile is defined by the loads of all flights at 5-minute-intervals for 24 hours of the Typical Peak Day. All flights from the Forecast Timetable and capable of docking at a bridge are included, corresponding to nearly 10 turn-rounds per bridge. Thus, the system is designed for the case that all flights that are capable of docking at a bridge actually are served there, as expected for the year 2025 due to environmental legislation. The aircraft turn-round times (TRT) have to be estimated for this calculation. The Timetable specifies arrival and departure times; however, mostly, planes do not remain docked all the time in-between. The TRT for each aircraft type is defined by averaging a couple of turn-rounds for that specific aircraft as listed in the Timetable and comparing the same with usual TRTs according to IATA-recommendations as well as on the basis of experience. The estimated TRTs vary from 120 minutes for Jumbos and 65 minutes for the smallest aircraft. For most flights (89 %), TRTs equal to 100 or 80 minutes. Loads for individual flights are calculated with an average seating load factor of 70 %. This factor is generated as a mixed value considering various Master Plan requirements regarding scheduled and non-scheduled flights as well as international, domestic, and transit flights with their respective data about average seat capacity and seating load factor. Also included is the specified passenger movement at a Typical Peak Day of 75,000 passengers. At arrival, the number of persons in a plane is calculated to be the scheduled number of passengers plus full crew. During disembarking (15 to 25 minutes, depending upon aircraft type), the number of persons declines to the cockpit crew while during boarding (20 to 30 minutes) it rises to the previous level again. The overall cooling load profile (Figure 2) is calculated for a peak day at 5-minute-intervals and shows a peak load of 1,905 kw, various peaks, and frequently occurring strong capacity fluctuations originated by respective flow fluctuations at AHUs. Cooling demand exists also during the night.
5 2309, Page 4 Figure 1: Typical gate equipment (540 ton) Peak Load 1,905 kw Cooling Demand Installed 1,240 kw Cooling Demand, kw Each Chiller Two Chillers 0 05:00 07:00 09:00 11:00 13:00 15:00 17:00 Time 19:00 21:00 23:00 01:00 03:00 Figure 2: Overall cooling load profile 2.5 Central System Cooling Capacity and Control To attain the minimum chiller and ice storage capacities, capacity control methods and hydraulic connection of all components are of high significance. The design process for such sophisticated systems is a highly complex and iterative task. To meet the peak cooling load of 1,905 kw (see below), two chillers are required. There is no air-cooled chiller on the market who can do this job alone at the required low supply temperature. Furthermore, the system will operate more safely with two chillers.
6 2309, Page 5 The cooling system is divided into two circuits: primary and secondary. The secondary circuit supply temperature is set to be controlled proportionally to the outside air temperature: t outside C t supply C To reduce electrical power peaks and to achieve highest possible overall equipment efficiency, the chillers are designed to cover basic load requirements, whereas the ice storage unit shall meet irregularly occurring peak loads. During low-load periods, the ice storage unit will be charged for the next peak period. The secondary circuit return temperature is set to +15 C at 35 C outside air temperature (summer design condition). With the supply temperature being -7 C, the secondary circuit (AHU circuit) operates at a temperature difference of 22 C. The primary circuit (chiller circuit) will not be able to cope with a temperature difference of 22 C. No chiller can operate at such a temperature difference the max. admissible temperature difference is 12 C. Therefore, the ice storage unit is switched in series before the chillers. The warmed brine is pre-cooled in the ice storage unit to the set ice storage outlet temperature of +5 C and then enters the chillers to be cooled down to the required temperature. Ice storage charging and discharging are allowed during day and nighttime. However, both processes, charging and discharging, must continue for a certain period of time (e.g. 30 minutes), requiring the application of an auto-adaptive control algorithm. As long as the ice storage unit does not need to be charged, the primary circuit supply temperature (chiller circuit) corresponds to the temperature in the secondary circuit (AHU circuit). If, during a low-load period, ice storage is not fully charged, and the low-load period is expected to be long enough, the primary circuit will be split. One chiller continues to supply the AHUs at the required temperature level, which is almost always too high for charging. The other chiller operates at the charging temperature, which is set to -7 C. After the charging process is completed, the supply temperature in the respective chiller is adopted to the secondary circuit temperature. Cooling is not required when the outside air temperature is below 10 C. Then the pumps in the secondary circuit are switched off; one or both chillers run(s) as necessary to restore ice to full capacity only. Evaluation of the overall cooling load profile under due consideration of the capacity control and hydraulic connection method of all components results in a minimum chiller capacity of 1,240 kw combined with an effective ice storage capacity of 3,800 kwh. 2.6 Central Refrigeration Plant The AHUs form the secondary (consumer) circuit. They are connected in parallel and require constant differential pressure. The circulating brine is pumped to the AHUs by three pumps (3*50%). The pumps are speed-controlled, providing a constant differential pressure at the consumers as required. Two chillers, charged with R407C and each having a capacity of 629 kw, are installed on the roof of the Main Terminal building. Deviating from the Master Plan, air-cooled chillers instead of water-cooled chillers are selected because there is not enough make-up water available for cooling towers. Furthermore, chiller operation without vapor clouds is a requirement to be fulfilled. As each chiller requires a pump of its own (imperative constant flow), two chiller pumps are installed. For ice storage, at least one pump is needed; for safety reasons, two pumps (2*50 %, with constant flow) are installed. They are in operation only upon ice storage discharge. The flow direction in the ice storage unit is the same for charging and discharging, i.e. the inlet ice storage connection serves as inlet for both, charging and discharging. The same applies to the outlet connection.
7 2309, Page 6 In case of chiller failure or power supply failure to the chillers, the ice storage unit is able to serve the AHUs on its own (emergency operation). Under such conditions, a supply temperature of as low as +3 C can be achieved. The operation time depends upon the ice storage charging level and cooling demand. When fully charged, the ice storage unit can serve the AHUs at least for 2 hours (calculated with regard to peak cooling demand). Ice storage, pumps, and other equipment are located in the PCA plant room at basement level of the Main Terminal building. The conveyed medium is brine, a mixture of water and 30 % (by volume) anti-freeze solution. For illustration refer to the simplified flow diagram (Figure 3). Chiller 1 Chiller 2 Ice Storage To / from AHUs (2,000 m) -7 / +5 C +5 / +15 C +15 / -7 C 2.7 Operation Modes Seven operation modes are defined. Figure 3: Simplified flow diagram Operation mode 1 Full Load Operation: AHUs require a cooling capacity between 1,905 and approx. 1,200 kw. Both chillers are operating at sliding supply temperatures; excess demand is met by the ice storage unit. Brine returning from the AHUs is pre-cooled in the ice storage unit and afterwards cooled-down in the chillers to the required temperature. Operation mode 2 Part-Load Operation: AHUs require a cooling capacity between 700 and 1,200 kw; high cooling demand is expected. Both chillers are operating at the supply temperature of -7 C; any excess capacity is supplied to the ice storage unit to restore ice.
8 2309, Page 7 Operation mode 3 Low-Load Operation and High Demand Expectation: AHUs require a cooling capacity of less than 600 kw, high cooling demand is expected. One chiller is operating at sliding supply temperatures and serves the AHUs. The other chiller is operating at the supply temperature of -7 C for ice restoration. Chillers are interchangeable (sub-modes 3A and 3B). Operation mode 4 Low-Load Operation and Low Demand Expectation: AHUs require a cooling capacity between 800 and 600 kw, expected cooling demand is lower than 2/3 of the max. cooling capacity. Only one of two chillers is running and operates at sliding temperatures to serve the AHUs. Brine returning from the AHUs is pre-cooled in the ice storage unit and afterwards cooled-down in the chillers to the required temperature. Chillers are interchangeable (sub-modes 4A and 4B). Operation mode 5 Very Low-Load Operation and Very Low Demand Expectation: AHUs require a cooling capacity of less than 600 kw, expected cooling demand is lower than 1/2 of the max. cooling capacity. Only one of two chillers is running and operates at the supply temperature of -7 C. AHUs are served with sliding temperature medium (mixed flow). Any excess capacity is supplied to the ice storage unit to restore ice. Chillers are interchangeable (sub-modes 5A and 5B) Operation mode 6 Low or Very Low-Load Operation, Low Demand Expectation, Ice Storage is Fully Charged: AHUs require a cooling capacity which does not exceed the capacity of one chiller or both chillers. One chiller is or both chillers are in operation at sliding temperatures (sub-mode 6A and 6B, respectively). Chillers are interchangeable (sub-modes 6AA and 6AB). Operation mode 7 Emergency Operation In case of chiller failure or in case of power supply failure to chillers, the ice storage unit is able to serve the AHUs on its own. The flow diagram (Figure 3) allows for all listed operation modes. It can be seen in the flow diagram that the secondary circuit (AHU circuit) return flow is never passed directly to the primary circuit (chiller circuit). The AHU return flow fluid is either pre-cooled in the ice storage unit (modes 1 and 4) or mixed with the return flow from the ice storage unit when it is being charged (modes 2, 3 and 5) or mixed with some part of cold brine bypassing the secondary circuit (mode 6). Nevertheless, an additional bypass connection with a 3-way control valve is installed to ensure that the temperature difference at the chillers does not exceed the set value. This valve functions in all modes with sliding supply temperatures. It also protects the chillers during start-up and similar phases. Bypassing of some cold brine occurs in all modes where the chiller(s) operate(s) at sliding temperatures (i.e. modes 1, 3, 4, and 6), because the primary circuit always requires constant flow conditions, while strong flow fluctuations are typical for the secondary circuit. 2.8 Heating Due to the climatic conditions prevailing in Athens, the AHUs are equipped with electric heating (30 kw for both types). According to Airport Handling Manual AHM 973, there are two heating modes: Technical heating, maintaining the cabin in an anti-freeze condition at a temperature of +5 C during night stop; this kind of heating is not required in Athens with a winter ambient design temperature of -1 C. Passenger comfort heating, providing for a cabin temperature of +15 C. Taking into account the electrical load originated by the 400 Hz connection (some 30 kw for B ), no aircraft in Athens even when empty needs significant heating. Actually, it is ventilation that counts. However, to ventilate the cabin, cold outside air may have to be heated.
9 2309, Page AHUs and Other Gate Equipment The AHUs for PCA differ to a great extent from AHUs used in normal HVAC applications. The main differences are the very high velocity in the air delivery path (up to 45 m/s in the aircraft adapter), the very high air pressure (up to 11,000 Pa), and the much lower supply air temperature (-4 C). Two AHU types are used, one for Jumbo and one for Wide/Narrow Body aircraft with rated airflows of 200 and 110 kg/min, cooling capacities of 217 and 121 kw, and electrical power supply of 22.4 and 44.8 kw, respectively. In contrast to Wide/Narrow Body aircraft, Jumbos are equipped with two air input connections and are supplied with air through two flexible service hoses. For this reason, Jumbo-suited AHUs are equipped with dual air delivery facility as accessory. They serve smaller aircraft in single hose operation mode. The AHUs consist of air filter, fan (with frequency transformer), two cooling coils, electric heater, outlet plenum, and digital controls. Icing may occur at the first cooling coil only (seen in flow direction), which has much wider fin spacing than the second coil. Defrosting is achieved by controlling a built-in brine valve. The timer on the valve is set to around 90 seconds every approx. 17 minutes of operation. During the defrost cycle brine bypasses the cooling coil, so that any ice accumulated on the coil will melt by the hot outside air (as mentioned before, defrosting is required in summer only). The AHUs are installed under the passenger-boarding bridge cab and connected to the terminals using so-called services transportation units (STU), being a telescopic device to carry the brine and condensate water piping as well as cables and wires from the terminal to the front end of the bridge. The AHUs and STUs move together with the bridge cab some 10 times a day whereby bridge length, cab height, and bridge position vary depending upon the aircraft served (normal bridge length about 17.5 m retracted and 33.5 m extended, cab height between 4 and 7 m, bridge rotation by 180 ). The mounting brackets and the STUs are provided with some constructional technicalities to meet such high requirements. Supply air is delivered to the plane via a service hose. The service hose and its aircraft adapter are stored in a basket attached to the bridge. 3. CONCLUSIONS Compared with conventional APU-based systems, central PCA systems feature higher energy efficiency, lower levels of noxious emissions, fuel gas odors, and a 10-fold lower noise level at the airfield apron. For air-conditioning of parked aircraft, it is outside air and cooling supply that count. Heating is of minor importance. For Point-of-use PCA systems, the design of all equipment is determined by the maximum aircraft position occupancy. For central PCA systems, the maximum position occupancy is decisive only for the design of gate equipment. The design of central equipment is determined by the simultaneous aircraft position occupancy involving the beneficial application of diversity factors. The overall diversity factor for the central PCA plant at Athens Airport (ratio between central system cooling capacity and total gate equipment capacity) is as low as 31 %. The overall cooling load profile for the central PCA system shows various peaks and frequently occurring strong capacity fluctuations originated by respective flow fluctuations. Cooling demand exists also during the night. For central PCA systems, the method of capacity control is of high significance. The central cooling system requires sophisticated hydraulic connection of its components and as many as 6 operation modes. The AHUs for PCA differ to a great extent from AHUs used in normal HVAC applications. ACKNOWLEDGEMENT Thanks to the courtesy of caverion GmbH (formerly Krantz-TKT), especially to Dipl.-Ing. Detlef Makulla of the R&D Department, for having made available to me related material.
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw
INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company
Heat Pumps for Swimming Pools
Page 1 of 5 Heat Pumps for Swimming Pools This factsheet provides members with invaluable information about heat pumps and their use for heating swimming pool water. There is a consumer factsheet already
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets
2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.
Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Natural geothermal energy.
ROTEX ground source heat pump Natural geothermal energy. ROTEX HPU ground the ground source heat pump that heats with free geothermal energy. Compact, environmentally responsible and uniquely efficient.
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS
HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS INTRODUCTION 1. There are no general EU regulations and standards for outdoor swimming pool heating. Local regulations in the member countries are covering most
Basic Technology Series
Basic Technology Series Fundamentals of Car Air Conditioning 2007 Air Conditioning #003 The Rear Cooler Construction Fan Fan Filter Figure A : Trunk Figure B : Overhead Dual Air-Conditioner In This Issue
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
FOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
UNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
How To Use A Water Source Heat Pump
Geothermal Energy Using Water-Source Heat Pumps By VIRSTAR Corporation Geothermal Expertise Since 1978 All information contained herein is the exclusive property of VIRSTAR Corporation, all rights reserved.
FAN SYSTEM REPLACEMENTS IN HVAC EQUIPMENT TO IMPROVE ENERGY
FAN SYSTEM REPLACEMENTS IN HVAC EQUIPMENT TO IMPROVE ENERGY Thomas Heine, Dipl.-Ing. (BA), BSc (Hons) Market Manager EC Upgrades, ebm-papst A&NZ 10 Oxford Road, Laverton North VIC 3026 [email protected]
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
Field test of a novel combined solar thermal and heat pump system with an ice store
Field test of a novel combined solar thermal and system with an ice store Anja Loose Institute for Thermodynamics and Thermal Engineering (ITW), Research and Testing Centre for Thermal Solar Systems (TZS),
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
Enclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP [email protected] CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
The natural ombination
The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Crowne Plaza Copenhagen Towers The world s greenest hotel
Crowne Plaza Copenhagen Towers The world s greenest hotel The new Crowne Plaza Copenhagen Towers in Copenhagen, has been designed with sustainability in top of mind. The hotel is one of the first hotels
CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!
CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different
Challenges for air conditioning and heating solutions in electrobuses
Dr.-Ing. Robert Basile, Director R&D Challenges for air conditioning and heating solutions in electrobuses The energy supply to electric buses remains a major challenge. Against a background of limited
New Trends in the Field of Automobile Air Conditioning
New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic
Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling
for Simultaneous Heating and Cooling F. Sustainable Energy Centre, University of South Australia Mawson Lakes Boulevard, Mawson Lakes 5095 AUSTRALIA E-mail: [email protected] Abstract The high efficiency
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed
Tim Facius Baltimore Aircoil
Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of
SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM
SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM organization / project coordinator (address, telephone, email) Solel Solar Systems Ltd./ Mr. Avi Brenmiller 3, Hac'shara St, Industrial Zone
Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75
Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
Gree Solar Hybrid Hi Wall Inverter Air Conditioner
Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
ECO-AIR AIR CONDITIONING www.northamericanhvac.com
INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Research on the Air Conditioning Water Heater System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014
III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014 III.1. Large Roof Mount PN: 89-3037 Roof Mount Unit Eco 136 Parallel roof mount Air-conditioning and ventilation systems The Eco 136
Hybrid heat pumps. saving energy and reducing carbon emissions
Hybrid heat pumps saving energy and reducing carbon emissions Bart Aspeslagh Product planning and new technology manager, Daikin Europe NV. [email protected] Stefanie Debaets Design engineer,
How to choose a heat pump and use it wisely
How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
EHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions