Boiler Condensate Return Basics February 24, 2016

Size: px
Start display at page:

Download "Boiler Condensate Return Basics February 24, 2016"

Transcription

1 Boiler Condensate Return Basics February 24, Explain what you mean by saturated steam. A: Saturated steam is really saturated water which has been heated to the point where no additional Btu s are absorbed without the water changing state and becoming a vapor. When this pound of water, now steam, condenses, it gives off its latent energy, and becomes water again, and that is the condensate we want to capture. The hotter, the better! 2. Is it always possible to recover TDS controlling blowdown and save energy? A: It s always possible to save energy in this way, but the amount of the blowdown and frequency will dictate the payback potential, and if it equals a legitimate ROI. It s certainly worth looking at. 3. Isn t it possible to avoid stall by properly selecting the right trap with an adequate minimum static head; avoiding the use and cost of a power pump? A: Absolutely this is possible, but many times there is insufficient height (2.3 feet/pound) to provide the differential (static head) required at low loads for the trap to properly function. The last thing you want is for the heat exchanger to flood. 4. What is the maximum distance (not to exceed) for drip pocket placement in a straight length of pipe? A: Never more than 300 feet. 5. You mentioned condensate transfer pumps not having sufficient NPSH What s that? A: NPSH stands for Net Positive Suction Head which means the amount of static head required on the pump inlet at specific duty points including operating temperature, pumping rate and discharge pressure (TDH). Insufficient head will result in pump cavitation which reduces the pumping rate and tears up the pump. 6. Can you review the flash steam calculation again? A: Say you have condensate coming out of a process at 150# saturated and it is discharging into a 15# condensate line. You go to a steam table and note the sensible Btu s at 150# (338) and the sensible Btu s at 15# (218). Subtract the two (120) and divide that result by the latent Btu s at 15# (946). It will be about 13%.

2 7. Is it possible to have differential water hammer in a condensate line? A: Absolutely! As the amount of condensate increases, and the pressure differential increases as a result of higher pressure feeder lines discharging into the common condensate line, differential water hammer can result, potentially causing severe destruction. Remember, 7000 feet per minute velocity is about 80 MPH and a gallon of water weighs over 8 pounds 8. Should neutralizer kits be used to improve piping life? A: This answer really needs to come from a qualified water treatment expert. 9. How much is a cubic foot of condensate? A: One cubic foot contains approximately pounds of water. 10. Will the Condensate Return System eliminate the need for an Economizer? A: No. The economizer is used after the condensate has returned to the boiler feed system (vented receiver or deaerator), and then is pumped through the economizer to pick up additional heat from the boiler stack before the water is introduced into the boiler, saving additional energy. 11. We have a Machamer System for condensate return. We find ourselves not getting rid of condensate well enough, and our pressure vessels on the corrugator get water logged quite easily. What is the issue with the Cochran Pump/Machamer System that allows this to happen? A: If all of your steam traps on the corrugator are properly functioning (not fouled or plugged), the siphon tube is in its proper place with good working flexible joint(s), the return lines are properly sized for the pressure drop and amount of flash steam in the bi-phase line, and the boiler s operating pressure has not been raised or lowered, the pumping system should work properly. Is the Cochrane pump system piped to a modulating feed valve? If so, is this working properly? If not, it could be causing the condensate to back up because the pump is not allowed to fully discharge. What I m referring to here is a Cochrane balanced pumping system with no electric motor driving the pump to get the water in the boiler. 12. Can periodic blowdown of steam traps and strainers prevent or reduce water hammer? A: Possibly, if the trap is not fully closed after evacuating the condensate and (steam) blow through is occurring causing over pressurization of the condensate line which could lead to both thermal and differential water hammer.

3 13. What is the determining factor in selecting a FT or a thermodynamic trap and is it based on condensate load? A: Suggest you go to our website (cleaverbrooks.com) and under archived webinars, find the Boiler Steam System Supply Basics webinar (November 2015). All the popular traps are reviewed with their respective pros & cons. Then, depending on your particular situation you can begin evaluating your best option. 14. How does cold make-up water impact the operation of the boiler feed water system? A: Two problems with this: One, you reduce the feed water temperature, and for every 10 degree drop you lose 1% in efficiency. Two, the colder water entering the boiler could thermally shock it causing pressure vessel issues such as cracking of tube ligaments and boiler tube failure. In both of these cases I m referring to a firetube boiler. 15. How can someone identify how much condensate is being returned? A: You need to install a steam flow meter and a water meter to first determine the amount of steam going out to the system. This steam is water in vapor form. There are 8.3 pounds per gallon of water. Next with your water meter, you determine how much water you are taking in to make up for the condensate lost if there is any. If there is makeup, the difference from the steam out converted to gallons minus the gallons of makeup is your answer. In many cases where steam is not lost to the process, the amount of condensate returned is 75 85%. 16. In the diagram for a steam powered trap, there was a second steam trap downstream of the steam powered trap. What is the purpose for installing back to back steam traps? A: The power steam pump is only in play when the modulating steam valve controlling heat to the process is closing. This causes a loss of differential on the downstream trap. When this occurs, the steam power pump begins to fill and evacuates the condensate through the downstream trap which has lost its differential until the steam modulating valve goes full open again. 17. When is discharging condensate from a MP system into a LP pumped condensate return line ok? A: It s OK if the resultant effluent coming from the medium pressure line is properly flashed off or diffused into the LP line, and the LP line is sized properly to accommodate any remaining flash while not exceeding the pressure drop tolerance. Remember too, the condensate pump only pumps liquid so all flash has to be gone at this point.

4 18. How high should the column of steam from the vent of the receiver be? A: If you are talking about venting flash steam through the roof the steam plume height will vary based on the pounds of flash being evacuated and the size of the vent line. Regardless, this is very wasteful. 19. How should low pressure condensate return and high pressure condensate return systems be combined when feeding back to a common boiler? A: The high pressure line should probably go to a flash tank where the flash steam can either be vented or recovered as explained in the program today. It would then be taken to the low pressure line where it should be diffused into the common return. Refer to today s program again for the criteria which needs to be considered for properly sizing this common return line. 20. Please explain again how CO2 is formed from the condensing process. A: The carbon dioxide I was referring to enters the feed system from the carbonate and bicarbonate alkalinity entering in from the raw makeup water. Once heated, it turns to carbon dioxide, a non-condensable gas, now carried along with the steam. When the steam condenses, the CO2 combines with the condensate and forms carbonic acid (H2CO3). 21. Can you have Steve explain the Float & Thermostatic trap after the Pressure Power Pump again, specifically how the pressure differential works when there are differences in the condensate loads. A: See question #16 above. 22. Do high pressure condensate receivers negate the use of steam traps? A: Absolutely not. The trap is there to trap steam and evacuate the hot condensate. Without the trap you would be blowing live steam through your condensate return line causing all sorts of problems and considerable energy waste. 23. How do you recommend connecting different pressure condensate lines together into one header if the boiler plant is far away in another building? A: You have a couple possibilities: One, take the condensate into a single medium to high pressure line (if this is what you have), sized for the blended effluent which will be a combination of liquid and steam (bi-phase). Based on the pressure now in the line (provided it s constant), size the line to account for the line transport loss and bring it directly to the DA or a high pressure receiver using the motive force exerted at the inlet of each trap. Two, bring the high pressure condensate into a flash tank or flash tank/recovery system before going to a low pressure common return with an adequately sized condensate pump to deliver the hot condensate back to the boiler room.

5 24. How do you size vertical condensate line that discharges into main header? A: It is all about the differential pressure through the trap and the height of your vertical condensate line above the trap s outlet. For every 2.3 feet you have 1# of pressure you have to overcome. Then, depending on the size of the vertical pipe, and the flow rate through it, there will be some friction loss, but this will be minimal if the pipe ID is not too small. 25. Do you recommend sloping the main condensate line before the main condensate pump and if so how much slope? A: A good rule of thumb is about 1 per 10 feet.

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound. Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of

More information

Steam System Best Practices Condensate System Piping

Steam System Best Practices Condensate System Piping Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum

More information

HS-901(A) BASIC STEAM HEATING SYSTEMS

HS-901(A) BASIC STEAM HEATING SYSTEMS HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,

More information

Steam System Efficiency. Bill Lumsden Leidos Engineering

Steam System Efficiency. Bill Lumsden Leidos Engineering Steam System Efficiency Bill Lumsden Leidos Engineering Steam System Efficiency Steam System Efficiency Key Take-aways: Review of the properties of ice, water, and steam Learn the basics of steam trap

More information

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy

More information

Heating Water by Direct Steam Injection

Heating Water by Direct Steam Injection Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space

More information

Steam Coil Installation, Operation and Maintenance

Steam Coil Installation, Operation and Maintenance Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been

More information

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University

More information

UNDERSTANDING REFRIGERANT TABLES

UNDERSTANDING REFRIGERANT TABLES Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,

More information

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance

More information

Gas Line Sizing. Z Maximum gas demand shall be determined by adding all of the equipment Btu ratings from appliances connected on the system.

Gas Line Sizing. Z Maximum gas demand shall be determined by adding all of the equipment Btu ratings from appliances connected on the system. Gas Line Sizing When sizing Gas piping systems certain factors must be considered. They are: Z It shall provide sufficient gas to meet the maximum demand of the gas equipment. Piping must be sized to supply

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

REGULATING VALVE APPLICATIONS

REGULATING VALVE APPLICATIONS REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Regulator Application & Installation Notes The following are considerations for all steam regulator installations, as system operation

More information

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7 Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator

More information

Steam Generation Efficiency Module Blowdown Losses Section

Steam Generation Efficiency Module Blowdown Losses Section Steam End User Training Steam Generation Efficiency Module Blowdown Losses Section Slide 1 Blowdown Losses Module This section will discuss blowdown loss and its affect on boiler efficiency. [Slide Visual

More information

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409 Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam

More information

Some Criteria for Choosing a Steam Boiler for a Microbrewery

Some Criteria for Choosing a Steam Boiler for a Microbrewery Some Criteria for Choosing a Steam Boiler for a Microbrewery Jack Coe Rite Engineering and Manufacturing Corporation Breweries rely on steam heating for a number of functions, primarily to heat the brew

More information

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank Unbiased, Third-Party, Water & Energy Management Consulting Firm: - Not affiliated

More information

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,

More information

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &

More information

Steam System Design and Best Practices Related to Kiln Drying

Steam System Design and Best Practices Related to Kiln Drying Steam System Design and Best Practices Related to Kiln Drying New England Kiln Drying Association Steam Design and Best Practices HerLine Technologies What is Steam? Like other substances water can exist

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat

More information

BOILER FEED AND CONDENSATE RECOVERY SYSTEMS Extend the life and efficiency of your boiler system

BOILER FEED AND CONDENSATE RECOVERY SYSTEMS Extend the life and efficiency of your boiler system BOILER FEED AND CONDENSATE RECOVERY SYSTEMS Extend the life and efficiency of your boiler system INTEGRATE BOILER FEED AND RECOVERY TO GET THE MOST FROM YOUR BOILER SYSTEM. Increase the safety, reliability,

More information

How To Clean Up A Reactor Water Cleanup

How To Clean Up A Reactor Water Cleanup General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component

More information

Energy Saving Solutions. Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing

Energy Saving Solutions. Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing Energy Saving Solutions Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing Combustion Efficiency Measure Heat Recovery Energy Saving Solutions Upgrade Repair Replace Audits Financial

More information

C. starting positive displacement pumps with the discharge valve closed.

C. starting positive displacement pumps with the discharge valve closed. KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the

More information

Forgotten savings: Heat recovery from surface blowdown

Forgotten savings: Heat recovery from surface blowdown Forgotten savings: Heat recovery from surface blowdown 1. Introduction The purpose of this article is to inform thermal plant operators of the interesting fuel savings that can be obtained by recovering

More information

A basic introduction to steam

A basic introduction to steam A basic introduction to steam FOR HOT, COLD, MOIST AND DRY, FOUR CHAMPIONS FIERCE. STRIVE HERE FOR MASTERY Milton 1666 Steam Wonderful Steam Very high heat content Recyclable Clean, non toxic Biodegradable

More information

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng Condensing Economizers Workshop Enbridge Gas, Toronto MENEX Boiler Plant Heat Recovery Technologies Prepared by: Jozo Martinovic, M A Sc, P Eng MENEX Innovative Solutions May 15, 2008 MENEX INC. 683 Louis

More information

Energy Saving Ideas for Your Box Plant

Energy Saving Ideas for Your Box Plant General Session Energy Saving Ideas for Your Box Plant Moderator: Jeff Pallini Fosber America, Inc. Program Overview: Immediate Ideas: Jim Simko of Simtek Systems, Inc. Mid-Term Ideas: John Donahue of

More information

IGEMA BOILER LEVEL & TDS CONTROLS

IGEMA BOILER LEVEL & TDS CONTROLS IGEMA BOILER LEVEL & TDS CONTROLS IGEMA offers boiler level and TDS control products of the highest quality standard, being certified to ISO 9001. Made in Germany, IGEMA products are manufactured in compliance

More information

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

HOW TO SELECT A LOW VOLUME (L.V ) BOILER HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement

More information

Frequently Asked Questions Generators

Frequently Asked Questions Generators Frequently Asked Questions Generators Fuel Related How much fuel do the generators use during normal operation? At exercise? The generator fuel consumption is given in each of the product knowledge books

More information

Boiler Preparation, Start-Up and Shutdown

Boiler Preparation, Start-Up and Shutdown Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.

More information

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 TABLE OF CONTENTS Description Page Number SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 Indeck Keystone Energy, LLC. 5451 Merwin Lane, Suite 100 Erie,

More information

Float and Thermostatic Traps Series H, C and X

Float and Thermostatic Traps Series H, C and X Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT

More information

Recover Heat from Boiler Blowdown Water

Recover Heat from Boiler Blowdown Water Prepared for California Energy Commission (CEC) Prepared By: Southern California Gas Company (A Sempra Energy Utility) E3M Inc. May 2012 i Disclaimer The CEC and its contractor, Southern California Gas

More information

How does solar air conditioning work?

How does solar air conditioning work? How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

HOT WATER SYSTEMS CONTENTS

HOT WATER SYSTEMS CONTENTS HOT WATER SYSTEMS CONTENTS MECHANICAL CONSIDERATIONS.............................................. 3 Code Considerations..................................................... 3 Boiler Selection Considerations..............................................

More information

Boiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown

Boiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown Boiler Blowdown Even with the best pretreatment programs, boiler feedwater often contains some degree of impurities, such as suspended and dissolved solids. The impurities can remain and accumulate inside

More information

Energy Efficiency in Steam Systems

Energy Efficiency in Steam Systems Energy Efficiency in Steam Systems Fundamentals of Energy Efficiency: An Introductory Workshop April 2008 John S. Raschko, Ph.D. Mass. Office of Technical Assistance www.mass.gov/envir/ota (617) 626-1093

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers. Michael Pace Lead Engineer C & I Efficiency Programs

Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers. Michael Pace Lead Engineer C & I Efficiency Programs Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers Michael Pace Lead Engineer C & I Efficiency Programs Agenda Energy Efficiency Opportunities for Small/Mid Commercial Facilities

More information

DESIGN OF FLUID SYSTEMS STEAM UTILIZATION

DESIGN OF FLUID SYSTEMS STEAM UTILIZATION DESIGN OF FLUID SYSTEMS STEAM UTILIZATION Published by $19.95 per copy Copyright 2004 by Spirax Sarco, Inc. All Rights Reserved No part of this publication may be reproduced, stored in a retrieval system

More information

RECON WATER HEATER INSTALLATION FORM

RECON WATER HEATER INSTALLATION FORM RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM.

More information

VACUUM REFRIGERATION SYSTEMS

VACUUM REFRIGERATION SYSTEMS VACUUM REFRIGERATION SYSTEMS CHILL VACTOR The Croll-Reynolds CHILL-VACTOR is a chiller that uses a vapor flashing process. Water has a pressure-temperature relationship which is its boiling point. If its

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Energy Efficient Operations and Maintenance Strategies for Boilers

Energy Efficient Operations and Maintenance Strategies for Boilers Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must

More information

How To Clean Water From An Ammonia Refrigeration System

How To Clean Water From An Ammonia Refrigeration System Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

FLASH TANK ECONOMIZER PRODUCT GUIDE

FLASH TANK ECONOMIZER PRODUCT GUIDE FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

Desuperheater Online Program Sizing Guidance

Desuperheater Online Program Sizing Guidance Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

steam centre of excellence Steam Boiler System Optimization

steam centre of excellence Steam Boiler System Optimization Steam Boiler System Optimization Introduction Gas Cost Metering Fluids Fuel, Water, Steam Steam Costs Boiler House Stack Losses Boiler Waterside Surfaces Blowdown Current Natural Gas Cost Projected Cost

More information

No. Name Description Main input Data Main Output Data. cooling duty, process in/out temperature, inlet air temperature

No. Name Description Main input Data Main Output Data. cooling duty, process in/out temperature, inlet air temperature 1 AIRCOOLER Air cooler preliminary sizing cooling duty, process in/out temperature, inlet air temperature No of fans, Air cooler Dimension, bare area, no of rows, Fan Diameter, fan power 2 BLOW DOWN FACILITATOR

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

Selection Of Centrifugal Pumping Equipment 1

Selection Of Centrifugal Pumping Equipment 1 Circular 1048 Selection Of Centrifugal Pumping Equipment 1 Dorota Z. Haman, Fedro S. Zazueta, Forrest T. Izuno 2 INTRODUCTION The pump is an essential component of an irrigation system. Proper selection

More information

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain

More information

Energy Saving Fact Sheet Boilers

Energy Saving Fact Sheet Boilers Energy Saving Fact Sheet Boilers Turn a burning issue into real energy savings You need a boiler to heat your premises and provide hot water or to generate steam for use in industrial processes. Unfortunately,

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging

More information

ENERGY RETROFIT PROGRAM

ENERGY RETROFIT PROGRAM ENERGY RETROFIT PROGRAM An innovative but simple retrofit for existing hot water and chilled water piping systems that will help you save money. REDUCE FLOW BY 50% REDUCE PUMP HEAD BY 75% REDUCE PUMP POWER

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

MFP14, MFP14S and MFP14SS Automatic Pumps

MFP14, MFP14S and MFP14SS Automatic Pumps Page 1 of 6 TI-P136-02 ST Issue 12 Cert. No. LRQ 0963008 ISO 9001, S and SS utomatic Pumps Description The Spirax Sarco automatic pump is a displacement receiver operated by steam or compressed air. It

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

OIL & GAS PRODUCTION AUDITING

OIL & GAS PRODUCTION AUDITING OIL & GAS PRODUCTION AUDITING Wayne C. Dussel Offshore Measurement Supervisor El Paso Production GOM Basic Measurement Audit Steps I. Select location (s) to be reviewed. II. Review contracts, commingling

More information

Industrial Steam System Process Control Schemes

Industrial Steam System Process Control Schemes Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental

More information

Facility Operations Physical Safety Guidance Document

Facility Operations Physical Safety Guidance Document Facility Operations Physical Safety Guidance Document Title: Guide on Pipe Identification Standards (ASME A13.1-1996) Original Date: December 18, 2000 Section: 4.0 Facility Operations Revised Date: Number:

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from

More information

Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency

Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency For many years competent professional HVAC engineers have been aware of exaggerated or deceptive

More information

UNIT 2 REFRIGERATION CYCLE

UNIT 2 REFRIGERATION CYCLE UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E. Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics

More information

Maximizing Boiler Plant Efficiency. Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc.

Maximizing Boiler Plant Efficiency. Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc. Maximizing Boiler Plant Efficiency Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc. Efficient Boiler Design Boiler Types Efficiency Definition Non-Condensing Condensing Maximizing Efficiency

More information

Factory owners must ensure the boiler is:

Factory owners must ensure the boiler is: Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised

More information

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities Water Efficiency Water Management Options Boilers for Commercial, Industrial and Institutional Facilities Boiler Water Impurities All boiler make-up water contains impurities. As clean steam is released

More information

Less Exhaust Gas Less Pollution More Dollar Savings

Less Exhaust Gas Less Pollution More Dollar Savings Less Exhaust Gas Less Pollution More Dollar Savings CASE STUDIES Dow Corning - RTV Silicone Plant ConDex System utilized to heat boiler make up water from 50 F up to 180 F with recovered energy from boiler

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

1 DESCRIPTION OF THE APPLIANCE

1 DESCRIPTION OF THE APPLIANCE 1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers

More information

Problems with Hypo: Best Design Practices for Smooth and Efficient Sodium Hypochlorite Feed Systems Chad Hantelman, City of Bremerton Jeff Zahller,

Problems with Hypo: Best Design Practices for Smooth and Efficient Sodium Hypochlorite Feed Systems Chad Hantelman, City of Bremerton Jeff Zahller, Problems with Hypo: Best Design Practices for Smooth and Efficient Sodium Hypochlorite Feed Systems Chad Hantelman, City of Bremerton Jeff Zahller, PE, HDR Engineering Outline Common Options Available

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Energy and Cost Required to Lift or Pressurize Water

Energy and Cost Required to Lift or Pressurize Water University of California Tulare County Cooperative Extension Energy and Cost Required to Lift or Pressurize Water Bill Peacock, Tulare County Farm Advisor Pub. IG6-96 Power Requirements to Lift Water It

More information

Best Practice in Boiler Water Treatment

Best Practice in Boiler Water Treatment Best Practice in Boiler Water Treatment Boiler Water Treatment Part 2 Internal Treatment Objectives of Internal Water Treatment 1 To control the level of total dissolved solids (TDS) within the boiler

More information

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2 WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials

More information

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose: PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters When water is heated, it naturally expands and allowance has to be made for this. Vented water heaters usually

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 38 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia CAUSTIC AND CHEMICAL TABLE OF CONTENT

More information

from the turbine manufacturer.

from the turbine manufacturer. Specifying Steam Surface Condensers by Elliot Spencer Graham Mfg.Co., Inc., Great Neck, Long Island, N.Y. Factors affecting condenser design and selection. A typical air conditioning surface condenser

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability. Codes and High Performance Hot Water Systems Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Annual Energy Use for Heating Water Natural Gas Gallons Per Day

More information

Heat Recovery In Retail Refrigeration

Heat Recovery In Retail Refrigeration This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information