MICROGRIDS BLACK START AND ISLANDED OPERATION
|
|
|
- Bertha Skinner
- 9 years ago
- Views:
Transcription
1 MICROGRIDS BLACK START AND ISLANDED OPERATION J. A. Peças Lopes, C. L. Moreira, F. O. Resende INESC Porto Instituto de Engenharia de Sistemas e Computadores do Porto and FEUP Faculdade de Engenharia da Universidade do Porto Rua Dr. Roberto Frias 378, Porto, Portugal [email protected] Abstract A low voltage distribution network with large amounts of small sized dispersed generation can be operated as an isolated system in certain conditions. This paper presents the control strategies to be used in such a system to deal with islanded operation and to exploit the local generation resources as a way to help in power system restoration after a general blackout. A sequence of actions for the black start procedure is identified and it is expected to be an advantage for power system operation in terms of reliability as a result from the presence of a very large amount of dispersed generation. Keywords: microgrids, power system restoration, microgenerators, energy storage, islanded operation 1 INTRODUCTION Following the increasing penetration of Dispersed Generation (DG) in Medium Voltage (MV) networks, the connection of microgeneration to Low Voltage (LV) grids starts attracting attention due to its potential for reducing greenhouse gas emissions, increasing reliability to final consumers and positive impacts it may carry to global system operation, planning and expansion. In this context, a new concept the MicroGrid (MG) is under development. A MG corresponds to a LV electrical grid where electrical loads and small generation systems (fuel cells, microturbines, wind generators, photovoltaic panels) together with storage devices (like flywheels and batteries) coexist through an embedded management and control system [3]. If a general or local blackout occurs, local generation capabilities in the LV grid can be exploited to reduce customer interruption times by: a) providing a fast black start recovery in the LV grid; b) allowing MG islanded operation to feed local consumers until the MV network becomes available. Conventional power system restoration is a very complicated process, usually involving tasks carried out manually according to predefined guidelines [1]. They have to be completed in a fast way, in a real-time basis and under extreme stressed conditions. The complexity of this process makes decision support tools extremely valuable to assist system operators [2]. In a MG the whole restoration procedure is much simpler because of the reduced number of controllable variables (loads, switches and microsources). On the other hand, most of the microsources (MS) are not suitable for a direct connection to the LV grid due to the characteristics of the electric power produced in such units. Usually a DC/AC or AC/DC/AC power electronic interface is required. Furthermore, it is not expected to have fully controllable synchronous generators directly connected to the LV grid, which will be liable for controlling system frequency and voltage (balance of load and generation). A scenario with the absence of controllable synchronous in a MG demands some of the MS inverters to be capable of emulating a synchronous machine operation in order to allow running into islanded mode in parallel with other MS. These units play a key role in the restoration process, as discussed in this paper. MS specificities (like primary source response time constants, intermittency of renewable energy sources, technical limits), the control characteristics of the power electronic interfaces and its thermal limitations lead to the identification of very specific restoration sequences. After understanding the interaction among MS and local controllable loads, it is possible to define a totally automatic procedure for MG restoration, since a central control and a communication infrastructure are available. Under the MG concept such approach is possible due to specific control architecture and to the possibility of establishing communication among different types of controllers spread over the LV network. In this paper an identification of a sequence of actions to be carried out during the MicroGrid Black Start (BS) is presented and discussed. Two inverter control techniques are described and combined to find a suitable approach for LV distribution system restoration and ensure its stable operation. In order to identify the restoration sequences two simulation platforms were developed and exploited when dealing with a LV study case network: an EMTP-RV tool used to analyse initial fast transients and a MatLab Simulink simulation platform used to evaluate the longer term dynamic behaviour of the islanded MG. 2 MICROGRID ARCHITECTURE As mentioned before, a MG involves a LV electrical grid, loads (some of them interruptible), controlled and uncontrolled MS, storage devices and a hierarchicaltype management and control scheme supported by a communication system [3]. Such concept has been developed within the framework of the EU R&D Micro- Grids project [3]. In this architecture the MG is controlled and managed by a MicroGrid Central Controller (MGCC) installed at the MV/LV substation. The MGCC possesses several key functions (such as load forecasting, demand 15th PSCC, Liege, August 2005 Session 27, Paper 4, Page 1
2 side management, economic scheduling of microgenerators, security assessment, etc.) and heads the hierarchical control system. In a second hierarchical control level, controllers located at loads or groups of loads (LC) and controllers located at the microsources (MC) exchange information with the MGCC and control local devices. Figure 1: Microgrid with several microsources, loads, control and management equipment The whole system operation requires communication and interaction between two sets of devices: LC on one hand, as interfaces to control loads through the application of an interruptability concept, and on the other hand MC controlling microgeneration active and reactive power production levels. The MGCC, as central controller, promotes adequate technical and economical management policies and provides set-points to LC and MC. In the approach described in this paper, the MGCC is also responsible for local BS functionalities. The BS procedure identified in advance, together with system technical limitations, will be embedded in the MGCC as a software module. It is important to understand that the amount of data to be exchanged among the several network controllers is small, as it includes mainly set-points to LC and MC, information about the active and reactive powers and voltage levels or messages to control the LV system restoration. At the same time, the MG covers a small geographical area. These factors contribute to ease the establishment of the required communication system. 3 DYNAMIC MODELS This section provides a brief explanation on the dynamic models adopted for MS and power electronic interfaces used in the simulation tools. 3.1 Microsource Modelling Several MS technologies were considered to coexist in the MG and the corresponding dynamic models were derived. A detailed description of the models adopted for solid oxide fuel cells (SOFC) and single shaft microturbines (SSMT) can be found in [4]. A small asynchronous wind generator (fixed speed) directly connected to the LV grid was also included in the simulation platforms. Details of the maximum power tracking control system were not included in the PV model. Instead, it was assumed that the array is always working at its maximum power level for a given temperature and irradiance as described in [5]. Storage devices like flywheels and batteries are modelled as constant DC voltage sources (taking into account the time span under analysis) coupled with static converters to be connected to the LV electrical network. Usually its active power is injected into the MG proportionally to the frequency deviation [6]. 3.2 Inverter Modelling Several MS, such as SSMT, SOFC and PV are not suitable for supplying power directly to the grid, since either this electricity generation is in DC form or it is generated as AC at high frequencies. Inverters are then needed to provide AC grid interface. Inverter control strategies are crucial for an adequate MG operation. Inverter controls can be divided into two types [7]: a) PQ inverter control; b) Voltage Source Inverter (VSI) control logic. It is important to mention that when analysing the dynamic behaviour of the MG, inverters detailed modelling is usually avoided. Inverters long term dynamic models are represented by their control functions. This means that fast transients related with commutation of the solid state switches are not considered, assuming, in this way, that power is injected at the AC side without harmonics, distortions, losses or delays. If a transient analysis is required this approach demands instead a full representation of the inverter. 1) PQ Inverter Control A PQ inverter control corresponds to a combined control of both inverter and primary energy source, when this becomes physically possible. This means that the inverter only injects into the grid the power available at its input. An example of the application of a PQ control stays in a PV unit. The reactive power injected corresponds to a pre-specified value defined locally or from the MGCC. The PQ control of an inverter can be performed using a current control technique: the inverter current is controlled in amplitude and phase to meet the desired set-points of active and reactive power [8]. 2) Voltage Source Inverter Control In this case the inverter is controlled to feed the load with pre-defined values for voltage and frequency according to a specific control strategy. The control principle of a VSI to be installed in a MG should emulate the behaviour of a synchronous machine. There is thus a possibility to control voltage and frequency on the AC system by means of inverter control. Considering such a VSI operating in parallel with an AC system with angular frequency ω grid, the active output power of the VSI is automatically defined by the well known frequency droop characteristic, as depicted in Figure 2. Dispatching the inverter output power can be achieved by means of a convenient modification on the idle frequency (ω 01, ω 02 ). If the main AC system is lost, 15th PSCC, Liege, August 2005 Session 27, Paper 4, Page 2
3 the output power of each inverter is adjusted according the droop settings and the network frequency drifts towards a new value. The active power is shared among the inverters at the new frequency value according to these droop characteristics. Frequency variations provide an adequate way to define power sharing among several VSI operating in parallel in an islanded grid [9]. Similar considerations can be made in what concerns the voltage/reactive power control, using also a voltage droop concept [11]. A three-phase balanced model of a VSI implementing these two droop concepts was derived from a single-phase version presented in [10] and is shown in Figure 4. Figure 2: Active power versus frequency droops The VSI terminal voltage and current are measured to compute active and reactive power levels. This measuring stage introduces a delay that corresponds to a decoupling, performed through the Decoupling transfer functions shown in Figure 4. The active power determines the frequency of the output voltage by the active power/frequency droop (K f ). Similarly, the reactive power determines the magnitude of the output voltage by the reactive power droop (K v ). A phase feedforward control was included for stability purposes [10], corresponding to the K ff loop in Figure 4. 4 CONTROL STRATEGIES FOR MICROGRIDS OPERATION If there are no synchronous machines to balance demand and supply, inverters should be responsible for controlling frequency during islanded operation. A voltage regulation strategy is also required; otherwise the MG could experience voltage and/or reactive power oscillations [9, 12]. If a cluster of MS is operated within a MG and the main power supply (the MV network) is available, all the inverters can be operated in the PQ mode, because a voltage and frequency reference is available. However if the MV network is lost all the inverters will shut down because there will not be a voltage reference within the MG and it will not be possible to obtain an exact balance between load and generation. This means that a general frequency control strategy should be followed in order to operate the MG in islanded mode. Two main strategies are possible: - Single Master Operation (SMO): A VSI is used to provide the reference voltage when the main power supply is lost; - Multi Master Operation (MMO): Two or more inverters are operated as VSI; The presence of a VSI unit is crucial in order to provide a voltage and frequency reference during the emergency mode. A VSI has the ability to react to power system disturbances (for example, load-following or wind fluctuations) based only on information that is available locally at the inverter voltage and current measurements [11]. Such a VSI should be coupled with a storage device with a limited capacity in order to be able to compensate natural load and production variations. This is an important issue for a successful BS and islanded operation. 4.1 Single Master Operation In a SMO mode, most of the MS are connected to the network through inverters with a PQ control type and a single VSI inverter associated with an energy storage device the master that provides the frequency reference, as depicted in Figure 3. Figure 3: SMO architecture sin(u) 1 T dp s s 2π sin(u ) 3 2π sin(u+ ) 3 1 T dq s + 1 Figure 4: VSI three phase control model 15th PSCC, Liege, August 2005 Session 27, Paper 4, Page 3
4 Such VSI should be responsible for fast load-tracking. If necessary droop settings of the VSI can be changed from the MGCC according to the operating conditions and in order to avoid large frequency excursions. In this case, PQ controlled MS can receive from the MGCC setting points or can adopt a local PI frequency control, defining target values for active output powers of its primary energy sources. Assuring a zero frequency deviation during any islanded operating condition should be considered as a key issue for any control strategy. As a matter of fact such procedure is needed to avoid storage units to inject (or absorb) active power whenever the MG frequency deviation is different from zero. 4.2 Multi Master Operation In a multi master approach, there are several inverters operating as VSI with a pre-defined frequency/active power and voltage/reactive power droop. Other PQ controlled inverters may also coexist. Figure 5: MMO architecture Correction of MG frequency deviations can be performed by changing the idle frequency value (defined in Figure 2), as used in proportional integral frequency governors of synchronous generators. Change of the idle frequency can instead be performed centrally by the MGCC, as a kind of centralized secondary control, using the communications infrastructure. In this control strategy the issue of obtaining a zero frequency deviation is also a driving concern, as in the SMO approach and for the same reasons. 5 MICROGRID BLACK START The MG black start involves a sequence of control actions, defined through a set of rules and conditions to be checked during the restoration stage. These rules are identified in advance and embedded in MGCC software. 5.1 General Assumptions The success of a MG restoration procedure requires availability of some MS with BS capability, which involves an autonomous local power supply to feed local auxiliary control systems and to launch generation. However the MS restart procedure is not dealt in the work presented in this paper. The implementation of BS functionalities in a MG with an architecture as the one described before, is possible since there is also availability for: - Bidirectional communication between the MGCC and local controllers (MC and LC); - Updated information, obtained before disturbance, about the status of load/generation in the MG and about availability of MS to restart. - Automatic load disconnection after system collapse to avoid large frequency excursions and MS overload during the initial stages of the restoration procedure; - Capability to disconnect the MV/LV Distribution Transformer (DT) from the MV network, before starting the BS procedure; - Capability for LV network area separation. The BS procedure was developed assuming that MS with BS capability (SSMT and SOFC) have storage devices (batteries or supercapacitors) in the DC bus of their inverters and the MG adopts, at least during the first stages of this sequence, a multi master control approach. In order to operate in a MMO mode these inverters operate as VSI. During normal operation the MGCC periodically receives information from LC and MC about consumption levels and electric production and stores this information in a database. It also has information about the technical characteristics of the different MS, like active and reactive power limits. 5.2 Sequence of Actions for MG Black Start After a system blackout, the MGCC will try to restore the last MG load scenario. The main problems to deal with during the restoration procedure include building the LV network, connecting microgenerators, controlling voltage, controlling frequency and connecting controllable loads. Considering these problems the following sequence of actions for MG restoration should be carried out: - Disconnection of all loads in order to avoid large frequency and voltage deviations when energizing the network. The MG should also be sectionalized around each MS with standalone restart capabilities in order to allow it to feed its own (protected) loads. These actions lead to the creation of small islands inside the MG to be synchronized later. - Building the LV network. The MGCC decides which MS energizes the LV cables and the DT based on information about rated powers, load percentage or other market conditions. In order to comply with the LV grid earthing safety procedures [13] when building the LV network, it is necessary to energize the DT as soon as possible, since the earth connection is performed at the DT neutral point and it is restored only after DT energization. When energizing the transformer by the LV side, a large inrush current is experienced, and cannot be supported by the electronic components of the inverters. To overcome this problem, transformer energization should be performed using a ramp-wise voltage generated by the inverter of the MS selected for this task. - Small islands synchronization. MS already in operation in standalone mode should be synchronized 15th PSCC, Liege, August 2005 Session 27, Paper 4, Page 4
5 with the LV network. The synchronization conditions (phase sequence, frequency and voltage differences) should be verified by local MC in order to avoid large transient currents and power exchanges. If there are controllable MS without BS capability, they can then also be synchronized with the LV to supply their local controls and prepare to launch generation. - Connection of controllable loads to the LV network is performed if the MS running in the LV network are not at fully loaded. The amount of power to be connected should take into account the available storage capacity in order to avoid large frequency and voltage deviations during load connection. - Connection of non-controllable MS, like PV and wind generators. At this stage the system has MS and loads capable of smoothing voltage and frequency variations due to power fluctuations in noncontrollable MS, so they can now be connected. - Load increase. In order to feed as much load as possible, depending on production capability, other loads can then be connected. - MG synchronization with the MV network when it becomes available. The synchronization conditions should be verified again. Before a general blackout two situations can occur: the MG is importing power or the MG is exporting power to the MV network. If the MG was importing power, it will not be possible to connect all the local loads. In this case, remaining unsupplied load can then be restored. creation of islands operating in standalone mode with the SSMT and the SOFC. The sequence of actions defined for MG black start, described in section 5, was tested in the simulation platforms and analysed through the results obtained. Network behaviour during BS initial stages was evaluated with the EMTP-RV platform, including in this case the inverter commutation details. The general dynamic behaviour of the MG was analysed using the MatLab Simulink platform. Figure 6: Study case LV network. 6 SIMULATION PLATFORMS Two simulation platforms were implemented under EMTP-RV and MatLab Simulink environments in order to evaluate the transient and dynamic behaviour of several MS and the corresponding power electronic interfaces during the BS sequence. To analyse, in a more detailed way, the initial behaviour of the MG restoration process, the EMTP-RV platform was used. This required implementing the MS models and their controls to these simulation platforms. At this stage of the carried research only three-phase balanced operation of the MG was considered. A study case LV network was defined by NTUA within the MicroGrids project [3] and was used in this research. This network is shown in Figure 6. The simulation platform developed under EMTP-RV is presented in Figure 7. A similar platform was also developed under MatLab Simulink. Because of space limitations this simulation platform is not presented in the paper. 7 RESULTS For this LV test system it was assumed that a general collapse took place and was followed by: a) the disconnection from the MV grid of the MV/LV transformer; b) the disconnection of the loads and c) the automatic Figure 7: Study case LV network in EMTP-RV platform. 15th PSCC, Liege, August 2005 Session 27, Paper 4, Page 5
6 As the other MS are assumed to be feeding their protected loads, the storage device shown in Figure 6 was selected for energizing the LV network and the DT at t=0.5s, using a voltage ramping control in this inverter, through 0.5 seconds. The obtained inverter current is presented in Figure 8 and it can be observed that the DT magnetizing current was kept in low values. remains for some time a local secondary control is used. Voltage and reactive power control can be easily performed by adjusting the droop settings of each VSI or the reactive set-point of PQ inverters. Synchronizations Figure 8: Storage inverter current during the initial BS stage As mentioned previously, after energizing the DT and building the LV network, the next step of the MG black start procedure is the synchronization of both SOFC and SSMT operating in standalone mode and feeding their protected loads. To check the synchronization conditions the MGCC sends instructions to the VSI inverters (initially to the SOFC and later to the SSMT) to produce a small frequency change, as it can be seen in Figure 9 (at t=1.8s and t=4.5s). After synchronizing the SOFC and SSMT it is possible to connect some controllable loads and non-controllable MS. Figures 9 and 10 show the impact of these control actions in the VSI frequencies and MS active power outputs, with SOFC and SSMT being synchronized at t=2.3s and t=4.6s respectively. The impact in the storage inverter current resulting from these synchronizations can also be observed in Figure 8. Figure 9: Frequency in each VSI. Load connection It can be observed in Figure 10 that active powers present some small oscillations. These oscillations are the result of VSI filter interactions and occur in the absence of active damping of the loop formed by the filter capacitors and the tie-line inductance [11]. These oscillations are not uncommon in power systems and can be damped by the inverters, given sufficient inverter bandwidth [11]. In order to get an extended overview of the BS sequence, the MG MatLab Simulink platform was used. The results obtained for VSI frequencies, active and reactive power outputs and bus voltages are described in next figures. In this case, in less than 1/3 of EMTP simulation time it is possible to get these results. Load reconnection is a critical issue in this procedure because of frequency deviation it induces, requiring therefore a special attention. If a frequency deviation Figure 10: Active power in each VSI. Active Power (kw) Frequency (Hz) SOFC SSMT STORAGE Time (s) Figure 11: Active power and frequency at each VSI During the BS procedure, voltage regulation through droops ensures MG stability and no reactive power oscillations among the MS are observed (Figure 12). Contrary to what happens with active power sharing (which is defined through droops), the reactive power sharing is greatly influenced by the voltage drops at each specific node where reactive loads are connected (due to LV cable impedances). When the MV network becomes available, the MGCC requires all the VSI to change frequency and voltage, to check synchronization conditions, by slightly and equally changing their idle frequencies and voltages. This procedure guarantees that no significant changes in MS power output occur. After synchronizing the MG with the MV network, VSI idle frequency and 15th PSCC, Liege, August 2005 Session 27, Paper 4, Page 6
7 voltages are restored to the values they had before in order to maintain the power dispatch in the MG. Reactive Power (kvar) VSI RMS Voltage (V) SOFC SSMT 100 STORAGE Time (s) Figure 12: Reactive power in each VSI and storage device terminal voltage By comparing the active power outputs of the SSMT and SOFC after a load increase, described in Figures 11 and 13, it is possible to observe that the response of their primary sources is delayed (according to their physical characteristics) relatively to the corresponding VSI active power outputs. This happens because of the almost instantaneous initial contribution provided by the storage devices assumed to be installed in their DC links. Active Power (kw) SSMT SOFC Time (s) Figure 13: Active power in the primary energy source (SSMT and SOFC) 8 CONCLUSIONS This paper described the set of control strategies needed for islanded and black start operation of Micro- Grids where no directly grid connected synchronous generation machines are used. From the results obtained it was observed that storage devices play a key role for the success of system islanding and restoration. The identification of a set of rules and conditions to be checked during the restoration stage by the Microgrid components was derived and evaluated through numerical simulation, proving the feasibility of such procedures. Such a successful verification constitutes a significant contribution and shows that microgeneration resources should be exploited further. ACKNOWLEDGMENTS The authors want to express their thanks to the research team of the MicroGrids project for valuable discussions that helped developing this research and to the EU for funding the project. REFERENCES [1] J. J. Ancona, A Framework for Power System Restoration Following a Major power Failure, IEEE Transactions on Power Systems, vol. 10, pp , [2] M. M. Adibi, R. J. Kafka, D. P. Milanicz, Expert System Restoration, IEEE Transactions on Power Systems, vol. 9, pp , [3] J. A. Peças Lopes et al., Management of Microgrids, JIEEC2003, Bilbao, October [4] Y. Zhu, K. Tomsovic, Development of Models for Analyzing Load-Following Performance of Microturbines and Fuel Cells, Electric Power Systems Research vol. 62, pp 1-11, [5] N. Hatziargyriou et al, Modelling of Microsources for Security Studies, Proceedings of the CIGRÉ 2004 Conference, Paris, France, August 30 September 3, [6] G. Kariniotakis, et al, DA1 Digital Models for Microsources, MicroGrids project Deliverable DA1, [7] S. Barsali, M. Ceraolo, P. Pelacchi, D. Poli, Control Techniques of Dispersed Generators to Improve the Continuity of Electricity Supply, Trans. of PES Winter Meeting 2002, IEEE, vol. 2, pp , Jan [8] H. Akagi, Y. Kanazawa, A. Nabae, Instantaneous Reactive Power Compensators Comprising Switching Devices without Energy Storage Components, IEEE Transactions on Industry Applications, vol. IA-20, No. 3, pp , May/June [9] R. H. Lasseter, P. Piagi Providing Premium Power through Distributed Resources, Proceedings of the 33 rd Hawaii International Conference on System Sciences, vol. 4, Maui, Hawaii, 4-7 Jan [10] A. Engler Regelung von Batteriestromrichtern in Modularen und Erweiterbaren Inselnetzen, Dissertation.de, Berlim, May 2002, ISBN [11] M. C. Chandorkar, D. M. Divan, R. Adapa, Control of Parallel Connected Inverters in Standalone AC Supply Systems, IEEE Transactions in Industry Applications, vol. 29, No. 1, January/February [12] R. H. Lasseter, P. Piagi, Microgrid: A Conceptual Solution, Proceedings of the 35th PESC, pp , Aachen, Germany, June [13] N. Jayawarna, M. Lorentzou, S. Papathanassiou, Review of Earthing in a Microgrid, DRAFT Issue No 1, MicroGrids project Deliverable of WP E, th PSCC, Liege, August 2005 Session 27, Paper 4, Page 7
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 1, FEBRUARY 2007 395
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 1, FEBRUARY 2007 395 Using Low Voltage MicroGrids for Service Restoration C. L. Moreira, F. O. Resende, and J. A. Peças Lopes, Senior Member, IEEE Abstract
Control of Distributed Generation Units in Stand-Alone Industrial Networks
2 nd International Conference on Electrical Systems Design & Technologies, Hammamet Tunisia, Nov. 8-10, 2008 Control of Distributed Generation Units in Stand-Alone Industrial Networks Ali Asghar Ghadimi
Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical
Droop Control Forhybrid Micro grids With Wind Energy Source
Droop Control Forhybrid Micro grids With Wind Energy Source [1] Dinesh Kesaboina [2] K.Vaisakh [1][2] Department of Electrical & Electronics Engineering Andhra University College of Engineering Visakhapatnam,
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
INTERFACES FOR RENEWABLE ENERGY SOURCES WITH ELECTRIC POWER SYSTEMS
INTERFACES FOR RENEWABLE ENERGY SOURCES WITH ELECTRIC POWER SYSTEMS Paulo Ferreira, Manuel Trindade, Júlio S. Martins and João L. Afonso University of Minho, Braga, Portugal [email protected],
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
Agent based Micro Grid Management System
1 Agent based Micro Grid Management System J. Oyarzabal, J. Jimeno, A. Engler, C. Hardt and J. Ruela Abstract This paper describes the Micro Grid Management System developed using agent based technologies
Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System
Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System W. EL-KHATTAM M. M. A. SALAMA Electrical & Computer Engineering, Waterloo University, Ontario, Canada Abstract: Due
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink
Transient analysis of integrated solar/diesel hybrid power system using ATLAB Simulink Takyin Taky Chan School of Electrical Engineering Victoria University PO Box 14428 C, elbourne 81, Australia. [email protected]
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
Control Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, [email protected].
High Intensify Interleaved Converter for Renewable Energy Resources
High Intensify Interleaved Converter for Renewable Energy Resources K. Muthiah 1, S.Manivel 2, Gowthaman.N 3 1 PG Scholar, Jay Shriram Group of Institutions,Tirupur 2 Assistant Professor, Jay Shriram Group
Deep Dive on Microgrid Technologies
March 2015 Deep Dive on Microgrid Technologies 2 3 7 7 share: In the wake of Superstorm Sandy, a microgrid kept the lights on for more than for the more than 60,000 residents of Co-Op City in the northeastern
Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems
Project description Title: Power Electronics for Reliable and Energy efficient Renewable Energy Systems OBJECTIVES Principal objective Provide competence and decision basis for enabling reliable and energy
TECHNICAL CHALLENGES ON MICROGRIDS
TECHNICAL CHALLENGES ON MICROGRIDS A. A. Salam, A. Mohamed and M. A. Hannan Department of Electrical, Electronic and Systems Engineering, University Kebangsaan Malaysia, Selangor, Malaysia E-Mail: [email protected]
Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)
Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS) Josep Pou Antoni Arias Page 1 Outline 1. Renewable Energy Perspectives 2. Solar Photovoltaic (PV) 3. Wind Generation
The design and performance of Static Var Compensators for particle accelerators
CERN-ACC-2015-0104 [email protected] The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,
Coordination Control of a Hybrid AC/DC Microgrid With Various Renewable Energy Sources
Coordination Control of a Hybrid AC/DC Microgrid With Various Renewable Energy Sources 1 Hema Surya Teja Beram, 2 Nandigam Rama Narayana 1,2 Dept. of EEE, Sir C R Reddy College of Engineering, Eluru, AP,
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Energy Systems Integration
Energy Systems Integration Dr. Martha Symko-Davies Director of Partnerships, ESI March 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy,
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
Field experience and best practices in managing MW scale Li-ion energy storage systems coupled to large wind and solar plants
Field experience and best practices in managing MW scale Li-ion energy storage systems coupled to large wind and solar plants Michael Lippert & Jesus Lugaro IRES Düsseldorf 1 March 215 Summary 1. Characterization
A Design of DC/DC Converter of Photovoltaic Generation System for Streetcars
Journal of International Council on Electrical Engineering Vol. 3, No. 2, pp.164~168, 2013 http://dx.doi.org/10.5370/jicee.2013.3.2.164 A Design of DC/DC Converter of Photovoltaic Generation System for
Control of a Three Phase Inverter Feeding an Unbalanced Load and Operating in Parallel with Other Power Sources
Control of a Three Phase Inverter Feeding an Unbalanced Load and Operating in Parallel with Other Power Sources Keywords Hauck Matthias, Späth Helmut Elektrotechnisches Institut, Universität Karlsruhe
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
CERTS Microgrid Research and Lessons Learned
CERTS Microgrid Research and Lessons Learned Advanced Grid Technologies Workshop Microgrid Controls and Management Systems July 9, 2015 Bob Lasseter University of Wisconsin Madison Power System of the
Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a
Harmonics and transformers Harmonic component filter Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics
Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, [email protected], Armando Altamirano, [email protected] Osama A. Mohammed, [email protected] Energy Systems
Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)
Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC) Dr. Prasad Enjeti Power Electronics Laboratory Department of Electrical Engineering College Station, TX -
SPECIFICATION COG-2007
Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On
Guidelines for Large Photovoltaic System Integration
1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration
Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage
Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,
Advanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
Advanced Electricity Storage Technologies Program. Smart Energy Storage (Trading as Ecoult) Final Public Report
Advanced Electricity Storage Technologies Program Smart Energy Storage (Trading as Ecoult) Final Public Report Introduction Ecoult, working with CSIRO as its principal subcontractor, was provided $1,825,440
Energy Storage System for Dc Micro Grid Using PIC Microcontroller
Energy Storage System for Dc Micro Grid Using PIC Microcontroller Sanas Renuka V 1, Patil Anupama S 2 P.G. Student, Department of Electrical Engg, Dnyanganga College of Engineering & Research, Pune, India
IEEE Smart Grid Series of Standards IEEE 2030 TM (Interoperability) and IEEE 1547 TM (Interconnection) Status. #GridInterop
IEEE Smart Grid Series of Standards IEEE 2030 TM (Interoperability) and IEEE 1547 TM (Interconnection) Status #GridInterop Smart Grid (IEEE 2030): the integration of power, communications, and information
Solar Power Plant Design and Interconnection
Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive
VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES
VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
Coordinated and Optimized Control of Distributed Generation Integration
Coordinated and Optimized Control of Distributed Generation Integration Hui Yu & Wenpeng Luan China Electric Power Research Institute July, 2015 1 Background and introduction 2 Coordinated control of distributed
Power Electronics for Renewable Energy Integration into Hybrid AC/DC Microgrids Kai SUN Aug 27, 2015
Power Electronics for Renewable Energy Integration into Hybrid AC/DC Microgrids Kai SUN Aug 27, 2015 厚 德 载 物 自 强 不 息 Dept. of Electrical Engineering Outlines Introduction Series-distributed Renewable Generation
EMI in Electric Vehicles
EMI in Electric Vehicles S. Guttowski, S. Weber, E. Hoene, W. John, H. Reichl Fraunhofer Institute for Reliability and Microintegration Gustav-Meyer-Allee 25, 13355 Berlin, Germany Phone: ++49(0)3046403144,
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Integration of Hybrid Distributed Generation Units in Power Grid
Integration of Hybrid Distributed Generation Units in Power Grid Marco Mauri 1, Luisa Frosio 1 and Gabriele Marchegiani 2 1 1 Politecnico di Milano, 2 MCMEnergyLab s.r.l Italy 1. Introduction The use of
Hybrid Wind-Fuel Cell Renewable Energy Utilization Scheme for Village Electricity
Proceedings of the 4 th International Middle East Power Systems Conference (MEPCON 0), Cairo University, Egypt, December 9-, 00, Paper ID 3. Hybrid Wind-Fuel Cell Renewable Energy Utilization Scheme for
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the
AC COUPLED HYBRID SYSTEMS AND MINI GRIDS
, Michael; Hermes, Matthias SMA Technologie AG Hannoversche Str. 1-5 34266 Niestetal GERMANY E-mail: [email protected] E-mail: [email protected] 1. INTRODUCTION Distributed supply based on renewable
EssPro Energy Storage Grid Substation The power to control energy
EssPro Energy Storage Grid Substation The power to control energy EssPro Grid gives you the power to control energy helping to keep smart grids in balance Maximizing the value and performance of energy
Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing Switches
21, rue d Artois, F-75008 PARIS C6 _113 _2012 CIGRE 2012 http : //www.cigre.org Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing
ETAP 11 The Future of Power Systems Engineering & Operation - Today
ETAP 11 The Future of Power Systems Engineering & Operation - Today Innovation Automation Collaboration Multi-Dimension Database Lock & unlock element properties 10 States to track equipment conditions
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES by Kazuhiro Takeda Research Manager, Research and Development Center and Kengo Hirano Instrument and Control Engineer,
System configuration of v-f control with solar PV generator operating at MPPT with a battery storage System
ISSN: 2278 1323 All Rights Reserved 2015 IJARCET 4222 International Journal of Advanced Research in Computer Engineering & Technology (IJARCET) System configuration of v-f control with solar PV generator
Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid
Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy
DG Modeling Challenges & Results. Jens Schoene
DG Modeling Challenges & Results Jens Schoene December 13, 2013 2 Outline PV Caused Issues on Distribution Systems Modeling Challenges Case Study 3 PV Caused Issues on Distribution Systems 4 Potential
Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
Distributed Load Balancing for FREEDM system
Distributed Load Balancing for FREEDM system Ravi Akella, Fanjun Meng, Derek Ditch, Bruce McMillin, and Mariesa Crow Department of Electrical Engineering Department of Computer Science Missouri University
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique
Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique NKV.Sai Sunil 1, K.Vinod Kumar 2 PG Student, GITAM University, Visakhapatnam, India. Asst.Professor, Department
Application Note AN- 1095
Application Note AN- 1095 Design of the Inverter Output Filter for Motor Drives with IRAMS Power Modules Cesare Bocchiola Table of Contents Page Section 1: Introduction...2 Section 2 : Output Filter Design
Distributed Generation and Power Quality Case Study
16 Distributed Generation and Power Quality Case Study Vu Van Thong and Johan Driesen C16.1 DISTRIBUTION NETWORK A segment of an existing Belgian medium-voltage distribution system is used to study the
Context: significant penetration of DG = increased risks for system security
Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:
Overview brochure. Energy Storage Keeping smart grids in balance
Overview brochure Energy Storage Keeping smart grids in balance Reliable power, where and when it s needed Energy storage is not a new concept in itself. It has been an integral component of electricity
Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System
Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter Go Electric Inc. www.goelectricinc.com 1 Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous
Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder
Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction
Energy Storage Systems. New solutions for a new energy environment
Energy Storage Systems New solutions for a new energy environment Facilitating the integration of renewable energy The increase in the quantity of electricity produced by renewable sources is creating
Isolated-Parallel UPS Configuration
Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Power supply output voltages are dropping with each
DESIGNER S SERIES Second-Stage LC Filter Design First Inductor by Dr. Ray Ridley First Capacitor Power supply output voltages are dropping with each new generation of Integrated Circuits (ICs). Anticipated
Input and Output Capacitor Selection
Application Report SLTA055 FEBRUARY 2006 Input and Output Capacitor Selection Jason Arrigo... PMP Plug-In Power ABSTRACT When designing with switching regulators, application requirements determine how
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Output Ripple and Noise Measurement Methods for Ericsson Power Modules
Output Ripple and Noise Measurement Methods for Ericsson Power Modules Design Note 022 Ericsson Power Modules Ripple and Noise Abstract There is no industry-wide standard for measuring output ripple and
What Matters for Successful Integration of Distributed Generation
What Matters for Successful Integration of Distributed Generation Thomas Ackermann Energynautics GmbH, Germany [email protected] Expert User of DIgSILENT PowerFactory for Power Systems Studies
Data center energy efficiency and power quality: an alternative approach with solid state transformer
Data center energy efficiency and power quality: an alternative approach with solid state transformer Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES
SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES E Bompard*, E Carpaneto*, R Napoli*, P Ribaldone**, C Vercellino** * Dipartimento di Ingegneria Elettrica Industriale,
Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems
Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems This Agreement is made and entered into this day of, 20, ( Effective Date ) by and between the Orlando Utilities Commission
Modeling Grid Connection for Solar and Wind Energy
1 Modeling Grid Connection for Solar and Wind Energy P. J. van Duijsen, Simulation Research, The Netherlands Frank Chen, Pitotech, Taiwan Abstract Modeling of grid connected converters for solar and wind
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current
Summary Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current Joachim Härsjö, Massimo Bongiorno and Ola Carlson Chalmers University of Technology Energi och Miljö,
RECENTLY, interest in distributed generation systems
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL 19, NO 6, NOVEMBER 2004 1551 Control of Distributed Generation Systems Part II: Load Sharing Control Mohammad N Marwali, Member, IEEE, Jin-Woo Jung, Student
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS C.P. ION 1 C. MARINESCU 1 Abstract: This paper presents a new method to supply single-phase loads using a three-phase induction
Distributed Generation: Benefits & Issues
Distributed Generation: Benefits & Issues Johan Driesen K.U.Leuven ESAT/ELECTA http://www.esat.kuleuven.be/electa Traditional low voltage grid Limited number of loads Energy supplied top-down from central
Connection of micro-generation to the electricity distribution network
Connection of micro-generation to the electricity distribution network Network recommendation YA9:09 Sivu 1(20) CONTENTS INTRODUCTION...3 1. MARKINGS AND DEFINITIONS...3 2. DEFINITION OF MICRO-GENERATION
Basics electronic speed Governor
Basics electronic speed Governor 1 MAN B&W Diesel Aktiengesellschaft, Augsburg Why do we need Governors? Power sources must be controlled to be converted to useful work. Uncontrolled prime movers, not
CONSULTANT REPORT. Behavior of Two Capstone 30kW Microturbines Operating in Parallel with Impedance Between Them CALIFORNIA ENERGY COMMISSION
CALIFORNIA ENERGY COMMISSION Behavior of Two Capstone 3kW Microturbines Operating in Parallel with Impedance Between Them CONSULTANT REPORT MARCH 2 CEC-2-2 Arnold Schwarzenegger, Governor CALIFORNIA ENERGY
Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor
International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 11 No. 2 Nov. 2014, pp. 445-449 2014 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/
