SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES

Size: px
Start display at page:

Download "SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES"

Transcription

1 Issued DESIGN Section DVD00 INFORMATION SECTION Page 1 of 1 INDEX SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER INTRODUCTION... Page 2 LOAD ESTIMATING AND TRANSFORMER SIZING GUIDELINES...Page 3 TOOLS FOR ESTIMATING TRANSFORMER LOAD AND CALCULATING VOLTAGE DROP... Page 7 VOLTAGE DROP AND TRANSFORMER SIZING PROGRAM... Page 7 VOLTAGE DROP CHARTS...Page 12 SECTION DVD02: VOLTAGE FLICKER DEFINITION... Page 1 INTRODUCTION... Page 1 PERMISSIBLE FLICKER LIMITS... Page 1 VOLTAGE FLUCTUATION CAUSES... Page 1

2 Issued DESIGN Section DVD01 INFORMATION SECTION Page 1 of 21 ALLIANT ENERGY VOLTAGE DROP / VOLTAGE FLICKER AND TRANSFORMER September, 1998 Voltage Drop Team: Mark Peterson Mike Warntjes Tony Mak Ron Johnson Revised January 2005: Mark Peterson

3 Section DVD01 DESIGN Issued Page 2 of 21 INFORMATION SECTION 1. INTRODUCTION Voltage Drop: The difference between the voltage magnitudes at the source and the receiving (load) ends of a feeder, secondary, or service. This drop is based on the length, the resistance and the reactance of the conductor and the amount of load being carried. Impedance: The characteristic of electrical conductors (lines or transformers) that tends to oppose or resist the flow of alternating current (AC) electricity. Impedance is composed of two parts: resistance and reactance. The impedance of a conductor decreases as the length of the conductor decreases or the size of the conductor selected increases. Nominal Voltage: A term used to describe a class of voltage levels, such as 120/240 V, 120/208 V, 277/480 V, 7.2/12.47 kv, etc. Service Voltage: The voltage at the customer s meter or point of interconnection between the utility s system and the customer s system. Steady State Voltage: A voltage level that exists for an extended period of time, usually five minutes or longer. Voltage Fluctuations: Sharp changes in voltage level which persist for only a few seconds or cycles. The objective of system voltage control is to economically provide to each customer the voltage that conforms to the voltage design limitations of electrical equipment. Voltage drop exists in each part of the power system from the source to the customer s service entrance and is proportional to the magnitude and phase angle (power factor) of the load current flowing through the entire power system. This means that a customer electrically close to the source would receive a higher voltage than a customer more remote from the source. Each customer operates practically the same electrical equipment, which makes it necessary to provide each with almost equal supply voltage. A compromise has been required between the allowable deviation from nameplate voltage that is supplied and the deviation above and below the nameplate voltage at which satisfactory performance can be obtained. If voltage limits maintained by the power company were too broad, the cost of appliances would be high because they would have to be designed to operate at any voltage within the limits. If voltage limits were too narrow, the cost of providing power would become too high. Alliant Energy has several nominal voltages that it offers to its customers in the various operating companies electric tariffs. Generally, for retail service the variations of voltage will be no more than five percent above or below the nominal voltage.

4 Issued DESIGN Section DVD01 INFORMATION SECTION Page 3 of 21 Typically, the voltage level at the distribution substation is set at 125 Volts. The control on voltage regulators or load tap changer (LTC) will typically maintain this level within +/- 1 Volt of the voltage setting. This would be a 2 Volt bandwidth. Using 120 V as a base, +/- 5% gives a range of V as the allowable voltage level. The table below shows Alliant s voltage drop guidelines. MAXIMUM DESIGN DISTRIBUTION SYSTEM VOLTAGE DROPS Feeder Component Residential Feeder Rural Feeder Primary Feeder 4.35 % 5.6 % Distribution Transformer 2.0 % 2.0 % Secondary 2.0 % * Service 0.75 % 1.5 % TOTAL: 9.1% 9.1% * For rural applications, it is assumed the majority of applications will have no secondary. The maximum design voltage drops shown above are intended to be a guide for those responsible for the planning, design and engineering of the distribution system. The voltage drop for each component is intended to minimize the cost of the distribution system while maintaining an acceptable voltage to all Alliant Energy customers. The table is based on a typical Alliant Energy distribution system and will not be applicable to all situations. 2. LOAD ESTIMATING AND TRANSFORMER In 2005, new guidelines for estimating transformer loads and sizing transformers were developed by the Distribution Transformer Sizing Six Sigma Team. The team s recommendations for loading distribution transformers, along with a list of the team s members, are shown on the following page. Flow charts that were developed by the team for estimating load and sizing transformers are also included. The team also revised the equations used by the GIS transformer load management (TLM) program so the results provided will reflect the most resent company load data.

5 Section DVD01 DESIGN Issued Page 4 of 21 INFORMATION SECTION Lean Six Sigma Transformer Utilization Team Distribution Transformer Loading Recommendations 03/02/05 The following guidelines should be considered when installing distribution transformers. The guidelines are based on the loss of insulation life characteristics (of our present standard transformers), the average load profiles of each class of customers and average annual temperatures across the Alliant Energy territory. Residential For new developments or rebuilds, distribution transformers should be typically loaded at 110% at peak. This will allow 40 years of load growth at.75% per year, which has been the average load growth per transformer in the past. The goal is to ultimately load residential transformers to a target maximum of 140%. Transformers will be flagged in TLM when the load exceeds 180%. Residential load estimating tools Load on existing transformers can be estimated using the TLM program in ArcFM. Load for new homes can be estimated using the transformer sizing spreadsheet or the residential diversity curves. The diversity curves were developed using load research data and are a better representation of smaller existing homes. Tools will be added to the Design Voltage Drop (DVD) section of the Electric Construction Standards (ECS) manual. Small Commercial For new small commercial installations or rebuilds, or transformers serving a combination of residential and commercial customers, distribution transformers should typically be loaded to 110% of rating at peak if expected load growth is unknown. The goal is to ultimately load transformers to a target maximum of 140%. If enough information is available to estimated expected load growth, the transformer should be sized such that the initial load plus expected load growth does not exceed 140%. Voltage drop must be considered as it may be the most limiting factor. Large Commercial New or replacement transformer installations for large commercial customers (with load factors greater than 60%) should be loaded to a maximum of 105%. If excessive harmonic loads are suspected, the maximum loading limit may need to be reduced. Consult with distribution engineer. Industrial The typical load factor for industrial customers is about 80%. At this level, large pad mount transformers will not loose significant insulation life if loaded below 105% at peak. However, due to the high harmonic content of many of the more common industrial loads such as variable speed drives, florescent lighting, arc welders, arc furnaces, electronic power supplies and battery chargers, the maximum loading may need to be reduced significantly. Consult with distribution engineer when sizing transformers for industrial loads. Commercial and Industrial load estimating tools - Load on existing transformers can be estimated using the TLM program in ArcFM. Individual demand metered loads are available in CSS or CIS. Load for new customers can be estimated using information from the customer, load from similar customers or section D3PUD-3 (and appendix A) of the ECS manual. Team members: John Helbling, Black Belt Steve Carlson, Special Projects Manager Mark Peterson, Lead Distribution Engineer Centerville, IA Bruce Bielema, Manager Customer Service Clinton, IA Dan Holzman, Engineering Technician Berlin, WI Nate Pollock, GIS Business Analyst

6 Issued DESIGN Section DVD01 INFORMATION SECTION Page 5 of 21

7 Section DVD01 DESIGN Issued Page 6 of 21 INFORMATION SECTION

8 Issued DESIGN Section DVD01 INFORMATION SECTION Page 7 of 21 AVAILABLE TOOLS FOR ESTIMATING TRANSFORMER LOAD AND CALCULATING VOLTAGE DROP Several tools are available to estimate transformer load and to calculate voltage drop on the distribution transformer, secondary and service. A transformer sizing and voltage drop spreadsheet program is available as well as a set of load estimating and voltage drop charts. The spreadsheet is intended as a tool for designing the distribution systems for new residential subdivisions whereas the voltage drop charts may be used to calculate the voltage drop on any section of conductor. The transformer sizing spreadsheet is also provided in a hard copy table and graph. A table and graph is provided for estimating load for existing homes as well. Primary voltage drop and motor start calculations should be referred to the area Distribution Engineer. 1. VOLTAGE DROP AND TRANSFORMER SIZING PROGRAM An Excel spreadsheet program has been developed which will size the distribution transformer and calculate the voltage drop on the transformer, secondary and service (overhead or underground) to residential customers. There are four customer types to choose from and up to four secondaries or pedestals may be modeled. The program will calculate the load in kva on each secondary and on the distribution transformer. A suggested minimum transformer size is calculated based on a given loading factor. The advantage of this program is that the customer diversity load curves are built into the program. This means that the user does not have to adjust for the fact that most customers do not peak at the same time. As more customers are modeled on a transformer, the program automatically reduces the load per customer according to the diversity curves within the program. Detailed step by step instructions for using the spreadsheet and a hard copy of the program as it appears on the computer screen are included in the following pages. A graph of the output of the transformer sizing spreadsheet is also available for summer loads with air conditioning (type A and C) which may be easier to use. However, for the results to be accurate all of the customers served from the transformer must be of the same type. A table and graph is provided for estimating load for existing homes as well. Copies of the voltage drop and transformer sizing program as well as the graphs mentioned above are available on the IPL Field Engineering Team West web site. The methodology to calculate the transformer loading is based on the project team of Dick Wight of Energy Market Solutions, Diane Cunningham of Applied Energy Group, Dr. Russ Heikes and Dr. Bill Hines of Georgia Institute of Technology. Please refer to WP&L Residential Load Modeling 1995 report prepared by Energy Market Solutions.

9 Section DVD01 DESIGN Issued Page 8 of 21 INFORMATION SECTION VOLTAGE DROP AND TRANSFORMER SIZING PROGRAM INSTRUCTIONS Description Any questions call Mark Peterson (641) This spreadsheet contains three worksheets, a "Transformer Sizing" worksheet and two "Secondary / Service Voltage Drop" worksheets. The Transformer Sizing worksheet contains an algorithm to determine the peak kva demand for a group of "new" customers based on the number and type of each customer. The customers can be grouped by up to four load distribution points "nodes" which can be overhead or underground. The outputs include the non-coincident peak for each load point (Node 1 through Node 4) and the peak transformer load. The transformer load includes diversity between the load points. An additional table is included called Inputs to: "Coincident Peak kva" which displays the coincident load at each node (their sum equals the calculated transformer load). These loads can then be entered into either "Secondary / Service Voltage Drop" worksheet to calculate the voltage drop at any point on a secondary system. The voltage drop worksheets are identical except "Secondary-Service Volt Drop (%)" will calculate voltage drop in percent and "Secondary-Service Volt Drop (V)" will calculate the voltage on a 120 V base. Refer to section DVD-1 of the Electric Construction Standards manual for the maximum design distribution system voltage drops. Instructions Transformer Sizing Spreadsheet 1. Fill in "Location", "Pole or Pedestal No.", and "Tx No." if needed to identify file or hard copy. 2. Determine appliance codes from "Electric Appliance Combo Table". 3. Enter number of customers on a white box - always start with "Node 1". The "Noncoincident Peak kva" table will display the calculated peak load for each node (load point) and the transformer, as well as the minimum transformer size (load + loading factor) and the number of customers. 4. The "Coincident Peak kva" table will display the calculated transformer load, distributed proportionally to each pedestal. These outputs are also displayed in the "Secondary-Service Volt Drop" sheets. Secondary-Service Voltage Drop 1. Click the "Clear Sheet" button to zero the conductor lengths and kva loads on the pedestals and meters. 2. Enter the inputs as instructed for each input variable. The outputs from the "Transformer Sizing" worksheet are available in the table in the upper right portion of each "Secondary-Service Volt Drop". 3. Transformer voltage drop and load will be shown in the table representing the transformer. 4. The voltage drop for each pedestal and meter will be shown at each location modeled. Modeling More Than Four Load Points If it is desired to model more than four load points utilizing the Transformer Sizing worksheet, all of the customers served by the transformer of each type should be entered into a single node (1) location. The load should then be distributed to each node in the volt drop worksheet by the proportion of customers served at the node.

10 Issued DESIGN Section DVD01 INFORMATION SECTION Page 9 of 21 New Residential Customer Transformer Sizing Module

11 Section DVD01 DESIGN Issued Page 10 of 21 INFORMATION SECTION Single Phase Secondary / Service Voltage Drop Calculator

12 Issued DESIGN Section DVD01 INFORMATION SECTION Page 11 of 21

13 Section DVD01 DESIGN Issued Page 12 of 21 INFORMATION SECTION Load Estimating Graphs for New and Existing Homes 2. VOLTAGE DROP CHARTS The voltage drop charts on the following pages are designed to show the percent voltage drop between the source and load ends of a length of secondary or a service. The charts show percent voltage drop per 100 feet. Follow these steps to use the charts: 1. Determine the proper chart to use by determining whether the load is single- or three-phase and what the nominal voltage is. 2. Determine the AWG size and length of the secondary/service conductor. 3. Determine the load current in amperes. For parallel runs (i.e. More than one conductor per phase), divide the total load in amps by the number of runs. Use this number in the charts. 4. Locate the value of amps on the X (horizontal) axis. 5. Read the percent voltage drop from the Y (vertical) axis corresponding to the conductor being used. 6. For conductor lengths other than 100 feet, adjust this number accordingly. Example: for 200 feet, multiply the number by two. For 50 feet, multiply the number by 0.5

14 Issued DESIGN Section DVD01 INFORMATION SECTION Page 13 of 21

15 Section DVD01 DESIGN Issued Page 14 of 21 INFORMATION SECTION

16 Issued DESIGN Section DVD01 INFORMATION SECTION Page 15 of 21

17 Section DVD01 DESIGN Issued Page 16 of 21 INFORMATION SECTION

18 Issued DESIGN Section DVD01 INFORMATION SECTION Page 17 of 21

19 Section DVD01 DESIGN Issued Page 18 of 21 INFORMATION SECTION

20 Issued DESIGN Section DVD01 INFORMATION SECTION Page 19 of 21

21 Section DVD01 DESIGN Issued Page 20 of 21 INFORMATION SECTION

22 Issued DESIGN Section DVD01 INFORMATION SECTION Page 21 of 21 (END)

23 Issued DESIGN Section DVD02 INFORMATION SECTION Page 1 of 6 VOLTAGE FLICKER 1. DEFINITION VOLTAGE FLICKER: A phenomenon caused by sudden changes of brief duration in the voltage supplied to a customer. 2. INTRODUCTION Electric Utility delivery systems provide relatively constant voltage. Power system voltage fluctuations are generally caused by large changes with customers loads. Large current changes are causing the voltage to fluctuate and another customer has seen lamp flicke, experienced problems with a process, or otherwise been disturbed. There are two forms of power system voltage fluctuations: (1) voltage fluctuations caused by utilization equipment resulting in lamp flicker, and (2) voltage fluctuations caused by transient system faults resulting in utilization equipment downtime. Human sensitivity and tolerance varies considerably and depends upon the magnitude and frequency of the voltage flicker. It is, therefore, difficult to establish flicker limits that are economically justified and satisfactory to all customers. Historically, voltage fluctuation limit guidelines have been based on customer and equipment tolerance curves. More recently, flicker limits and system design guidelines have been established by regulatory bodies through input from consumer organizations and utilities. 3. PERMISSIBLE FLICKER LIMITS The maximum amount of acceptable flicker voltage cannot be stated concisely for several reasons. Flicker that one individual may feel is objectionable may not be perceptible to another. The type of lighting fixture used is also important. Incandescent and fluorescent lamps are affected differently by a change in supply voltage. Cyclic or rapidly recurring voltage changes are generally more objectionable than non-cyclic. For non-cyclic changes, the annoyance due to the flicker is affected by the rate of change, duration of change, and frequency of occurrence of the flicker. 4. VOLTAGE FLUCTUATION CAUSES Most of the voltage fluctuations on distribution systems are due to the operation of customers utilization equipment. Following are some of the more common types of equipment known to cause flicker. Several more typical solutions for correcting the voltage fluctuation to within permissible limits are also provided. a. Motor Starting 1) Probably the most common cause of voltage flicker problems is the starting of motors. For reasons of cost, efficiency, and reliability, commercial general purpose motors require a momentary starting current several times their full load running current in order to produce sufficient starting torque. The magnitude of starting current may cause a dip in the reference voltage and result in objectionable flicker.

24 Section DVD02 DESIGN Issued Page 2 of 6 INFORMATION SECTION VOLTAGE FLICKER There are three general classes of motor installations: Single-phase fractional horsepower motors commonly used in homes and small stores. Small multi-horsepower single and polyphase motors operated from secondary distribution circuits, such as in small shops, large stores and buildings, and recently in an increasing number of homes for air conditioning. Large horsepower three-phase motors operated from primary lines, mostly for industrial applications. 2) The magnitude of voltage dip caused by a motor load during starting depends on: a) The system impedance (size and length of transmission line, size of substation transformer, and size and length of distribution line). b) The size and impedance of the (distribution) transformer feeding the load. c) The length and size of the secondary conductor between the motor and transformer. d) The starting current (locked rotor amps) requirements of the motor. 3) Flicker can be improved by reducing the system impedance by: a) Increasing the size of the substation and/or distribution transformers. b) Adding distribution transformers or moving existing transformers closer to the load to reduce the length of the secondary conductor. c) Increasing the size or number (parallel runs) of the secondary conductor. d) Reducing the starting current requirements of the motor through reduced voltage starting equipment (auto transformer and reactor type reduced voltage starter, wye-delta starting, or part winding starting). * Note this is the preferred method, however the effects of reduced voltage starting equipment on the starting torque characteristics of the motor must be analyzed. Consult your distribution engineer for assistance. Motor nameplate information, as well as specifics concerning the use and type of application, will be required. b. Electric Welders Due to their relatively small size and widespread use, welders can create voltage fluctuations on many segments of the distribution and delivery systems. Most welders have a smaller on time than off time, and consequently, the total energy consumed is small compared with the instantaneous demand. Fortunately, most welders are located in industrial applications with other processes, which may require a larger amount of power. Supply facilities typically are of larger capacity to reduce the amount of flicker. In isolated cases,

25 Issued DESIGN Section DVD02 INFORMATION SECTION Page 3 of 6 VOLTAGE FLICKER but nonetheless important, the welder may be the major load in the area, and serious flicker may be imposed on distribution systems that are otherwise adequate for serving ordinary loads. Practically all welders in service are single phase, and the most commonly used welder is the resistance welder. Various types of electric welders are: 1) Flash welders 2) Pressure butt welders 3) Projection welders 4) Resistance welders a. Spot b. Seam Basically, the source of voltage, usually 240, 480, or 2,300 volts, is stepped down to a few volts to send high currents through the parts to be welded. Although bridge rectifier circuits are used in resistance welders, some saturation of the welding transformer usually will exist. This effect, together with the short successive pulses of high current, creates the objectionable voltage dip. Corrective measures for voltage dips caused by welders range from motor-generator sets installed in the customer s plant to supply circuit changes by the utility. Supply circuit changes may be accomplished by increasing the feeder size or the substation capacity. Separate distribution feeder lines to the welding load also are possible economic solutions. As with all fluctuating loads, the object is to decrease the system impedance between the source and objectionable load. Consult your distribution engineer for assistance. Welder nameplate information, as well as specifics concerning the use and type of application, will be required. c. Electric Furnaces There are three types of electric furnaces resistance, induction, and arc. Depending on the size of the furnace, each type could cause a voltage fluctuation problem. When an electric furnace load is proposed for our system, distribution engineering and/or distribution planning must perform a detailed study of possible voltage problems. Induction furnaces are single-phase devices that are typically connected phase-tophase. When configured with capacitors and inductors, induction furnaces can simulate a three-phase load and operate relatively balanced with a power factor close to unity. Induction furnaces connected phase-to-phase cause significant voltage fluctuations due to delivery system load imbalance. One phase will see a significant voltage drop while the other phase incurs a slight voltage rise during the operation of the furnace. Induction furnaces,depending upon the size and operated to simulate a three-phase load create minimal, if any, voltage concerns.

26 Section DVD02 DESIGN Issued Page 4 of 6 INFORMATION SECTION VOLTAGE FLICKER Consult your distribution engineer for assistance. Furnace nameplate information, as well as specifics concerning the use and type of application of the equipment and system supply impedance, will be required. d. Miscellaneous Under this category comes special equipment such as electric shovels, strip mining equipment, stone crushers, heavy rolling mills, and similar installations. Most of these must be considered individually as to special features and the type of power supply required. Again, your Distribution Engineer should be consulted for assistance to assure that these devices can be operated with the least amount of system voltage fluctuation. e. Residential Voltage Flicker Tables On the next several pages are tables showing maximum secondary and service lengths for various transformer sizes. These tables are based on voltage flicker limits only. In most cases, if not all, these limits are more restrictive than voltage drop limits. In other words, taking voltage flicker into account tends to restrict the length of secondary and services more so than voltage drop due to steady state load. However, the voltage drop should also be checked against the guidelines to make sure limits are not exceeded. The tables are set up to limit flicker at points common to multiple customers (transformers, pedestals) to 3% and at the meter to 4%.

27 Issued DESIGN Section DVD02 INFORMATION SECTION Page 5 of 6 VOLTAGE FLICKER 10 kva Transformer, No Secondary* Maximum Service Length (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) *Do not serve multiple residential customers from a 10 kva transformer. Assuming 60 amp inrush at 0.65 pf, which creates 3.4% flicker through 10 kva transformer. Allowing meter, primary flicker not accounted for. 25 kva Transformer, Maximum Service Length (Ft.) No Secondary #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) kva Transformer, 1/0 Secondary Length of 1/0 Secondary Maximum Service Length Conductor (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) kva Transformer, 4/0 Secondary Length of 4/0 Secondary Maximum Service Length (Ft.) Conductor (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) kva Transformer, 350 Secondary Length of 350 Secondary Maximum Service Length (Ft.) Conductor (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) Assuming 100 amp inrush at 0.65 pf, which creates 2% flicker through 25 kva transformer. Allowing 3% pedestal, meter, primary flicker not accounted for.

28 Section DVD02 DESIGN Issued Page 6 of 6 INFORMATION SECTION VOLTAGE FLICKER 50 kva Transformer, No Secondary Maximum Service Length (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) kva Transformer, 1/0 Secondary 50 kva Transformer, 4/0 Secondary Length of 1/0 Secondary Con- Maximum Service Length (Ft.) ductor (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) Length of 4/0 Secondary Maximum Service Length (Ft.) Conductor (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) kva Transformer, 350 Secondary Length of 350 Secondary Conductor (Ft.) Maximum Service Length (Ft.) #2 (OH) #1/0 (OH/UG) #4/0 (OH/UG) 350 MCM (UG) Assuming 100 amp inrush at 0.65 pf, which creates 1% flicker through 50 kva transformer. Allowing 3% pedestal, meter, primary flicker not accounted for. (END)

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

1. The type of service available at any particular location should be determined by inquiry at PG&E's local office.

1. The type of service available at any particular location should be determined by inquiry at PG&E's local office. Revised Cal. P.U.C. Sheet No. 11257-E Cancelling Revised Cal. P.U.C. Sheet No. 6925-E ELECTRIC RULE NO. 2 Sheet 1 A. GENERAL 1. The type of service available at any particular location should be determined

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

Power Quality Standards for Electric Service

Power Quality Standards for Electric Service Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

BC Hydro. Electric Distribution System Cost of Service Study

BC Hydro. Electric Distribution System Cost of Service Study BC Hydro Electric Distribution System Reimer Consulting Group Inc. Arnie Reimer May 7, 2010 Table of Contents 1. Executive Summary... 3 2. BC Hydro Electric Distribution System... 4 2.1. General Description...

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B WHITE PAPER PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS BULLETIN 1497, 1497A, AND 1497B CONTROL CIRCUIT TRANSFORMERS The proper selection of the control circuit transformers is important for suitable

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi

More information

Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns

Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, mcint015@fiu.edu, Armando Altamirano, araltami@fiu.edu Osama A. Mohammed, mohammed@fiu.edu Energy Systems

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

Primary Electric Distribution for Industrial Plants

Primary Electric Distribution for Industrial Plants PDH Course E242 Primary Electric Distribution for Industrial Plants Adolph A. Biss, P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

Voltage Tolerance Boundary

Voltage Tolerance Boundary Pacific Gas and Electric Company Voltage Tolerance Boundary The only national standard for utilization voltage regulation is ANSI C84.1. Its title is American National Standard for Electric Power Systems

More information

ENA Customer Guide to Electricity Supply

ENA Customer Guide to Electricity Supply ENA Customer Guide to Electricity Supply Energy Networks Association Limited ENA Customer Guide to Electricity Supply August 2008 DISCLAIMER This document refers to various standards, guidelines, calculations,

More information

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8 DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2 Kinds and Uses of Service... 2-1-1 and 2-1-2 Wye Network Area Maps Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8 Transformer Connections

More information

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003 Technical Note No. 7 August 2003 Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses voltage fluctuations, their causes and adverse effects, what levels

More information

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1 Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =

More information

How To Wire A Three Phase, Single Phase, Wye Transformer

How To Wire A Three Phase, Single Phase, Wye Transformer Three-Phase Transformers When more power is needed - three transformers can be tied together. This is called three-phase. Here s a simple way of comparing single-phase to threephase power. Single-Phase

More information

POWER FACTOR CORRECTION

POWER FACTOR CORRECTION [CATALOGUE PFC-SFC] POWER FACTOR CORRECTION INDUSTRIAL SWITCHGEAR & AUTOMATION SPECIALISTS A component of nhp s green star solution... www.nhp.com.au Power Factor - What does it mean? Where open electricity

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore. Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Chapter 12: Three Phase Circuits

Chapter 12: Three Phase Circuits Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Tamura Closed Loop Hall Effect Current Sensors

Tamura Closed Loop Hall Effect Current Sensors Tamura Closed Loop Hall Effect Current Sensors AC, DC, & Complex Currents Galvanic Isolation Fast Response Wide Frequency Bandwidth Quality & Reliability RoHs Compliance Closed Loop Hall Effect Sensors

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

AUSTIN UTILITIES. CHARACTER OF SERVICE: AC, 60 cycles, 120/240 Volt, three wire, single-phase; or 120 Volt, two wire.

AUSTIN UTILITIES. CHARACTER OF SERVICE: AC, 60 cycles, 120/240 Volt, three wire, single-phase; or 120 Volt, two wire. AVAILABLE: Within established City Limits. AUSTIN UTILITIES Schedule (110) Issued 11/12/13 Supersedes (110) Issued 11/13/12 Sheet No. 1 of 1 RESIDENTIAL SERVICE APPLICABLE: To single-family residences

More information

Section 3: Load Planning Bill Brown, P.E., Square D Engineering Services

Section 3: Load Planning Bill Brown, P.E., Square D Engineering Services Section 3: Load Planning Bill Brown, P.E., Square D Engineering Services Basic Principles The most vital, but often the last to be acquired, pieces of information for power system design are the load details.

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category

More information

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 2, March-April, 2016, pp.19-28, Article ID: IJEET_07_02_003 Available online at http:// http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=2

More information

13 common causes of motor failure

13 common causes of motor failure 13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Motor Efficiency and Power Factor ME 416/516

Motor Efficiency and Power Factor ME 416/516 Motor Efficiency and Power Factor Motivation More than half of all electric energy generated goes to power electric motors. Electric motor converts electric power into shaft power. In thermodynamics terms,

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution APPLICATION NOTE Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution INCREASING PV HOSTING WITH EMPOWER TM SOLUTION Executive Summary Distributed solar photovoltaic

More information

Voltage Unbalance and Motors

Voltage Unbalance and Motors Voltage Unbalance and Motors Background Voltage unbalance occurs when the RMS line voltages on a poly-phase system are unequal. Voltages are seldom perfectly balanced between phases, but when this unbalance

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection

More information

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB

More information

Supply Standards: Electricity Supply Standard July 2011 4 JULY 2011 ISSUE 6 UNCLASSIFIED UNCONTROLLED COPY IF PRINTED

Supply Standards: Electricity Supply Standard July 2011 4 JULY 2011 ISSUE 6 UNCLASSIFIED UNCONTROLLED COPY IF PRINTED s: Electricity Supply Standard July 2011 4 JULY 2011 ISSUE 6 OPERATIONAL PROCEDURE - s: Electricity PREPARED BY: Power Quality Manager AUTHORISED BY: General Manager Network Support DOCUMENT NUMBER: -

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

RETAIL ELECTRIC SERVICE TARIFF P.S.C. Md. No. 3 R Sheet 61

RETAIL ELECTRIC SERVICE TARIFF P.S.C. Md. No. 3 R Sheet 61 R Sheet 61 SCHEDULE R RESIDENTIAL SERVICE AVAILABILITY Available throughout the area served by the Cooperative to individual residences and individually metered dwelling units in multiple-occupancy buildings

More information

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.

More information

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how

More information

3-Phase AC Calculations Revisited

3-Phase AC Calculations Revisited AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who

More information

WHR Series STABILINE Voltage Regulators

WHR Series STABILINE Voltage Regulators WHR Series STABILINE Voltage Regulators The WHR Series is the most extensive line of STABILINE Voltage Regulators Superior Electric has ever offered. This line of regulators includes units for use on all

More information

Power Quality. Uninterruptible Power Supply

Power Quality. Uninterruptible Power Supply Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Basics of Electricity

Basics of Electricity Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components

More information

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering

More information

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question

More information

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...

More information

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt. Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

Current and Temperature Ratings

Current and Temperature Ratings Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and

More information

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage

More information

Power Factor The Basics

Power Factor The Basics Power Factor The Basics OK. I ve heard a lot about this power factor stuff. What exactly is it? We hope to give you an easy explanation of what power factor is, and to answer the following most asked questions:

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

ACCURACY OF POTENTIALTRANSFORMERS

ACCURACY OF POTENTIALTRANSFORMERS 8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"

More information

PowerFlex Dynamic Braking Resistor Calculator

PowerFlex Dynamic Braking Resistor Calculator Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing

More information

Power Quality for Information Technology System

Power Quality for Information Technology System Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS

More information

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) 2 European MEPS for transformers The EU MEPS (European Minimum Energy Performance Standard) Transformers

More information

Module Title: Electrotechnology for Mech L7

Module Title: Electrotechnology for Mech L7 CORK INSTITUTE OF TECHNOLOGY INSTITIÚID TEICNEOLAÍOCHTA CHORCAÍ Autumn Examinations 2012 Module Title: Electrotechnology for Mech L7 Module Code: ELEC7007 School: School of Mechanical, Electrical and Process

More information

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Presented by: Marianne Mannschreck Date: Welcome A Look at the Net Energy Metering

More information

Modeling and Simulation of a Large Chipper Drive

Modeling and Simulation of a Large Chipper Drive The Open Electrical & Electronic Engineering Journal, 009, 3, 1-8 1 Modeling and Simulation of a Large Chipper Drive Open Access Christian Kral, Anton Haumer, Hansjörg Kapeller and Gert Pascoli Austrian

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

Power System Harmonics

Power System Harmonics Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic

More information

FIXED CHARGE: This is a cost that goes towards making the service available, including

FIXED CHARGE: This is a cost that goes towards making the service available, including ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

Voltage Drop. Voltage Drop 1

Voltage Drop. Voltage Drop 1 Voltage Drop The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences. Qualified person is defi ned in Article 100 of

More information

Power Quality & Custom Power

Power Quality & Custom Power Day-3 Power Quality & Custom Power Arindam Ghosh Dept. of Electrical Engineering Indian Institute of Technology Kanpur,, India E-mail: aghosh@iitk iitk.ac.in Power Quality (PQ) The term electric power

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks Proceedings of the World Congress on Engineering and Computer Science 009 Vol I WCECS 009, October 0-, 009, San Francisco, USA eduction of Power Losses Using Phase Load Balancing Method in Power Networks

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2

INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2 INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2 By: R.C. Zowarka T.J. Hotz J.R. Uglum H.E. Jordan 13th Electromagnetic Launch Technology Symposium, Potsdam (Berlin), Germany,

More information

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and

More information

Inverter technology. bulletin

Inverter technology. bulletin Inverter technology application bulletin What is the inverter component? The inverter is an electronic power component that continuously varies the electricity supply frequency of an electric motor. The

More information