EZIO-4THIE * External CJC Sensor** (National LM19)
|
|
|
- Timothy Casey
- 9 years ago
- Views:
Transcription
1 TM E Z I/O EZIO-4THIE * Enhanced Thermocouple Input Module Part Number: EZIO-4THIE EZIO family offers two modules for interfacing to thermocouples: EZIO-4THI (not recommended for new applications) EZIO-4THIE This document describes EZIO-4THIE module. Note: This module requires EZPLC editor version 1.4 or later; firmware revision C.3 or later. To check the firmware revision of your EZPLC: Using the EZPLC Editor Software access the menu item EZPLC > INFORMATION... a window will open displaying the current EXEC Software and BOOT Software revisions. To upgrade the firmware: Download firmware at (down loads section).once downloaded, use EZPLC editor and select Setup>Upgrade Firmware menu item. The module has following features: Up to 4 thermocouple inputs with user selectable thermocouple types on each input User programmable broken thermocouple detection User programmable units for temperature -- Centigrade, Fahrenheit or Kelvin Automatic Cold Junction Compensation (CJC) with Internal or External Sensor Wiring Pin # Thermocouple Input Pin Functions Internal CJC Sensor* 1 INPUT1 + INPUT1 + 2 INPUT1 - INPUT1-3 INPUT2 + INPUT2 + 4 INPUT2 - INPUT2-5 INPUT3 + INPUT3 + 6 INPUT3 - INPUT3-7 INPUT4 + DO NOT USE External CJC Sensor** (National LM19) 8 INPUT4 - CJC Sensor Vout 9 DO NOT USE CJC Sensor Vs+ 10 DO NOT USE DO NOT USE 11 DO NOT USE CJC Sensor Gnd Pin #1 CJC Sensor LM 19 Pin Out * CJC : Cold Junction Compensation ** Only 3 thermocouple inputs are available when External CJC is used Which CJC Sensor, internal or external, to use? The module provides automatic cold junction compensation (CJC). It can use internal (default) or external temperature sensor for this purpose. With both sensor types, the module provides very repeatable temperature readings. You may select internal or external based on below given guidelines: Use Internal CJC Sensor: If you need repeatable but not very accurate readings (typical +/- 6 deg C). This allows you to use 4 thermocouples with the module. Internal sensor is automatically used if external sensor is not selected for input #4.
2 Use External CJC Sensor: If you need repeatable as well as more accurate (max +/- 3 deg C) readings. You will need to use LM19 temperature sensor, and you can use only 3 thermocouples. To use External Sensor, select CJC Sensor (LM19) for Input #4 type, in the configuration dialog box. (see below). Specifications Number of Channels: 4 Thermocouples supported: See table below PLC Update Rate: All inputs every PLC scan Base Power Required: 3.3 VDC supplied by base Operating Temperature: 32 to 140 F (0 to 60 C) Storage Temperature: -4 to 158 F (-20 to 70 C) Relative Humidity: 5 to 95% (non-condensing) Environmental Air: No corrosive gases permitted Vibration: MIL STD 810C Shock: MIL STD 810C Noise Immunity: NEMA ICS3-304 Cold Junction Compensation (CJC): Automatic, Internal or External sensor External CJC Sensor: LM19 Conversion Time: 1ms per channel Warm-Up Time: 30 minutes typically ± 1 C repeatability Linearity Error (End to End): ± 1 C max. ± 0.5 C typical Maximum Inaccuracy:* ± 3 C (excluding thermocouple error) Replacement Terminal Block: EZIO-TERM11 * When used with an external CJC sensor; with internal sensor, the inaccuracy may be larger, but readings still repeatable. Type of Thermocouple & ranges supported, and error values: Thermocouple Type Range Value reported with Open Thermocouple or incorrect configuration Centigrade Fahrenheit Kelvin Do not report Low Value High Value J -210 C to C -346 F to F 6 3 K t o 1473 K K C F 1645 K S C t o C F t o F 223 K to 2041 K T +400 C +752 F 673 K E +980 C F 1253 K R C t o C F t o F 223 K to 2041 K B C t o C F t o F 523 K to 2093 K Random 0 (0x0000) (0xFFFF) N Ambient Temp C F 1573 K This selection would read modules s ambient temperature
3 Thermocouple Module Setup To setup the module in EZPLC, follow these steps: 1. In I/O configuration select 4 Enhanced Thermocouple Module (EZIO-4THIE) as shown below, and assign desired starting Input and starting output addresses: The module takes up 4 input registers (IRs) and 4 output registers (ORs). Input Registers return thermocouple readings. Output registers are used for configuration of respective thermocouple. The starting Input Register is used for Input # 1, the next for Input# 2, etc. For example if the starting input address is IR1, then reading from thermocouple at input # 1 would be returned in IR1, from#2 in IR2, from #3 in IR3, and from #4 in IR4. Similarly Starting OR would configure Thermocouple #1, and next OR would configure Input #2, and so on. 2. Click on Click to define setup parameters. Following dialog comes up: For each input, select Type of Thermocouple, Unit of measurement, and Option to report error (such as due to open thermocouple, wrong configuration, etc.). These choices create a config value that is written to corresponding OR registers when the program is written to EZPLC. These values can also be written or modified using ladder logic, but it may be easier to use the dialog box. That is all required to setup the module. The programmable parameters, namely type, unit, and report error, as well as the computed config value, are described below:
4 Type Select the type of the thermocouple using this field. The possible choices are: J Type, K Type, S Type, T Type, E Type, R Type, B Type, N Type, Ambient Type. The display-only range field depends on the type of the thermocouple selected (along with the unit). For Input#4 ONLY: If using external sensor for CJC, select CJC Sensor (LM19) for Input#4. Unit Select the unit for measurement for each thermocouple. The possible choices are: Celsius, Fahrenheit and Kelvin. The display-only range field depends on the unit selected (along with the type of the thermocouple). Report Error The Report Error function on the thermocouple module provides diagnostic capabilities to detect open or burnt thermocouple, or incorrect configuration (which can happen if the ladder logic writes an incorrect value to the config register). The following table describes the choices and the resulting actions. You can use these values in ladder logic to detect possible problems with the thermocouples or configurations. Choice Value Returned All types EXCEPT B Type B Type Do Not Report Interminate Interminate Use low value Use high value Config Value The computed ConfigValue (determined by above choices) is the value written to the config (output) register. Each thermocouple input is configured via its config register. The Config Value Display Format option allows you to display (in this dialog box) the config value in either decimal or hex. The actual config value depends on the selections made for the type, unit and report error as shown in the following table: Bits in Config Registers Determined by Default value Bit 3 Bit 0 Thermocouple type 0000 (J -type) Bit 5- Bit 4 Unit Selection 00 (Celsius) Bit 7 Bit 6 Report-Error Selection 00 (Do not report) The values of bits for various selections can be seen from the configuration dialog box.
5 Thermocouple Module Operation The Thermocouple provides 4 inputs for thermocouples. Each input can independently configured for by writing to corresponding configuration register. The configuration can be done using the dialog box as described above. Alternately the configuration can be done by writing appropriate values in the Output Registers of the module. Tag Data Types In EZPLC the ladder logic accesses memory using tags. Therefore create tags for each of the Input (IR) and output registers (OR) associated with the module. Each tag has a data type to interpret the data values appropriately. Please follow below given guidelines for the tag data types for the module: Tags associated with the Output Registers (OR) must be declared UNSIGNED_INT_16 Tags associated with the Input Registers (IR) must be of SIGNED_INT_16 for all thermocouple types EXCEPT type B in which case it should be UNSIGNED_INT_16. Interpreting Temperature Values The thermocouple module provides temperature values with one digit after the decimal point. However these values are presented as whole integer numbers, not as floating point or real numbers. The decimal point is implied. Thus if a reading from the module is 1234, it should be interpreted as 123.4, or alternately if the temperature is degrees (C or F or K), the input register would return a value of Open Thermocouple detection Thermocouple module can detect open or burnt thermocouples. On detecting an open/burnt thermocouple, the module provides a lowest or highest possible value in corresponding Input Register. The choice of low or high value is user programmable. See configuration dialog box, and specification to see the values returned for each thermocouple type. External CJC Sensor Diagnostics The thermocouple module provides automatic cold junction compensation. User has an option to use internal (default) or external temperature sensor for this purpose. If external sensor is not selected in Module setup (see setup section), the internal option is automatically used. The wiring of the 3-terminal external sensor is shown in wiring section above. The reading in input-register corresponding to input #4 can be used to detect incorrect wiring of the sensor. If the reading is above 100 or below 0, the sensor may not be wired correctly.
K-Type Thermocouple Sensor User s Guide
K-Type Thermocouple Sensor User s Guide 1 TABLE OF CONTENTS: 1 INTRODUCTION... 2 2 TYPICAL APPLICATION:... 2 3 INSTALLATION RULES:... 2 3.1 Connecting the sensor to M1/MD4 data logger:... 2 3.2 Connecting
DL05 Memory Cartridge / Real Time Clock. Manual Number D0 01MC M
DL05 Memory Cartridge / Real Time Clock Manual Number D0 01MC M WARNING Thank you for purchasing automation equipment from Automationdirect.com. We want your new DirectLOGIC automation equipment to operate
User s s Manual. LG Programmable Logic Controller GLOFA MASTER-K G3F TC4A G4F TC2A G6F TC2A. LG Industrial Systems
User s s Manual LG Programmable Logic Controller GLOFA MASTER-K G3F TC4A G4F TC2A G6F TC2A LG Industrial Systems REVISIONS Date REV. No Description 2001.4. 702004908 G6F-TC2A Module added SAFETY PRECAUTIONS
User s Guide DDS-3X25 USB ARBITRARY FUNCTION GENERATOR
User s Guide DDS-3X25 USB ARBITRARY FUNCTION GENERATOR Content General safety summary...1 Introduction...2 Chapter 1 Getting started...3 System Requirements...4 Installing Hardware...5 Installing Software...8
Omron I/O Driver (Series 2) Programmable Serial Interface Card
Omron I/O Driver (Series 2) Programmable Serial Interface Card USER MANUAL Rev. P1.55 June 8, 2012 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998, 1999.
Wahl C50 Calibrator FEATURES
NEW! On Site Multifunction Portable Far Superior Accuracy as Compared to Fluke! Simultaneous Measurement and Generation Quick Connect Terminals Anti-Shock Boot Quick Connect Terminals Navigator Power Supply,
1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3
Contents Moxa Technical Support Team [email protected] 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements... 4 4 Configuration...
DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual
DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages
Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
USB-500 Series Stand-Alone, Low-Cost Data Loggers
Stand-Alone, Low-Cost Data Loggers Features Stand-alone, remote data loggers Measure temperature, humidity, voltage, or current 1 or 2 channels Low cost, small size Battery powered Software Included, easy-to-use
Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description... 3. 1.1 Objective... 3 1.2 Goals...
Moxa MGate 5105-MB-EIP Contents Moxa Technical Support Team [email protected] 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements...
PROGRAMMABLE LOGIC CONTROLLERS Unit code: A/601/1625 QCF level: 4 Credit value: 15 TUTORIAL OUTCOME 2 Part 1
UNIT 22: PROGRAMMABLE LOGIC CONTROLLERS Unit code: A/601/1625 QCF level: 4 Credit value: 15 TUTORIAL OUTCOME 2 Part 1 This work covers part of outcome 2 of the Edexcel standard module. The material is
Table of Contents. SMS Messaging SMS MESSAGING... 1. Creating SMS Messages & Variables... 5 Message Properties... 6
SMS Messaging Table of Contents SMS MESSAGING... 1 About SMS messaging... 2 Using SMS Messaging... 3 SMS Message Conditions and Elements... 4 Creating SMS Messages & Variables... 5 Message Properties...
SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2
SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2 USER MANUAL Rev. P1.11 September 13, 2006 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998,
User Manual Weather station V 0.2
& User Manual Weather station V 0.2 Last update: July 2012 All software-related descriptions refer to the software V1279. We recommend to update older versions of the system. Small deviations in the description
All Analog Outputs, voltage/current 20mA 35mA 5mA 48mA/30mA* *If the analog outputs are not configured, then subtract the higher value.
Vision OPLC V350-35-RA22/V350-J-RA22 Technical Specifications The Unitronics V350-35-RA22/V350-J-RA22 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include 2 Analog,
Online Infrared Flue Gas Analyzer Gasboard 3000
Online Infrared Flue Gas Analyzer Gasboard 3000 O 2 CO CO2 SO 2 NO NO x Use of measurement methods Proprietary Infrared NDIR Detectors - Micro-flow in ppm range: CO, NO, SO2, CO2 - Dual beam in % volume
OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3
2 Phase Stepping Motor Driver 2M542 OPEATING MANUAL Table of contents Introduction page 2 Specifications page 2 Timing chart page 3 Setting page 4 Current set page 4 educe current function page 4 Micro
M-series FOUNDATION Fieldbus I/O
April 2013 Page 1 M-series FOUNDATION Fieldbus I/O Use DeltaV state-of-the-art FOUNDATION Fieldbus redundant I/O for your process control system Increases input/output Takes advantage of all smart device
L5354 ControlNet Communications Interface
L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or
CMC-DN01 DeviceNet Slave Communication Card Operation Manual
CMC-DN01 DeviceNet Slave Communication Card Operation Manual 2011-12-26-A Warning This operation manual provides introduction on the functions, specifications, installation, basic operation and settings
2011, The McGraw-Hill Companies, Inc. Chapter 5
Chapter 5 5.1 Processor Memory Organization The memory structure for a PLC processor consists of several areas, some of these having specific roles. With rack-based memory structures addresses are derived
T-SERIES INDUSTRIAL INCLINOMETER ANALOG INTERFACE
T-SERIES INDUSTRIAL INCLINOMETER ANALOG INTERFACE T-Series industrial inclinometers are compact high performance sensors used to determine inclination in roll and pitch axes with excellent precision and
Siemens and National Instruments Deliver Integrated Automation and Measurement Solutions
Siemens and National Instruments Deliver Integrated Automation and Measurement Solutions The Need for Integrated Automation and Measurement Manufacturing lines consist of numerous decoupled systems for
Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111
, GH Q631 0030 R0111 SK 0010 B 98 The application unit is a DIN rail mounted device for insertion in the distribution board. The connection to the EIB is established via a bus connecting terminal at the
V350-TA24 V350J-TA24. 225mA@24VDC 240mA@24VDC 240mA@24VDC
Vision OPLC V130/ V350/ Technical Specifications Order Information V130-33-TA24 PLC with Classic panel, Monochrome display 2.4" V130-J-TA24 PLC with Flat panel, Monochrome display 2.4" V350-35-TA24 PLC
Microcontroller to Sensor Interfacing Techniques
to Sensor Interfacing Techniques Document Revision: 1.01 Date: 3rd February, 2006 16301 Blue Ridge Road, Missouri City, Texas 77489 Telephone: 1-713-283-9970 Fax: 1-281-416-2806 E-mail: [email protected]
HWg-STE HWg-STE PoE MANUAL
HWg-STE HWg-STE PoE MANUAL www.hw-group.com Page 2 HWg-STE connectors LED indicators Green: Power & Mode Yellow: Link & Activity SENSORS S1 and S2 ports for connecting temperature or humidity sensors.
Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
CPU systron S 200 - S 250 - S 250c. systron S 200 - S 250 - S 250c. CPUs to the process modules. Stand-alone PLC
E031019 000823 systron S 200 - S 250 - S 250c CPU systron S 200 - S 250 - S 250c 45 mm width Flexible and expandable Easy to use software for bus connection (S 250/ S 250c) CPUs to the process modules
Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples
Connecting Grounded and Floating Thermocouples For best performance, Thermocouple sensors should be floating. This will ensure that no noise currents can flow in the sensor leads and that no common-mode
DS1621 Digital Thermometer and Thermostat
Digital Thermometer and Thermostat www.dalsemi.com FEATURES Temperature measurements require no external components Measures temperatures from 55 C to +125 C in 0.5 C increments. Fahrenheit equivalent
Adafruit BME280 Humidity + Barometric Pressure + Temperature Sensor Breakout
Adafruit BME280 Humidity + Barometric Pressure + Temperature Sensor Breakout Created by lady ada Last updated on 2016-04-26 12:01:06 PM EDT Guide Contents Guide Contents Overview Pinouts Power Pins: SPI
KSH-3000-MI. Swipe Card Reader. ( Magnetic / IC Card two in One Reader ) Revision Reason Date V2.0 03-16-2006
KSH-3000-MI Swipe Card Reader ( Magnetic / IC Card two in One Reader ) Version: V2.7 Revision Reason Date V2.0 03-16-2006 V2.1 1. Update mechanical drawing 04-09-2006 V2.2 1. Update KSH-3000-061 drawing
Repeater Mil-Std-1553B Datasheet
Repeater Mil-Std-1553B Datasheet 1 Summary 1. Environment specification...3 2. Electronic diagram...5 3. Output...6 4. Electrical specifications...7 3. Test...8 3.1. Bus Monitor...8 3.2 Bus Controller...11
WIRELESS ASSET MONITORING
WIRELESS ASSET MONITORING WITH ANALYSIS AND DYNAMIC DATA TRANSLATOR SOFTWARE WAM 661 WAM 761 WAM 56U Rev. 2.11 WAM WIRELESS ASSET MONITORING SYSTEM OVERVIEW: Spectrum Instruments Ltd s WAM product line
ControlLogix Remote I/O Communication Module
User Manual ControlLogix Remote I/O Communication Module Catalog Number 1756-RIO Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power
July 2010 PACSystems* RX3i Non-Isolated Analog Output Module with HART Communications, IC695ALG728 Non-Isolated Analog Output Modules, IC695ALG704, IC695ALG708 MODULE OK FIELD STATUS TB IC695ALG708 Q1
Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.
Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling
O WA-120U series IP67. 120W Single Output Switching Power Supply. Features. Aplications
Features UniversalACinput/Fulrange Built-inactivePFCfunction Higheficiencyupto91% Protections:Shortcircuit/Overcurent/ Overvoltage/Overtemperature Fanlesdesign,colingbyfreairconvection Colingbyfreairconvection
XC series BD board for special functions. Operate Manual
68117 XC series BD board for special functions Operate Manual Catalog 一 CONFIGURE METHOD OF BD BOARD...3 二 ANALOG INPUT AND OUTPUT SAMPLING BOARD XC-2AD2DA-BD...4 2 一 Configure method of BD board Configure
Using Ladder Logic Instructions to Communicate with an Ethernet IP Nexus Unit
Communicating to an AMCI Ethernet IP Nexus unit is typically accomplished by using a scanner module in the PLC rack. However, it is also possible to communicate with these units directly using instructions
Ethernet/IP Explicit Messaging Using Unity Software
Data Bulletin 8000DB1025 07/2010 Raleigh, NC, USA Ethernet/IP Explicit Messaging Using Unity Software Retain for future use. Overview Presumption Requirements This data bulletin illustrates how to setup
TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
DCDC-USB. 6-34V 10A, Intelligent DC-DC converter with USB interface. Quick Installation Guide Version 1.0c P/N DCDC-USB
DCDC-USB 6-34V 10A, Intelligent DC-DC converter with USB interface Quick Installation Guide Version 1.0c P/N DCDC-USB Introduction The DCDC-USB is a small yet powerful DC-DC power supply designed to power
DS1721 2-Wire Digital Thermometer and Thermostat
www.dalsemi.com FEATURES Temperature measurements require no external components with ±1 C accuracy Measures temperatures from -55 C to +125 C; Fahrenheit equivalent is -67 F to +257 F Temperature resolution
HOBO Single Channel Thermocouple Data Logger (UX100-014M) Manual
HOBO Single Channel Thermocouple Data Logger (UX100-014M) Manual HOBO Single Channel Thermocouple Data Logger UX100-014M Included Items: Command strip Double-sided tape Hook & loop strap Required Items:
Cold-Junction-Compensated K-Thermocoupleto-Digital Converter (0 C to +1024 C)
19-2235; Rev 1; 3/02 Cold-Junction-Compensated K-Thermocoupleto-Digital General Description The performs cold-junction compensation and digitizes the signal from a type-k thermocouple. The data is output
Kurz Instruments Inc. Document 360209-AV Document Title: MFTB Event Code Definitions. MFT B-Series Event Codes
MFT B-Series Event Codes The MFT B-series status information is contained in a 4-byte long word (32-bit) Event Code. This Event Code provides a bit-wise mapping of the status of the flow meter with each
MLC 9000+ TM Maximum Productivity and Versatility for Control without Compromise!
Data Sheet Maximum Productivity and Versatility for Control without Compromise! Basic Bus Communication Module DESCRIPTION The Basic Bus Communication Module (BCM) is part of the MLC 9000+ DIN rail mount
UPS PIco. to be used with. Raspberry Pi B+, A+, B, and A. HAT Compliant. Raspberry Pi is a trademark of the Raspberry Pi Foundation
UPS PIco Uninterruptible Power Supply with Peripherals and I 2 C control Interface to be used with Raspberry Pi B+, A+, B, and A HAT Compliant Raspberry Pi is a trademark of the Raspberry Pi Foundation
Using IDENT M System T with Modbus/TCP
Using IDENT M System T with Modbus/TCP Introduction The Pepperl+Fuchs IDENT M System T consists of two models MTT3000-F180-B12- V45-MON, which is a read only unit and the MTT6000-F120-B12-V45 which is
User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger
USB-500/600 Series Low-Cost Data Loggers and Accessories
Low-Cost Data Loggers and Accessories Features Stand-alone, remote data loggers and portable logger assistant Measure temperature, humidity, voltage, current, or event/state change 1 or 2 channels Low
AN2680 Application note
Application note Fan speed controller based on STDS75 or STLM75 digital temperature sensor and ST72651AR6 MCU Introduction This application note describes the method of defining the system for regulating
WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK
WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue
Hydras 3 LT Quick Start
Catalog Number 6234218 Hydras 3 LT Quick Start SOFTWARE MANUAL December 2005, Edition 2 Hach Company, 2005. All rights reserved. Printed in the U.S.A. Catalog Number 6234218 Hydras 3 LT SOFTWARE MANUAL
User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com
Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Document updates: Version Data Description V1.0 2015.05.25 Finish new document HVAC Controller User Manual INDEX 1. Overview...1
BECKHOFF. Application Notes. www.beckhoffautomation.com. BC9000: Getting Started Guide. For additional documentation, please visit.
BECKHOFF Application Notes www.beckhoffautomation.com BC9000: Getting Started Guide BC-AppNote-002 1.0 27 August 2007 This application note is intended for the first time user of the BC9000 and TwinCAT
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
USB TC-08. Temperature Logger. User's Guide. usbtc08.en r7 Copyright 2005-2013 Pico Technology Limited. All rights reserved.
USB TC-08 Temperature Logger User's Guide USB TC-08 User's Guide I Contents 1 Introduction...1...1 1 Overview...1 2 Leg al information...2 3 Safety warning...3 4 Company details 2 Getting Started...4...4
Conversion Between Analog and Digital Signals
ELET 3156 DL - Laboratory #6 Conversion Between Analog and Digital Signals There is no pre-lab work required for this experiment. However, be sure to read through the assignment completely prior to starting
isppac-powr1220at8 I 2 C Hardware Verification Utility User s Guide
November 2005 Introduction Application Note AN6067 The isppac -POWR1220AT8 device from Lattice is a full-featured second-generation Power Manager chip. As part of its feature set, this device supports
Programmable Terminal. NPSeries. Easy Setup with the Low-cost, Compact NP Series
Programmable Terminal NPSeries Easy Setup with the Low-cost, Compact NP Series Simpler and More Versatile.OMRON s Compact NP Series Connect! Easier connection to OMRON PLCs and Temperature Controllers,
Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
HTM2500LF Temperature and Relative Humidity Module
Hermetic Housing Humidity calibrated within +/-2% @55%RH Temperature measurement through NTC 10kOhms +/-1% direct output Small size product Typical 1 to 4 Volt DC output for 0 to 100%RH at 5Vdc DESCRIPTION
Evaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS
Build a emperature Sensor Project A sensor is a device that measures a physical quantity and converts it into an electrical signal. Some sensors measure physical properties directly, while other sensors
WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01
WinCC Communication Manual Manual 2 This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 Release: September 1999 WinCC, SIMATIC, SINEC, STEP are trademarks of Siemens.
EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16290(LED TYPES) EXAMINED BY : FILE NO. CAS-10251 ISSUE : JUL.03,2001 TOTAL PAGE : 7
EXAMINED BY : FILE NO. CAS-10251 EMERGING DISPLAY ISSUE : JUL.03,2001 APPROVED BY: TECHNOLOGIES CORPORATION TOTAL PAGE : 7 VERSION : 1 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 16290(LED TYPES) FOR
LADDER LOGIC/ FLOWCHART PROGRAMMING DIFFERENCES AND EXAMPLES
page 1/10 This document is designed as a quick-start primer to assist industrial automation programmers who are familiar with PLCs and Relay Ladder Logic programming to better understand the corresponding
INTMOD485-LH Protocol Converter
For Use with L-GAGE LH Series Sensors Features Converts an LH Network to the 485-RTU protocol Supports baud rates up to 230,400 baud Supports LH Networks with up to 32 sensors Model Protocol Conversion
SDN INSTRUCTIONS 07/10, Ver 1.2. Somfy Digital Network (SDN) Installation and Programming
Somfy Digital Network (SDN) Installation and Programming SSoomffyy SSyysst teemss IInncc.. 1 Table of Contents 1 General Information and Features... 3 1.1 ILT2 Motor... 3 1.2 SDN Switches... 4 1.3 ILT2
Low Cost, Precision IC Temperature Transducer AD592*
a FEATURES High Precalibrated Accuracy:.5 C max @ +25 C Excellent Linearity:.15 C max ( C to +7 C) Wide Operating Temperature Range: 25 C to +15 C Single Supply Operation: +4 V to +3 V Excellent Repeatability
4-Channel Thermometer / Datalogger
USER GUIDE 4-Channel Thermometer / Datalogger RTD and Thermocouple Inputs Model SDL200 Introduction Congratulations on your purchase of the Extech SDL200 Thermometer, an SD Logger Series meter. This meter
User manual Rev. 1.2 (17/04/2015)
User manual Rev. 1.2 (17/04/2015) CompactPCI Serial power supply CompactPCI Serial power supply (for illustration only) CompactPCI Serial is a new standard that supports the fast serial protocols PCI Express,
USB-500/600 Series Low-Cost Data Loggers and Accessories
Low-Cost Data Loggers and Accessories Features Stand-alone, remote data loggers and portable logger assistant Measure temperature, humidity, voltage, current, or event/state change 1 or 2 channels Low
Lab Experiment 1: The LPC 2148 Education Board
Lab Experiment 1: The LPC 2148 Education Board 1 Introduction The aim of this course ECE 425L is to help you understand and utilize the functionalities of ARM7TDMI LPC2148 microcontroller. To do that,
Quick installation guide for the Vista Quantum QNVR Network Video Recorder
QNVR range Quick Instalation guide Quick installation guide for the Vista Quantum QNVR Network Video Recorder Full manual found on the CD supplied with the NVR Contents SCOPE OF USE... 3 1. FRONT PANEL
Hexadecimal and Numeric Indicators. Technical Data 5082-7300 5082-7302 5082-7304 5082-7340
H Hexadecimal and Numeric Indicators Technical Data 5082-7300 5082-7302 5082-7304 5082-7340 Features Numeric 5082-7300/-7302 0-9, Test State, Minus Sign, Blank States Decimal Point 7300 Right Hand D.P.
(Cat. No. 1775-L3) Product Data
(Cat. No. 1775-L3) Product Data When it comes to programmable controllers, the more power you can put into a chassis slot, the more control potential you have. The PLC-3 programmable controller, already
GV- RK1352 Card Reader
GV- RK1352 Card Reader The GV-RK1352 is a card reader with keypad, designed to recognize PIN codes, identification cards or both. Featured with the Wiegand and RS-485 outputs, the unit can be connected
Programmer/Controller
Systems Plus START 7 8 9 envirotronics ALARM STOP 4 5 6 ALARM ACK Instrument Manual Systems Plus Programmer/Controller OFF HELP 1 2 0 3. ENTER ALARM RESET DEL Revision 6 9/12/97 Table of Contents 2 Menu
CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device
CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device SIMATIC PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device Introduction 1 Preparation 2 Learning units 3 Further Information
Configuring SMC-Flex for Communications over Remote I/O Network using 20-COMM-R Card This document is intended to be used for reference purposes only.
Configuring SMC-Flex for Communications over Remote I/O Network using 20-COMM-R Card This document is intended to be used for reference purposes only. Objective: This document is intended to provide an
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
Technical Specifications: The specifications represent a particular hardware platform. Application-specific software is provided.
Preliminary TECHNICAL DATASHEET #TDAX020700 HYDRAULIC VALVE CONTROLLER 24 I/O 5 Analog and 6 Digital Inputs 1 Temperature Sensor and 1 RPM Sensor Interface 2 PWM Inputs 6 Proportional and 4 ON/OFF Current
EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16400(LED TYPES) EXAMINED BY : FILE NO. CAS-10068 ISSUE : JAN.19,2000 TOTAL PAGE : 7 APPROVED BY:
EXAMINED BY : FILE NO. CAS-10068 APPROVED BY: EMERGING DISPLAY TECHNOLOGIES CORPORATION ISSUE : JAN.19,2000 TOTAL PAGE : 7 VERSION : 3 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 16400(LED TYPES) FOR
HOBO U14 Data Logger User Manual
HOBO U14 Data Logger User Manual The U family of data loggers offers reliability and convenient monitoring for applications that require higher accuracy, better resolution, more memory, or USB connectivity
Automation Unit TM 1703 ACP Flexible automation and telecontrol
Automation Unit Flexible automation and telecontrol Power Transmission and Distribution Outstanding performance: Automate simply with Highly complex and yet fully transparent automation solutions are not
Connection to an RS-485 Network
VBW108 Vibrating Wire Interface Connection to an R485 Network he information below shows how to connect the VBW108 to a general purpose R485 multidrop network Only a simple command structure is required
USB-Based Temperature & Humidity Sensor
DLP-TH1b *LEAD-FREE* USB-Based Temperature & Humidity Sensor The DLP-TH1 is a USB-based digital temperature and humidity sensor. Software provided with the DLP-TH1 sensor displays temperature, humidity,
USER MANUAL V5.0 ST100
GPS Vehicle Tracker USER MANUAL V5.0 ST100 Updated on 15 September 2009-1 - Contents 1 Product Overview 3 2 For Your Safety 3 3 ST100 Parameters 3 4 Getting Started 4 4.1 Hardware and Accessories 4 4.2
DS1621 Digital Thermometer and Thermostat
www.maxim-ic.com FEATURES Temperature measurements require no external components Measures temperatures from -55 C to +125 C in 0.5 C increments. Fahrenheit equivalent is -67 F to 257 F in 0.9 F increments
LM35 Precision Centigrade Temperature Sensors
Precision Centigrade Temperature Sensors General Description Typical Applications The LM35 series are precision integrated-circuit temperature sensors, whose output voltage is linearly proportional to
EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 20400 (LED TYPES) EXAMINED BY : FILE NO. CAS-10184 ISSUE : DEC.01,1999 TOTAL PAGE : 7 APPROVED BY:
EXAMINED BY : FILE NO. CAS-10184 APPROVED BY: EMERGING DISPLAY TECHNOLOGIES CORPORATION ISSUE : DEC.01,1999 TOTAL PAGE : 7 VERSION : 2 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 20400 (LED TYPES) FOR
Application Note Profinet Modules
BusWorks XT Series XT1xx3-000 I/O Models for Profinet 10/100MB Industrial Ethernet I/O Modules Application Note Profinet Modules Communicating with Acromag Model XTxxx3-000 Profinet I/O Modules From a
Nemo 96HD/HD+ MODBUS
18/12/12 Pagina 1 di 28 MULTIFUNCTION FIRMWARE 2.30 Nemo 96HD/HD+ MODBUS COMMUNICATION PROTOCOL CONTENTS 1.0 ABSTRACT 2.0 DATA MESSAGE DESCRIPTION 2.1 Parameters description 2.2 Data format 2.3 Description