An Alternative Approach to Improving SAIDI and SAIFI Indicators
|
|
|
- Byron Lambert
- 9 years ago
- Views:
Transcription
1 An Alternative Approach to Improving SAIDI and SAIFI Indicators Philippe Deschamps - Schneider Electric Industries - France Jean-Christophe Orsini - Schneider Electric Industries - France Kaare Seest Rasmussen - DONG Energy - Denmark
2 Summary Abstract...p 1 Introduction...p 2 DONG Energy's network...p 3 The concept of a SACSe substation...p 4 SACSe control unit architecture...p 7 F200C: Possible further enhancement...p 8 Conclusion...p 9
3 Abstract Under the pressure of regulating authorities, utilities are being challenged to improve their SAIDI and SAIFI indicators. Usually, to reach this goal, more intelligence is put inside DMS, increasing at the same time the amount of data to be processed and the importance of communication in the network. An alternative way, discussed in this paper, consists of using local automation, allowing faster reactions, and therefore a drastic reduction of the number of customers affected by permanent faults, without requiring heavy communication infrastructure. In addition, this paper introduces a further enhancement allowing a faster power restoration for the remaining affected customers. Paper
4 Introduction Challenged by the Danish authorities, DONG Energy has for a long time experimented with several methods to optimize network management and particularly increase power availability. An important step was reached when it was decided to reduce the maximum time to reenergize a faulty location to less than a minute to avoid the outage to be counted as a long one, that is degrading the SAIDI and SAIFI indexes. Paper
5 DONG Energy's network DONG Energy is a major DNO in Denmark, however this experience involves only one part of its network. FLA04 FLA FLA FLA FLA FLA FLA FLA FLA FLA FLA FLA FLA FLA FLA FLA Fig.1 - Typical feeder (neighbouring feeders in white) The 10 kv grid in DONG Energy North, is a 100 per cent underground radial network, with a high degree of access to neighbouring feeders for backup, as shown in Fig. 1. The grid is mainly urban and consists of approximately 7000 substations on 600 feeders. Paper
6 The concept of a SACSe substation First of all, let s clarify the management of phase to-phase and phase-to-earth faults in the DONG Energy network: phase-to-phase faults: these cause the tripping of a breaker and therefore an outage which explains how SACSe limits the number of customers affected phase-to-earth faults: the network is Petersen coil grounded, allowing temporary operation with single earth fault. However, SACSe provides an earth-fault localization information because a second earth fault would cause a tripping. SACSe means "Sectionalizing And Changeover System enhanced". The concept of SACSe described below is the latest evolution of the network, which has already seen significant improvement over the last 10 years. A first step was taken by deploying circuit breakers in the network [1]. The goal is to put in one strategic MV/LV substation, a line circuit breaker intended to split the feeder into 2 segments in order to minimize the number of customers affected by a fault, if it happens on the downstream side. Time selectivity is used to prevent primary substation CB from tripping simultaneously. In some cases, there could be up to two line CBs on the feeder: in such a case they would use the same setting and trip simultaneously. The second concept is a step further. In case of a phase-to-phase fault upstream in the same substation, it allows the faulty segment to be automatically isolated and the healthy ones to be automatically resupplied. This process is based on local automation, allowing a fast reaction, and not needing any human intervention or communication infrastructure. The solution was developed in collaboration with Schneider Electric, which offers a wide range of products for network automation. SACSe - Main principle First of all, in a given feeder, one or two substations are selected to support the automation. They are chosen because of their location: they divide the feeder into two or three segments, each supplying roughly the same number of customers. They are also chosen because of the ease of upgrading them. The principle of layout in the network of these substations is described in the ref [2]. Second, a backup line coming from the neighbour feeder is connected to these strategic MV/LV substations to allow a backup supply if required (Fig. 2). Incoming/outgoing/backup MV/LV transformer Fig. 3 - Typical make-up of a switchgear in a SACSe MV/LV substation HV/MV sub Feeder 1 Feeder 2 Feeder n Fig. 2 - Principle of a SACSe substation layout in DONG Energy s network These substations are equipped with a fourfunction switchgear (Fig. 3): 1 fuse switch or circuit breaker for the transformer protection. It can be forgotten since it has no role in the concept. 2 circuit breakers and 1 switch distributed among the incoming, the outgoing, and the backup lines. There are two circuit breakers among the three to be sure that there will be at least one in the circuit in all network configuration cases. Backup line MV/LV sub SACSe MV/LV sub Paper
7 If a fault occurs downstream, the breaker opens instantaneously, isolating the downstream segment(s). The status of the switchgear is then sent to the SCADA. If a fault occurs upstream, the switchgear acts as an auto changeover (ACO): the circuit breaker will not trip, but the lack of voltage releases the auto changeover process, ordering the incoming to open and the backup to close, which supplies the healthy downstream segment. This is the general principle. Two cases are shown in Fig. 4. Since the breaker in the HV/ MV substation is delayed and those in the SACSe are not, the breaker in the HV/MV sub will only trip when the fault is in the first segment (Fig. 4 - case 1). Trip Open + backup Case 1 Case 2 Fig. 4 - ACO - principle of fault restoration Trip Open + backup In a particular case (2 SACSe on the same feeder), a fault downstream in the second SACSe results in both SACSe circuit breakers tripping. In order to resupply the segment between the two SACSe circuit breakers, the downstream one will act as a Reverse Auto Changeover (RACO): based on the CB tripping information, it will keep the incoming closed, and order the backup to close, therefore resupplying the upstream segment (Fig. 5). Trip Trip + reserve backup In all cases, the time required to reconfigure is less than 20 seconds, saving automatically up to 2/3 of the customers normally affected by such a fault. In addition, several logic processes are embedded in the automation in order to avoid any improper action in certain cases: once the ACO/RACO has operated, it is blocked until there is some human interaction from the control center to prevent further action in a nonstandard network configuration a logic process is in action to avoid any ACO and/or RACO action if the network is subject to a global outage, from the transport for instance. This event is detected by monitoring the voltage presence on the backup line. If an absence of voltage is observed on both incoming and backup lines, then no action is taken in case of a frequency drop, a recovery process exists in the HV/MV substation and it, it reacts by switching off some feeders. So in this case, the ACO/RACO is inhibited to allow the load-shedding process to be prioritized. Fig. 5 - ACO - principle of fault restoration Paper
8 Infrastructure Basically, the system does not require any means of communication to react properly and fulfil its purpose. In fact this is even an advantage in terms of security and reliability. But of course, it is linked with the SCADA to report the outage on the faulty segment, in order to restore the power. In addition, it reports its status to the operating staff, as Danish regulations require the operator to know the real status of all switches and breakers in the network all times. By these means, other information available in the MV/LV substation can also be transmitted. In this case, and thanks to good coverage of the area by GSM infrastructure, GPRS has been chosen to transfer data in a very economical way. Earth fault As explained above, SACSe also integrates directional fault passage indicators (FPIs). These FPIs allow the staff to locate the fault in the field more accurately and faster, and therefore prevent a tripping due to a second fault. All these features are embedded in a single box provided by Schneider Electric, which is described below. Paper
9 SACSe control unit architecture Functional description The unit integrates the following functions (Fig. 6): phase-to-phase fault protection ensured by two protection relays, for the incoming/outgoing and backup breakers phase-to-earth fault detection ensured by two directional fault passage indicators on the same functions voltage presence on incoming, outgoing, and backup cables automation ensuring the ACO/RACO logic communication with the SCADA on the status of the substation power supply with batteries to supply the unit under all conditions. In addition, LV and MV measurement features have been included in the unit to provide a much better knowledge of the substation and the network load. Phase I protection I Eart detection U Fig. 6 - General architecture of the SACSe system U I ACO RACO logic Com Power supply Design SACSe is designed as an industrial solution integrating existing or slightly modified products from the Schneider Electric Easergy offer: relays from the SEPAM range FPI for earth protection is based on the Flair range automation is based on the Easergy T200 which includes peripheral functions such as backup/main power supply and modem. All these products were designed specifically for the network automation environment. As a consequence, they comply with the specificities of this application: harsh environment withstand (temperature, EMC, electrical insulation -10 kv on mains, dust, humidity, etc.), allowing the high level of robustness required by such an application, openness in terms of communication protocols, and a ready-to-use product to minimize the settings on-site during the installation. All these products are integrated in a single box (Fig. 7) in a way to make it easy to integrate into DONG Energy's existing installed base. No assembling is needed on-site, just the mounting of one box, and the connection of the sensors and the commands in the switchgear. In terms of size, the system is made to be mounted directly on the wall of the substation. The dimensions allow it to be used even in a compact substation with reduced volume available. Interfaces are designed to make installation simple and minimize the risk of mistakes by using prefabricated cables and connectors to link the unit with sensors. The box is equipped with a transparent window on the front door, allowing all indicators of the status of the system to be read locally. If needed, Fig. 7 - SACSe control unit operating staff have access to the local operation by opening the front door. Paper
10 F200C: Possible further enhancement Thanks to the unit presented above, the SAIDI index is drastically reduced, but ultimate quality requires some additional instrumentation of the network: In case of a phase fault, only half (if 1 SACSe) or one third (of 2 SACSe) of the feeder customers are affected by an outage more than one minute. However, the half or third of customers in the faulty segment still need to get power back as soon as possible. In case of an earth fault, the SACSe control unit can indicate whether the fault is upstream or downstream the SACSe substation. But a more accurate localization is required in order to allow faulty cable isolation without power interruption for any customer. Accurate localization would ideally mean knowing which cable between the two substations is faulty. Schneider Electric has recently launched a new communicating fault passage indicator, the Flair 200C, combining in a single cost-effective product the phase-to-phase and phase-to-earth fault detection and the GPRS communication functions. This would suit the above purpose particularly well. It should be noted that this new Flair 200C embeds a new algorithm for detection of phase-to-earth faults on compensated networks not requiring voltage sensing. This allows the commissioning of such devices to be drastically simplified, especially for retrofit in existing substations, and it reduces the global cost. Of course, for obvious cost and complexity reasons, more than two SACSe substations on a feeder are not possible. Increasing the number of SACSe substations is therefore not a way to achieve ultimate quality. Additionally, the Flair 200C can optionally provide measurements, further increasing the knowledge of network load. This means a device allowing accurate localization of both phase faults and earth faults is needed in the other substations, both upstream and downstream from the SACSe. Paper
11 Conclusion Increasing pressure on SAIDI/SAIFI improvement usually requires more performance from DMS, and at the same time the management of more and more information. A complementary solution involves the use of local automation able to perform simple actions quickly. By this means, when a fault occurs, a rough but fast reconfiguration is done while the operation is simplified. The implementation of this requires a dedicated device to prevent complex commissioning from spoiling the solution, and therefore the Return On Investment. References [1] Peter Vinter, Henrik Vikelgaard, 2005, "A novel approach to distribution grid automation at NESA A/S", CIRED Conference 18th international conference on electricity distribution. Session 3. [2] Kåre Seest Rasmussen, 2009, "A real case of self healing distribution network", CIRED Conference 20 th international conference on electricity distribution. Session 3. Paper
12 Schneider Electric Industries SAS 35, rue Joseph Monier CS F Rueil Malmaison Cedex RCS Nanterre Capital social This document has been printed on ecological paper Schneider Electric. All Rights Reserved.
Secure your electrical network. PACiS The Safety Solution for Healthcare Institutions
Secure your electrical network The Safety Solution for Healthcare Institutions Fast Secure : the solution for fault isolation and electrical network restoration in less than 500 ms 03 A Real Time System
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
Easily connect your switchboards to facility management solutions
Easily connect your switchboards to facility management solutions Acti 9 communication system gives your customers complete control of their installations 100% exclusive to Schneider Electric Acti 9: The
What will MV switchgear look like in the future? by Jean-Marc Biasse
What will MV switchgear look like in the future? by Jean-Marc Biasse Table of contents Introduction... 2 Brief history of the technologies used in medium voltage switchgear and control gear... 4 Evolution
Power products and systems. Intelligent solutions for power distribution Zone concept
Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,
Investor day. November 17, 2010. Energy business Michel Crochon Executive Vice President
Investor day November 17, 2010 Energy business Michel Crochon Executive Vice President We built a global leadership in medium voltage and grid automation with Areva Distribution MV switchgears & systems
Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850
Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Chapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
ADMS(Advanced Distribution Management System ) in Smart Grid
ADMS(Advanced Distribution Management System ) in Smart Grid 柯 佾 寬 博 士 Yi-Kuan Ke, Ph.D. 2014/03/28 Smart Grid Solution Smart Grid Solution Overview Smart Grid Solutions Smart Network Operation - Distribution
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring
Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation
How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse
How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission
Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server
Gain energy insight and control with PowerLogic PowerLogic EGX300 integrated gateway-server Plug into your energy usage with a simple mouse click The PowerLogic EGX300 is an integrated gateway-server that
Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver
www.siemens.com/fusesaver Siemens Fusesaver Highest availability and cost savings for your MV distribution network Answers for infrastructure and cities. 2 In high demand: An intelligent solution Improving
IEC 61439-1 & 2 standard. The reference for safe and reliable LV switchboards
IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Il Progetto INTEGRIS. Risultati e nuove prospettive per lo sviluppo delle Smart Grid October 2nd 2013 Brescia
Il Progetto INTEGRIS. Risultati e nuove prospettive per lo sviluppo delle Smart Grid October 2nd 2013 Brescia From INTEGRIS a solution architecture for energy smart grids Jean Wild - Schneider Electric
F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China
ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution
Industrial IT for Substation Automation & Protection
Industrial IT for Substation Automation & Protection Exploit the potential of ABB substation automation Improve your performance In view of the increasingly competitive arena where power providers are
CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services
CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
S c h n e i d e r E l e c t r i c BUSINESS IMPACT. Jack Hack Enterprise System Engineer 19 November 2015
S c h n e i d e r E l e c t r i c BUSINESS IMPACT Datacenter means business - create the bridge between IT en Facilities. Jack Hack Enterprise System Engineer 19 November 2015 1 Your ability to compete
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE
Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity
Substation Automation based on IEC 61850
Substation Automation based on IEC 61850 Ivan De Mesmaeker 1, Peter Rietmann, Klaus-Peter Brand, Petra Reinhardt ABB Switzerland Ltd. (Switzerland) Introduction The more than 4000 Substation Automation
A MODERN DISTRIBUTION MANAGEMENT SYSTEM FOR REGIONAL ELECTRICITY COMPANIES
A MODERN DISTRIBUTION MANAGEMENT SYSTEM FOR REGIONAL ELECTRICITY COMPANIES A Roberts, T Berry, W D Wilson Schneider Electric Ltd, UK SYNOPSIS This paper describes the features of a modern Distribution
MV NETWORK REMOTE MONITORING AND CONTROL EXPERIENCES FROM DISTRIBUTION UTILITIES IN CROATIA
MV NETWORK REMOTE MONITORING AND CONTROL EXPERIENCES FROM DISTRIBUTION UTILITIES IN CROATIA Darijo RUNJIC, Goran LECI Koncar-Power Plant And Electric Traction Engineering Inc, Croatia [email protected];
Ralf Christian, CEO Low and Medium Voltage. Making Things Right with Totally Integrated Power (TIP)
Ralf Christian, CEO Low and Medium Voltage Making Things Right with Totally Integrated Power (TIP) siemens.com/hannovermesse Making Things Right with Totally Integrated Power (TIP) Trade LV 100 kw Industrial
GSM ATT Modules Simply effective remote control
GSM ATT Modules Simply effective remote control To control electrical loads via mobile phone The benefits Remote management of electrical devices is an increasingly widespread requirement in residential
Substation Automation and Smart Grid
GE Energy Substation Automation and Smart Grid John D. McDonald, P.E. GM, T&D Marketing IEEE PES Past President IEEE Division VII Director IEEE Fellow The Smart Grid POWERING POTENTIA L Current Situation
Agenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman. [email protected]. [email protected]
Agenda do Mini-Curso Sérgio Yoshio Fujii [email protected] Ethan Boardman [email protected] Agenda do Mini-Curso Sistemas de Distribuição (DMS) Characteristics of Distribution Network
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK F. Malone*, P.D. Doyle *ESB International, Ireland [email protected] ESB International, Ireland [email protected]
Distribution Automation / Smart Grid. Kevin Whitten
Distribution Automation / Smart Grid Kevin Whitten Main Overview Distribution Reliability Distribution Automation Smart Grid Distribution Reliability Distribution Reliability - Overview Introduction to
Galaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
ENVIRONMENTAL MONITORING SYSTEM WITH WORLD-WIDE COVERAGE AND BIDIRECTIONAL COMMUNICATION VIA INMARSAT SATELLITE NETWORK
ENVIRONMENTAL MONITORING SYSTEM WITH WORLD-WIDE COVERAGE AND BIDIRECTIONAL COMMUNICATION VIA INMARSAT SATELLITE NETWORK THE WORLD S MOST COST-EFFECTIVE, ALL-IP BGAN MACHINE-TO-MACHINE SATELLITE TERMINAL
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
DISTRIBUTION RELIABILITY USING RECLOSERS AND SECTIONALISERS
ABB DISTIBUTION ELIABILITY USING ECLOSES AND SECTIONALISES obert E. Goodin Chief Engineer ABB Inc. Lake Mary, FL Timothy S. Fahey, PE Sr. Application Engineer ABB Inc. aleigh, NC Andrew Hanson, PE Executive
EDP DISTRIBUIÇÃO S ASSET MANAGEMENT TOOL SUPPORTED BY REAL TIME MONITORING
EDP DISTRIBUIÇÃO S ASSET MANAGEMENT TOOL SUPPORTED BY REAL TIME MONITORING Hugo FERREIRA Pedro CARREIRA Rui BERNARDO Jorge GOMES EDP Distribuição - EDP Distribuição EDP Distribuição - EDP Distribuição
Monitoring Underground Power Networks
Monitoring Underground Power Networks By Mark Stiles Merve Cankaya ABSTRACT Underground electric distribution systems are common in large cities throughout the United States. Power usage for the entire
MV vacuum circuit breaker Evolis. When trust guides your steps
MV vacuum circuit breaker Evolis When trust guides your steps Evolis From the world specialist in MV/LV electrical distribution Through its expertise in circuit breaker design, Merlin Gerin specialists
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
Electrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
Product overview brochure. ABB Medium Voltage Products Our one-stop approach for every medium voltage application
Product overview brochure ABB Medium Voltage Products Our one-stop approach for every medium voltage application Overview ABB meets every need for reliable, safe and energy-efficient medium voltage switchgear,
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
Solutions for Photovoltaic Systems. Large buildings and power plants
Solutions for Photovoltaic Systems Large buildings and power plants Helping you achieve the lowest cost of energy for your project When it comes to large-scale installations, you need a solar solution
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
Basics in Energy Information (& Communication) Systems Summary Substation Automation
Basics in Energy Information (& Communication) Systems Summary Substation Automation Dr. Johann Pohany, xxxx x xxx xxx xx Substation Integration and Automation Levels Integrated utility business operation
New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems
International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Choosing for tranquility
Medium voltage switchgear with withdrawable circuit breakers MCset Choosing for tranquility Web enabled Power & Control Building a New Electric World Innovation at every level Busbar compartment This section
DISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT
DISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT Dr. Dipesh Patel 1, Jigar Juthani 2, Harsh Parikh 3, Rushit Bhavsar 4, Ujjaval Darbar 5 1 Head of Electrical Department, BITS edu campus, Vadodara
RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER. tgood.com. Energy. Fast.
RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER tgood.com Energy. Fast. TGOOD is a world leading manufacturer of prefabricated renewable energy substations PRODUCT CONCEPT ENVIRONMENTAL
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
Electrical Distribution Services for Mining and Metals Industries
Electrical Distribution Services for Mining and Metals Industries Solutions to help maximize plant reliability and ensure personnel safety Make the most of your energy SM Electrical Systems are Serious
ASSET MANAGEMENT LCNI 2014 Wednesday 22 nd October. Jennifer Woodruff Innovation & Low Carbon Networks Engineer
ASSET MANAGEMENT LCNI 2014 Wednesday 22 nd October Jennifer Woodruff Innovation & Low Carbon Networks Engineer Asset Management Efficient asset management ensures that risk is effectively managed and returns
TSX Micro on support with sockets. Study and programming in PLC language
TSX Micro on support with sockets Study and programming in PLC language TSX Micro on support with sockets 1. Presentation of the equipment The "TSX Micro on support with sockets" consists in a PLC TSX
ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
UPS system for emergency lighting and smoke extraction
UPS system for emergency lighting and smoke extraction Requirements There are a number of standards that apply to emergency lighting and smoke extraction systems (for example: NFS 61-940 [France only]
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-xxx PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small
Modular Systems wind portfolio overview Power Collection and Grid Connection products
Modular Systems wind portfolio overview Power Collection and Grid Connection products Slide 1 Modular Systems wind portfolio Wind power - definition A wind turbine is a device that converts kinetic energy
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
P System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009
A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based
Educational solutions. MV/LV power grid design and operation laboratory
Educational solutions MV/LV power grid design and operation laboratory Presentation Context A growing development of the power supply requires a staff competent in its engineering, operation and maintenance.
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
BL20A0501 Electricity distribution technology. Introduction Jarmo Partanen
BL20A0501 Electricity distribution technology Introduction Jarmo Partanen Introduction to ED Prof. Jarmo Partanen, D.Sc Jukka Lassila Topics of lectures Introduction to Electricity Distribution, 27.10
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
ATS - Automatic Changeover
ATS - Automatic Changeover Manufacturers of Electrical Switchgear Choosing an Automatic Transfer System Switchgear Systems offer a variety of solutions for multiple supply switching needs. As well as our
Enhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
A Case Study: How a Utility Automated and Integrated Data/Control for 4000 Pole-Top Switches and Protection Relays, and Reduced its SAIDI
A Case Study: How a Utility Automated and Integrated Data/Control for 4000 Pole-Top Switches and Protection Relays, and Reduced its SAIDI Hervé Delmas, Eng. - Hydro-Quebec Patrick Cossette, Eng. - Cooper
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
Ladies and Gentlemen,
Ladies and Gentlemen, I would like to begin my speech by thanking deeply the Maniatakeion Foundation and especially the Chairman, Mr. Dimitris Maniatakis for his invitation and to congratulate him for
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy
Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay
DMS - Breakthrough Technology for the Smart Grid
DMS - Breakthrough Technology for the Smart Grid The emerging smart grid is expected to address many of the current challenges in the electrical power industry. It is expected to make the electric grid
know-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
Installation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
S&C TripSaver Dropout Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing S&C s new TripSaver Dropout Recloser: A better solution for overhead lateral circuit protection at
Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains
Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three
Medium Voltage Distribution FLUVAC. Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka. Operation Maintenance Instructions. www.schneider-electric.
Medium Voltage Distribution FLUVAC Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka Operation Maintenance Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists,