Technical catalogue. Low-voltage moulded-case circuit-breakers /012 en ABB SACE
|
|
|
- Sophie Casey
- 9 years ago
- Views:
Transcription
1 Technical catalogue Low-voltage moulded-case circuit-breakers /02 en
2
3 Contents Presentation Main features 2 Ranges Accessories 4 Characteristic curves and technical information 5 Dimensions and circuit diagrams 6 Order codes 7 /
4 SACE Isomax S. The greatest project for moulded-case circuit-breakers A single series for all applications SACE Isomax S is a project which evolves continually and is today the largest and most complete family of low voltage moulded-case circuit-breakers on the market, able to fulfil all installation requirements, from the small user up to large industrial electrical power distribution plants. Innovation, Technology and Quality have always been the main guides for ABB SACE in developing products and are at their peak in the SACE Isomax S series the moulded-case circuit-breakers characterised by high quality, reliability, and performance under all conditions, simplicity of installation and safety of operation. The continual and constant evolution of the series has led to further extending the range of products, thereby making the SACE Isomax S offer increasingly complete over time. The series, which is divided rationally into eight basic sizes from S to S8, does, in fact, consist of different ranges destined to fulfil any installation need in a specific and optimal way. The completeness of the series can also be noted in better rationalisation of use: the overall dimensions, methods of installation and possibility of applying accessories are all the same, regardless of the type of range the circuit-breaker is placed in. Great importance is also put on the microprocessor-based electronic releases (mounted on the circuitbreakers starting from 60A): SACE PR2/P, PR22/P and SACE PR22/MP (International Patent), specifically designed to actuate dedicated functions for motor starting and protection. Thanks to innovative and state-of-the-art protection functions, they ensure reliability and precision and are unaffected by electromagnetic interference. A basic characteristic of these types of releases is their ability to communicate and dialogue with the SACE SD-View 80 self-configuring software, thereby allowing full integration of the circuitbreakers in the management logics relative to electric network supervision and control systems. /2
5 The new series has been studied respecting the most modern ergonomic criteria. Witness to this is the prize awarded with the IF seal to the circuitbreakers at the Design Forum in Hannover. GSIS907 /
6 A world of solutions for installation design engineering. An answer to all requirements. The SACE Isomax S family is divided into eight basic sizes, S, S2, S, S4, S5, S6, S7 and S8 with rated uninterrupted currents from 25 to 200A. The types of devices consist of: fixed, plug-in and withdrawable circuit-breakers with seven ultimate rated breaking capacity levels - from 6 to 200kA (80-45V) - identified by the letters: B, N, S, H, L, V,. From this family, which is considered the common nucleus, a series of dedicated ranges are configured, which keep the same installation characteristics and accessory application possibilities. Within the series there are therefore circuit-breakers available for alternating and direct current distribution, current-limiting circuit-breakers, circuit-breakers for motor protection, switch-disconnectors, circuit-breakers for applications with voltages up to 000V, and residual current circuitbreakers, as well as specific ranges (for motor protection and switch-disconnectors) complying with the North American UL489 and CSA C22.2 Standards. This means wider application possibilities both in industrial and civil sectors. They can therefore be mounted in primary (Power Center) and secondary (Panel Board) distribution switchboards, for motor protection and control (Motor Control Center), in generators and for end users. Their performances are, however, of particular interest where critical situations arise (very high rated and fault currents), or where complex plant engineering solutions are needed (special coordination requirements and plant automation). They also guarantee total selectivity of the protections up to full breaking capacity of the circuit-breaker installed on the load side. Centralised supervision and control systems The reliability, efficiency and quality of a LV electrical power distribution service is considerably increased by constant supervision of users and all the parameters of the installation itself. The information regarding the installations is collected using microprocessor-based field components which can be mounted directly on board the apparatus, such as the SACE PR22/P release, or using the devices in the SACE SD family. Moreover, the use of the SACE SD-View 80 software allows a simple personal computer to be converted into a work station for supervising and controlling electrical power distribution plants. GSIS9072 Alternating current GSIS907 GSIS9074 V~ Circuit-breakers with thermomagnetic releases and circuit-breakers fitted with microprocessor-based SACE PR2/P, PR22/P releases are available for protection of alternating current networks. These feature an application field from 0 to 200A and a rated voltage of 690V. Apart from the more generic applications, they are particularly suited to protection of generators, capacitors, transformers and machine tools. Thanks to its special construction characteristics, this range of circuit-breakers combines normal Isomax safety characteristics with very high performances. The breaking technique used (double interruption per pole) and the special shape of the breaking parts, allow very high value short-circuit currents (200kA) to be tripped extremely rapidly, making these circuit-breakers ideal wherever protection close to the power supply source is needed. Direct current V Pole connection in series allows applications in the most severe operating conditions and in any type of network (insulated, with earthed polarity, and with median point of the power supply earthed). The circuit-breakers for direct current with thermomagnetic releases are available for operating currents between 0A and 800 A, with rated voltages up to 750 V, with poles in series, and 250 and 500V, with two poles in series. The range for applications at 000V in alternating current and direct current extends the use of the moulded-case circuit-breakers even further and is a good example of the continual evolution of the SACE Isomax S series. They are particularly suitable for installation in special ambients, such as mines, petrochemical plants and for electric traction. proposes various solutions, which allow type 2 coordinations to be made for switching and protecting motors, from 0.7kW to 55kW. It is possible to select either circuitbreakers suited just to protection against short-circuit, or circuit-breakers fitted with the new SACE PR22/MP electronic release, which is technologically advanced and has been specifically studied for motor protection. The latter integrates protection functions on /4
7 SACE Isomax S current-limiting circuit-breakers GSIS909 The switch-disconnectors are derived from the corresponding circuit-breakers, keeping the overall dimensions, versions and accessories unchanged. They guarantee operation and isolation in maximum safety and their release device can be activated either by the undervoltage release or by the shunt opening release. They can also be fitted with residual current releases, thereby constructing pure residualcurrent circuit-breakers. SACE Isomax S switch-disconnectors SACE Isomax S Power distribution GSIS9075 SACE Isomax S for applications up to 000V board the circuit-breaker which are normally carried out by other devices, thereby ensuring numerous installation and service advantages. GSIS909 SACE Isomax S according to UL/CSA Standards Thanks to a specific range of SACE Isomax S circuit-breakers complying with the UL489 and CSA22.2 Standards, there are also greater possibilities for those customers operating on markets subject to the specifications defined in the North American standards. The range consists of seven sizes with rated uninterrupted current from 00A to 2500A and breaking capacities, at 480 V AC, which can reach 00kA. Within the basic series, there are circuit-breakers with magnetic only releases (MCP - Motor Control Protection) for motor protection, and switches (Moulded-Case Switch - MCS) for use as isolators or switching devices for lines, busbars or plant parts. SACE Isomax S for motor protection classical and advanced /5
8 A world of success The SACE Isomax S offer has been constantly renewed according to market requirements and often even anticipating these and is always to the fore from the technological viewpoint. Meanwhile, the quality and reliability have always remained at the maximum levels expected and the market has shown its appreciation of this. Behind every reference lies a requirement fulfilled. It is facts which speak for SACE Isomax S. SACE Isomax S is a highly successful product of recognised quality, with many fields of application and it involves different sectors all over the world, with either standard or highly personalised products. There is nowhere electrical power is used where SACE Isomax S is not to be found: manufacturing industries, steelworks, refineries and chemical plants, drilling rigs, gas pipelines, water pipelines, hospitals, airports, trains, railway and underground railway stations, calculation centres, offices, congress centres, theatres, and skyscrapers, as well as the most prestigious buildings worldwide. has, moreover, acquired knowledge which is practically unsurpassed in application areas where the highest degree of safety is required, and this has qualified it as the world leader in various sectors. Thousands of ships of all types cruise ships, container ships, bulk carriers, tankers, etc. and flying the flags of all nations are equipped with products, which are also widely used in railway traction and are the favourite product in the depths of mines. apparatus is also responsible for protection (sometimes also integrated with control functions) of plants of considerable economic and technological importance, constructed within the sphere of large infrastructure projects. Orders are processed which stand out both for their size (such as the pumping stations of gas pipelines thousands of kilometres long) and for their advanced context (astronomical observatories and international research centres). SACE Isomax S imposes itself on the markets worldwide. For example, apparatus has been supplied to some of the most important European and Middle Eastern electricity boards as well as to North American and Asian electrified transport companies. Particularly severe environmental conditions such as mines and steelworks Protection and control in installations for electric traction Refineries and chemical plants as well as gas pipelines, water pipelines Installation on board ships /6
9 Offices, theatres, shopping malls and residential complexes GSIS9076 Underground railway stations Off-shore drilling rigs Protection and control of motors, generators /7
10 Selection and design engineering tools, management flexibility, services and consultancy: an all-round offer With the aim of guiding and facilitating selection of its products, ensures 60 support, both before and after the sale. For this purpose, to design and size electrical installations, it makes various work tools available, which facilitate calculations, ensure compliance of the installation with the Standards and reduce the risks of any errors. These are basically divided into calculation, design and estimate software, and manual tools. D.O.C. (Design Optimization & Computation) is a system which allows correct sizing of industrial low voltage electrical installations, able to propose the most suitable design selections regarding cables, busbars and protection devices. It allows the design engineer to develop clear and complete design documentation rapidly, based on the calculation models provided by the most recent standards. C.A.T. (Computer Aided Technical Selection) is both an electronic catalogue and a technical aid tool for selecting and applying accessories to each individual circuitbreaker. By means of a guided pathway, it is possible to select, configure and order the most suitable apparatus for your own installation requirements. The calculation methods and data indicated on the slide rules are taken from the CEI, IEC and NFC Standards in force and from installation practice. The Guide to low voltage installations is a brief collection of legal and technical regulations based on the current standards, regarding design, sizing and installation of an electrical plant. The guide takes into consideration the user plant from the electric power delivery point (MV/LV substation) in st category systems. Four Slide rules of different colours, which make up the ABB Kits, allow rapid sizing calculations of the electrical installation. The following can be carried out: - Cable sizing and calculation of the short-circuit currents (yellow slide rule) - Checking the protections against direct contact and short-circuit of the cables (orange slide rule) - Selective and back-up coordination (green slide rule) - Sizing of motor lines and transformer outgoing feeders (blue slide rule) Immediate ordering and management flexibility Rapid ordering procedures have been provided for circuit-breakers in the SACE Isomax S series, and the configuration logic of the series enables efficient and flexible warehouse management. An order file can be generated compatible with the EDIFACT (Metel or ABB) standard, ready to be converted into EDI format and transmitted electronically. /8
11 Using EDI (Electronic Data Interchange) to send orders rationalises the logistics chain, thereby reducing transit times and the risk of errors. EDI transmission allows the order to be loaded automatically at so that the request is immediately sent to production, together with the order acknowledgement to the customer. The availability of standardised accessories for groups of circuit-breakers makes it possible to reduce the number kept in the warehouse and very short procurement times allow limited stocks to be kept as these can be rapidly replenished. Training: an indispensable tool for professionals By means of its technical training courses, is committed to putting its wealth of experience gained in over more than 60 years of operation at disposal. The courses are an opportunity for all operators in the sector to update their knowledge and compare notes, under the guidance of experts. Information and training have always been success factors for professional growth and development. Professional refresher training on both technical aspects and product developments, as well as on the standards and legislation, is essential, considering that these have such important implications for the safety of people and plants. The primary aim is to meet the information needs of professionals, especially by converting the technical-standard and legislative concepts into practical terms which can be applied directly to the various products and installations. Service Training courses are also provided for operators and maintenance personnel who work on apparatus and systems. For this purpose and to meet the need for evaluation and maintenance of existing electrical installations, the company has set up the Service Division within its own structure, which acts as a qualified interlocutor working in close collaboration with the managers/users of the plants, to carry out maintenance, repair and overhauling activities at and on the user s premises. The division also offers a spare parts, assembly and commissioning service for its own switchboards. /9
12 Just one product for everyone SACE Isomax S is a product which has been thought up and constructed for all types of customers: the user, the design engineer, the switchboard builder, the installer, the maintenance technician and the wholesaler. proposes technical solutions to the user which fulfil all requirements and are always up to date with technological innovations in the field of electrical power distribution. It offers high quality products, reliability and precision, which guarantee high performances under any conditions, safe products during service and, when necessary, simple replacement of any faulty parts. GSIS9092 GSIS9090 The design engineer has simple installation inside the products available which switchboard. The whole comply perfectly with the range of products is divided international technical into eight sizes and con- standards and which are structed in only three depths, able to do the job simply, thereby allowing standardi- safely and reliably at the sation of the supporting highest levels of perform- structures and of the switch- ance. SACE Isomax S circuit- boards and installation in breakers offer the design prefabricated structures. engineer solutions for sizing, The dimensional uniformity coordination and flexibility of and the possibilities of application which allow him connection, thanks to the to draw up a state-of-the-art variety of terminal available, project, selecting from considerably facilitates among well-known ranges connections by means of and circuit diagrams to be integrated in a complete busbars or cables. GSIS9079 system, and satisfying all installation requirements and performances according to the standards. The requirements of a switchboard builder are fully satisfied thanks to careful design of the product. The limited volumes of the pieces of apparatus allow the switchboard dimensions to be kept to a minimum and the modularity and compactness the ranges of products are conceived with allow provides the installer with products for any type of plant, which are practical to install, simple to use, assemble and connect and easy to check, thanks also to the quality of the accessories supplied with the apparatus and the technical support documentation provided. SACE Isomax S circuitbreakers allow easy and safe maintenance to be carried out, enabling the accessories to be inserted conveniently on the front of the circuitbreaker. Construction rationality as well as modularity of the structure, allow the maintenance technician to carry out replacements without the need for any special adaptation, even when changing from one type of circuitbreaker to another (for to a current-limiting circuitbreaker). Standardisation of Isomax S circuit-breakers and their accessories means simple and economical management of the spare parts warehouse for the wholesaler. Furthermore, the clarity of product coding considerably helps product ordering, reduces procurement times and allows limited stocks to be kept in the warehouse since the products can be example from an automatic replenished rapidly. /0
13 Main characteristics Index Panorama of the SACE Isomax S family A single series for all applications... 2/2 Construction characteristics 2 Distinctive features of the series... 2/4 Conditions of use... 2/8 Modularity of the series SACE Isomax S... 2/0 Compliance with the Standards Standards, Approvals, Certifications and company quality system... 2/2 2/
14 Panorama of the SACE Isomax S family A single series for all applications SACE Isomax S SACE Isomax S2 CIRCUIT-BREAKERS FOR AC / DC DISTRIBUTION S S2 Poles [nr.] Iu [A] Ue (AC) [V~] Icu (80/45V AC) [ka] B 6 6 N 25 5 S 50 H L V Ue (DC) [V ] CURRENT-LIMITING CIRCUIT-BREAKERS S2 00 Poles [nr.] Iu [A] 00 Ue [V~] 690 Icu (80/45V) [ka] 70 Icu (690V) [ka] 0 CIRCUIT-BREAKERS FOR MOTOR PROTECTION S2 80 Poles [nr.] Iu [A] 80 In [A] 80 Ue [V~] 690 Magnetic only release IEC Electronic release PR2/P (I), IEC Electronic release PR22/MP, IEC CIRCUIT-BREAKERS FOR APPLICATIONS AT 000 V AC Poles Iu Icu (000V AC) [nr.] [A] [ka] CIRCUIT-BREAKERS FOR APPLICATIONS AT 000 V AC Poles Iu Icu (000V DC), 4 poles in series [nr.] [A] [ka] SWITCH-DISCONNECTORS according to IEC Standard S2D Poles [nr.] - 4 Ith [A] Ue [V~] 690 Icm [ka], Icw [ka] 2,2 Circuit-breakers according to UL 489 and CSA 22.2 Standards SN Poles [no.] Maximum continuous current (40 C) [A] 00 Maximum Ampere Breaking Capacity (480 V) [ka] 20 Thermal-magnetic trip unit Microprocessor based trip unit - MCP - MCS - 2/2
15 SACE Isomax S SACE Isomax S4 SACE Isomax S5 SACE Isomax S6 SACE Isomax S7 SACE Isomax S8 S S4 S5 S6 S7 S S S4 S S / S S4 / S4 S5 S6 / S6 S / / / SL / S S4L / S4 S5L S6L / S6 60 / / / 60 6 / 0 8 / / 0 SL S5L S6L / / 50 SD S6D S7D S8D ,5 85 6, S B/N/H/L S4 N/H/L S5 N/H/L S6 N/H/L S7H S8V SL S4 N/H/L S5 N/H/L S6 N/H/L S7H S8V S H-D 50/225 S4 H-D S5 H-D S6 H-D S7 H-D S8 V-D 2/
16 Construction characteristics Distinctive features of the series Terminals 2 Identification nameplate Fixed contacts Arcing chamber Moving contacts Operating lever Microprocessor-based electronic release GSIS9069 2/4
17 GSIS9048 GSIS905 Double insulation The double insulation technique consists of total separation between the power circuits and the auxiliary circuits and is a characteristic of all SACE Isomax S apparatus from size S up. The housing of each electrical accessory is completely segregated from the power circuit, thus avoiding all risk of contact with live parts, thereby increasing operator safety conditions during management and inspection of the installations. Moreover, the circuit-breaker has redundant insulation between the internal live parts, both regarding thickness of materials and the distances, which are greater than those required by the IEC Standards and are in accordance with American usage. Positive operation The operating lever always indicates the exact position of the circuit-breaker moving contacts, thereby guaranteeing safe and reliable indications (I Closed; O Open; yellow-green line Open due to release trip). The circuit-breaker operating mechanism has free release, regardless of the pressure on the lever or the speed of operation. Release tripping automatically opens the moving contacts: to close them again, it is necessary to reset the operating mechanism by pushing the operating lever from the intermediate position to the lower limit of the open position. For plug-in or withdrawable circuit-breakers, the moving part can only be detached from the fixed part with the circuit-breaker open (moving contacts separate from the relative fixed contacts). 2 GSIS0074 GSIS9050 Selectivity The complete range of releases means that the protection functions of the apparatus can be coordinated according to current-type, time-type, energy-type or residual-current selectivity chains. It is therefore possible to isolate only the areas affected by the fault, ensuring maximum service continuity. Circuit-breakers in category B are available from 400 A up. Possibility of inspection With the circuit-breaker out of service, it is possible to check the state of the internal parts and live components of the circuit-breaker directly. The arcing chambers and the fixed and moving contacts are accessible simply by removing the circuit-breaker cover. The operation, facilitated by the limited number of components, reduces maintenance times and ensures a higher degree of safety. 2/5
18 Construction characteristics Distinctive features of the series GSIS925 GSIS926 2 Isolation behaviour In the open position, the circuit-breaker guarantees isolation of the circuit in compliance with the IEC Standard. For plug-in or withdrawable version circuit-breakers, in the rackedout or withdrawn position, the power and auxiliary circuits are isolated, ensuring that no parts are live. Under these conditions and by means of special connectors, it is possible to carry out blank tests, operating the circuit-breaker in complete safety. The redundant insulation distances guarantee the absence of leakage currents and dielectric strength in the event of any overvoltages between the input and output. Racking-out with the door closed This system, starting from 60 A, allows the circuit-breaker to be racked in and out with the compartment door closed, increasing operator safety and allowing construction of internal arc proof low voltage switchboards. Racking out can only take place with the circuit-breaker open, using a special rackingout crank handle supplied with the withdrawable version circuit-breaker. GSIS927 GSIS929 Electromagnetic compatibility By using SACE PR2/P, PR22/P, PR22/MP microprocessorbased overcurrent releases and SACE RC20, RC2, RC22 electronic residual-current releases, the absence of unwarranted trips is guaranteed even in the presence of interference caused by electronic equipment, atmospheric disturbance or discharges of electrical type. Furthermore, the apparatus does not generate interference with other electronic equipment in the vicinity of the installation. This is in compliance with the IEC Appendix F, IEC 000-4, EN , EN 5008-, EN , EN , EN European Directive No. 89/ 6 specifications regarding electromagnetic compatibility EMC. Tropicalisation The SACE Isomax S series of circuit-breakers and accessories comply with the strictest regulations for use in hot-humid-saline climates (in compliance with climatograph 8 of the IEC Standards), thanks to: insulating cases made of fibreglass-reinforced synthetic resins; anti-corrosion treatment on all main metal parts (C UNI environment); Fe/Zn 2 galvanisation (UNI ISO 208), protected by a conversion layer consisting mainly of chromates (UNI ISO 4520). 2/6
19 Installation positions The circuit-breaker can be installed in any position without any effect on its rated characteristics. In compliance with the IEC Standards, SACE Isomax S circuit-breakers can be supplied through either top or bottom terminals, without jeopardising operation of the apparatus. They can be installed in switchboards, mounted directly on the base plate or on Din rails up to size S5. GSIS9 GSIS928 Mounting on DIN rail up to 60 A The brackets for fixing onto standardised DIN EN rails for S, S2 and DIN EN 5002 rails for S, S4, S5 simplify assembly of the circuit-breakers up to 60 A in standard switchboards. This allows standardised supporting structures to be used and facilitates the stage for designing and constructing the switchboard metalwork structure. GSIS90 GSIS Resistance to vibration Degrees of protection The circuit-breakers are unaffected by vibrations generated mechanically or due to electromagnetic effects, in compliance with the IEC Standards and the strictest regulations of the major classification organisations: RINA DET Norske Veritas Lloyd s Register of Shipping Germanischer Lloyd Bureau Veritas. Different measures have been taken in SACE Isomax S circuitbreakers to achieve IP20 degree of protection for the fixed, plug-in and withdrawable version circuit-breaker, excluding the terminals, and IP0 for the front parts of the circuit-breakers installed in switchboards. The fixed parts are always provided with IP20 degree of protection. It is possible to achieve IP54 degree of protection in accordance with the IEC Standard with the circuit-breaker installed in a switchboard fitted with rotary handle operating mechanism transmission on the compartment door and the special insulation gaskets which can be ordered separately. 2/7
20 Construction characteristics Conditions of use Degrees of protection (according to CEI EN Standard file 59) Circuit-breaker IP20 Circuit-breaker in switchboard IP0 IP0 2 GSIS9080 Direct operating mechanism GSIS908 without terminal covers IP0 with terminal covers GSIS908 Front for lever operating mechanism IP40 () Direct rotary handle Rotary handle transmission GSIS9084 IP50 GSIS9085 GSIS9082 IP40 IP54 IP0 (2) GSIS9086 Special IP54 protection GSIS9087 with terminal covers and direct rotary handle Motor operator GSIS9088 ( ) IP0 for withdrawable circuit-breakers ( 2 ) IP40 for S-S2 and S6-S7 circuit-breakers 2/8
21 Operating temperature SACE Isomax S circuit-breakers can be used in ambient conditions where the temperature in the surrounding atmosphere varies between -25 C and +70 C and stored in ambients with temperatures between -40 C and +70 C. The circuit-breakers fitted with thermomagnetic overcurrent release have their thermal element set for a reference temperature of +40 C. For temperatures between +40 C and +70 C, with the same setting, there is lowering of the thermal trip threshold due to the temperature-related behaviour of the bimetallic strip of the release itself. For temperatures lower than +40 C, on the other hand, there is an increase in the thermal trip threshold as indicated in the table on page 5/9. The electronic microprocessor-based overcurrent releases do not undergo any variations in performance with changes in temperature but, in the case of temperatures higher than 40 C, the maximum setting of the protection against overloads (function L) must be reduced to take into consideration inertial phenomena that occur in the copper parts of the circuitbreaker through which the phase current passes (moving and fixed contacts, and connection terminals) which cause a decrease in the rated uninterrupted current as indicated in the table on page 5/4. The performances of the circuit-breaker cannot be guaranteed for temperatures above +70 C. To ensure service continuity of the installations, careful thought must be given as to how to keep the temperature within acceptable levels for operation of all the various devices and not only the circuit-breakers. For example, forced ventilation in the switchboards and in the areas where they are installed may be necessary. 2 Altitude Up to an altitude of 2000 m SACE Isomax S circuit-breaker rated performances are unaffected. As the altitude increases, the atmospheric properties change in terms of composition, dielectric strength, cooling capacity and pressure. The circuit-breakers therefore undergo derating, which can basically be measured through the change in significant parameters such as the rated maximum operating voltage and the rated uninterrupted current. Altitude [m] Rated service voltage, Ue [V~] Rated uninterrupted current, Iu %Iu 00% 95% 90% 2/9
22 Construction characteristics Modularity of the series SACE Isomax S 2 Starting from the fixed version circuit-breaker and by means of mounting the conversion kit, all the other versions which are used for the various requirements are obtained. The following are available: kit for conversion from fixed circuit-breaker to moving part of a plug-in or withdrawable circuit-breaker conversion kit for the connection terminals which make it possible to obtain front and rear terminals for Copper or Aluminium cables, and front and rear terminals for flat bar terminals. Various accessories are also available: shunt opening releases undervoltage releases auxiliary contacts position contacts the bracket for rear fixing onto DIN EN rail for S-S2 circuit-breakers, DIN EN 5002 rail for S-S4-S5 circuit-breakers direct action motor operator, with stored energy and with solenoid. rotary handle operating mechanisms directly on the circuitbreaker and with transmission on the compartment door residual-current releases accessories for microprocessor-based overcurrent releases such as the signalling, dialogue and actuation unit and external CTs. the fixed parts for plug-in or withdrawable circuit-breakers with front terminals for cables or for flat bars and rear terminals for flat bars. 2/0
23 2 GSIS059 2/
24 Compliance with the Standards Standards, Approvals, Certifications and company quality system SACE Isomax S circuit-breakers and their The attention paid to protecting the en- accessories comply with the IEC vironment is another important priority 2, EN (unified in 7 countries for, and as confirmation of of CENELEC), CEI EN and IEC this, the environmental management 6000 international Standards and con- system has been certified by RINA. form with the EC directive: Low Voltage Directives (LVD) no. 7/2 EEC Electromagnetic Compatibility Directive (EMC) no. 89/6 EEC. Certification of compliance with the 2 GSIS98 GSIS99 above-mentioned product Standards, is carried out, in respect of the European EN 450 Standard, by the Italian certification organisation, ACAE (Association for Certification of Electrical Apparatus),- member of the European organisation LOVAG (Low Voltage Agreement Group). ISO 900 The Quality System complies with the International ISO 900 Standard (model for assuring quality in design, development, construction, installation and assistance) and to the equivalent European EN ISO 900 and Italian UNI EN ISO 900 Standards. The certification Organisation is RINA- QUACER. obtained its first certification in 990. The Test Room is accredited by SINAL. The apparatus complies with the prescriptions for on-board installations and is approved by major Shipping Registers, such as: LLOD S REGISTER OF SHIPPING, GERMANlSCHER LLOD, BUREAU VERITAS, RINA, DET NORSKE VERITAS, POLSKI REIESTR STATKOW and the AMERICAN BUREAU OF SHIP- PING. GSIS99 was the first industrial company in the electro-mechanical sector in Italy to obtain this recognition, and, thanks to a revision of its production process with an eye to ecology, has managed to reduce consumption of raw materials, processing waste and the risk of accidents by 20%. The attention paid to protecting the environment and to the safety of workers is a priority commitment of and as confirmation of this, the company developed the Environmental Management System in compliance with the International ISO 400 Standard, certified in 997, integrating this in 999 with the Health and Safety in the Workplace Management System in accordance with BS 8800 (British Standards). The prizes obtained by at the Forum Design in Hannover and at Electro in Paris bear witness to the consideration given to man and the respect for ergonomic criteria. Please contact for information regarding the types of circuit-breakers approved, the performances approved and their relative validity. GSIS92 2/2
25 The ranges Index SACE Isomax S circuit-breakers for power distribution... / Electrical characteristics IEC /4 General characteristics... /6 Thermomagnetic releases... /8 Electronic releases... /0 SACE Isomax S current-limiting circuit-breakers... /5 Electrical characteristics IEC /6 General characteristics... /8 SACE Isomax S circuit-breakers for motor protection (protection against short-circuit)... /2 Electrical characteristics IEC /24 General characteristics... /26 SACE Isomax S circuit-breakers for motor protection (integrated protection)... /28 Electrical characteristics IEC and IEC /28 General characteristics... /0 SACE Isomax S circuit-breakers for applications up to 000V... /5 Electrical and general characteristics IEC /6 SACE Isomax S switch-disconnectors... /9 Electrical and general characteristics IEC /40 SACE Isomax S circuit-breakers in accordance with UL489 and CSA C22.2 Standards... /4 Electrical and general characteristics... /44 /
26
27 Circuit-breakers for power distribution Eight sizes to optimise use for all plant and installation requirements 690V A 6-20 ka (80/45 V) GSIS906 /
28 SACE Isomax S circuit-breakers for power distribution Electrical characteristics IEC GSIS9 GSIS94 GSIS95 SACE Isomax S SACE Isomax S2 SACE Isomax S Rated uninterrupted current, Iu Poles [A] Nr Rated service voltage, Ue (AC) 50-60Hz [V] (DC) [V] Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui [kv] [V] Test voltage at industrial frequency for min. Rated ultimate short-circuit breaking capacity, Icu [V] B 000 N 000 B N S 000 N H L (AC) Hz 220/20 V (AC) Hz 80/45 V[kA] [ka] () () (AC) Hz 440 V (AC) Hz 500 V (AC) Hz 690 V (DC) 250 V - 2 poles in series (DC) 500 V - 2 poles in series (DC) 500 V - poles in series [ka] [ka] [ka] [ka] [ka] [ka] (5) (DC) 750 V - poles in series Rated short-circuit service breaking capacity, Ics (2) [ka] [%Icu] % 50% % 75% 75% % 75% 75% Rated short-circuit making capacity (45 V) Opening time (45V at Icu) [ka] [ms] 2 52, Rated short-time withstand current for s, Icw Utilisation category (EN ) [ka] A A A Isolation behaviour IEC , EN Releases: thermomagnetic T fixed, M fixed 5 Ith T fixed, M fixed 0 Ith T adjustable, M fixed Ith T adjustable, M fixed 5 Ith T adjustable, M fixed 0 Ith T adjustable, M adjustable magnetic only with microprocessor M fixed PR2/P (I-LI) PR22/P (LSI-LSIG) Interchangeability Versions Terminals fixed F - P FC-R F - P EF - FC - FC CuAl - R F - P - W F- EF - ES - FC FC CuAl - RC - R plug-in FC-R FC - R EF - FC - R withdrawable () - - EF - FC - R Fixing on DIN rail Mechanical life [No. operations / hourly operations] DIN EN /240 DIN EN /240 DIN EN /20 Electrical life (at 45 V) [No. operations / hourly operations] Basic dimensions, fixed /4 poles L [mm] 8000/20 78/0 8000/20 90/ (60A)-8000(250A)/20 05/40 D [mm] H [mm] ,5 70 Weights fixed /4 poles [kg] plug-in /4 poles [kg] 0,9 /,2 /,4,/,5,/,7 2,6 /,5, / 4, withdrawable /4 poles [kg] - -,5 / 4,5 () All the versions with Icu5kA are certified at 6kA (2) For S N/H/L, S4 N/H/L, S5 N/H, and S6 N/S/H circuitbreakers the performance percentage of Ics at 690V is reduced by 25%. () The withdrawable version circuit-breakers must be fitted with the front flange for the lever operating mechanism or with its alternative accessories, such as the rotary handle or the motor operator (4) For the S5 circuit-breaker, the plug-in version is only available for the version with 400 A rated current (5) The SACE S circuit-breaker with breaking capacity L at 690 V can only be supplied from above /4
29 GSIS9095 GSIS9096 GSIS9097 GSIS9098 GSIS96 SACE Isomax S4 SACE Isomax S5 SACE Isomax S6 SACE Isomax S7 SACE Isomax S N H L 000 N H L 000 N S H L 000 S H L H 2500 V () () () % 00% 75% % 00% 75% % 00% 00% 75% % 75% 50% % 50% A 5 (400A) B (400A) - A (60A) 7,6 (60A) - 0 (800A) B 5 (250A) - 20 (600A) B 5 B F - P - W F - EF - ES - FC F - P (400) - W F - EF(400A) - ES - FC F - W F - EF - ES - FC CuAl F - W F - EF - ES - FC CuAl (250A) F F ( A) - VR FC CuAl - RC - R EF - FC - R FC CuAl (400A)-RC (400A)-R EF - FC - R RC - R - HR - VR - - EF - FC - R EF(400A) - ES - FC (400A) R - VR (60A) EF - HR - VR EF - HR - VR - DIN EN /20 DIN EN / / / / (60A)-8000(250A)/20 05/ (400A)-5000(60A)/60 40/ (60A)-5000(800A)/60 20/ (250A)-5000(600A)/20 20/ (2500A)/20-500(200A)/0 406/556 0, , , , / 5, 4,5 / 5,9 5 / 7 6, / 8,4 9,5 / 2-7 / 22-57/76-4,9 / 6, 6,4 / 8,7 2, / 5, 2,8 / 29,2 - KE TO VERSIONS F Fixed P Plug-in W Withdrawable KE TO TERMINALS F Front EF Extended front ES Extended spreaded front FC Front for copper cables FC CuAl Front for copper or aluminium cables R Rear threaded RC Rear for copper or aluminium cables HR Rear horizontal flat bar VR Rear vertical flat bar /5
30 SACE Isomax S circuit-breakers for power distribution General characteristics The SACE Isomax S series of moulded-case circuit-breakers conforming to the IEC Standard, is divided into eight basic sizes, with rated uninterrupted currents from 25 to 200 A and breaking capacities from 6 to 20 ka (80/45 V). Selection of the size allows the basic electrical characteristics to be identified simply and immediately, whereas selection of the overcurrent release depends on the type of application required. Range of application of the alternating current circuit-breakers GSIS0078 For protection of alternating current networks, SACE S, S2, and S circuit-breakers fitted with thermomagnetic releases and SACE S4, S5, S6, S7, and S8 circuitbreakers fitted with SACE PR2/P or PR22/P electronic releases are available. These are characterised by an application range from 0 to 200 A and by a rated voltage of 690 V. KE TM Thermomagnetic M Magnetic only PR2-PR22 Electronic releases /6
31 Range of application of the direct current circuit-breakers GSIS0079 SACE S, S2, S, S5, and S6 circuitbreakers fitted with thermomagnetic releases are used in protection of direct current networks, with an application range from 0 to 800 A and a minimum operating voltage of 24 V DC. With 2 poles in series, SACE Isomax S circuit-breakers can be used with rated voltage of 250 and 500 V and breaking capacities up to 00 ka (250 V DC) and 65 ka (500 V DC); whereas the SACE S, S5, and S6 circuit-breakers with poles in series can reach 750 V and breaking capacities up to 50 ka. The various possible wiring diagrams and the trip threshold correction factors are indicated on page 5/47. KE TM Thermomagnetic M Magnetic only /7
32 SACE Isomax S circuit-breakers for power distribution Thermomagnetic releases SACE Isomax S, S2, S, S5, and S6 circuit-breakers can be fitted with thermomagnetic releases and are used for protection of alternating current networks with the S, S2, and S circuit-breakers (for applications from 0A to 250A) and in direct current with the S, S2, S, S5, and S6 circuit-breakers (from 0A to 800A). They allow protection against overloads using a thermal device (with fixed threshold for S and adjustable threshold for S2, S, S5, and S6) carried out using the bimetallic strip technique, and protection against short-circuit using a magnetic device (with fixed threshold for S, S2, and S and adjustable threshold for S5 and S6). The four-pole circuit-breakers are always fitted with the neutral protected by the release. GSIS9058 Thermomagnetic releases L - L2 - L R0 R2,5 R6 R20 R25 R2 R2 R40 R50 R50 R6 R80 R00 R25 R25 neutral R0 R2.5 R6 R20 R25 R2 R2 R40 R50 R50 R6 R80 R00 R25 R80 S 25 S2 60 S 60 S 250 S5 400 S5 60 S6 60 S x Ith L-L2-L neutral x Ith L-L2-L neutral x Ith L-L2-L neutral TM adjustable L-L2-L neutral /8
33 Magnetic only releases L - L2 - L R6 R40 R50 R50 R6 R80 R00 R25 R25 R25 R60 R200 R250 neutral R6 R40 R50 R50 R6 R80 R00 R25 R80 R80 R00 R25 R60 S 25 S2 60 S 60 S x Ith L-L2-L neutral x Ith L-L2-L neutral The magnetic only releases which equip the SACE S, S2, and S circuit-breakers have a fixed trip threshold as indicated in the table. For S, the magnetic only release is available in the version with breaking capacity N 25 ka; for S2, breaking capacities N 6 ka and S 50 ka are available. The latter version is only available in the 0 x Ith version. GSIS0068 R60 R200 R250 R20 R400 R500 R60 R800 R00 R25 R60 R200 R250 R20 R400 R500 The letter R identifies the setting current for phase (L-L2-L) and neutral protection (second line). The ones indicated are the combinations provided as standard. On request, circuit-breakers with neutral at 00% of the phase setting can be supplied. The thermomagnetic releases which equip the SACE S2 and S circuit-breakers have the thermal element with threshold adjustable from 0.7 x In. The regulated current value which is obtained by using the appropriate selector must be intended as the rated value at 40 C. The magnetic element has fixed trip threshold, with trip values which vary according to the phase setting. The S2 circuit-breaker with breaking capacity S 50 ka is only available in the 0 x Ith version. GSIS0069 The thermomagnetic releases which equip SACE S5 and S6 circuit-breakers have the thermal element with threshold adjustable from 0.7 x In. The regulated current value which is obtained by using the appropriate selector must be intended as the rated value at 40 C. The magnetic element can be adjusted from 5 0 x In. The table gives the maximum magnetic trip values (0 x In) for protection of the phases (L - L2 - L) and of the neutral. GSIS The trip thresholds of the magnetic protection are a function of the setting used both for protection of the phases (L - L2 - L) and of the neutral. The releases denominated 0 x Ith are indicated for all distribution applications, whereas the releases denominated 5 x Ith and x Ith are used where a low magnetic trip threshold is required. With regard to this, the x Ith are particularly suitable for protection of generators /9
34 SACE Isomax S circuit-breakers for power distribution Electronic releases The SACE Isomax S4, S5, S6, S7 and S8 circuit-breakers for protection in alternating current can be fitted with SACE PR2/P or SACE PR22/P overcurrent releases, constructed using electronic microprocessor-based technology. This allows protection functions to be obtained which guarantee a high level of reliability and tripping precision and which are unaffected by the external ambient. The power supply needed for correct operation is supplied directly by the release current transformers, in the presence of a phase current higher than or equal to 8% of their rated current, even with a single phase supplied with voltage. There is only one adjustment for all the phases and the neutral and the release is simultaneous for all the circuit-breaker poles, with trip characteristics which are unaffected by the external ambient. The functions and settings of the release protections can be verified by means of the SACE TT and SACE PR00/T Test units. GSIS9060 SACE PR2/P SACE PR22/P The SACE PR2/P release (available from S4 to S7) provides protection functions against overload L and instantaneous short-circuit I, and is available in the versions with functions I and LI. The wide range of adjustments make this release particularly suitable in all distribution where tripping reliability and precision is required and where magnetic only protection is needed (from.5 to 2 x In), using the SACE PR2/P version I release. The SACE PR22/P release (available from S4 to S8) provides protection functions against overload L, delayed shortcircuit S and instantaneous short-circuit I, and against earth fault G. It is available in the versions PR22/P with functions LSI and LSIG; both allow use of the PR00/K signalling unit, the PR22/D dialogue unit and the PR22/T actuator unit, which can be used either simultaneously or individually, except for the PR22/T actuator unit which is always supplied when the dialogue unit is required. It is particularly suitable in applications with selective coordination requirements, for earthing protection against the risk of fire and evolutionary faults, and for remote control and parametrisation, network supervision and centralised load management. In 00 A 60 A 250 A 20 A S4 60 S4 250 S5 400 S5 60 S6 60 S6 800 S7 250 S7 600 S S S8 200 L S I G neutral (50%) neutral (00%) /0
35 For four-pole circuit-breakers fitted with SACE PR22/P release (LSI-LSIG), protection of the neutral can be set to 50% or 00% of the phase protection setting (by means of dip-switches on the front of the release). For those with SACE PR2/P release (I- LI), protection of the neutral at 00% can be ordered by means of an additional code SDA07505R. With three-pole and distributed neutral circuit-breakers, external toroids can be used by connecting these directly either to the SACE PR2/P release, or to the SACE PR22/P release. On request, it is possible to obtain full protection of the neutral with setting equal to 00% of the protection. The SACE PR2/P and SACE PR22/P microprocessor-based releases are self-supplied and ensure correct operation of the protection functions, even with only a single phase supplied with voltage, in the presence of a current higher than or equal to 8% of the rated phase value. The protection release consists of current transformers (three or four according to the circuit-breaker polarity), the SACE PR2/P or SACE PR22/P protection unit and an OS demagnetising opening solenoid which acts directly on the circuit-breaker operating mechanism group. The current transformers are housed inside the release box and supply the energy needed for correct operation of the protection and the signal required to determine the current. They are available with primary rated current as indicated in the table below. When the protection intervenes, the circuit-breaker opens by means of the opening solenoid (OS), which changes over a contact for signalling release tripped. Resetting the signal is of mechanical type and takes place with resetting of the circuit-breaker operating lever. It is possible to test the opening solenoid (OS) by means of the SACE TT test device. A positive result of the test coincides with circuit-breaker opening. All the protection functions with relative trip times can be verified and tested using the SACE PR00/T accessory unit (only for PR22/P). In the versions with SACE PR22/P - LSI/ LSIG release, it is possible to set the adjustment parameters of the protection functions directly from the front (dipswitch positioned on MAN), or to set the parameters remotely (dip-switch positioned on ELT) thanks to the use of the SACE PR22/D dialogue units. In case of any anomalies in remote parametrisation, the protection automatically uses the set of parameters set manually on the front of the circuitbreaker. The PR00/K signalling or PR22/D dialogue units supply the PR22/P (24 VDC ±20%) protection release continuously and this allows the adjustment parameters to be set even with the circuitbreaker open. 400 A 60 A 800 A 000 A 250 A 600 A 2000 A 2500 A 200 A /
36 SACE Isomax S circuit-breakers for power distribution Electronic releases Protection functions and parametrisation of the SACE PR2/P, PR22/P releases Protection function Trip threshold CANNOT BE ECLUDED Against overload with inverse long time delay and trip characteristic according to a time dependent curve (I 2 t constant) I 0,4-0,5-0,6-0,7-0,8-0,95 - x In PR2/P (I - LI) I 0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,8-0,85-0,875-0,9-0,925-0,95-0,975 - x In PR22/P (LSI - LSIG) Release between,05...,0 x I (IEC ) CAN BE ECLUDED Against short-circuit with inverse short time delay and trip characteristic with dependent time (I 2 t constant) or independent time I 2 tcost ON I 2 tcost OFF I x In Tolerance + 0% I x In Tolerance + 0% CAN BE ECLUDED Against short-circuit with adjustable instantaneous trip I, x In (*) Tolerance + 20% (*) For S5 60, I max 8 x In CAN BE ECLUDED Against earth fault with short inverse time delay and trip characteristic according to a dependent time curve (I 2 t constant) I4 0,2-0, -0,4-0,6-0,8-0,9 - xin Tolerance + 20% SACE PR2/P electronic release, functions I or LI Protection L Against overload Protection I Against short-circuit with instantaneous trip Socket for Test SACE TT Test unit GSIS9054 /2
37 Trip curves A B C D at 6 x I at 6 x I at 6 x I at 6 x I t s t 6s t 2s t 8s (tolerance: + 0% up to 2 x In; + 20% above 2 x In) at 8 x In at 8 x In at 8 x In at 8 x In t2 0,05s t2 0,s t2 0,25s t2 0,5s (tolerance: + 20% ) t2 0,05s t2 0,s t2 0,25s t2 0,5s (tolerance: + 20% ) Characteristics of SACE PR2/P, SACE PR22/P electronic releases Operating temperature 25 C +70 C Relative humidity 90% Service frequency Hz able to measure harmonics up to 550 Hz Electromagnetic compatibility (LF and HF) IEC Annex F Electrostatic discharges IEC Radiated electromagnetic field IEC Short-time transients IEC Mean time between failure (MTBF) 5 years (at 45 C) Characteristics of the signalling contact Maximum interrupted current 0,5 A Maximum interrupted voltage 24 VDC/AC up to,25 x I4 up to 2,25 x I4 up to,6 x I4 up to,25 x I4 t4 00ms t4 200ms t4 400ms t4 800ms (tolerance: + 20% ) Breaking capacity Contact/contact insulation Contact/coil insulation W/VA 500 VAC 000 VAC SACE PR22/P electronic release, functions LSI or LSIG Protection L Against overload Protection S Against short-circuit with delayed trip Protection I Against short-circuit with instantaneous trip Protection G Against earth fault Socket for Test SACE TT Test unit selection for electronic or manual setting dip-switch for setting the neutral Socket for connection of SACE PR00/T Test unit GSIS9056 /
38
39 SACE Isomax S current-limiting circuit-breakers To interrupt and limit even the worst faults 690V 00-60A kA (80/45 V) GSIS9064 /5
40 SACE Isomax S current-limiting circuit-breakers Electrical characteristics IEC GSIS97 Rated uninterrupted current, Iu [A] Poles No. Rated service voltage, Ue (AC) 50-60Hz [V] Rated impulse withstand voltage, Uimp [kv] Rated insulation voltage, Ui [V] Test voltage at industrial frequency for min. Rated ultimate short-circuit breaking capacity, Icu (AC) Hz 220/20 V [ka] (AC) Hz 80/45 V [ka] (AC) Hz 440 V [ka] (AC) Hz 500 V [ka] (AC) Hz 690 V [ka] Rated service short-circuit breaking capacity, Ics () [%Icu] Rated short-circuit making capacity (45 V) [ka] Opening time (45V at Icu) [ms] Utilisation category (EN ) Isolation behaviour IEC , EN Releases: thermomagnetic - T adjustable, M fixed 0 Ith with microprocessor PR2/P (I-LI) with microprocessor PR22/P (LSI-LSIG) Interchangeability Versions Terminals fixed plug-in withdrawable Fixing on DIN rail Mechanical life [No. operations / hourly operations] Electrical life (at 45 V) [No. operations / hourly operations] Basic dimensions, fixed L (/4 poles) [mm] D [mm] H [mm] Weights, /4 poles fixed [kg] plug-in [kg] withdrawable [kg] () The value of Ics at 500V and 690V for S, S4 and S6 is reduced by 25% (2) For S with R2 setting: Icu (690V) 50 ka and Ics 00% Icu Icu (500V) 75 ka and Ics 00% Icu () S at 690V can only be supplied from above SACE Isomax S % 54,5 A F-P EF - FC - FC CuAl - R FC-R - DIN EN / /20 90/ ,/,5,/,7 - KE TO VERSIONS F Fixed P Plug-in W Withdrawable /6
41 GSIS98 GSIS9099 GSIS900 SACE Isomax S SACE Isomax S4 SACE Isomax S (2)() 00% 440,5 A % 440,5 A % 440,5 A F-P-W F - EF - ES - FC - FC CuAl - RC - R F-P-W F - EF - ES - FC - FC CuAl - RC - R F-W F - EF - ES - FC CuAl - RC - R EF - R EF - R EF - R EF - R - EF - HR - VR DIN EN /20 DIN EN / / (25A)-8000(200A) / 20 05/ / 20 05/ (60A)-5000(800A)/60 20/280 0, ,5 9 0,5 268,6 / 4,8 6, / 8,7 5 / 7 8,2 / 0,7 9,5 / 2-7, / 9,5 9 /,5 2, / 5, KE TO TERMINALS F Front EF Extended front ES Extended spreaded front FC Front for copper cables FC CuAl Front for copper or aluminium cables R Rear threaded RC Rear for copper or aluminium cables HR Rear horizontal flat bar VR Rear vertical flat bar /7
42 SACE Isomax S current-limiting circuit-breakers General characteristics SACE Isomax S S - S4 - S6 current-limiting circuit-breakers These pieces of apparatus are characterised by a rated voltage Ue of 690 V AC, by rated uninterrupted currents from 00 A to 60 A, by service currents from to 60 A and by an ultimate short-circuit breaking capacity up to 200 ka at 80/45 V AC and 75 ka at 690 V AC. The circuit-breakers, which comply with IEC Standards, are available in the three- and four-pole type (only three-pole for S2 00) in the fixed, plug-in and withdrawable versions. The function carried out by the current-limiting circuit-breakers is to limit the specific let-through energy to a maximum in the case of short-circuit, safeguarding the integrity of the circuits and of the apparatus located on the load side. The breaking system used, which foresees double interruption per pole, allows very high value short-circuits to be interrupted extremely rapidly. Moreover, the special shape of the interruptive parts allows the peak values of fault currents to be limited to figures considerably lower than those of the short-circuit current present at the point of installation. For the circuit-breakers on the load side, the rapidity of opening notably reduces exposure to the electrodynamic stresses which occur in the case of a fault. GSIS9028 Integration with the SACE Isomax S family The range of current-limiting circuitbreakers has been conceived as a prod- low voltage application requirements to application flexibility which allows all uct aimed at particularly severe requirements, but comes within the sphere of In the SACE Isomax S series, the cur- be covered. the general SACE Isomax S project in rent-limiting circuit-breakers offer the any case. same benefits of modular construction. The user gains considerable advantages because it means being able to the basic version of the current-limit- All the other versions can be made from optimise stocks, standardise support ing circuit-breaker by means of special and installation structures and rationalise circuit-breaker selection thanks conversion kits. to For S, S4 and S6, conversion from the fixed circuit-breaker into the moving part of plug-in or withdrawable circuit-breaker is carried out by means of special kits listed under the chapter entitled Ordering codes (for S2 00, the kit is the same as the corresponding S2 B/N/S one). The fixed parts of current-limiting plugin or withdrawable version circuit-breakers can, on the other hand, be used either for the current-limiting circuit-breakers themselves or for the corresponding SACE S2 - S - S4 and S6 automatic circuit-breakers. GSIS94 GSIS9029 With regard to accessories, too, the S2 00, S, S4 and S6 current-limiting circuit-breakers use the same accessories provided for the corresponding automatic circuit-breakers and also keep the same electrical characteristics. SACE Limitor SACE Isomax S LN A S2 00 LN 00 / LN 25 S 25 LN 60 / LN 200 S 200 LN 20 (setting 250 A) S4 250 LN 20 S6 400 LN 500 / LN 60 S6 60 The electrical characteristics of the SACE Isomax S currentlimiting circuit-breakers allow a comparison with the circuitbreakers in the previous SACE Limitor series to be established, to determine any replacements in the case of installation upgrading. /8
43 Only the following are an exception: the mechanical interlocking plate for two superimposed circuit-breakers the bracket for fixing onto DIN rail (for S and S4) The wiring diagrams are those of the corresponding SACE S2, S, S4 and S6 circuit-breakers. Apart from S2 00 which are identical to the corresponding S2 B/N/S, of the circuit-breakers, the S, S4 and S6 current-limiting circuit-breakers keep the standardised depth of 0.5 mm, standardised widths of 05 mm (S- S4) / 20mm (S6) for the three-pole versions and 40 mm (S-S4) / 280mm (S6) for the four-pole versions, identical drilled fixing holes for the plugin and withdrawable versions and identical drilled holes for the compartment door in all the versions and for all the accessories. Applications The current-limiting circuit-breakers are suitable for installation in all types of civil, industrial and service sector plants, as well as in electrical installations on board ships, in mines, on offshore oil rigs and, generally, wherever very high short-circuit currents can occur due to the high powers of the generators and transformers up to 200 ka at 80/45 V AC, 80 ka at 440 V AC and 75kA at 690 V AC. The circuit-breakers can be placed near the power supply source both for general protection (plants, user groups and electrical lines) and for protection of electric machines (motors, generators, transformers, capacitor banks). They can also be inserted in plants where back-up protection is foreseen, which allows use on the load side of circuit-breakers with breaking capacity lower than the prospective short-circuit current at the point of installation. The breaking capacities of the SACE Isomax S current-limiting circuit-breakers have exceeded the best performances achieved by other apparatus of this type. Limited let-through current Prospective short-circuit current GSIS0084 The increased contact opening speed, the dynamic blast action produced by the magnetic field and the structure of the arcing chamber contribute to extinguishing the arc in the shortest possible time, limiting the specific let-through energy value I 2 t and the peak current. /9
44 Thermomagnetic overcurrent releases SACE Isomax S current-limiting circuit-breakers General characteristics The table below summarises the size values for the different types of releases: Ith - rated current of the thermomagnetic release, referred to an ambient temperature of 40 C Im - magnetic trip current In - rated current of the electronic release Thermomagnetic overcurrent releases Circuit-breaker L - L2 - L phases Neutral S2 00 S 25 S 200 Setting Thermal adjustment [A] Magnetic trip [A] Setting [A] x Ith Im 0 x Ith [A] R R, R R R R R R R R R (S2 00) (S) R 2 (S) R R R 00 (S) R R R 80 (S) R R 00 (S) R R 80 R R 00 R R 25 GSIS9057 SACE S2 00 and S circuit-breakers, with thermomagnetic overcurrent releases /20
45 Electronic overcurrent releases SACE PR2/P - PR22/P electronic overcurrent releases Circuit-breaker Release L - L2 - L phases Neutral Neutral ( ) S4 250 S6 400 S6 60 current L S I G (50% Ith) (00% Ith) In [A] I [A] I2 [A] I [A] I4 [A] [A] [A] L Protection function against overload S Protection function against short-circuit with delayed trip I Protection function against short-circuit with instantaneous trip G Protection function against earth fault with delayed trip ( ) Only for PR22/P. Available on request for PR2/P, with additional ordering code SDA07505R. N.B. For more detailed information about the protection functions, please see page /2. GSIS95 SACE S4, S6 circuit-breakers, with microprocessorbased overcurrent releases /2
46 /22
47 SACE Isomax S circuit-breakers for motor protection Protection against short-circuit Magnetic only and electronic circuit-breakers for classical switching coordinations and motor protection of any power 690V A ka (80/45 V) Integrated protection The evolution of motor protection: intelligence on board the circuit-breaker to design protection around the motor, optimising space and time 690V A ka (80/45 V) GSIS9065 /2
48 SACE Isomax S circuit-breakers for motor protection (protection against short-circuit) Electrical characteristics IEC and IEC GSIS99 GSIS95 GSIS98 S2 80 S S Rated uninterrupted current, Iu [A] / / 200 Rated service current, In Poles [A] Nr / / Rated service voltage, Ue (AC) 50-60Hz Rated impulse withstand voltage, Uimp [V] [kv] Rated insulation voltage, Ui Test voltage at industrial frequency for min. [V] [V] Rated ultimate short-circuit breaking capacity, Icu (AC) Hz 220/20 V [ka] 00 N H L (AC) Hz 80/45 V (AC) Hz 440 V [ka] [ka] () (AC) Hz 500 V (AC) Hz 690 V Rated service short-circuit breaking capacity, Ics (2) Rated short-circuit making capacity (45 V) [ka] [ka] [%Icu] [ka] % % 75% 75% () 00% 440 Opening time (45V at Icu) Utilisation category (EN ) [ms],5 A A,5 A Isolation behaviour IEC , EN Releases: magnetic only, fixed xin magnetic only, adjustable 4 2xIn microprocessor-based, PR2/P (I) Interchangeability Versions Terminals fixed F - P EF - FC F - P - W F - EF - ES - FC F - P - W F - EF - ES - FC plug-in FC CuAl - R FC - R FC CuAl - RC - R EF - FC - R FC CuAl - R - RC EF - R withdrawable Fixing on DIN rail - DIN EN EF - FC - R DIN EN 5002 EF - R DIN EN 5002 Mechanical life Basic dimensions fixed, poles [No. operations / hourly operations] L [mm] 25000/ / /20 05 D [mm] H [mm] ,5 70 0,5 255 Weights fixed, poles [kg] plug-in, poles [kg],, 2,6,,6 6, withdrawable, poles [kg] -,5 7, () All the versions with Icu5kA are certified at 6kA (2) For SN/H/L, S4N/H/L, S5N/H, and S6N/H circuit-breakers, the percentage performance of Ics at 690V is reduced by 25% () S at 690V can only be supplied from above KE TO VERSIONS F Fixed P Plug-in W Withdrawable /24
49 GSIS90 GSIS902 GSIS90 GSIS904 GSIS905 GSIS906 S4 S4 S5 S6 S6 S7 60 / / / / / , 60 / , 60, , 400 / / , 400 / , 250 / N H L N H L N S H L S H L () () () % 00% 75% % % 00% 75% % 00% 00% 75% % % 75% 50% A,5 A B(400A) / A(60A) B,5 A B F - P - W F - EF - ES - FC F -P - W F - EF - ES - FC F - P(400A) - W F - EF - ES - FC F - W F - EF - ES F - W F - EF - ES F - W F - EF - ES - FC CuAl - R - RC EF - FC - R FC CuAl - R - RC EF - R FC CuAl - R - RC(400A) EF - FC - R FC CuAl - R - RC - FC CuAl - R - RC - FC CuAl (250A) - HR - VR - EF - FC - R DIN EN 5002 EF - R DIN EN 5002 EF - FC - R - VR (60A) DIN EN 5002 EF - HR - VR - EF - VR - HR - EF - VR - HR / / / / / / , ,5 9 0, , , , ,5 5 8,2 5 6, 9, ,9 9 6,4 2, 25,4 2,8 KE TO TERMINALS F Front EF Extended front ES Extended spreaded front FC Front for copper cables FC CuAl Front for copper or aluminium cables R Rear threaded RC Rear for copper or aluminium cables HR Rear horizontal flat bar VR Rear vertical flat bar /25
50 Magnetic and electronic overcurrent releases SACE Isomax S circuit-breakers for motor protection (protection against short-circuit) General characteristics IEC and IEC Three-phase asynchronous motor starting, switching and protection are essential operations for its correct use. The traditional system used for this purpose has three different devices: a circuit-breaker for protection against short-circuit, a thermal relay for protection against overload and lack of or unbalanced phase, and a counter for the motor operations. Everything must necessarily take into account the problems which arise on start-up. In particular, different factors must be taken into account when selecting these devices, such as: - the motor power - the starting diagram - the type of motor: with cage rotor or with wound rotor - the fault current at the point of motor installation in the network. proposes a wide range of circuit-breakers, which by implementing the protection against short-circuit exclusively, are suitable for use inside protected starters of traditional type. The new SACE S2 80, with fixed magnetic protection at times the rated service current, is an extremely compact circuit-breaker, which stands out for its exceptional performances in terms of breaking capacity and limitation of the specific letthrough energy. Extremely simple and rapid to install, it has the same possibility of mounting accessories and personalisation as the S2B/N/S circuit-breakers. It can be used in a vast range of start-ups, from 0.7kW to 7kW and from 400V-50kA up to 690V-50kA. SACE S N/H/L 60/250 circuit-breakers and the S 25/200 current-limiting circuit-breaker are fitted with a magnetic only release adjustable from 4 to 2 times the rated service current. They cover coordinations from 7 to 2kW and allow optimal motor protection thanks to their great flexibility due to the wide setting range of the magnetic threshold. Finally, SACE S4 60/250, S5 400/60, S6 60/800, and S7 250/600, with different N-S-H-L breaking capacity levels, like the current-limiting S4 and S6, can be fitted with the Magnetic only fixed overcurrent releases SACE Isomax S2 80 Phases L - L2 - L Setting Magnetic trip [A] Im x In [A] R R.6 2 R2 26 R2.5 2 R.2 42 R4 52 Circuit-breaker with magnetic release Contactor Thermal relay R5 65 R R8.8 0 R 45 Motor R2.5 6 R6 20 R R25 25 GSIS96 R2 45 R R R6 820 R /26
51 PR2/P (I) electronic microprocessor-based release. Above all, they are used for protection of high power motors and, thanks to adjustment of the protection against short-circuit from.5 to 2 times, allow the optimum trip value to be selected for any type of motor. GSIS94 Magnetic only adjustable overcurrent releases Circuit-breaker Phases L - L2 - L SN 60 SH 60 SN 250 S 25 S 200 Setting Magnetic adjustment [A] SL 60 SH 250 SL 250 [A] Im x Ith R R R (*) R R R R R (0 x Ith) R R (*) Only to be used in coordination with contactors SACE PR2/P (I) electronic microprocessor-based overcurrent releases for motor protection Circuit-breaker Phases L - L2 - L S4N 60 S4N 250 S5N 400 S6N 60 S6N 800 S7S 250 S7S 600 S4 250 S6 400 S6 60 Rated current I (*) S4H 60 S4H 250 S5H 400 S6H 60 S6H 800 S7H 250 S7H 600 of release S4L 60 S4L 250 S5L 400 S6L 60 S6L 800 S7L 250 S7L 600 In [A] I [A] (*) I Protection function against short-circuit /27
52 SACE Isomax S circuit-breakers for motor protection (integrated protection) Electrical characteristics IEC and IEC GSIS907 S4 Rated uninterrupted current, Iu [A] Rated service current, In [A] Poles Nr. Rated service voltage, Ue (AC) 50-60Hz [V] Rated impulse withstand voltage, Uimp [kv] Rated insulation voltage, Ui [V] Test voltage at industrial frequency for min. [V] Rated ultimate short-circuit breaking capacity, Icu (AC) Hz 220/20 V [ka] (AC) Hz 80/45 V [ka] (AC) Hz 440 V [ka] (AC) Hz 500 V [ka] (AC) Hz 690 V [ka] Rated service short-circuit breaking capacity, Ics (2) [%Icu] Rated short-circuit making capacity (45 V) [ka] Opening time (45V at Icu) [ms] Utilisation category (EN ) Isolation behaviour IEC , EN , IEC , EN PR22/MP (LRIU) microprocessor-based releases Interchangeability Versions Terminals fixed plug-in withdrawable Fixing on DIN rail DIN EN 5002 Mechanical life [No. operations / hourly operations] Basic dimensions, fixed poles L [mm] D [mm] H [mm] Weights fixed, poles [kg] plug-in, poles [kg] withdrawable, poles [kg] 60 / , 60 / N H L () % 00% 75% A F - P - W F - EF - ES - FC FC CuAl - R - RC EF - FC - R EF - FC - R 20000/ , ,5 4,9 () All the versions with Icu5kA are certified at 6kA (2) For S4N/H/L, S5N/H, and S6N/H circuit-breakers the percentage performance of Ics at 500V and 690V is reduced by 25% KE TO VERSIONS F Fixed P Plug-in W Withdrawable /28
53 GSIS908 GSIS909 GSIS90 GSIS9 GSIS92 S4 S5 S6 S6 S / , 60, % 440,5 A N H L () % 00% 75% B N H L () % 00% 75% B 20, 400 / % 440,5 A S H % 75% B F - P - W F - EF - ES - FC FC CuAl - R - RC EF - R EF - R F - P - W F - EF - ES - FC FC CuAl - R - RC EF - FC - R EF - FC - R F - W F - EF - ES FC CuAl - R - RC - EF - HR - VR - F - W F - EF FC CuAl - R - RC - EF - VR - HR - F - W F - EF - ES FC CuAl - HR - V - EF - VR - HR / , , / , , 6, / , ,5-2, 20000/ , ,4 0000/ , ,8 KE TO TERMINALS F Front EF Extended front ES Extended spreaded front FC Front for copper cables FC CuAl Front for copper or aluminium cables R Rear threaded RC Rear for copper or aluminium cables HR Rear horizontal flat bar VR Rear vertical flat bar /29
54 SACE Isomax S circuit-breakers for motor protection (integrated protection) General characteristics SACE PR22/MP electronic microprocessor-based releases SACE Isomax S4N-H-L 60/250, S5N-H-L 400, S6N-H-L 800, S7S-H 250 and S4 250, S6 400/60 circuit-breakers are fitted with SACE PR22/MP electronic releases constructed using microprocessor-based electronic technology. This allows functions to be obtained which guarantee high trip precision, utmost reliability and insensitivity to variations in the external temperature. The SACE PR22/MP electronic release guarantees complete motor protection as is fully integrated on board the circuit-breaker; moreover, it is able to control contactor opening in the case of a fault (except for short-circuit), by means of the SACE PR22/CI contactor accessory operating mechanism unit. Furthermore, the PR00/T unit for testing the release and checking the protection functions, the PR00/K signalling unit and the PR22/D dialogue unit are available. The electronic microprocessor-based releases are self-supplied and consist of three current transformers, the SACE PR22/MP protection unit and an opening solenoid which acts directly on the circuit-breaker operating mechanism unit. The current transformers housed inside the release box, supply the energy and the signal required for correct operation of the protection. The release is temperature-compensated and sensitive to lack of phase according to Table IV of the Standard. Circuit-breaker with SACE PR22/MP electronic microprocessor-based release Contactor Motor SACE PR22/MP electronic microprocessor-based releases for motor protection Circuit-breaker Phases L - L2 - L S4N 60 S4N 250 S5N 400 S6N 800 S7S 250 S4 250 S6 400 S6 60 Release rated L R I U S4H 60 S4H 250 S5H 400 S6H 800 S7H 250 current S4L 60 S4L 250 S5L 400 S6L 800 In [A] I [A] I5 [A] I [A] Iu [A] x I ,4 x I L Protection function against overload with relative setting current (I x In, with 0.0 steps - Class 0A, 0, 20, 0) R Protection function against rotor block with relative setting current and time (I x I - t s) I Protection function against short-circuit with relative setting current (I x In) U Protection function against lack of or unbalance of phase with relative setting current and time (Iu 0.4 x I - t 4 s) /0
55 The SACE Isomax S range of mouldedcase circuit-breakers for motor protection is perfectly coordinated with the new ABB line of contactors. The latter, defined as A-Line, together with the line of overload thermal relays and SACE Isomax S moulded-case circuit-breakers, is the basis for the new generation of apparatus specially designed to guarantee a system of products which can be integrated according to the applications required. All this is done with the aim of not only continuously improving the products, but above all to provide designers, installers and end users with the best solutions in terms of performance and reliability, combined with simplicity of the system. In particular, SACE Isomax S circuitbreakers and the A series of contactors are an extraordinary solution in terms of compactness, since they share the same width and design characteristics, thereby saving space, assembly material, installation time and relative cabling operations. The circuit-breaker-contactor group enhances this characteristic even further with the SACE PR22/MP electronic overcurrent release, which allows construction of an extremely compact protected starter, implementing protection against overload in accordance with the IEC Standard. SACE Isomax S moulded-case circuit-breakers and the new A series contactors share the same width and depth and have been designed to construct a single compact unit Typical operating characteristic of an asynchronous motor GSIS906 l trip current function L l trip current function I I5 trip current function R t5 trip time function R I6 trip current function U t6 trip time function U le rated service current of the motor la starting current of the motor Ip peak value of the subtransient starting current ta motor starting time tp duration of the starting subtransient phase m typical motor starting curve c example of trip curve of a motor protection circuit-breaker with electronic release GSIS0082 The different curves of the functions, with numerous threshold and time settings, allow an overall trip curve to be drawn which is really close to the motor starting curve, thereby optimising its protection /
56 SACE Isomax S circuit-breakers for motor protection (integrated protection) General characteristics Protection functions and parametrisation of the SACE PR22/MP release Function L Protection against overload Function L protects the motor against undesired overloads according to the indications and classes defined in the IEC Standards. Protection is based on a pre-established thermal model ( International Patent) which, by simulating the copper and iron overtemperatures inside the motor, allows precise safeguarding of the machine. The protection intervenes when the preset overtemperature is reached. The trip time is fixed by selecting the trip class defined in the above-mentioned Standards. The function is temperature-compensated and sensitive to phase missing/unbalance in accordance with the IEC Standard. In the case of auxiliary power supply, the thermal memory function is guaranteed, which allows the release to continue calculating the motor temperature even after an opening operation. Parametrisation of protection L l 0,4... x In with 0.0 x In steps where l is the rated service current of the circuit-breaker, which must be the same or higher than that of the motor to be protected (I > Ie), and In is the rated current of the current transformers. t s where t is the trip at 7.2 x I cold, depending on the class selected Class 0A are the motor starting classes which determine the trip times for overload according to the IEC Table II Standards. Release of the contactor: in normal operating mode Tolerances: in accordance with the IEC Standard. Function R Protection against rotor block Function R protects the motor against any rotor block during operation. This protection is automatically disabled for the whole of the motor starting phase and is then re-activated. The protection already provides its function from low current increases (from times the l service current of the circuit-breaker) and can also be disabled. Both the current level to be tripped and the trip time delay can be selected. The protection intervenes when at least one of the phase currents exceeds the preset value and remains above that threshold for the set t5 time. Function I Protection against short-circuit This protection function intervenes in the case of a short-circuit between phases. It is sufficient for a single phase to exceed the set threshold to cause immediate opening of the circuit-breaker (the protection cannot be excluded). The trip current can be adjusted up to times the rated current of the release, whereas the time is fixed. To prevent unwarranted trips during starting, the protection recognises whether the motor to be protected is in the starting phase or whether there is a short-circuit. This is to allow starting under completely safe conditions. Function U Protection against lack of and/or unbalance of a phase Function U can be used in those cases where particularly precise control is needed regarding lack of and/or unbalance of phase currents. This function can be excluded and intervenes if the effective value of one or two currents drops below the level of 0.4 of the l current set with function L and remains there for more than 4 seconds. Parametrisation of protection R l5 OFF x l where l5 is the current at which the rotor is considered to be blocked and l is the rated service current of the circuit-breaker selected for function L. t s where t5 is the preset time threshold above which the release trips. Release of the contactor: in normal operating mode Tolerances: ± 0% of the trip thresholds ± 20% of the trip times Parametrisation of protection I l x In where I is the instantaneous trip current for short-circuit and In is the rated current of the current transformers. To prevent unwarranted trips during the inrush phase of the motor, instantaneous tripping of protection I takes place at.5 x I (for I < 9 x In), whereas for higher values (I > 9 x In) tripping takes place at.5 x In. Tolerances: ± 20% of the trip thresholds ± 20% of the trip times Parametrisation of protection U On, (with I6 0.4 x l and t6 4 s). Off, in the Off position, the release remains sensitive to the lack of phase according to the IEC Standard, modifying the trip curves for protection L. Release of the contactor: in normal operating mode Tolerances: ± 20% of the trip thresholds ± 20% of the trip times /2
57 Parametrisation of the release By means of the microswitch located on the front, the release can be fitted for parametrisation: Man. (manual), thresholds and times are adjusted by using the microswitches on the front of the relay Elt. (electronic), thresholds and times are adjusted remotely by means of the SACE PR22/D dialogue unit. Operating methods Normal mode: in the case of a fault detected by functions L-R-U, contactor opening can be controlled by means of the accessory SACE PR22/CI module or directly, without the need for external modules, with an ABB contactor fitted with an electronic interface with the circuit-breaker. Heavy duty mode: the circuit-breaker opens for any type of L-R-I-U fault. Back-up protection The electronic release verifies whether the circuit-breaker or the contactor is effectively in the open or relay tripped position following an opening command. If this is not so, after a delay set to long or short time, the command for circuit-breaker opening is given again. Protection L against motor overload luminous signalling of overload: fixed for I > 0.9 x I; flashing for I >.05 x I Protection R against blocked rotor Protection I against instantaneous short-circuit Protection U against the lack and/or unbalance of a phase Man. / Elt. release parametrisation methods socket for connection of SACE PR00/T Test unit Class class of motor starting according to the IEC Standards socket for SACE TT Test unit selection between: - PTC (*) temperature sensor input - 0/ generic input setting the back-up time setting the Reset following a trip: - manual - automatic setting the work methods GSIS905 (*) A special input is available to connect a PTC temperature probe, inserted in the motor to be protected Characteristics of the SACE PR22/MP electronic microprocessor-based release Overloading capacity 2 x In continuously, 7.2 x In for 5 s at 45 C Operating temperature 25 C C Maximum relative humidity percentage 90% without condensation Rated service frequency Hz, able to measure harmonics up to 550 Hz Current measurement methods r.m.s. up to x In (functions L, R, U) peak value for values over x In (functions L, R, U) peak value for function I Electromagnetic compatibility According to: IEC Standard Annex F Electrostatic discharges According to: IEC Standard Radiated electromagnetic field According to: IEC Standard Short-time transients According to: IEC Standard Mean time between failure (MTBF) 5 years (at 45 C) /
58 /4
59 SACE Isomax S circuit-breakers for applications up to 000V Taking the SACE Isomax S limits higher and higher 000 V A 6-50 ka GSIS9066 /5
60 Within the panorama of Isomax proposals, there is also the range of circuitbreakers and switch-disconnectors for direct current and alternating current applications up to 000V. The typical application sectors are installations in mines, road or railway tunnels, traction and industrial applications in general. The circuit-breakers for direct current (connection diagrams on page 5/47) are available in the four-pole version, whereas those for alternating current are available in the three-pole version, with adjustable or electronic thermomagnetic releases and have the same dimensions as the standard versions. They can also be combined with all the accessories available for the Isomax series. SACE Isomax S circuit-breakers for applications up to 000V Electrical and general characteristics IEC Range at 000 V in a.c. V~ Rated uninterrupted current, Iu [A] Poles Nr. Rated service voltage, Ue (AC) 50-60Hz [V] Rated impulse withstand voltage, Uimp [kv] Rated insulation voltage, Ui [V] Test voltage at industrial frequency for min. Rated ultimate short-circuit breaking capacity, Icu (AC) Hz 000 V [ka] Rated short-circuit making capacity [ka] Opening time [ms] Rated short-time withstand current for s, Icw [ka] Utilisation category (EN ) Isolation behaviour IEC , EN Thermomagnetic releases T adjustable, M fixed 0 Ith PR2/P (LI only) microprocessor-based releases PR22/P (LSI-LSIG) microprocessor-based releases Versions Terminals Fixing on DIN rail Mechanical life [No. operations / hourly operations] Dimensions L [mm] D [mm] H [mm] Weights [kg] S L 6 9,2 20 A F F DIN EN / ,5 70 2,6 Range at 000 V in d.c. S S5 S6 S6 Rated uninterrupted current, Iu Poles V [A] Nr. Rated service voltage, Ue [V ] Rated impulse withstand voltage, Uimp [kv] Rated insulation voltage, Ui [V] Test voltage at industrial frequency for min. Ultimate rated short-circuit breaking capacity, Icu (4 poles in series) [ka] Rated short-circuit making capacity [ka] Opening time [ms] Rated short-time withstand current for s, Icw [ka] Utilisation category (EN ) Isolation behaviour IEC , EN Thermomagnetic releases, T adjustable - M fixed 0 Ith Thermomagnetic releases, T adjustable - M adjustable Versions Terminals Fixing on DIN rail Mechanical life [No. operations / hourly operations] Basic dimensions, fixed L [mm] D [mm] H [mm] Weights, fixed [kg] L A F F DIN EN / ,5 70, L B F F DIN EN / , L ,6 B F F 20000/ , L B F F 20000/ , /6
61 S S4 S4 S5 S6 S A L 8,6 0 A A L 8,6 0 5 B L ,6 (60A)-0 (800A) B A F F DIN EN / ,5 255,6 F F DIN EN / , F F DIN EN / , F F DIN EN / , F F 20000/ , ,5 F F 20000/ , Circuit-breakers with electronic release for alternating current In00 In250 In400 In60 In800 S4L 60 S4L 250 S4 250 S5L 400 S6L 60 S6 60 S6L 800 Im,5 2 x In [A] Circuit-breakers with thermomagnetic release for alternating current (thermal threshold adjustable from 0.7 to x In; fixed magnetic threshold) SL 60 S 25 Im AC (0xIn) [A] R2 R50 R80 R00 R25 R60 R200 R Circuit-breakers with thermomagnetic release for direct current R2 () R50 () R80 () R00 () R25 () R60 () R200 () R250 () R400 (2) R60 (2) R800 (2) SL 60 SL 250 S5L 400 S6L 60 S6L 800 Im DC (0xIn) [A] Im DC (5-0xIn) [A] () Thermal threshold adjustable from 0.7 and x In; fixed magnetic threshold (2) Thermal threshold adjustable from 0.7 and x In; magnetic threshold adjustable between 5 and 0 x In. /7
62 /8
63 SACE Isomax S switch-disconnectors Close, carry and isolate. The certainty of operating in complete safety. 690 V A,-85 KA (Icm) 2,2-40 ka (Icw) GSIS9067 /9
64 SACE Isomax S switch-disconnectors Electrical and general characteristics IEC GSIS942 GSIS94 S2D SD Conventional thermal current at 60 C, Ith Number of poles [A] Nr. 25 / 60 /4 00 / 60 / 250 / 20 /4 Rated service voltage, Ue (AC) 50-60Hz [V~] (DC) [V ] Rated current, Iu Rated impulse withstand voltage, Uimp [A] [kv] Rated insulation voltage, Ui Test voltage at industrial frequency for min. [V] [V] Rated short-circuit making capacity (45 V~), Icm Rated short-time withstand current for s, Icw [ka] [ka], 2,2 0 6,5 Isolation behaviour IEC Versions Terminals fixed plug-in F - P EF - FC - FC CuAl R - RC FC - R F - P - W F - EF - FC FC CuAl - R - RC F - FC - R Mechanical life withdrawable [No. of operations / hourly operations] /240 F - FC - R 25000/20 Basic dimensions, fixed L (/4 poles) [mm] D [mm] 90/ /40 0,5 H [mm] Weights, fixed /4 poles [kg] 20,/,5 70 2,6/,5 Coordination with the circuit-breakers (ka at V AC) LOAD SIDE S2D 25 S2D 60 SD 00 SD 60 SD 250 SD 20 S6D 400 S6D 60 S6D 800 S7D 000 SB 6 6 SN S2B S2N S2S SN SUPPL SIDE SH S5N S5H S6N S6S S6H S7S 50 S7H 65 S8H S8V /40
65 GSIS944 GSIS945 GSIS946 S6D S7D S8D 400 / 60 / 800 / / 250 / 600 / , / 2500 / 200 / The switch-disconnectors derive from the corresponding circuit-breakers, of which they keep the same overall dimensions, versions, fixing systems and possibility of mounting accessories. They are characterised by a rated voltage of 690 V in alternating current and 750 V in direct current. Applications F - W F - EF - FC CuAl R - RC - F - HR - VR 20000/20 20/280 0, ,5/2 F - W F - EF - FC CuAl (250A) HR - VR - F - HR - VR 0000/20 20/280 8, /22 F EF (2500A)-R /20 406/ /76 They can be used as general circuit-breakers in sub-switchboards, as switching and isolating parts for lines, busbars or groups of apparatus, or as bus-ties. They can be part of general isolation devices of groups of machines or units for motor switching and protection. Isolation The main function carried out by these circuit-breakers consists of isolating the circuit they are inserted in. Once open, the contacts are at a sufficient distance to prevent an arc striking, in accordance with the standard prescriptions relative to isolation behaviour. The position of the operating lever corresponds with certainty to that of the contacts (positive operation). S7D 250 S7D 600 S8D 2000 S8D 2500 S8D 200 Protection Each switch-disconnector must be protected on the supply side by a coordinated device which safeguards it against shortcircuits. The coordination table at the side shows the SACE Isomax S circuit-breaker which can carry out the protection function for each switch-disconnector. These are always pieces of apparatus of a size corresponding to or lower than that of the switch-disconnector. Making capacity The making capacity, Icm, is of considerable importance, since a switch-disconnector must be able to withstand the dynamic, thermal and current stresses that can occur during closing without being destroyed, up to and including closing under short-circuit conditions Endurance in the closed position This identifies the capacity for maintaining the closed position for short-time overcurrents. It is an important parameter which qualifies the performances of these pieces of apparatus. /4
66 /42
67 SACE Isomax S circuit-breakers according to UL489 and CSA C22.2 Standards SACE Isomax S quality to conquer New worlds 480/600 V A ka (480V) GSIS9068 /4
68 SACE Isomax S circuit-breakers according to UL489 and CSA C22.2 Standards Electrical and general characteristics Circuit-breaker type S S 50 S 225 Maximum frame continuous current 40 C [A] Number of poles Nr Rated operational voltage (AC) Hz [V] 277/ (B); 480 (N/H/L) (DC) [V] Test voltage (min.) Hz [V] UL/CSA short-circuit interrupting capacity [ka rms] N N H L B N H L 240 V AC [ka rms] V AC [ka rms] 4 (R5) 65 (R5, R0) 20 (R20-R00) V AC [ka rms] V DC (2 poles in series)[ka rms] V DC ( poles in series) [ka rms] Overcurrent trip relays Thermal-magnetic Microprocessor based Interchangeability Dimensions H [in/mm] 4,72 / 20 6,70 / 70 6,70 / 70 fixed version W [in/mm],07 / 78 4, / 05 4, / 05 D [in/mm] 2,75 / 70 4,07 / 0,5 4,07 / 0,5 Mechanical duration [op./ frequency] / / /20 Weights (fixed - P) [lbs.] 2,42 6,75 6,75 In the field of moulded-case circuit-breakers, complying with the UL489 and CSA22.2 standards, the SACE Isomax S offer is enriched by the following ranges: circuit-breakers for power distribution (fitted with thermomagnetic or electronic releases) circuit-breakers with magnetic only releases for motor protection (Motor Control Protection MCP) switch-disconnectors for use as isolators or switching devices for lines, busbars or parts of a plant circuit-breakers (Moulded Case Switch MCS). The SACE Isomax S offer in compliance with UL/CSA Standards is completed with the introduction of three new sizes. There are therefore increasing possibilities for those customers who also operate on markets subject to the standards defined in the UL/CSA Standards, with a whole range of moulded-case circuit-breakers available, with rated currents which go from 00A to 2500A and breaking capacities, at 480 V AC, which can reach 00kA. Apart from lowering the range of rated currents, introduction of the S size allows all those applications typical of power subdistribution where a circuit-breaker characterised by limited dimensions, but guaranteeing great versatility of application of accessories and installation, is particularly convenient. They further increase the possibility of selection, thanks to the introduction of the new rating for S, Iu225A, with three levels of breaking capacity (N/H/L), up to service voltage values of Ue480V AC and 500 V DC. Finally, the S8 circuit-breaker according to the UL/CSA Standard also allows completion towards higher rated currents. Isomax S8V 600, 2000 and 2500 are suited to installation immediately to the load side of power supply sources of low voltage systems and can operate safely under the most severe service conditions required by modern installations. Their high performances, great flexibility in mounting accessories, simple coordination with the devices on the load side and the possibility of limiting the depth of the switchboards thanks to their compact overall dimensions, make Isomax S8 a particularly advantageous choice. /44
69 S4 S5 S6 S7 S N H L N H L N H L H V ,00 / 254 0,00 / 254 (00A);,62 / 46 (400A) 4,25 / / 406 5,75 / 400 4, / 05 5,5 / 40 8,27 / 20 8,27 / 20 5,98 / 406 4,07 / 0,5 4,07 / 0,5 4,07 / 0,5 5,45 / 8.5 9,25 / / / / / / 20 8,8 22 7,5 5 Motor Control protection - MCP Type SL S4 N/H/L S5 N/H/L S6 N/H/L S7H S8V Poles Trip Unit Adjustable magnetic only (4...2xIn) PR2/P - I Rating [A] Interrupting capacity L L N H L N H L N H L H V 240 V AC V AC V AC V DC 65 () V DC 50 () () Performance available only for the 25 A rating version Moulded Case Switches - MCS Type S H-D 50 S H-D 225 S4 H-D S5 H-D S6 H-D S7 H-D S8 V-D Rating [A] Poles Magnetic trip [A] Rated voltage (AC) Hz [V~] (DC) poles in series [V ] /45
70 /46
71 Accessories Index Versions... 4/ Connection terminals... 4/6 Service releases... 4/0 Electric signals... 4/4 Remote controls... 4/7 Operating mechanisms and locks... 4/22 Residual current releases... 4/26 Accessories for electronic releases... 4/0 Installation accessories and spare parts... 4/5 4 4/
72 4 GSIS9070 4/2
73 Accessories Versions SACE Isomax S circuit-breakers are available in the FIED, PLUG-IN or WITHDRAWABLE, three-pole or four-pole versions. GSIS920 GSIS92 GSIS922 F P W FIED PLUG-IN WITHDRAWABLE The FIED version circuit-breaker with The PLUG-IN version circuit-breaker consists three or four-poles has: of: the same upper and lower terminals fixed part to be installed directly on the lever operating mechanism base plate of the cubicle thermomagnetic or electronic release moving part obtained from the fixed flange for the front door of the switchboard circuit-breaker with the addition of the isolating contacts in correspondence possibility of assembly on base plate with the connection terminals, of the or on DIN rail (up to 60A) rear frame for fixing to the fixed part circuit-breakers featuring only four and of the terminal covers. depths (70mm for S-S2, 0.5 for Circuit-breaker racking out is carried out S...S6, 8.5 for S7 and 242 for S8) by unscrewing the top and bottom fixing standardised front for groups of circuitbreakers screws. A special lock prevents the cir- (45mm for S...S5, 05mm for cuit-breaker from being racked in and out S...S7). with the contacts in the closed position. F P W Fixed Plug-in Withdrawable S 25 S2 60 S 60 S 250 S4 60 S4 250 S5 400 S5 60 S6 60 S6 800 S7 250 S7 600 S S S8 200 The WITHDRAWABLE version circuitbreaker is made up of: fixed part, to be installed directly on the base plate of the cubicle with the side group mounted on the fixed part to allow the racking-out/racking-in movement moving part obtained from the fixed circuit-breaker with the addition of the isolating contacts in correspondence with the connection terminals, of the rear frame (which is coupled with the side piece provided on the fixed part for sliding) for fixing to the fixed part, and of the terminal covers. accessory to be applied on the front of the circuit-breaker with selection between front for lever operating mechanism, motor operator and rotary handle operating mechanism; application of one of these accessories allows the circuit-breaker lock to be made in the withdrawn position. Racking-in/out of the moving part is carried out by means of the special operating lever supplied with the circuit-breaker in the moving part for withdrawable version or with the conversion kit of the fixed circuit-breaker into moving part of withdrawable circuit-breaker. The special mechanism allows the circuit-breaker to be put into the isolated position (with power and auxiliary circuits disconnected) with the compartment door closed, providing increased operator safety. The lever can only be inserted with the circuit-breaker open. Once racked out or withdrawn, the circuit-breaker can be operated in the open/ closed position and, by means of the special connection extensions, blank operating tests of the auxiliary control circuits can be carried out. 4 4/
74 Accessories Versions Starting from the fixed version with front terminals, SACE Isomax S circuit-breakers can be converted into the various versions using the Conversion kits. This makes management of the product, its versions and stocks as a whole highly flexible. It is, in any case, always possible to ask for the circuit-breaker in the required version fully prepared in the factory. Conversion kit into moving part for plug-in circuit-breaker This allows the fixed circuit-breaker with front terminals to be converted into the moving part of a plug-in circuit-breaker. The kit consists of: tulip isolating contacts frame assembly screws and nuts. The fixed part is needed to complete the circuit-breaker. S-S2 S-S4 GSIS906 GSIS00 GSIS002 4 Fixed part The fixed part allows the circuit-breaker to be constructed in the plug-in or withdrawable version. It can also be provided in the switchboard as a reserve power supply to be completed with a circuit-breaker at the appropriate time. For plug-in or withdrawable version circuit-breakers, different circuit-breaker positions are possible: Plug-in: racked-in racked-out Withdrawable: racked-in racked-out - withdrawn. The fixed part for withdrawable version circuit-breaker is fitted with a guide for supporting the moving part during the isolation or withdrawal operations of the moving part. For SACE S6-S7 circuitbreakers, there are two guides. GSIS92 GSIS924 4/4
75 Conversion kit into moving part for withdrawable circuit-breaker This allows the fixed circuit-breaker with front terminals to be converted into the moving part of a withdrawable circuitbreaker. The kit consists of isolating contacts, frame, assembly screws and nuts. The circuit-breakers in the withdrawable version must always be completed, alternatively, with one of the following accessories: front for lever operating mechanism rotary handle operating mechanism motor operator, in order to make the racking-out lock if necessary. The fixed part is needed to complete the circuit-breaker. GSIS907 4 Conversion kit for fixed part of plug-in into fixed part of withdrawable A guide for converting the fixed part of a plug-in version circuit-breaker into the fixed part of a withdrawable version circuit-breaker is available for SACE S-S4- S5 circuit-breakers. GSIS9047 Racking-out handle GSIS902 This allows racking-out and racking-in even with the door closed of the circuit-breaker in the fixed part. The handle is the same for the whole range of circuit-breakers and is supplied as standard with the Conversion kit or with the circuit-breakers supplied in the withdrawable version. 4/5
76 Accessories Connection terminals The basic version of the circuit-breaker is supplied with: front terminals for SACE S, S4, S5, S6, S7, and S8 circuitbreakers front terminals for copper cables for SACE S, and S2 circuit-breakers. Different types of terminals are available, which can be combined in different ways (upper of one type, lower of another type), allows the circuit-breaker to be connected to the plant in the most suitable way for installation requirements. The following distinctions can be made between: front terminals which allow connection of cables or busbars by acting directly from the front of the circuit-breaker. rear terminals which allow installation of the circuit-breakers in switchboards with rear access to both cable and busbar connections. Terminals for connection of busbars or cables terminated with cable terminals and terminals for direct connection of bare cable are available. The information needed to make the connections is summarised for each type of terminal on pages 4/8-9. Flat bars of different dimensions and composition are recommended for connection with busbars. Furthermore, the minimum depth the flat bar to be connected must have is also indicated, if it is of a different composition to the one recommended. The minimum and maximum cross-section of the cables which can be tightened in the terminals and the diameter of the terminal are indicated for connection with bare cables The torque values to be applied to the tightening screws of the terminals for cable and to the screws used for connecting the busbars to the flat bar terminals are given. The circuit-breakers can be ordered complete with the terminals required, mounted directly in the factory, or the terminals can be ordered individually in packs of pieces. Codes for ordering circuit-breakers directly in the configuration with upper / lower terminals of the same type are available. 4 GSIS0086 GSIS0087 GSIS0088 GSIS0089 Front Front extended Front extended Front terminals terminals terminals spreaded terminals for copper cables S 25 S2 60 S2 80, S2 00 S 60 / 250 S 25 / 200 S4 60 / 250 S4 250 S5 400 / 60 S6 60 / 800 S6 400 / 60 S7 250 / 600 S / 2500 / 200 F - P F F - P F F - P F F - P - W F F - P - W F F - P - W F F - P - W F F - P - W F F - P - W F F - P - W F F - P - W F F(400A)-P(400A)-W(400A) F - W(60A) F - P(400A) - W(400A) F F - W F F F - W (only at the bottom) F F F - W F F (2000A / 2500A) F Fixed P Plug-in W Withdrawable 4/6
77 Insulating terminal covers The terminal covers are applied to the terminals of the circuitbreaker to prevent accidental contacts with live parts and thereby guarantee protection against indirect contacts. The following are available: lower terminal covers, which guarantee IP40 degree of protection for fixed circuit-breakers with rear terminals and for moving parts of plug-in or withdrawable circuit-breakers. upper terminal covers for fixed circuit-breakers with front terminals, front terminals for cables and rear terminals, which guarantee IP40 degree of protection. terminal covers for fixed parts of plug-in or withdrawable circuit-breakers, guarantee IP40 degree of protection on the front with moving part connected. They are available in a single version. The degrees of protection indicated are valid for circuit-breakers installed in switchboards. Screws for sealing the terminal covers These are applied to the terminal covers of fixed circuit-breakers or to the moving parts of plug-in or withdrawable circuitbreakers. They prevent removal of the upper or lower terminal covers, and can be locked with wire and a lead seal. GSIS GSIS090 GSIS09 GSIS092 GSIS09 GSIS094 Front terminals Rear threaded Rear terminals Rear terminals Rear terminals for Cu/Al cables terminals for Cu/Al cables in horizontal flat bar in vertical flat bar F - P F F - P F F - P F F - P - W F F F - P - W F F F - P - W F F F - P - W F F(400A) F - P(400A) - W F(400A) W(60A) F F W W F F F W W F(250A) F - W F - W F 4/7
78 Accessories Connection terminals S-S4-S5 S6 S7 S2 S-S4-S5 S6 60 Front terminals These allow busbars or cables terminated with a cable terminal to be connected Type version pieces busbars [mm] tightening terminal covers L H P hole B [Nm] upper lower fixed part S 60, S 25 F R R S 250, S 200 F R R S4 60 F R R S4 250, S4 250 F R R S5 400 F R R S5 60 F R R S6 60, S F x 7 9 R R S6 800 F x 7 9 R R S7 250 F x 8 R S7 600 F x 8 R S F x 5 70 (2) R S F x 5 70 (2) 4 S6 800 PF S-S4-S5 PF S7 S-S4-S5 S6 S7 PF S6 PF S5 60 S7 Front extended terminals These allow busbars or cables terminated with a cable terminal to be connected Type version pieces busbars [mm] cable term. [mm] tightening [Nm] terminal covers L P hole L hole A B upper lower fixed p. S2 60 F R R S 60, S 25 F-P-W R R R S 250, S 200 F-P-W R R R S4 60 F-P-W R R R S4 250, S4 250 F-P-W R R R S5 400 F-P-W R R R S6 60, S F-W R S6 800 F-W R S7 250 F-W x (4) 45 8 R S7 600 F-W x (4) 45 8 R Front extended spreaded terminals These allow busbars or cables terminated with a cable terminal to be connected Type version pieces busbars [mm] cable term. [mm] tightening [Nm] terminal covers L P hole L hole A B upper lower fixed p. S F S S4 F S S5 400 F S S5 60 F-W S S6 F x 4 x S7 600 F x 4 x Front terminals for copper cables These allow bare copper cables to be connected directly to the circuit-breaker. They are not suitable for tube cable terminals Type version pieces cable busbars cable term. tightening Ø clamps terminal covers [mm 2 ] L [mm] L [mm] B [Nm] [mm] upper lower fixed p. S 25 F-P max.0 max () R R S2 60 F-P max.2 max () 2.5 R R S 60, S 25 F-P-W R R S S 250, S 200 F-P-W R R S S4 60 F-P-W R R S S4 250, S4 250 F-P-W R R S S5 400 F-P-W R R S S5 60 F-W S S-S2 S-S4-S5 GSIS0095 Key () Tightening torque of 2.5 Nm for < 0 mm 2 cable cross-section (2) M2 class 8.8 screws () M6 class 8.8 screws (4) Only use two holes diagonally A Tightening of the terminal onto the circuit-breaker B Tightening the cable/busbar or cable terminal onto the terminal R On request S Standard 4/8
79 Front terminals for copper or aluminium cables These allow copper or aluminium cables to be connected directly to the circuit-breaker (it is not possible to use solid aluminium cables). For the SACE S2 circuit-breaker, these terminals must be connected to the front extended terminals, which are supplied if the circuit-breaker is ordered fitted directly in the factory, whereas the front extended terminal kit must be specified if they are ordered as loose parts.. S2-S-S4-S5 S5 Type version pieces cable tightening Ø clamps terminal covers [mm 2 ] A [Nm] B [Nm] [mm] upper lower fixed p. S2 60 F S F S S 60 (R00A) F R S 60, S 25 F R S 250, S 200 F R S4 60 F R S4 250, S4 250 F R S5 400 F S F R S6 60, S F R S6 800 F S S7 250 F S Rear terminals for copper or aluminium cables These allow copper or aluminium cables to be connected directly to the circuit-breaker. Type version pieces tightening Ø clamps terminal covers A [Nm] B [Nm] [mm] upper lower fixed p. S 60, S 25 F 9 6 S S 250, S 200 F 9 6 S S4 60 F 9 6 S S4 250, S4 250 F 9 6 S S5 400 F S S6 60, S F S S6 800 F S Rear threaded terminals These allow rear connection of busbars. Type version pieces busbars [mm] cable term. [mm] tightening terminal covers L P hole L hole A B upper lower fixed p. S 25 F S P 6 8 S2 60 F S P S 60, S 25 F S P-W S 250, S 200 F S P-W S4 60 F S P-W S4 250, S4 250 F S P-W S5 400 F S P-W S5 60 F S P-W S6 60, S F S S6 800 F S S6 60 S6 800 S7 S-S4-S5 S6 60 S6 800 S-S2 S-S4-S5-S6 PF S-S4-S5-S5 60 S7 PF S Rear terminals in horizontal and vertical flat bar These allow rear connection of busbars. Type version pieces busbars [mm] cable term. [mm] tightening terminal covers L P hole L hole B [Nm] upper lower fixed p. S5 60 W S6 60, S W S6 800 W S7 250 F-W x (4) 20 S S7 600 F-W x (4) 20 S S F x5 70 (2) S F x5 70 (2) S8 200 F x8 00 () PF S6 PF S7 GSIS0096 4/9
80 Accessories Service releases The service releases, shunt opening and undervoltage releases, housed and fixed in a slot in the left part of the circuit-break er are always alternative to each other. The power supply is made by means of special connectors for sizes S to S7, whereas for S-S2, it is made by means of free wires 0.6 m long or with plug-socket connectors which can be supplied on request. Assembly is carried out by pressure into the appropriate housing in the left part of the circuit-breaker. Shunt opening release This allows circuit-breaker opening by means of an electric command. Release operation is guaranteed for a voltage between 70% and 0% of the rated power supply voltage Un, both in AC and in DC. It is always fitted with an auxiliary limit contact. S-S2 GSIS007 S-S4-S5 (*) GSIS008 S6-S7 S8 GSIS900 4 (*) For the SACE S-S2 circuit-breakers, the service releases are fixed to the circuit-breaker cover GSIS009 GSIS00 Power supply voltages S - S2 S -S4 - S5 S6 - S7 S Hz DC Hz DC Hz DC Hz DC [V~] [V ] [V~] [V ] [V~] [V ] [V~] [V ] Powers absorbed on inrush S...S5 S6...S7 S8 Circuit-breaker opening times S S4...S7 S8 Number of operations S-S4 S5 S6-S7 AC DC AC DC AC DC [VA] [W] [VA] [W] [VA] [W] [ms] [ms] [ms] [nr.] [nr.] [nr.] < 5 < 5 < /0
81 Undervoltage release This opens the circuit-breaker due to a power supply failure to the release, or voltage drops to minimum values of 0.7 x Un with a trip range from 0.7 to 0.5 x Un. After tripping, the circuit-breaker can be closed again, starting with a voltage higher than 0.85 x Un. With the undervoltage release de-energised, neither circuit-breaker nor main contact closure is possible. S-S2 (*) GSIS0 S-S4-S5 GSIS008 S6-S7 S8 GSIS009 GSIS02 GSIS9002 Power supply voltages (*) For the SACE S-S2 circuit-breakers, the service releases are fixed to the cover of the circuit-breaker S - S2 S -S4 - S5 S6 - S7 S8 50 Hz 60 Hz DC Hz DC Hz DC 50 Hz 60 Hz DC [V~] [V~] [V ] [V~] [V ] [V~] [V ] [V~] [V~] [V ] Powers absorbed during continuous service S...S5 S6 - S7 S8 AC DC AC DC AC DC [VA] [W] [VA] [W] [VA] [W] Circuit-breaker opening times S...S2 S S4...S7 S8 [ms] [ms] [ms] [ms] < 5 < 8 < 25 < 25 Number of operations S-S4 S5 S6-S7 [nr.] [nr.] [nr.] /
82 Accessories Service releases Time-delayed undervoltage release The undervoltage release can be combined with an external electronic power supply time-delay device, which allows circuit-breaker opening to be delayed in the case of a power cut to the release itself, according to fixed time-delays of [s], so as to avoid unwarranted trips caused by temporary malfunctions. It is available for the SACE S, S4, S5, S6, and S7 circuit-breakers with power supply voltages at V (50-60 Hz) only coupled with an undervoltage release at 0 V DC. Different power supply voltages are possible for S8. GSIS9042 Shunt closing release This allows circuit-breaker closure by means of an electric command. Operation of the release is guaranteed for a voltage between 80% and 0% of the rated power supply voltage Un, both in AC and in DC. S8 Power supply voltages S8 50 Hz 60 Hz DC [V~] [V~] [V ] GSIS GSIS Powers absorbed on inrush S8 AC DC [VA] [W] Circuit-breaker closing times S8 [ms] < 55 4/2
83 Connectors for service releases These allow the shunt opening release or the undervoltage release to be connected to the power supply circuit. They are available in the following versions: plug-socket for S-S2 circuit-breakers (free cables always supplied) for fixed S... S7 circuit-breakers for plug-in/withdrawable S... S7 circuit-breakers. Assembly is by means of pressure into special slots in the left side of the circuitbreaker. Cables of different lengths are available. S - S2 S... S7 GSIS90 GSIS05 GSIS0 GSIS04 GSIS06 4 Extension for testing service releases Available for SACE S, S4, S5, S6, and S7 circuit-breakers, this allows supply to the service releases with the circuitbreaker in the racked-out position. It is therefore possible to carry out blank operating tests of the circuit-breaker with the circuit-breaker in safe conditions, i.e. isolated in relation to the power circuits. GSIS907 4/
84 Accessories Electric signals These allow information relative to the circuit-breaker state of operation to be taken outside the circuit-breaker. Installation of these accessories is carried out directly from the front of the circuit-breaker in special slots, completely se gregated from the live parts, with increased operator safety. Auxiliary contacts 4 These carry out electrical signalling of the operating state of the circuit-breaker: Open/closed: indicates the position of the circuit-breaker contacts. Release trip: signals circuit-breaker opening because the overcurrent release has tripped (for an overload or short-circuit), the residual current, shunt opening or undervoltage release has tripped, or the emergency opening pushbutton of the motor operator or the test pushbutton has been pressed. Signalling is reset when the circuit-breaker is reset (recovery). For SACE S, S4, S5, S6, and S7 circuitbreakers the auxiliary contacts of the circuit-breaker are also available in the gold-plated version for digital signals, also suitable for use with voltages Un < 24 V with the same type of signalling and versions. The signals indicated in the table are available: S-S2 S-S4-S5 S6-S7 (*) GSIS09 GSIS07 (*) For SACE S-S2 circuit-breakers the auxiliary contacts are fixed to the cover of the circuit-breaker GSIS08 GSIS9004 Signals 2 contacts during open/closed changeover contact during open/closed changeover + contact during release tripped changeover circuit-breaker open signal + circuit-breaker closed signal + release tripped signal S...S2 S S4...S7 S8 NO or NC contacts release tripped signal microswitch for signalling closing springs charged S-S2 S-S4-S5-S6-S7 S8 Rated voltage Un ohmic load V ~ (50-60 Hz) V In [A] inductive In [A] A (cos 0,) A (cos 0,) Rated voltage Un ohmic load V ~ (50-60 Hz) V In [A] 25 0, 250 0, Rated voltage Un ohmic load V ~ (50-60 Hz) V In [A] /4
85 Connectors for auxiliary contacts These allow the auxiliary contacts to be connected to the relative power supply circuit. For S, S2 circuit-breakers, the power supply is made by means of free wires or with mobile plug-socket connectors. For SACE S, S4, S5, S6, and S7 circuit-breakers, the auxiliary contacts (fitted with plug connector) can only be supplied by means of the specific connection connectors to be ordered specifying the size and version of the circuitbreaker (fixed or plug-in/withdrawable). Assembly is carried out by pressure into special slots in the right side of the circuit-breaker. S - S2 S... S7 GSIS020 GSIS02 GSIS0 GSIS04 (*) GSIS905 (*) Connectors for auxiliary contacts, for fixed, plug-in or withdrawable circuit-breakers Extension for testing auxiliary contacts Available for SACE S, S4, S5, S6, and S7 circuit-breakers, this allows the auxiliary contacts to be connected to the relative power supply circuit with the circuitbreaker in the racked-out position. With the circuit-breaker in safe conditions, i.e. isolated in relation to the power circuits, blank tests of circuit-breaker operation can be carried out. GSIS /5
86 Accessories Electric signals Early auxiliary contact for undervoltage release The early auxiliary contact for the undervoltage release, interlocked with the rotary handle operating mechanism, keeps the release de-energised with the circuitbreaker open. It is supplied complete with socket connector of the type with double slide for simultaneous connection of the undervoltage release and the accept contact. S... S7 GSIS908 GSIS022 GSIS02 4 Circuit-breaker position contacts For the fixed part of the SACE S2, S, S4, S5, S6, and S7 circuit-breakers, these S... S7 carry out electrical position signalling of the circuit-breaker in relation to the fixed part: racked-in, racked-out. They can only be connected by means of free wires and are available in the following versions: Contacts for signalling circuit-breaker racked in Contacts for signalling circuit-breaker racked out. A maximum of three contacts for S2, two contacts for S, three contacts for S4-S5 and five contacts for S6-S7 can be installed on the fixed part, in any combination. S2 The circuit-breaker position contacts are Rated voltage Un ohmic load also available in the gold-plated version for digital signals also suitable for use with voltages Un < 24 V with the same type of signals and combinations. V ~ (50-60 Hz) V 0 In [A] inductive In [A] 2A (cos 0,) 2A (cos 0,) GSIS060 S-S4-S5-S6-S7 Rated voltage Un ohmic load V ~ (50-60 Hz) V In [A] 25 0, 250 0, GSIS9006 4/6
87 Accessories Remote controls These allow remote control of circuit-breaker opening and closing and are particularly suitable for use in electrical network supervision and control systems. They are complete with manual operating lever and emergency opening pushbutton (starting from S). A selector allows changeover from automatic to manual operation. They are always fitted with a padlock and, on request, can be fitted with a key lock in the open position. Solenoid operating mechanism for SACE S-S2 circuit-breakers S-S2 This operates both opening and closing of the circuit-breaker, acting directly on its lever. There are two versions available, one placed beside the circuit-breaker (for installation on a panel or DIN EN rail), the other on the front, suitable for being installed directly on the front of the circuit-breaker. Both versions can be used either for S or for S2 and in the three- and four-pole version. GSIS024 GSIS025 Rated voltage, Un AC DC [V] 48 [V] 0 60 GSIS9022 GSIS902 [V] [V] 220 Operating voltage % Un % Un Inrush power absorption, Ps [VA] [W] Duration opening [s] < 0. closing [s] < 0. Mechanical life [no. operations] Degree of protection, on the front IP 0 Minimum duration of the opening and closing command impulse [ms] > /7
88 Accessories Remote controls Direct action motor operator for SACE S-S4 and S5 circuit-breakers Both the opening and closing command is controlled by the motor, which acts directly on the circuit-breaker lever. The table shows the power supply voltage values Un [V]. S-S4-S5 GSIS902 GSIS026 GSIS027 4 Rated voltage, Un AC DC [V] 24 [V] [V] [V] [V] 80 [V] 440 Operating voltage % Un % Un Inrush power absorption, Ps 500 [VA] 500 [W] Service power absorption, Pc 50 [VA] 50 [W] Operating frequency [Hz] Time constant [ms] 8 Duration opening [s] 0. closing [s] 0. Mechanical life [no. operations] 5000 (S-S4) / 0000 (S5) Degree of protection, on the front IP 0 Minimum duration of the opening and closing command impulse [ms] > 50 4/8
89 Stored energy motor operator for SACE S6-S7 circuit-breakers With the stored energy operating mechanism, during circuit-breaker opening the release mechanism automatically precharges a system of springs: the stored energy is exploited for closing the circuitbreaker. It is supplied complete with shunt closing release (Ps00VA~/ 00W ) and flange for the compartment door. The table shows the power supply voltage values Un [V]. In the case of interlocked circuit-breakers, the key lock against manual operation is necessary. S6-S7 GSIS028 GSIS029 GSIS9020 Rated voltage, Un AC DC [V] 24 [V] 48 [V] 60 [V] 0 0 [V] [V] [V] 80 [V] Operating voltage % Un % Un Inrush power absorption, Ps 660 [VA] 600 [W] Service power absorption, Pc 80 [VA] 80 [W] Operating frequency [Hz] Time constant [ms] 22 Duration closing 0.09 opening.2 resetting 2 Mechanical life [no. operations] 0000 (S6) / 5000 (S7) Degree of protection, on the front IP 0 Minimum duration of the opening and closing command impulse [ms] > /9
90 Accessories Remote controls Geared motor for SACE S8 circuit-breaker This allows the springs of the circuitbreaker closing mechanism to be charged automatically, immediately following an closing operation. It includes a limit microswitch for electrical signalling of closing springs charged. Rated voltage, Un AC DC [V] 24-0 [V] [V] [V] Inrush power absorption, Ps 000 [VA] 000 [W] Service power absorption, Pc 20 [VA] 20 [W] Charging time [s] Mechanical life [no. operations] 5000 GSIS9007 Connectors for motor operators The motor operators, from S to S7, can only be supplied by means of the spe- S... S7 cific connection connectors. They are of the slide type and allow simultaneous connection of both the motor operator and the auxiliary contacts to the relative power supply circuit. They are an alternative to the corresponding connectors 4 for the auxiliary contacts only since they are housed in the same seat. They must be ordered specifying the size and version of the circuit-breaker (fixed or plug- GSIS00 GSIS904 in/withdrawable). Extension for testing motor operators For the SACE S, S4, S5, S6, and S7 circuit-breakers, this allows both motor operators and the auxiliary contacts to be connected to the relative power supply circuit with the circuit-breaker in the racked-out position. With the circuitbreaker in safe conditions, i.e. isolated in relation to the power circuits, blank operating tests of the circuit-breaker can be carried out. It must be ordered specifying the size and version of the circuitbreaker (fixed or plug-in/withdrawable) and automatically excludes the corresponding extension for testing the auxiliary contacts S... S7 GSIS906 4/20
91 Rotary handle operating mechanism The rotary handle operating mechanism facilitates operation thanks to its ergonomic handle. It is always fitted with a padlock in the open position, which prevents the circuit-breaker being closed. The lock slot can take up to padlocks stem Ø 6 mm (not supplied). On request it can be fitted with a compartment door lock or a key lock in the open position. For SACE S2, S, S4, S5, S6, and S7 circuit-breakers, application of the rotary handle operating mechanism is an alternative to the front flange for the lever operating mechanism and for the motor operator. Different types of rotary handle operating mechanism are available. The position of the rotary handle indicates with certainty the position of the contacts: open, closed, relay tripped. The release settings and the nameplate data remain accessible to the user. For the SACE S6, S7 circuit-breakers, the direct rotary handle operating mechanism on the circuitbreaker is always supplied complete with flange for the compartment door. The rotary handle operating mechanism in the emergency version, complete with red-yellow handle and yellow plate, suitable for machine tool control, is also available for all the circuit-breakers. S-S2 S-S4-S5 GSIS02 GSIS0 S6-S7 GSIS02 4 S-S2 S-S4-S5 S6-S7 GSIS9025 GSIS9024 F / P F / P W F W Direct Direct emergency Transmitted with fixed distance 9,5 mm Transmitted with fixed emergency distance 9,5 mm Transmitted with adjustable distance 00 mm 00 mm 500 mm 500 mm Transmitted with adjustable emergency distance 00 mm 500 mm Extension for transmitted handle 80/500 mm 500 mm 4/2
92 Accessories Operating mechanisms and locks Front flange for lever operating mechanism This can be installed on SACE S, S4, S5, S6, and S7 fixed, plug-in or withdrawable circuit-breakers. In the case of withdrawable circuit-breakers installed in compartments, it allows the IP40 degree of protection to be kept for the whole isolation run of the circuit-breaker. It is always fitted with a padlock in the open position (stem Ø 6 mm - up to three padlocks - not supplied) which prevents closing of the circuit-breaker. On request, it can be fitted with a key lock in the open position for one or more circuit-breakers and with the compartment door lock. It is available in the following versions: for fixed or plug-in circuit-breaker. for withdrawable circuit-breaker. For the SACE S6, S7 circuit-breakers, it is always supplied complete with flange for the compartment door, whereas for the SACE S, S4, and S5 circuit-breakers the flange supplied with the circuit- S-S4-S5 S6-S7 4 GSIS9008 GSIS9026 GSIS0 GSIS04 breaker can be used. Key lock in open position This allows the mechanical closing operation of the circuit-breaker to be locked. S... S7 The following versions are available: lock with different key for each circuitbreaker lock with the same key for groups of circuit-breakers. Different locks are supplied for direct action motor operator, for stored energy motor operator, and for rotary handle or front flange for lever operating mecha- GSIS05 GSIS06 nism. The circuit-breaker lock in the open position ensures circuit isolation in compliance with the IEC Standard. 4/22
93 Compartment door lock This prevents the compartment door being opened with the circuit-breaker closed. It can be used with the SACE S, S4, S5, S6, and S7 circuit-breakers in the fixed, plug-in or withdrawable version and fitted with rotary handle operating mechanism or front flange for lever operating mechanism. It consists of two elements: one applied to the rotary handle operating mechanism or to the front flange for the lever operating mechanism, the other, consisting of a metal striker, to be applied onto the compartment door. For the SACE S-S2 circuit-breakers it is an integral part of the rotary handle operating mechanism. S...S7 GSIS900 4 GSIS9009 GSIS07 Lock for fixed part of withdrawable circuit-breaker Key locks or padlocks are available to be applied to the guide of the fixed part of a withdrawable circuit-breaker to prevent the moving part from being rackedin. The following different versions are available: Padlock, which can take up to three padlocks with stem Ø 6 mm (not supplied). Key lock in the open position with different key for each circuit-breaker Key lock in the open position between two or more circuit-breakers with the same key for groups of circuit-breakers Key lock of Ronis type (without key). S...S7 GSIS08 GSIS09 GSIS040 4/2
94 Accessories Operating mechanisms and locks Padlock for operating lever This is applied on the cover of the SACE S-S2 circuit-breakers to prevent the operating lever movement. If activated, the circuit-breaker remains locked in the open position, guaranteeing circuit isolation in compliance with the IEC Standard. S-S2 GSIS905 4 S2-S GSIS044 GSIS9049 GSIS042 GSIS04 GSIS04 Anti-tampering lock This is applied on the cover of the SACE S2, S circuit-breakers in correspondence with the regulator of the thermal element of the thermomagnetic release and prevents it being tampered with. 4/24
95 Mechanical interlock between two circuit-breakers This allows installation of two circuitbreakers on a single support and, by means of special lever mechanism, makes them mechanically inter-dependent. It prevents operation in parallel of two power supply sources (e.g.: normal - emergency). It consists of a kit with levers and assembly accessories and a metallic support. The circuit-breakers and any operating mechanism accessories must be ordered separately. The mechanical interlock is available for SACE S, S4, S5, S6, and S7 circuit-breakers in side by side and superimposed versions. To be able to take the circuit-breakers mounted directly on the interlocking plate, the code SDA05009R must be specified as an accessory of the second circuit-breaker (or fixed part) which is to be interlocked. N.B. for the S, S4, S6 circuit-breakers, only the version side by side can be used. S... S7 GSIS045 GSIS /25
96 Accessories Residual current releases All the circuit-breakers in the SACE Isomax S series are preset for combined assembly with residual current releases. In partic ular, the SACE S, S2, and S circuit-breakers can be combined with residual current releases in the SACE RC20, RC2 or RC22 series, in the version side by side or underneath the circuit-breaker. Apart from the protection against overloads and short-circuits typical of circuit-breakers, the residual current circuit-breake rs which are derived from them also guarantee protection against earth fault currents, thereby ensuring protection against the ris k of fire. The residual current releases can also be mounted on the SACE S2D and SD switch-disconnectors. In that case, the derived apparatus is a pure residual-current circuit-breaker, which therefore guarantees only residual current protection an d not the protections typical of circuit-breakers. The pure residual-current circuit-breakers are only sensitive to the earth f ault current and are generally applied as main isolators in small distribution switchboards towards end users. The use of pure and non-pure residual-current circuit-breakers allows continuous monitoring of the state of insulation of t he installation, ensuring effective protection against the risk of fire and explosion and, in the case of devices with I n 0mA, they guarantee protection of people against indirect and direct contacts to integrate the compulsory measures foreseen by the standards and by the accident prevention regulations. The residual-current releases are constructed in compliance with the following standards: IEC appendix B IEC 255- and IEC 000: for protection against unwarranted trips. SACE RC20 polarised residual-current release 4 The SACE RC20/ polarised residualcurrent release is available for four-pole SACE Isomax S circuit-breakers for assembly side by side on DIN rail. The release is constructed using polarised type technology and acts directly on the release operating mechanism of the circuit-breaker, by means of a small piston which passes through a pre-cut window on the side of the circuit-breaker. It is fitted with a test button for periodically checking the circuit-breaker. S GSIS047 GSIS9027 SACE RC2, RC22 electronic residual current releases The SACE RC2 and RC22 residual current releases can be installed both on the SACE S, S2 and S circuit-breakers and on the SACE S2D and SD switch-disconnectors, in the fixed fourpole version, and can be supplied in two versions as follows: for assembly in position beside the circuit-breaker for assembly in position under the circuit-breaker. The following releases are available: SACE RC2/, RC22/ for S circuitbreakers SACE RC2/2, RC22/2 for S2 circuitbreakers SACE RC2/, RC22/ for S circuitbreakers. They are constructed using analogue technology and act directly on the circuit-breaker by means of an opening solenoid, supplied with the release, to be housed in the special slot made in the area of the third pole. They do not require an auxiliary power supply since they are supplied directly from the network and their operation is guaranteed even with only a single phase supplied with voltage and in the presence of one-direction pulsating currents with continuous components. The operating conditions of the apparatus can be controlled constantly by means of the test pushbutton of the electronic circuit and the residual current trip magnetic indicator. The circuit-breaker complete with residual current release can be fitted with the electrical accessories normally available for the circuit-breaker. The opening and undervoltage releases are housed in the special slot made in the fourth pole. 4/26
97 Residual current release beside the four-pole version circuit-breaker This is supplied complete with: power cables for connection to the lower terminals of the circuit-breaker (respecting correspondence with the neutral and phases) an opening solenoid to be housed in the area of the third pole, complete with plug-socket connector for connection to the residual current release 2 brackets for fixing on DIN rail (one for the circuit-breaker and one for the residual current release) plug connector to make the connection of the remote opening pushbutton (to be provided by the customer). For SACE S-S2 circuit-breakers the residual current release is fitted with front terminals for cables. For the SACE S circuit-breaker, the residual current release is fitted with front terminals and is also supplied with a front flange H 45 mm for the circuit-breaker. S-S2-S beside On request, the front terminals for cables can be mounted, using the standard circuit-breaker kit. GSIS048 Residual current release under the four-pole version circuit-breaker This is supplied complete with: an opening solenoid to be housed in the area of the third pole, complete with plug-socket connector for connection to the residual current release plug connector to make the connection of the remote opening pushbutton (to be provided by the customer) with the SACE RC22 residual current release flange for compartment door (one for SACE S, S2; two for SACE S) protection for assembly in the area between the circuit-breaker and residual current release. For SACE S, S2 circuit-breakers, the residual current release is supplied with front terminals for cables On request, the rear threaded terminals can be mounted, using standard kit of the circuit-breaker. For SACE S circuit-breakers, the residual current release is supplied with front terminals (together with a front flange H 45mm for circuit-breaker). On request, using the standard kit of the circuit-breaker, front terminals for cables, extended front terminals, or rear termi- S-S2-S under nals for cables can be mounted or the rear terminals using the kit with 4 pieces for the circuit-breaker can be mounted (code SDA0265R) and the kit for residual current release (code SDA02554R). GSIS /27
98 Accessories Residual current releases Technical characteristics Residual current releases SACE RC20 SACE RC2 SACE RC22 Technology polarised type electronic electronic Action direct with solenoid with solenoid Primary operating voltage [V] up to Operation frequency [Hz] Hz ± 0% Hz ± 0% Hz ± 0% Range of test operation [V] Rated service current [A] up to 25 up to 250 up to 250 Trip thresholds I n [A] 0, - 0,5 0,0-0, - 0, 0,0-0, - 0, - 0,5 - Tolerance for I n [%] +0, , -20 Trip times [s] instantaneous instantaneous 0-0, - 0,25-0,5 - -,5 Tolerance over trip times [%] ± 20 Trip signalling Self-supply Input for remote opening Indication of pre-alarm at 50% AC type only for alternating current Type A for alternating current, pushbutton Low sensitivity High sensitivity Mounting under the circuit-breaker Mounting beside the circuit-breaker Dimensions (L x H x P) [mm] 0 x 20 x x 20 x x 70 x 08 Connection to the residual current circuit-breaker network 4 Network connection diagrams for which the protection is active even with only one phase supplied with voltage Network connection diagrams for which the protection is active with at least two phases supplied with voltage GSIS0077 () Terminal to be connected to the neutral or to the earthing conductor. 4/28
99 SACE RCQ switchboard residual-current relays The SACE Isomax S4, S5, S6, and S7 circuit-breakers can be combined with the SACE RCQ switchboard residual-current relay with separate toroid (to be installed externally on the line conductors) and satisfies requirements with trip thresholds up to 0 A and times up to 5 s or where the installation conditions are particularly restrictive, such as circuit-breakers already installed, limited space in the circuit-breaker compartment. Thanks to its wide setting range, the SACE RCQ switchboard residual-current relay is suitable for applications where a coordinated residual current protection system is to be constructed at the various distribution levels, from the main switchboard to the end user. It is particularly suitable where low sensitivity residual current protection is required, for example in partial (current-type) or total (time-type) selective chains, and for high sensitivity applications (with physiological sensitivity) to realise protection of people against direct contacts On a drop in the auxiliary power supply voltage, the opening command intervenes after a minimum time of 00 ms and after the time set plus 00 ms. The SACE RCQ relay is suitable for use in the presence of earth currents of alternating type only (AC Type), for alternating current and/or pushbutton with continuous components (Type A) and is suitable for carrying out residual current selectivity. The SACE RCQ relay is of the type with indirect action and acts on the release mechanism of the circuit-breaker by means of the circuit-breaker shunt opening release (to be ordered by the user) to be housed in the special slot made on the third pole of the circuit-breaker. GSIS9046 Residual-current relay SACE RCQ Power supply voltage AC [V] DC [V] Operation frequency [Hz] Hz ± 0% Trip threshold adjustment I n - a range of adjustments [A] 0,0-0,05-0, - 0, - 0,5-2 a range of adjustments [A] Trip time adjustment [s] 0-0, - 0,2-0, - 0,5-0, Pre-alarm threshold adjustment [%] x I n % x I n Range of use of the closed transformers I n - Toroidal transformer Ø 60 [mm] [A] 0, Toroidal transformer Ø 0 [mm] [A] 0, Toroidal transformer Ø 85 [mm] [A] 0,... 0 Range of use of the transformers which can be opened I n - Toroidal transformer Ø 0 [mm] [A] 0, Toroidal transformer Ø 80 [mm] [A] 0, Toroidal transformer Ø 20 [mm] [A]... 0 Alarm pre-threshold signalling ellow flashing LED N.O. changeover contact 6 A V AC 50/60 Hz Residual-current relay trip signalling ellow flashing LED 2 changeover contacts (N.O. N.C.; N.O.) 6 A VAC 50/60 Hz Remote opening command N.O. Contact Trip time 5 ms Connection to the toroidal transformer By means of 4 twisted conductors Maximum length 5 m Dimensions L x H x D [mm] 96 x 96 x,5 Drilling for assembly on door [mm] 92 x /29
100 Accessories Accessories for electronic releases SACE PR22/D-M Modbus and SACE PR22/D-L Lon dialogue unit 4 The dialogue unit is a device which allows two-way communication from the circuit-breaker to the outside and vice versa. has built two distinct dialogue units able to support two different standard market protocols: SACE PR22/D-M (Modbus RTU protocol) and SACE PR22/D-L (LonTalk protocol by Echelon). Both units are housed in external modules, which can be installed on DIN rails, and can be used with the S4, S5, S6, and S7 circuit-breakers fitted with SACE PR22/P electronic release, both in the LSI and LSIG versions, or SACE PR22/MP release. They must be supplied with a stabilised voltage of 24 VDC (±20% with maximum ripple ±5%) and be earthed. Communication towards the outside is generally addressed to a supervision and control unit, which has the task of collecting and storing the information regarding the part of the plant controlled. In the case of an error in the serial communication due to a fault in the dialogue unit or lack of auxiliary power supply, the SACE PR22/P protection unit works according to the last parameters set and, in any case, in accordance with what has been set manually. The SACE PR22/ D-M and SACE PR22/D-L dialogue units are always fitted in combination with the SACE PR22/T actuator unit, which allows remote closing or opening operation of the circuit-breaker (Remote Control) by means of two digital outputs which can be disabled thanks to the dip-switch (LOC/REM) positioned on LOC. Information available State of the circuit-breaker: open; closed; tripped Installation alarms: pre-alarm L; tripped L-S-I-G-R-V-PTC Measurements: currents; N operations; N trips Reading and writing curves and trip thresholds: only manual reading (MAN), electronic reading and writing (ELT) Circuit-breaker commands: opening; closing; reset. PR22/DM PR22/D-M PR22/D-L Protocol Modbus RTU LonTalk Physical means of transmission EIA RS485 TP (Twisted Pair) Speed bit/s 78Kbit/s Architecture bus bus 4/0
101 SACE PR22/T actuator unit The SACE PR22/T actuator unit allows circuit-breaker opening and closing by means of the motor operator mounted on the circuit-breaker. It is always supplied in combination with the SACE PR22/D dialogue unit. An auxiliary power supply with a stabilised voltage of 24 VDC (±20%, with maximum ripple - ±5%) and earthed is required for operation of the unit. The PR22/D dialogue unit sends the digital opening and closing commands, received from the supervision and control system, to the inputs of the SACE PR22/T actuator unit, which carries out circuit-breaker closing and opening by means of a power relay. The motor operator of the circuit-breaker (use the versions with power supply voltage at 0 V AC/DC or 220 V AC) must be connected to these relays. GSIS904 SACE TT Test unit This allows control of tripping of the SACE PR2/P, SACE PR22/P, and SACE PR22/MP electronic releases and the trip test of the opening solenoid OS. The device is supplied by means of a 2 V replaceable battery and is fitted with a two-pole polarised connector-tracer point housed on the bottom of the box, which allows connection of the device to the test input bushings located on the front of the SACE PR2/P, SACE PR22/P, or SACE PR22/MP releases. The limited dimensions of the accessory make it practically pocket-type. The trip test device can be used on the SACE Isomax S4, S5, S6, S7, and S8 circuitbreakers. GSIS90 4 SACE PR22/K signalling unit The SACE PR22/K signalling unit, only available for S8, is able to convert the digital signals supplied by the SACE PR22/P - (LSIG) protection unit into electric signals by means of normally open electrical contacts. An auxiliary power supply is needed to operate the unit. It is connected to the internal bus of the protection unit by means of a dedicated serial line over which the information regarding the state of activation of the protection functions passes, on the basis of which the relative power contacts are closed to signal: pre-alarm for protection function L (I>0.9 x I) protection function L, S, I, G trip release trip communication error with protection unit. GSIS904 PR22/K Auxiliary power supply 24 V DC ±20% maximum ripple 5% Maximum current interrupted 5 A Maximum voltage interrupted 250 V AC / 0 V DC Breaking capacity resistive load 50 W / 800 VA (48 V DC and 220 V AC) Breaking capacity - inductive load 25 W / 500 VA (48 V DC and 220 V AC) Contact/contact insulation 000 Veff Contact/coil insulation 2000 Veff 4/
102 Accessories Accessories for electronic releases SACE PR00/K signalling unit The SACE PR00/K signalling unit can convert the signals received via the bus from the SACE PR22/P (LSI or LSIG) and SACE PR22/MP (LRIU) protection units into electric signals by means of normally open electrical power contacts. An auxiliary power supply with a voltage stabilised at 24V DC (±20% with maximum ripple - ±5%) and earthed is needed to operate the unit. It is connected to the Internal Bus of the protection unit by means of a dedicated serial line over which the information regarding the state of activation of the protection functions passes, on the basis of which the relative power contacts are closed. In particular, the following signals are available: Alarm signalling remains active for the whole duration of the overload up to any release trip. The protection trip signals remain active during the timing phase and remain that way even after release trip. A Reset pushbutton on the front of the unit allows the state of all signals to be reset. There are also two LEDs available on the unit for visually signalling the following information: Power ON : auxiliary power supply present T (Int Bus) : flashing synchronised with the communication activity with the Internal Bus The table below shows the characteristics of the signalling relays available in the SACE PR00/K unit. GSIS947 4 K5 PR22/P (LSI-LSIG) Protection L alarm 2 Protection S alarm Protection I alarm 4 Protection G alarm 5 Bus K.O. 7 Release trip 8 Protection L pre-alarm PR00/K Auxiliary power supply 24 V DC ±20% maximum ripple 5% Maximum current interrupted 5 A Maximum voltage interrupted 250 V AC / 0 V DC Breaking capacity resistive load 50 W / 800 VA (48 V DC and 220 V AC) Breaking capacity inductive load 25 W / 500 VA (48 V DC and 220 V AC) Contact/contact insulation 000 Veff Contact/coil insulation 2000 Veff K5 PR22/MP (LRIU) Protection L alarm 2 Protection R alarm Protection I alarm 4 Protection U alarm Welded contactor alarm contacts 5 Bus K.O. 6 PTC alarm (temperature sensor on motor) (*) Generic input 0/ 7 Release trip 8 Protection L pre-alarm Back-up protection alarm (*) alternatively by means of dip-switch 4/2
103 SACE PR00/T Test and Configuration Unit The SACE PR00/T unit is an instrument able to carry out the Test, programming and parameter readout functions for the protection units which equip the SACE Isomax S moulded-case circuit-breakers and the SACE Emax air circuit-breakers. In particular, for circuit-breakers fitted with SACE PR22/P or SACE PR22/MP releases, the test, programming and readout parameter functions are available. All the functions mentioned can be carried out ON BOARD by connection of the SACE PR00/T unit to the multipin front flange connector on the protection unit; connection is guaranteed by means of special interfacing cables supplied as standard with the unit. The man-machine interface is guaranteed by using a membrane keyboard and a multi-line alphanumerical display. There are also two LEDs on the unit which signal the following respectively: POWER-ON and STAND B situation situation of the battery charging state. Two different types of Test are provided: automatic and manual. By means of connection to the PC (with software provided by ), it is possible to upgrade the SW of the SACE PR00/T unit to allow adaptation of the Test unit to evolution of new products. The results of most importance regarding the test can also be stored in the unit itself and sent to the Personal Computer on explicit request for issue of report. Both in automatic and manual mode, the SACE PR00/T unit is able to test the following: protection functions L, S, I, G; protection functions LRIU for SACE PR22/MP; monitoring of correct operation of the microprocessor. The SACE PR00/T unit is of the portable type and operates with rechargeable batteries and/or with an external power supply. In its standard supply, the unit includes: SACE PR00/T Test unit complete with rechargeable batteries SACE TT Test unit V AC/2 V DC external power supply connection cables between the unit and the multipin connector present on the ranges of releases which equip the SACE Isomax S and the SACE Emax series connection cable between the unit and the PC (serial RS22) power supply cable instruction manual and diskette with application SW plastic container. GSIS SACE PR22/CI contactor control unit The SACE PR22/CI accessory unit can be associated with all the circuit-breakers fitted with SACE PR22/MP electronic release for motor protection. When the appropriate dip-switch on the front of the release is positioned on the Normal mode, it allows the contactor to be opened in the case of fault for overload L, blocked rotor R or phase missing/ unbalance U. The SACE PR22/CI unit can always be installed both on a DIN rail and on the rear of the door. GSIS9040 4/
104 Accessories Accessories for electronic releases CT for external neutral This is applied to the neutral conductor and allows protection against earth faults with three-pole circuit-breakers to be realised. The circuit-breaker must be fitted with SACE PR22/P LSIG release. The transformer must be connected to the release by means of the specific -4 connectors, selected according to the version of the circuit-breaker and the type of protection release used. S4 S5 S6 S7 S8 [A] [A] [A] [A] [A] GSIS9005 Connectors These allow connection of the microprocessor-based release to units or compo- 4 nents of external plants. They are, in fact, used to make the relay tripped signal available outside and to connect the protection transformer of the neutral conductor outside the circuit-breaker or to the actuator, dialogue and signalling units, if these are provided. Connector for circuit-breaker fixed fitted with releases SACE PR2/P Connector for plug-in/withdrawable circuit-breaker (to be applied in the fixed part) fitted with SACE PR2/P release Connectors -4 for fixed circuitbreaker fitted with SACE PR22/P release Connectors -4 for plug-in/withdrawable circuit-breaker fitted with SACE PR22/P release Connectors GSIS050 GSIS900 Connectors 4 GSIS05 4/4
105 Accessories Installation accessories and spare parts Bracket for fixing on DIN rail This is applied to the fixed circuit-breaker and allows installation on standardised DIN rails. It simplifies assembly of circuitbreakers up to 60 A in standard switchboards. S-S2 S-S4-S5 Bracket for fixing on DIN EN rail for SACE S-S2 circuit-breakers. Bracket for fixing on DIN EN 5002 rail for SACE S-S4-S5 circuit-breakers. The fixing bracket kit for SACE S-S4-S5 circuit-breakers also includes the front flange H 45mm. GSIS90 GSIS052 GSIS05 Flange for compartment door This is always supplied with the circuitbreaker and can also be used with the rotary handle operating mechanism for the SACE S, S4, S5, S6, and S7 circuitbreakers, the front flange for lever operating mechanism and the motor operator. In case of use of these accessories with SACE S6, S7 circuit-breakers, a flange is supplied to be used instead of the one supplied with the circuit-breaker. It is not supplied for SACE S, S2, and S circuit-breakers which are complete with SACE RC20, RC2, RC22 residual current releases in the version beside the circuit-breaker. GSIS908 S-S2 S... S7 withdrawable GSIS054 GSIS056 S... S7 fixed S8 GSIS057 GSIS /5
106 Accessories Installation accessories and spare parts IP54 protection for rotary handle This allows IP54 degree of protection to be attained. It is available in the following versions: for rotary handle operating mechanism on compartment door with fixed distance for SACE S-S2 circuit-breakers for rotary handle operating mechanism on compartment door with adjustable distance for circuit-breakers SACE S- S4-S5-S6 and S7 circuit-breakers. S-S2 GSIS058 GSIS904 Spare parts The following spare parts are available: operating lever cover group arcing chambers isolating contacts opening solenoid for the SACE RC2and RC22 residual current releases kit with washers, screws and dowels for assembly of the connection terminals. For further details, please ask the Service Division of for the spare parts catalogue. 4 4/6
107 Characteristic curves and technical information Index Characteristic curves Trip curves for distribution Circuit-breakers with thermomagnetic releases... 5/2 Circuit-breakers with SACE PR2/P, SACE PR22/P electronic releases... 5/7 Trip curves for motor protection Circuit-breakers with magnetic only releases... 5/9 Use of the trip curves of circuit-breakers with SACE PR22/MP electronic release... 5/0 Circuit-breakers with electronic release SACE PR22/MP... 5/2 Limitation curves 20 V... 5/ V... 5/7 500 V... 5/ V... 5/2 Specific let-through energy curves 20 V... 5/ V... 5/ V... 5/0 690 V... 5/ 5 Technical information Temperature performance Circuit-breakers with electronic releases... 5/4 Circuit-breakers with thermomagnetic releases... 5/9 Power loss values... 5/40 Operation and protection of the low-voltage side of three-phase transformers.. 5/42 Operation and protection of three-phase AC capacitors... 5/44 Protection of three-phase AC generators... 5/46 Applications in direct current... 5/47 Backup protection (backup table)... 5/50 5/
108 Trip curves for distribution Circuit-breakers with thermomagnetic releases SACE S 25 - S2 60 t [s] 0 4 Magnetic tripping threshold Im 0 x Ith S S2 R50 25 R50 60 R2 R20 R2,5 R40 R25 R6 R , x Ith GSIS020 SACE S 25 - S2 60 t [s] 0 4 Magnetic tripping threshold Im 5 x Ith S S2 R40 25 R40 60 R2 R25 R6 R20 R2,5 R , x Ith GSIS0202 5/2
109 SACE S2 00 t [s] 0 4 Magnetic tripping threshold Im 0 x Ith , x Ith GSIS020 SACE S Magnetic tripping threshold Im 0 x Ith R0 0 A ø R ø GSIS0024 GSIS0204 5/
110 Trip curves for distribution Circuit-breakers with thermomagnetic releases SACE S 60 - S 250 t [s] 0 4 Magnetic tripping threshold Im 0 x Ith S 60 R80 R60 S 250 R200, R , x Ith GSIS0205 SACE S 60 t [s] 0 4 Magnetic tripping threshold Im 5 x Ith R50 R , x Ith GSIS0206 5/4
111 SACE S 60 - S 250 t [s] 0 4 Magnetic tripping threshold Im x Ith Magnetic tripping threshold Im 5 x Ith S 60 R80 R60 S 250 R200, R , x Ith GSIS0207 SACE S5 400 (R20-400) SACE S5 60 (R500) t [s] Thermal tripping threshold In 0,7 x Ith Magnetic tripping threshold Im 5 0 x Ith , x Ith GSIS0208 5/5
112 Trip curves for distribution Circuit-breakers with thermomagnetic releases SACE S6 60 (R60) Thermal tripping threshold In 0,7 x Ith Magnetic tripping threshold Im 5 0 x Ith t [s] , x Ith GSIS0209 SACE S6 800 (R800) Thermal tripping threshold In 0,7 x Ith Magnetic tripping threshold Im 5 0 x Ith t [s] , x Ith GSIS020 5/6
113 Trip curves for distribution Circuit-breakers with electronic releases SACE S4-S5-S6-S7 t [s] 0 4 SACE PR2/P Functions LI - I 0 0,4 0,5 0,7 0,95 0,6 0,8 0,9 N.B. For S5 60 The maximum threshold that can be set for the I function is 8 x I n 0 2 D C B, A 6 D C B A , x I n GSIS02 SACE S4-S5-S6-S7-S8 t [s] 0 4 0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,8-0,85-0,875-0,9-0,925-0,95-0,975- SACE PR22/P Function LSI, S inverse short delay (I 2 t constant ON) N.B. For S5 60 The maximum threshold that can be set for the I function is 8 x I n ,4 D C B A D C B A, D C B A I 2 t ON , x I n GSIS022 5/7
114 Trip curves for distribution Circuit-breakers with electronic releases SACE S4-S5-S6-S7-S8 t [s] 0 4 0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,8-0,85-0,875-0,9-0,925-0,95-0,975- SACE PR22/P Function LSI, S definite short delay (I 2 t constant OFF) N.B. For S5 60 The maximum threshold that can be set for the I function is 8 x I n ,4 D C B A, D C B A D C B A I 2 t OFF , x I n GSIS02 SACE S4-S5-S6-S7-S8 SACE PR22/P Function G t [s] 0 4 0,2 0, 0,4 0,6 0,8 0, D C B A , x I n GSIS024 5/8
115 Trip curves for motor protection Circuit-breakers with magnetic only releases SACE S2 80 t [s] 0 4 Fixed magnetic tripping threshold Im x Ith SACE S 0 2 S S S280 Adjustable magnetic tripping threshold Im 4 2 x Ith , x I n GSIS /9
116 Trip curves for motor protection Use of the trip curves of circuit-breakers with SACE PR22/MP electronic release For correct parameter setting of the SACE PR22/MP electronic release, it may be useful to compare the overall circuit-breaker curve with the motor starting curve. For this purpose, with the protection function graphics shown on the following pages, it is possible to draw the overall curve required for the circuit-breaker fitted with SACE PR22/MP release simply and immediately. N.B. For function L, as for all the other functions, make sure you place a glossy tracing sheet over the curve so that the time s on the axis of the co-ordinates coincide. 5 Function L (cannot be excluded) - Protection against overload To protect the motor against any overloads, as a first step it is necessary to adjust function L to a current I higher than or equal to the rated current of the motor Ie: I > Ie. For example, if Ie 5 A, an S4H60 circuit-breaker can be selected with In 60 A and the following adjustment carried out: I 0.85 x In 6 A. The second step is to select the trip class according to the motor starting time ta. For a motor with a start-up overload of 6 seconds, class 0 can be selected, with a trip time of 8s at 7.2 x I. To trace the curve correctly on the glossy sheet, according to I/In, simply place the glossy sheet over the graph of function L so that I/In 0.85 (on the glossy sheet) corresponds to I/I (on the graph) and draw the curve relative to class 0. Function R (can be excluded) - Protection against rotor blockage Protection against rotor blockage can be set both with regard to the trip current I5... 0xI (in this case I x 0.85 x 60), and with regard to the trip time t5. To trace the curve correctly on the glossy sheet, simply place the glossy sheet over the graph of function R so that I/In I/In (on the glossy sheet) corresponds to I/I (on the graph). In this case I/In I/In 0.85, and draw the desired curve. Function I (cannot be excluded) - Protection against short-circuit This protection function against short-circuit recognises whether the motor is in the starting phase, thereby avoiding unwarranted trips; the trip threshold can be set from 6 x In to x In. To trace the curve correctly on the glossy sheet, simply place the glossy sheet over the graph of function I so that I/In (on the glossy sheet) corresponds to I/In (on the graph) and draw the desired curve. Function U (can be excluded) - Protection against loss and/or unbalance of a phase Protection against loss or unbalance of a phase, if set to ON, intervenes when one or two phases have a current lower than 0.4xI (0.4 x 0.85 x In 0.4 x 0.85 x 60 A 54.4A in this case). To trace the curve correctly on the glossy sheet, simply place the glossy sheet over the graph of function U so that I/In I/In (on the glossy sheet) corresponds to I/I (on the graph). In this case I/In I/In 0.85, and draw the desired curve. 5/0
117 Typical operating characteristic of an asynchronous motor l l I5 t5 I6 t6 le la Ip ta tp m c function L trip current function I trip current function R trip current function R trip time function U trip current function U trip time rated service current of the motor motor starting current peak value of the sub-transient starting current motor starting time duration of the sub-transient starting phase typical motor starting curve example of trip curve of a motor protection circuit-breaker with electronic release 5 GSIS0082 5/
118 Trip curves for motor protection Circuit-breakers with electronic releases SACE PR22/MP SACE S4-S5-S6-S7 t [s] 0 5 SACE PR22/MP Function L (hot and cold trip) 0 4 hot cold A A 0-0 -, I / I GSIS026 SACE S4-S5-S6-S7 t [s] 0 5 SACE PR22/MP Function L (hot trip with or 2 phases supplied) 0 4 hot A 0-0 -, I / I GSIS027 5/2
119 SACE S4-S5-S6-S7 t [s] 0 5 SACE PR22/MP Function R - U 0 4 Function U Function R , I / I GSIS028 SACE S4-S5-S6-S7 t [s] 0 SACE PR22/MP Function I , x I n GSIS029 5/
120 Limitation curves 20 V SACE S Ip [ka] , Is [ka] GSIS0220 SACE S2 Ip [ka] , Is [ka] GSIS022 5/4
121 SACE S 60, S 250 Ip [ka] Is [ka] GSIS0222 SACE S4 60, S4 250, S5, S6 60, S6 800, S7, S8 Ip [ka] S7 S S6 800 S6 60 S5 S4 250 S Is [ka] GSIS022 5/5
122 Limitation curves 20 V SACE S2 80, S2 00 Ip [ka] , ,5 8,5 6,5 5 4,2 2,5 2,6 0,0 0,0 0, Is [ka] GSIS0224 SACE S 25, S 200, S4, S6 Ip [ka] S S4 S 200 In200 S 200 In60 S 200 In25 S 25 In25 S 25 In00 S 25 In80 S 25 In50 S 25 In Is [ka] GSIS0225 5/6
123 Limitation curves V SACE S Ip [ka] , Is [ka] GSIS0226 SACE S2 Ip [ka] , Is [ka] GSIS0227 5/7
124 Limitation curves V SACE S 60, S 250 Ip [ka] Is [ka] GSIS0228 SACE S4 60, S4 250, S5, S6 60, S6 800, S7, S8 Ip [ka] S8 S S6 800 S6 60 S5 S4 250 S Is [ka] GSIS0229 5/8
125 SACE S2 80, S2 00 Ip [ka] ,5 8,5 6,5 5 4,2 2,5 2 0,,6 0,0 0,0 0, Is [ka] GSIS020 SACE S 25, S 200, S4, S6 Ip [ka] 00 S S4 S 200 In 200 S 200 In 60 S 200 In 25 S 25 In 25 S 25 In 00 S 25 In 80 S 25 In 50 S 25 In Is [ka] GSIS02 5/9
126 Limitation curves 500 V SACE S Ip [ka] , Is [ka] GSIS /20
127 Limitation curves 690 V SACE S2 Ip [ka] , Is [ka] GSIS02 SACE S 60, S 250 Ip [ka] Is [ka] GSIS024 5/2
128 Limitation curves 690 V SACE S4 60, S4 250, S5, S6 60, S6 800, S7, S8 Ip [ka] S8 S S6 800 S6 60 S5 S4 250 S Is [ka] GSIS025 SACE S2 80, S2 00 Ip [ka] ,5 8,5 6,5 5 4,2 0, 2,5 2,6 0,0 0,0 0, Is [ka] GSIS026 5/22
129 SACE S 25, S 200, S4, S6 Ip [ka] S6 S4 S 200 In 200 S 200 In 60 S 200 In 25 S 25 In 25 S 25 In 00 S 25 In 80 S 25 In 50 S 25 In Is [ka] GSIS /2
130 Specific let-through energy curves 20 V SACE S I 2 t [A 2 s] , Is [ka] GSIS028 SACE S2 I 2 t [A 2 s] , Is [ka] GSIS029 5/24
131 SACE S 60, S 250 I 2 t [A 2 s] Is [ka] GSIS0240 SACE S4 60, S4 250, S5, S6 60, S6 800, S7, S8 I 2 t [A 2 s] 0 9 S8 0 8 S S6 800 S6 60 S5 S4 250 S Is [ka] GSIS024 5/25
132 Specific let-through energy curves 20 V SACE S2 80, S2 00 I 2 t [A 2 s] ,5 8,5 6,5 5 4,2 2, ,6 0 0,0 0, Is [ka] GSIS0242 SACE S 25, S 200, S4, S6 I 2 t [A 2 s] S6 0 6 S4 S 200 In 200 S 200 In 60 S 200 In 25 S 25 In S 25 In 00 S 25 In 80 S 25 In 50 S 25 In Is [ka] GSIS024 5/26
133 Specific let-through energy curves V SACE S I 2 t [A 2 s] , Is [ka] GSIS0244 SACE S2 I 2 t [A 2 s] , Is [ka] GSIS0245 5/27
134 Specific let-through energy curves V SACE S 60, S 250 I 2 t [A 2 s] Is [ka] GSIS0246 SACE S4 60, S4 250, S5, S6 60, S6 800, S7, S8 I 2 t [A 2 s] 0 9 S8 0 8 S S6 800 S6 60 S5 S4 250 S Is [ka] GSIS0247 5/28
135 SACE S2 80, S2 00 I 2 t [A 2 s] ,5 8,5 6,5 5 4,2 2,5 2, ,0 0, Is [ka] GSIS0248 SACE S 25, S 200, S4, S6 I 2 t [A 2 s] S6 S4 S 200 In 200 S 200 In 60 S 200 In 25 S 25 In 25 S 25 In 00 S 25 In 80 S 25 In 50 S 25 In Is [ka] GSIS0249 5/29
136 Specific let-through energy curves 500 V SACE S I 2 t [A 2 s] , Is [ka] GSIS /0
137 Specific let-through energy curves 690 V SACE S2 I 2 t [A 2 s] , Is [ka] GSIS025 SACE S 60, S 250 I 2 t [A 2 s] Is [ka] GSIS0252 5/
138 Specific let-through energy curves 690 V SACE S4 60, S4 250, S5, S6 60, S6 800, S7, S8 I 2 t [A 2 s] S8 S7 0 7 S6 800 S6 60 S5 S4 250 S Is [ka] GSIS025 SACE S2 80, S2 00 I 2 t [A 2 s] ,5 8,5 6,5 5 4,2 2,5 2, ,0 0, 0 00 Is [ka] GSIS0254 5/2
139 SACE S 25, S 200, S4, S6 I 2 t [A 2 s] 0 8 S6 0 7 S4 S 200 In 200 S 200 In S 200 In 25 S 25 In 25 S 25 In 00 S 25 In 80 S 25 In 50 S 25 In Is [ka] GSIS /
140 Temperature performance Circuit-breakers with electronic releases SACE S4 60 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Plug-in - Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Front flat bar Front for cables Front flat bar Front for cables Rear for cables Rear threaded Rear for cables Rear threaded GSIS SACE S4 250 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Front flat bar Front for cables Plug-in - Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Front flat bar Front for cables Rear for cables Rear threaded Rear for cables Rear threaded GSIS0257 5/4
141 SACE S5 400 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Plug-in - Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Front flat bar Front flat bar Front for cables Rear for cables Rear threaded Front for cables Rear for cables Rear threaded GSIS0258 SACE S5 60 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear threaded Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear flat bar Rear threaded Front flat bar Rear flat bar Front for cables Rear threaded Front flat bar Rear threaded GSIS0259 5/5
142 Temperature performance Circuit-breakers with electronic releases SACE S6 60 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear vertical flat bar Rear horizontal flat bar Front flat bar Front flat bar Rear vertical flat bar Rear horizontal flat bar Front for cables Rear threaded GSIS SACE S6 800 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Front for cables Rear for cables Rear threaded Front flat bar Plug-in - Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear vertical flat bar Rear horizontal flat bar Front flat bar Rear vertical flat bar Rear horizontal flat bar Front for cables Rear for cables Rear threaded GSIS026 5/6
143 SACE S7 250 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear vertical flat bar Front for cables Rear horizontal flat bar Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear vertical flat bar Rear horizontal flat bar Front flat bar Rear vertical flat bar Front flat bar Rear vertical flat bar Rear horizontal flat bar Front for cables Rear horizontal flat bar GSIS0262 SACE S7 600 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear vertical flat bar Rear horizontal flat bar Front flat bar Rear vertical flat bar Withdrawable up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar Rear vertical flat bar Rear horizontal flat bar Front flat bar Rear vertical flat bar 5 Rear horizontal flat bar Rear horizontal flat bar GSIS026 5/7
144 Temperature performance Circuit-breakers with electronic releases SACE S SACE S Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar , ,85 Rear vertical flat bar ,9 Fixed up to 40 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Front flat bar , ,8 Rear vertical flat bar , , Rear vertical flat bar 2500 Rear vertical flat bar Front flat bar 2200 Front flat bar GSIS0264 SACE S8 200 Fixed up to 45 C 50 C 60 C 70 C Imax [A] I Imax [A] I Imax [A] I Imax [A] I Rear vertical flat bar , , , Rear vertical flat bar GSIS0265 5/8
145 Temperature performance Circuit-breakers with thermomagnetic releases SACE S 0 C 20 C 0 C 40 C 50 C 60 C 70 C R R 2, R , R , R , R R R R R R R SACE S2 R 2,5...5, ,5 9, ,5 8...,5 7,5...0,5 6,5...9,5 R , , , ,5... R ,5 6, , R , ,5...26,5 7, , R , , , R R R R R R R SACE S R R R R R R R R SACE S5 400/60 R R R SACE S6 60/800 R R /9
146 Power loss values Power [W] S S2 S S4 S5 S6 S7 S8 5 Setting Iu [A] F P F P F P-W F P-W F P-W F W F W F R ,5 R 2,5 2,5 6 6,5 6 6,5 R ,5 7,5 8,5 R ,5 8 9 R ,5 0 R R R R R R R R R R R R R R R In In In In In In In In In In In In In The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and four-pole fixed version apparatus. For the latter, the current of the neutral is nil by definition. 5/40
147 Power [W] S2 80 S2 00 S S4 S6 Setting Iu [A] F P F P F P-W F P-W F W R 8 8,2 8 8,2 R,6,6 8 8,2 8 8,2 R 2,5 2,5,2,2 R 4, 4,,2,2 R 6, 6,,2,2 R , 6 6, R 2,5 2, , 20 20, R ,6 0 0,6 R 20 20,6,6 R 25 25,7,7 R , ,6 R , ,9 R , 22 2, R , 22 24, R , 26 29, R ,4 R ,8 7,8 R In In ,4 0 In ,6 5,6 The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and four-pole fixed version apparatus. For the latter, the current of the neutral is nil by definition. Shock resistance Tests according to IEC Shock value [g] S ** 2 S2 ** 2 S-S * 2 S4-S4 * 2 S5 * 2 S6-S6 * 2 S7 * 2 5 * for fixed/plug-in/withdrawable circuitbrakekers with motor operator, undervoltage release and auxiliary contacts ** for fixed/plug-in circuit-brakekers with undervoltage release and auxiliary contacts 5/4
148 Operation and protection of the low-voltage side of three-phase transformers In order to choose the SACE Isomax S circuit-breakers to install both on the transformer risers and on the lines branching downstream of them, reference can be made to the following table dealing with transformers with no-load voltage on the secondary equal to 400 V which is the most common condition of use. The table has been drawn up considering infinite power upstream and the most unfavourable case has been assumed, that is, that the short circuit occurs on the transformer clamps. As regards users, the short circuit is considered downstream of the user circuit-breaker clamps. 5 Power supply transformers P U cc I b riser I b total [kva] % [A] [A] x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 600 6, x x x , x x Circuit-breaker "A"(secondary of transformer) I cc riser SACE Isomax S Release TM / PR2-22 [ka] type type settings 2,2 SB25 R00 0,95 2,2 SB25 R00 0,95,6 S2B60 R60 0,95,6 S2B60 R60 0,95 4,5 SN/S4N250 R200/I n 250 A 0,95/0,8 4,5 SN/S4N250 R200/I n 250 A 0,95/0,8 5,8 SN/S4N250 R250/I n 250 A 0,95/0,95 5,8 SN/S4N250 R250/I n 250 A 0,95/0,95 7,2 S5N400 I n 20 A 0,95 7,2 S5N400 I n 20 A 0,95 9 S5N400 I n 400 A 0,95 9 S5N400 I n 400 A 0,95, S6N60 I n 60 A 0,8, S6N60 I n 60 A 0,8 4,4 S6N60/S6N800 I n 60/800 A 0,95/0,8 4,4 S6N60/S6N800 I n 60/800 A 0,95/0,8 8 S6N800/S7S250 I n 800/000 A 0,95/0,8 8 S6N800/S7S250 I n 800/000 A 0,95/0,8 2 S7S250 I n 000 A 0,95 2 S7S250 I n 000 A 0,95 46 S7S250 I n 000 A 0,95 2 S7S250/S7S600 I n 250/600 A 0,95/0,8 2 S7S250/S7S600 I n 250/600 A 0,95/0,8 46 S7S250/S7S600 I n 250/600 A 0,95/0,8 29 S7S600 I n 600 A 0,95 29 S7S600 I n 600 A 0,95 58 S7H600 I n 600 A 0,95 6 S8H2000 I n 2000 A 0,95 6 S8H2000 I n 2000 A 0,95 72 S8H2000 I n 2000 A 0,95 7 S8H2500 I n 2500 A 0,95 7 S8H2500 I n 2500 A 0,95 74 S8H2500 I n 2500 A 0,95 46 S8H200 I n 200 A 0,95 46 S8H200 I n 200 A 0,95 92 S8V200 I n 200 A 0,95 5/42
149 GSIS0272 Circuit-breaker "B" (user outgoing) I cu user User rated current and type of circuit-breaker [ka] 2 A 6 A 25 A 60 A 250 A 400 A 60 A 800 A 250 A 600 A 2,2 S250 S250 4,4 S250 S250 SB25,6 S250 S250 SB25 7,2 S250 S250 SB25 4,5 S250 S250 SB25 S2B60 9 S250 S250 SB25 S2B60 5,8 S250 S250 SB25 S2B60,6 SB25 SB25 SB25 S2B60 SN250 7,2 S250 S250 SB25 S2B60 SN250 4,4 SB25 SB25 SB25 S2B60 SN250 S5N400 9 S250 S250 SB25 S2B60 SN250 8 SN25 SN25 SN25 S2N60 SN250 S5N400, SB25 SB25 SB25 S2B60 SN250 S5N400 22,6 SN25 SN25 SN25 S2N60 SN250 S5N400 S5N / S6N60 4,4 SB25 SB25 SB25 S2B60 SN250 S5N400 28,8 S2N60 S2N60 S2N60 S2N60 SN250 S5N400 S5N / S6N60 8 SN25 SN25 SN25 S2N60 SN250 S5N400 S5N / S6N60 6 S2N60 S2N60 S2N60 S2N60 SN250 S5N400 S5N / S6N60 S6N800 2 SN25 SN25 SN25 S2N60 SN250 S5N400 S5N / S6N60 S6N S2S60 S2S60 S2S60 S2S60 SH250 S5H400 S5H / S6S60 S6S800 S7S S200 S200 SL60 SL60 SL250 S5L400 S5L / S6L60 S6L800 S7L250 2 SN25 SN25 SN25 S2N60 SN250 S5N400 S5N / S6N60 S6N S2S60 S2S60 S2S60 S2S60 SH250 S5H400 S5H / S6S60 S6S800 S7S S200 S200 SL60 SL60 SL250 S5L400 S5L / S6L60 S6L800 S7L S2N60 S2N60 S2N60 S2N60 SN250 S5N400 S5N / S6N60 S6N800 S7S S200 S200 SH60 SH60 SH250 S5H400 S5H / S6H60 S6H800 S7H250 S7H S4L60 S4L60 S4L60 S4L60 S4L250 S5L400 S5L/S6L60 S6L800 S7L250 S7L250 6 S2N60 S2N60 S2N60 S2N60 SN250 S5N400 S5N/S6N60 S6N800 S7S250 S7S SL60 S4L60 SL60 SL60 SL250 S5L400 S5L/S6L60 S6L800 S7L250 S7L S25 S25(R80) S25 S200 S4250 S6400 S660 S8V2000 S8V2000 S8V S2S60 S2S60 S2S60 S2S60 SH250 S5H400 S5H/S6S60 S6S800 S7S250 S7S SL60 SL60(R80) SL60 SL60 SL250 S5L400 S5L/S6L60 S6L800 S7L250 S7L600 S25 S25(R80) S25 S200 S4250 S6400 S660 S8V2000 S8V2000 S8V S2S60 S2S60 S2S60 S2S60 SH250 S5H400 S5H/S6S60 S6S800 S7S250 S7S S4L60 S4L60 S4L60 S4L60 S4L250 S5L400 S5L/S6L60 S6L800 S7L250 S7L600 8 S25 S25(R80) S25 S200 S4250 S6400 S /4
150 Operation and protection of three-phase AC capacitors Table for choosing SACE Isomax S circuit-breakers in relation to the rated current of the bank and the power of the transformer installed. Circuit-breaker Icu Rated Rated Max Maximum rating Mechanical Electrical 80/45 V current of current of electronic/ of capacitor bank endurance endurance release capacitor magnetic in kvar-50 Hz release setting Type [ka] [A] [A] PR... / TM [V] [V] [V] [V] man man/h man man/h S B/N 25 6 / / Im0 In S2 B/N/S 60 6 / 5 / / Im0 In S N/H/L 60 5 / 65 / / Im0 In S N/H/L / 65 / / Im0 In S4 N/H/L 60 5 / 65 / I OFF / S4 N/H/L / 65 / I OFF / S5 N/H/L / 65 / I OFF / Im0 In S5 N/H/L 60 5 / 65 / /60 I OFF / Im0 In S6 N/S/H/L 60 5/50/65/ I OFF / Im0 In S6 N/S/H/L 800 5/50/65/ I OFF / Im0 In S7 S/H/L / 65 / I OFF / S7 S/H/L / 65 / I OFF / S8 H/V / I OFF / S8 H/V / I OFF / S8 H/V / I OFF / /44
151 Coefficient for calculating capacitor bank power in kvar/kw to increase the cos value. Cos to be obtained Initial Cos 0,8 0,85 0,9 0,9 0,92 0,9 0,94 0,95 0,96 0,97 0,98 0,99 0,60 0,584 0,74 0,849 0,878 0,905 0,99 0,97,005,04,08,,92,4 0,6 0,549 0,679 0,85 0,84 0,870 0,904 0,96 0,970,008,048,096,57,299 0,62 0,55 0,645 0,78 0,809 0,86 0,870 0,902 09,6 0,974,04,062,2,265 0,6 0,48 0,6 0,749 0,777 0,804 0,88 0,870 0,904 0,942 0,982,00, ,64 0,450 0,580 0,76 0,744 0,77 0,805 0,87 0,87 0,909 0,949 0,997,058,200 0,65 0,49 0,549 0,685 0,7 0,740 0,774 0,806 0,840 0,878 0,98 0,966,007,69 0,66 0,88 0,58 0,654 0,682 0,709 0,74 0,775 0,809 0,847 0,887 0,95 0,996,8 0,67 0,58 0,488 0,624 0,652 0,679 0,7 0,745 0,779 0,87 0,857 0,905 0,966,08 0,68 0,29 0,459 0,595 0,62 0,650 0,984 0,76 0,750 0,788 0,828 0,876 0,97,079 0,69 0,299 0,429 0,565 0,59 0,620 0,654 0,686 0,720 0,758 0,798 0,840 0,907,049 0,70 0,270 0,400 0,56 0,564 0,59 0,625 0,657 0,69 0,729 0,769 0,8 0,878,020 0,7 0,242 0,72 0,508 0,56 0,56 0,597 0,629 0,66 0,70 0,74 0,78 0,850 0,992 0,72 0,2 0,4 0,479 0,507 0,54 0,568 0,600 0,64 0,672 0,72 0,754 0,82 0,96 0,7 0,86 0,6 0,452 0,400 0,507 0,54 0,57 0,607 0,645 0,685 0,727 0,794 0,96 0,74 0,59 0,289 0,425 0,45 0,480 0,54 0,546 0,580 0,68 0,658 0,700 0,767 0,909 0,75 0,2 0,262 0,98 0,426 0,45 0,487 0,59 0,55 0,59 0,6 0,67 0,740 0,882 0,76 0,05 0,25 0,7 0,99 0,426 0,460 0,492 0,526 0,564 0,604 0,652 0,7 0,855 0,77 0,079 0,209 0,45 0,7 0,400 0,44 0,466 0,500 0,58 0,578 0,620 0,687 0,829 0,78 0,05 0,82 0,9 0,47 0,74 0,408 0,440 0,474 0,52 0,552 0,594 0,66 0,80 0,79 0,026 0,56 0,292 0,20 0,47 0,8 0,4 0,447 0,485 0,525 0,567 0,64 0,776 0,80 0,0 0,266 0,294 0,2 0,55 0,87 0,42 0,459 0,499 0,54 0,608 0,750 0,8 0,04 0,240 0,268 0,295 0,29 0,6 0,95 0,4 0,47 0,55 0,582 0, ,82 0,078 0,24 0,242 0,269 0,0 0,5 0,69 0,407 0,447 0,489 0,556 0,698 0,8 0,052 0,88 0,26 0,24 0,277 0,09 0,4 0,8 0,42 0,462 0,50 0,672 0,84 0,026 0,62 0,90 0,27 0,25 0,28 0, ,95 0,47 0,504 0,645 0,85 0,6 0,64 0,9 0,225 0,257 0,29 0,29 0,69 0,47 0,478 0,620 0,86 0,09 0,40 0,67 0,98 0,20 0,264 0,0 0,4 0,90 0,450 0,59 0,87 0,08 0,4 0,4 0,72 0,204 0,28 0,275 0,7 0,64 0,424 0,567 0,88 0,054 0,085 0,2 0,4 0,75 0,209 0,246 0,288 0,5 0,95 0,58 0,89 0,028 0,059 0,086 0,7 0,49 0,8 0, ,09 0,69 0,52 0,90 0,0 0,058 0,089 0,2 0,55 0,92 0,24 0,28 0,4 0,484 5/45
152 Protection of three-phase AC generators (Ue 400 V) Power generator In S S2 S S S4 S4 S5 S5 S6 S6 S7 S7 S8 S8 S [kva] [A] R R R R In [A] In [A] In [A] In [A] In [A] In [A] In [A] In [A] In [A] In [A] In [A] , , /46
153 Applications in direct current Connection diagrams Suitable connection arrangements must be adopted to obtain the number of poles in series necessary to guarantee the breaking capacity required at the various operating voltages. Circuit protection and isolation with three-pole circuit-breakers Diagram A:breaking with pole per polarity Diagram B:breaking with 2 poles in series per polarity and pole for the other polarity Diagram C:breaking with poles in series per polarity Load Load Load Poles in parallel Diagram D:breaking with 2 poles in parallel per polarity Diagram E:breaking with series of 2 poles in parallel per polarity Load Load Use at 000 V DC with four-pole circuit-breakers Diagram F: breaking with 4 poles in series for one polarity Diagram G:+ poles in series Diagram H:2+2 poles in series Load Load Load GSIS027 5 The following table shows which connection arrangement to adopt according to the number of poles to connected in series to obtain the required breaking capacity for the type of distribution network. Rated voltage < 250 < 500 < 750 < 000 Protection Function Isolation Distribution network isolated with one with median from earth polarity* to earth point to earth A, D A, D A, D - E - A, D B A, D - C, E - B G H - C - G, H - H - F - * The negative pole is assumed to be earthed. Notes ) The risk of a double fault to earth being sufficient for the fault current to affect only one side of the circuit breaking poles is considered negligible. 2) For rated voltages greater than 750V the 000 VDC range is required. ) Diagram D and diagram E only for S6. 5/47
154 Applications in direct current Connection diagrams Example of tripping threshold adjustment in DC - diagram A Setting S 25 S2 60 S 60 S 250 I th I m 0 Ith I m 5 Ith I th I m 0 Ith I m 5 Ith I th I m 0 Ith I m 5 Ith I th I m 0 Ith I m 5 Ith R R 2.5 2, ,5 208 R , R R , R , R R R R R R , , R R R N.B. For the lower settings R0, R2.5, R6 only the version I m 5 Ith can be used The correction value to adopt for the protection thresholds of each circuit-breaker is shown in the following table. Circuit-breaker Diagram A Diagram B Diagram C Diagram F Diagram G Diagram H 5 S S2 S k m k m k m k m k m k m,5 k m k m k m,5 k m k m k m S5 k m, k m k m k m, k m, k m, S6 k m, k m k m k m 0,9 k m 0,9 k m 0,9 5/48
155 Setting S5 400 S5 60 S6 60 S6 800 I th 0,7 xi n I m 5 0xI n I th 0,7 xi n I m 5 0xI n I th 0,7 xi n I m 5 0xI n I th 0,7 xi n I m 5 0xI n R R R R R Using these the correction factors means that the tripping current values will be higher for the same tripping threshold, or, vice versa, that having identified the tripping value one needs to set the tripping threshold following the reclassified scale range. Example Operating current: Ib 600 A Magnetic protection required: Im 5000 A Magnetic protection required to set: therefore in this specific case, having chosen circuit-breaker S6 R60 (ln 60 A), the magnetic threshold setting value will be: 5000 set 7, x 60 set I m k m x I n 5 5/49
156 Backup protection (backup table with Ue 400 V~) The table below shows the backup protection available, with the related breaking capacities for the rated voltage Ue400V~, between ABB moulded-case and air low voltage circuit-breakers (SACE Isomax S, SACE Limitor LNA and SACE Emax) and pro M system modular circuit-breakers. CIRCUIT-BREAKER UPSTREAM S270 S280/20 S280/20 S290 S500 SB S2B SN S2N SN S4N S5N S6N S2S S6S S7S In [A] < Icu [ka] CIRCUIT-BREAKER DOWNSTREAM 0 S240 S240 S240 S240 S240 5 S240 S240 S250 S250 6 S250 S250 S250 S250 S240 S250 S250 S270 SB SB S250 SB 20 S250 S2B S2B S2B S270 S240 S270 S270 S270 S280/20 S S250 S280/20 S280/20 SB S270 S280/25 S2B SB 0 S240 S280/20 S280/25 S280/25 S280/20 S280/25 SB SN SN SN S280/25 5 SB SN SN S2B S2B S250 SN SN 40 S4N S5N S6N S270 SB S2N S280/20 SN SN 50 S280/25 S2B S4N SB S2N S5N SN /50
157 In the interest of facilitating clear representation, the latter must be read using the follow key: S250: S250, S260, S270K S270: S270 (B-C-D), S280 (In... 8 A), S280 (In A), S290 S280/20: S280 (In A) S280/25: S280 (In A) SH S4H S5H S6H S7H S2 SL S4L S5L S6L S7L S S S4 S6 E2L EL S240 S250 S250 S250 S250 S270 SB SB S240 S270 SB SB S250 S250 S250 SB S2B S2B S2B S2B S2B S270 S280/20 S250 S270 S280/20 S270 S270 S270 S280/20 S280/20 S280/20 S280/20 S280/25 S280/25 S240 S280/25 S280/25 S280/20 S280/25 SB S2B S280/25 S280/25 SB SN SN SN S270 SB SN SN SN S5N S6N S2B S4N S2B S4N S5N S5N S6N SN S2B S6N SN S6N S280/20 SB S280/25 SB SN SN S2N S2N S2N S2N S2N SB S6S S2N S2S S2S S2S SN SN S2B S2S SN SN SN S4N S4N SN S4N S4N S5N SN SN S5N S5H SB S2N S6S S2S S6H SN SH S2N S2S S2S S2B S2N S5H S6H S2S SH SH SN S6S S7S SN SL SL S4N S6H S7H SH S4H S4H S7S SL S5H S7H SB SN S2S S5L S6L S2B S6L S7L S7L SN SN S5N S500 S500 LNA SH LNA LNA S2N SL S2N S2N S2S S4H S2S S2S SN S4L SN SH S5H SH SL S5L SL S6S S6H S6L 5 5/5
158 5 5/52
159 Overall dimensions and circuit diagrams Index Overall dimensions SACE Isomax S-S2 Fixed circuit-breaker... 6/2 Plug-in circuit-breaker... 6/ Circuit-breaker with SACE RC20-RC2-RC22 residual current releases... 6/4 Accessories... 6/5 SACE Isomax S-S4-S5-S-S4 Fixed circuit-breaker... 6/7 Mounting parts for fixed circuit-breaker... 6/9 Plug-in circuit-breaker - withdrawable circuit-breaker... 6/0 Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker... 6/ SACE S circuit-breaker with SACE RC2/ - RC22/ residual current releases... 6/2 Accessories... 6/4 SACE Isomax S6-S6 Fixed circuit-breaker... 6/8 Mounting parts for fixed circuit-breaker... 6/20 Withdrawable circuit-breaker... 6/22 Mounting parts for withdrawable circuit-breaker... 6/2 Accessories... 6/24 SACE Isomax S7 Fixed circuit-breaker... 6/28 Mounting parts for fixed circuit-breaker... 6/29 Withdrawable circuit-breaker... 6/0 Mounting parts for withdrawable circuit-breaker... 6/ Accessories... 6/2 SACE Isomax S8 Fixed circuit-breaker... 6/6 Mounting parts for fixed circuit-breaker... 6/7 Distances to be respected... 6/8 Minimum distance between centres... 6/9 6 Circuit diagrams Index... 6/4 6/
160 Overall dimensions SACE S-S2 Fixed circuit-breaker Mounting on sheet metal Mounting on DIN EN channel Terminal covers (to order when not included in supply) (*) 75 with sealable screws E B A E E (4 POL) ( POL) G (*) Low High D F C ( POL) (4 POL) 75 2 Terminals Front for Cu cables or flat bars (with separator plates between the phases) 24.5 H I Front for Cu cables or flat bars (with high or low terminal covers) H I Extended front for S2 (*) high terminal covers included in supply (*) 7.5 ø 8.5 M8 ø E E E Threaded rear (**) low terminal covers included in supply (protection class IP20) View A 42 L 02 9 A (**) M 75 Template for drilling sheet metal support (minimum thickness of sheet metal: mm) For front terminals For threaded rear terminals Template for drilling compartment door and fitting flange (thickness of sheet metal:.5-2 mm) (-4 POL) E M4/ø POL POL E E E ø M4/ø4.5 E 64 R.5 ø4 O N Q P 5 Key 2 4 Flange for compartment door Bracket for fitting circuit-breaker on DIN channel (to order) Separator plate Sealable screws GSIS000 A B C D E F G H I L M N POL 4 POL O POL 4 POL P Q S x S x /2
161 Plug-in circuit-breaker Fixed parts mounted on sheet metal or channel (terminal covers for mobile part with IP20 always included in supply) 70 B A E E E I O D F SAC o off C (4 POL) ( POL) 96 6 ( POL) (4 POL) ³ (*) 4 75 G (*)27 mm with sealable screws.5 2 mm Key 2 4 Flange for compartment door Sealable screws Fixed part Moving part complete with terminal covers Terminals Front 2.5 H I Threaded rear A View A M E 02 E 9 E 65.5 Drilling template for support (5) or channel (6) (minimum thickness of sheet metal: 2.5 mm) 44 For front terminals MA 5 L M M4 ø4.5 (4 POL) ( POL) For threaded rear terminals MA 02 R 5 L M 5.5 (4 POL) ( POL) R 5 6 R 6 84 Template for drilling compartment door and fitting flange (thickness of sheet metal:.5-2 mm) 64 R.5 O Q 5 6 A B R E M C R ( POL) (4 POL) D E F G H I E M L ( POL) (4 POL) M4 ø4.5 M N POL 4 POL O POL 4 POL ø4 P N Q P R GSIS0002 S x S x /
162 Overall dimensions SACE S-S2 Circuit-breaker with SACE RC20-RC2-RC22 residual current release Vertical installation RC2-RC22 (mounting on sheet metal) (*) Without terminal covers (**) With low terminal covers (***) With high terminal covers C A B Front terminals for Cu cables or flat bars (high terminal covers to order) Threaded rear terminals (low terminal covers included in supply) 7( ).5 2 mm Version with high terminal covers: front or rear output cables 7( ).5 2 mm 45 I O o off SAC (*) SAC (**) 25 (***) Template for drilling sheet metal support (minimum thickness of sheet metal: mm) D 4 POL POL D D ø20 ø8 75 G H 75 ( ) 75 with sealable screws Template for drilling compartment door and fitting flange (thickness of sheet metal:.5-2 mm) D D D I D M4 - Ø4,5 25 ø8 ø20 2 Holes for rear terminals only Holes for cables with rear outlet only Horizontal installation SACE RC20-RC2-RC E 5 64 ø4 F G R.5 Key Front terminals for cables and flat bars ~ Bracket for mounting on DIN EN channel Flange for compartment door Separator plate Note See the various different versions for the dimensions of the terminals GSIS000 A B C D E F G H I S - RC S - RC2/RC S2 - RC2/RC /4
163 Accessories Solenoid operator at the side of the circuit-breaker 24.5 A B E F Key Drilling for fixing the circuitbreaker and solenoid operator assembly onto sheet SACE S Plate for fixing circuitbreaker onto DIN EN rail (a richiesta) Separator plates between the phases C D 4 Spacer (for SACE S only) A POL B POL C 4 POL D 4 POL E F S ± ± 0.2 S ± 0. 6 ± 0.2 Solenoid operator on the front of the circuit-breaker B 50 A SACE S R GSIS0004 Key 2 S S2 Flange for compartment door Template for drilling compartment door and fitting flange Separator plates between the phases A POL B 4 POL 0 20 Interlock across two horizontally-installed circuit-breakers 20 (S2 S2) 7.5 (S S2) 5 (S S) SACE 2 25 S2 S2 4.5-M4 90 S S2 0 0 Key Interlock device 6 Note See the various different versions for the dimensions of the circuit-breakers S S 0 GSIS Template for drilling sheet metal support Tightening torque, Nm Remove the screws for stirruping the cover and replace them with the ones in the KIT. 6/5
164 Overall dimensions SACE S-S2 Accessories Compartment door-mounted rotary handle operating mechanism for fixed or plug-in circuit-breakers Fixed depth Adjustable depth (max 00 mm) (*) 8 20 (*) 47 2 max 68 A 68 min. 00 max (298*) Shaft lenght A+B max B 8 (20*) (*) If protection class IP54 required (*) If protection class IP54 required 5 2 A 298 B Adjustable depth (max 62,5 mm) 68 C 40 min max (69.5*) Shaft lenght C+B max ø B 8 (20*) R min (*) If protection class IP54 required C max 69.5 B GSIS ø5 ³ø 6.8 Key 2 Padlock device for open position (max padlocks with ø 6 to be provided by customer) Transmission assembly Rotary handle assembly Note See the various different versions for the circuitbreaker mounting holes Minimum radius of rotation for fulcrum of compartment door Circuit-breaker operating lever Drilling of compartment door Joint Shaft Support 6/6
165 Overall dimensions SACE S-S4-S5-S-S4 Fixed circuit-breaker Mounting on sheet metal Mounting on DIN EN 5002 channel Terminal covers (to order when not included in supply) 7 B A (4 POL) ( POL) Z V H D F C I O o off 6 G I O o off I O o off H 2 Low High 4 E E E Terminals Front for flat bars Front for cables 57 (S5 60) 5.8 (S5 400).8 ø5.5 (S5 400) ø20 (S5 60) 0 (S-S) 5 (S4-S5) (*) M8 (S/S-S4/S4) M0 (S5) L.2 ø2 (**) (**) high terminal covers included in the supply I 5 I 20 GSIS0007 (*) mm minimum admissible thickness for S5 400 For SACE S - S4 S S - S4 only x 240 mm 2 (S5 400) 2 x 20 mm 2 For SACE S S5 60 only Key 2 4 Flange for compartment door Bracket for mounting on DIN EN 5002 channel 45 mm front flange Tightening torque 2 Nm 6 A B C D E F G H I L V Z S Ø x S Ø x S Ø x S Ø S Ø x S Ø x /7
166 Overall dimensions SACE S-S4-S5-S-S4 Fixed circuit-breaker Terminals For rear Cu/Al cables Extended front 25.5 (S/S-S4/S4) 6.5 (S5) (**) L O (***) P I D N I I o O off (**) high terminal covers included in supply (***) Separator plates between the phases to order Extended front spreaded A B 0 G F E C C G F D D D E I 5 L H H I o I o O off O off POL 4 POL Threaded rear Q R 25 A (**) View A S U I 6 (**) low terminal covers included in supply T GSIS0008 D I L N O P Q R S T U A B C D E F G H I L S Ø 6 20 Ø M Ø S Ø 6 20 Ø M Ø S Ø 2 25 Ø M S M max... Ø 5 49 S Ø 6 20 Ø M Ø S Ø 6 20 Ø M Ø /8
167 Mounting parts for fixed circuit-breaker Template for drilling sheet metal support (minimum thickness of sheet metal: mm) For terminals: Front for flat bars Extended front Front for cables A B ( POL) (4 POL) For terminals for rear Cu/Al cables A B ( POL) (4 POL) E For threaded rear terminals A A M M A A A M5/ø5.5 D D F L D L D C C G N C N C A E M5/ø5.5 H E A B I ( POL) (4 POL) ( POL) M5/ø5.5 (4 POL) B For SACE S - S4 - S S - S4 only For threaded rear terminals Template for drilling compartment door and fitting flange (thickness of sheet metal: 2 mm) ø2 ø2 M5/ø ø7 ( POL) M5/ø5.5 (4 POL) For SACE S5 60 only GSIS A B C D E F G H I L M N S R Ø 24 4 S R Ø S R Ø 0 28 S R Ø S R Ø /9
168 Overall dimensions SACE S-S4-S5-S-S4 Plug-in circuit-breaker - withdrawable circuit-breaker Plug-in SACE S-S4-S5 400-S-S4 Witdrawable SACE S-S4-S5 400-S-S4 C D 7 B A I o O off (4 POL) ( POL) 2 T 5 6 G isolating travel 4 2 ø T G C D B A (4 POL) ( POL) 6 5 Key I M E E F 05 E 7,5 (S-S4) Fixed part 2 Moving part complete with IP20 protection class terminal covers Flange for compartment door (included in supply) 4 Lock for compartment door (to order) 5 Tightening torque, Nm (S-S4-S-S4) - 2 Nm (S5) Note The withdrawable circuit-breaker must be completed with one of the following accessories: front flange for operating lever mechanism rotary handle operating mechanism motor operator Terminals Front for flat bars (up to 400 A and S A) 2 P isolating travel 2 ø Front for cables (up to 400 A) Witdrawable SACE S Q R 5 5 C D E E E F B A A H 96 E E E F H 78,5 96 Threaded rear (4 POL) ( POL).25 6 G 270 L L L N S Front spreaded for SACE S5 60 Vertical flat bar rear terminals for SACE S , ø ,5 V View A U (S-S4-S-S4) 4 (S5 400) 54,5 (S5 60) , ø 59, (S-S4-S-S4) 84 (S5 400) 8 (S5 60) Z GSIS000 A B C D E F G H I L M N O P Q R S T U V Z S Ø x M2 00 S Ø x M2 00 S Ø x M6 08 S Ø x M24x2 4 S Ø M2 00 S Ø M2 00 6/0
169 Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker Template for drilling sheet metal support (minimum thickness of sheet metal: mm) SACE S-S4-S5 400-S-S4 SACE S5 60 For terminals: Front for flat bars Front for cables A ( POL) For terminals Threaded rear A B ( POL) (4 POL) For terminals: Vertical flat bar rear terminals Threaded rear 5 ( POL) 60 (4 POL) For terminals: Front Front for Cu cables Front spreaded 5 ( POL) 60 (4 POL) B (4 POL) F ø6 (M5) 52 ø6 (M5) 65 D D G C C H 5 5 F E E N I 52 R L M ( POL) (4 POL) 2,5 ( POL) 77,5 (4 POL) 44 ( POL) 88 (4 POL) Template for drilling compartment door and fitting flange (thickness of sheet metal: 2 mm) ø Nr. ø ø7 For plug in circuit-breaker ø R min. 200 For withdrawable circuit-breaker GSIS00 6 A B C D E F G H I L M N S - S M4-Ø R4 S4 - S M4-Ø R4 S M5-Ø R8 6/
170 Overall dimensions SACE S-S4-S5-S-S4 SACE S circuit-braker with SACE RC2/ - RC22/ residual current release Vertical installation (mounting on sheet metal) (*) Without terminal covers (**) with low terminal covers (***) with high terminal covers Front terminals for cables (terminal covers to order) Rear terminals (low terminal covers included in supply) ,5 6, ø 2 05 (*) (**) (***) ³ Version with extended front terminals Terminals for rear Cu/Al cables (high terminal covers included in supply) Key Tightening torque 2 Nm Flange for compartment door Note See the various different versions for the dimensions of the terminals ø Template for drilling sheet metal support (minimum thickness of sheet metal: mm) Template for drilling compartment door and fitting flange (thickness of sheet metal:.5-2 mm) 70 ± ± R Holes for threaded Holes for rear rear terminals only terminals for cables only 64 ± ± ø ø5.5 - M5 ø ± GSIS002 6/2
171 TEST SACE S circuit-braker with SACE RC2/ - RC22/ residual current release Horizontal installation SACE S I o 45 O off GSIS00 Key 2 Front terminals for cables Bracket for mounting on DIN EN 5002 channel 6 6/
172 Overall dimensions SACE S-S4-S5-S-S4 Accessories Motor operator for fixed circuit-breaker A B C (4 POL) ( POL) Key 2 Flange for compartment door (included in supply) Dimensions with connectors Drilling of compartment door Note See the various different versions for the circuit-breaker mounting holes A B C ø7 S-S4 S-S4 S Motor operator for plug in circuit-breakers Key isolating travel A B C (4 POL) ( POL) Flange for compartment door (included in supply) Dimensions with connectors Drilling of compartment door Note See the various different versions for the circuit-breaker mounting holes ø S-S4 S-S4 S5 A B C Motor operator for withdrawable circuit-breaker Key isolating travel A B 96 (4 POL) ( POL) C ø7 5 6 Nr. ø8 2 Flange for compartment door (included in supply) Drilling of compartment door Note See the various different versions for the circuit-breaker mounting holes ø ø7 25 R min. 200 GSIS004 S-S4 S-S4 A 40 B 05 C 58 S /4
173 Accessories Interlock across two horizontally-installed circuit-breakers (S5) A B B B C B B B E F D 05 G H 5 (S-S4) I L M P N N O 2 R Q R ø7 Key Interlock device Template for drilling 2 mounting holes in sheet metal Drilling template for all versions with rear terminals 4 5 Dimensions with four-pole withdrawable version mounted on right Tightening torque,7 Nm Note See the various different versions for the dimensions of the circuitbreakers A B C D E F G H I L M N O P Q R S R S4 S5 S S R5 R5 R5 R *, 5** 4*, 22.5** * Per interruttore estraibile con terminals posteriori ** Per interruttore fisso con terminals posteriori (uscita posteriore) Interlock across two vertically-installed circuit-breakers (S-S4-S5) A H N 2 Q 5 M P F 05 G N C M E O I Key Interlock device Drilling template for 2 mounting circuit-breakers on sheet metal Drilling template for all versions with rear terminals 4 Dimensions with four-pole withdrawable version 05 D F G M N 5 Tightening torque,7 Nm 6 isolating travel B B B.5 4 M R P Nr. 8 ø7 GSIS005 Note See the various different versions for the dimensions of the circuitbreakers A B C D E F G H I L M N O P Q R S R5 S R5 S R5 6/5
174 Overall dimensions SACE S-S4-S5-S-S4 Accessories Rotary handle operating mechanism on fixed or plug in circuit-breaker A Note See the various different versions for the circuit-breaker mounting holes ø7 ø R min S-S4 S-S4 S-S4 S-S4 S5 S5 Compartment door-mounted rotary handle operating mechanism with adjustable depth for fixed or plug in circuit-breaker 7 9 Key Rotary handle operating mechanism Lock for compartment door (to order) Drilling of compartment door Dimensions for connector for early contact for undervoltage release Flange for compartment door (included in supply) III IV III IV A R min 200 Note See the various different versions for the circuit-breaker mounting holes R min GSIS006 Key Transmission assembly 2 Rotary handle assembly with door lock device Padlock device for open position (maximum padlocks with max ø6mm to be provided by customer) 4 Minimum radius of rotation for fulcrum of door 5 Drilling of door 6 Support for depths of up to 500 mm mm (with IP54 protection min. 90) 8 Distance mm (shaft length) mm (with IP54 protection min.25) 0 Distance mm (Shaft length) 6/6
175 Accessories Rotary handle operating mechanism on withdrawable circuit-breaker ø Nr. 5 ø R min. 200 Key 2 Rotary handle operating mechanism Lock for compartment door (to order) Padlock device for open position (maximum padlocks max. ø 6 mm to be provided by user) Note See the various different versions for the circuitbreaker mounting holes Front flange for operating lever mechanism ø4 80 Key Front flange for lever operating mechanism ø Lock for compartment door (to order) Drilling of compartment door Flange for compartment door (included in supply) Note See the various different versions for the circuitbreaker mounting holes External neutral for SACE S4-S5 circuit-breakers In 5 6 Line Load GSIS007 6/7
176 Overall dimensions SACE S6 - S6 Fixed circuit-breaker (S6) (4 POL) ( POL) 2 ³ Terminal covers (to order when not included in the supply) low high Mounting on sheet metal Key Flange for compartment door (included in supply) Terminals 2 Tightening torque 2 Nm Front extended Front ø ø ± min. S6 60 S S ø Threaded rear (low terminal covers included in supply) M24x2 S6 800 S S6 800 Front extended spreaded ø Front for Cu/Al cables (IP20 high terminal covers included in the supply for S6 800) ø For rear Cu/Al cables (IP20 high terminal covers included in the supply) 9.5 ø2 2 6 S S6 800 S ø S6 60 ø7.5 2 S6 800 S6 800 GSIS008 6/8
177 Fixed circuit-breaker (S6) (4 POL) ( POL) Terminal covers (to order when not included in the supply) low high Key 52 Mounting on sheet metal Flange for compartment door (included in supply) Tightening torque 2 Nm Terminals Extended front Front for Cu/Al cables ø ø For rear Cu/Al cables (IP54 high terminal covers included in the supply) Front ø ± min. 9.5 ø Threaded rear (low terminal covers included in supply) M24x2 2 GSIS009 6/9
178 Overall dimensions SACE S6 - S6 Mounting parts for fixed circuit-breaker (S6) Template for drilling sheet metal support (minimum thickness of sheet metal: mm) For terminals: Front for flat bars Front extended Front for cables ( POL) (4 POL) For terminals for rear Cu/Al cables SACE S6 60 SACE S ( POL) (4 POL) ( POL) (4 POL) M5/ø5.5 M5/ø5.5 M5/ø5.5 R8 R ( POL) (4 POL) ( POL) (4 POL) For terminals threaded rear POL 4 POL Template for drilling compartment door and fitting flange (thickness of sheet metal: 2 mm) M5/ø5.5 ø5 M5/ø5.5 ø5 6 ø7 GSIS002 6/20
179 Mounting parts for fixed circuit-breaker (S6) Template for drilling sheet metal support (minimum thickness of sheet metal: mm) For terminals: Front for flat bars Front extended Front for cables ( POL) (4 POL) For terminals for rear Cu/Al cables 70 ( POL) 40 (4 POL) M5/ø M5/ø5.5 R ( POL) (4 POL) For terminals threaded rear Template for drilling compartment door and fitting flange POL 4 POL (thickness of sheet metal: 2 mm) M5/ø ø M5/ø ø5 79 ø GSIS /2
180 Overall dimensions SACE S6 - S6 Withdrawable circuit-breaker Key 27.5 isolating travel (4 POL) ( POL) 2 Fixed part Moving part Flange for compartment door (included in supply) 40 ø A Lock for compartment door (to order) Tightening torque 9 Nm 52 A S6 S Terminals Front for SACE S6 60, S ø Horizontal or vertical rear flat bar for SACE S6 60, S ø GSIS0022 6/22
181 Mounting parts for withdrawable circuit-breaker Template for drilling sheet metal support (minimum thickness of sheet metal: mm) ( POL) (4 POL (4 POL) 77.5 R ø8.5 (M8) (4 POL) ( POL) (4 POL) Template for drilling compartment door and fitting flange (thickness of sheet metal: 2 mm) ø4 80 ø Nr. 5 ø ø R min 200 GSIS /2
182 Overall dimensions SACE S6 - S6 Accessories Interlock across two horizontally-installed circuit-breakers R0 0 A Key Interlock device Drilling template for 2 mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals ø Dimensions with withdrawable version mounted on right Tightening torque 9 Nm Note See the various different versions for the dimensions of the circuit-breakers isolating travel 27.5 A mm Interlock across two vertically-installed circuit-breakers (for S6 only) S6 S6 29 (fixed, withdrawable) 267 (fixed) 29 (withdrawable) Key Interlock device R20 ø Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals Dimensions with withdrawable version mounted underneath Tightening torque 9 Nm isolating travel 09 GSIS0024 Note See the various different versions for the dimensions of the circuitbreakers 6/24
183 Accessories Motor operator for fixed circuit-breaker ± ± ø8 (7 fori) R ±0. R. min.200 Key 2 Note See the various different versions for the circuit-breaker mounting holes 2 Flange for compartment door (included in supply) Template for drilling compartment door Dimensions with connectors Motor operator for withdrawable circuit-breakers 27.5 isolating travel ± ± ø8 (7 fori) A 04 B R ±0. R. min GSIS Key S6 S6 A B Note See the various different versions for the circuit-breaker mounting holes 2 Flange for compartment door (included in supply) Template for drilling compartment door 6/25
184 Overall dimensions SACE S6 - S6 Accessories Rotary handle operating mechanism on fixed circuit-breaker ø4 80 Key Rotary handle operating mechanism on circuitbreaker Lock for compartment door (to order) ø R min Drilling of compartment door Flange for compartment door (included in supply) Tightening torque 2 Nm POL 27 (S6) 75 (S6) Drilling only required for version with rear terminals (S6) 244 (S6) 4 POL 27 (S6) 75 (S6) (S6) 79 (S6) (S6) 244 (S6) 24 (S6) 79 (S6) Note See the various different versions for the circuit-breaker mounting holes M5/ø5.5 ø5 M5/ø5.5 ø5 6 Compartment door-mounted rotary handle mechanism with adjustable depth for fixed circuit-breaker POL 27 (S6) 75 (S6) M5/ø R min 200 ø Drilling only required for version with rear terminals 06 (S6) 244 (S6) 4 POL 27 (S6) 75 (S6) (S6) 79 (S6) M5/ø ø5 06 (S6) 244 (S6) R min (S6) 79 (S6) 46 GSIS0026 Key Transmission assembly Rotary handle assembly with door lock device Padlock device (maximum padlocks max ø 6 mm to be provided by customer only for circuit-breaker open position) Minimum radius of rotation for fulcrum of door Drilling template for mounting circuit-breaker on sheet metal mm (with IP54 protection min. 96) 7 Distance 6-4 mm (shaft length) Note See the various different versions for the circuit-breaker mounting holes 6/26
185 Accessories Rotary handle operating mechanism on withdrawable circuit-breaker Key ø R min 200 Nr. 5 ø Rotary handle on circuit-breaker Lock for compartment door (to order) Padlock device for open position (maximum padlocks max. ø 6 mm to be provided by user) Note See the various different versions for the circuit-breaker mounting holes Front flange for operating lever mechanism ø7 ø Key Front flange for operating lever mechanism Lock for compartment door (to order) Drilling of compartment door Flange for compartment door (included in supply) Tightening torque 2 Nm 42.5 POL 27 (S6) 75 (S6) 04 8 M5/ø (S6) 244 (S6) ø5 24 (S6) 79 (S6) Drilling only required for version with rear terminals External neutral Note See the various different versions for the circuit-breaker mounting holes POL (S6) 75 (S6) 04 8 M5/ø (S6) 244 (S6) ø5 24 (S6) 79 (S6) Line In 00 A 60 A 200 A 250 A 20 A 400 A Load GSIS0027 6/27
186 Overall dimensions SACE S7 Fixed circuit-breaker (4 POL) ( POL) Terminal covers low Key 7 Terminals Flange for compartment door (included in supply) Tightening torque 2 Nm Front ø Front extended ø Front for Cu/Al cables for S ø Horizontal or vertical flat bar rear terminals Front extended spreaded ø A 07 B ø 4 22 GSIS0028 A horizontal installation B vertical installation 6/28
187 Mounting parts for fixed circuit-breaker Template for drilling sheet metal support (Minimum thickness of sheet metal: mm) For terminals: Front Front extended Front for Cu/Al cables ( POL) (4 POL) For flat bar rear terminals POL 4 POL 220 ø.6 H2 290 ø.6 H R R M5/ø5.5 5 ø5.5 - M5 ø5.5 - M5 5 Template for drilling compartment door and fitting flange (thickness of sheet metal: 2 mm) ø7 GSIS /29
188 Overall dimensions SACE S7 Withdrawable circuit-breaker Key (4 POL) ( POL) 2 Fixed part Moving part max Flange for compartment door (included in supply) Lock for compartment door (to order) Tightening torque 9 Nm 5 ø isolating travel Terminals Front 6 ø Horizontal or vertical flat bar rear terminals 08 ø GSIS000 6/0
189 Mounting parts for withdrawable circuit-breaker Template for drilling sheet metal support or channel (Minimum thickness of sheet metal: mm) ( POL) (4 POL) ø8.5 (M8) ( POL) (4 POL) Template for drilling compartment door and fitting flange (thickness of sheet metal: 2 mm) ø4 80 ø Nr. 5 ø ø R min 200 GSIS00 6 6/
190 Overall dimensions SACE S7 Accessories Interlock across two horizontally-installed circuit-breakers R Key Interlock device 2 Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals ø Dimensions with withdrawable version mounted on right Tightening torque 9 Nm isolating travel 27.5 Note See the various different versions for the dimensions of the circuitbreakers Interlock across two vertically-installed circuit-breakers Key 7 2 Interlock device Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals Tightening torque 9 Nm R ø isolating travel GSIS002 Note See the various different versions for the dimensions of the circuitbreakers 6/2
191 Accessories Motor operator for fixed circuit-breaker Nr. 7 ø8 8.25± ± R ±0. R. min Note See the various different versions for the circuit-breaker mounting holes Key 2 Flange for compartment door (included in supply) Template for drilling compartment door Dimensions with connectors Motor operator for withdrawable circuit-breaker 27.5 isolating travel Nr. 7 ø8 8.25± ± R ±0. R. min GSIS00 6 Key Note See the various different versions for the circuit-breaker mounting holes 2 Flange for compartment door (included in supply) Template for drilling compartment door 6/
192 Overall dimensions SACE S7 Accessories Rotary handle operating mechanism on fixed circuit-breaker ø7 ø R min Key Rotary handle operating mechanism on circuitbreaker 2 Lock for compartment door (to order) Drilling of compartment door Drilling template for 4 mounting circuit-breaker on sheet metal 5 Flange for compartment door (included in supply) Drilling only required for version with rear terminals 6 Tightening torque 2 Nm POL 4 POL ø5.5- M ø5.5- M5 Note See the various different versions for the dimensions of the circuitbreakers R 40 R 40 Compartment door-mounted rotary handle operating mechanism for fixed circuit-breaker R min 200 Drilling only required for version with rear terminals POL 6 4 POL R ø5.5- M5 ø.6 H R ø5.5- M R min 200 ø.6 H GSIS004 Key Transmission assembly 2 Rotary handle assembly with door lock device Padlock device (maximum padlocks max ø 6 mm to be provided by customer only for circuit-breaker open position) 4 Minimum radius of rotation for fulcrum of door 5 Template for drilling compartment door 6 Drilling template for mounting circuit-breaker on sheet metal mm (with IP54 protection min. 96) 8 Distance 7-4 mm (shaft lenght) Note See the various different versions for the dimensions of the circuitbreakers 6/4
193 Accessories Rotary handle operating mechanism on withdrawable circuit-breaker Front flange for operating lever mechanism , ø R min 200 Nr. 7 ø7 77 Key 2 Rotary handle operating mechanism on circuitbreaker Lock for compartment door (to order) Padlock device for open position (maximum padlocks max. ø 6 mm to be provided by user) Note See the various different versions for the circuit-breaker mounting holes ø7 ø Key Front flange for lever operating mechanism Lock for compartment door (to order) Drilling of compartment door Drilling template for mounting circuit-breaker on sheet metal Flange for compartment door (included in supply) 6 Tightening torque 2 Nm POL R 40 4 POL ø5.5- M5 Drilling only required for version with rear terminals External neutral Note See the various different versions for the circuit-breaker mounting holes R ø5.5- M Line In 00 A 60 A 200 A 250 A 20 A 400 A Load GSIS005 6/5
194 Overall dimensions SACE S8 Fixed circuit-breaker ø , ,5 Terminals POL 4 POL Front (S ) Rear (S ) Ø Ø Rear (S8 200) , Ø8 Ø Ø5 20 Key 2 Flange for compartment door Circuit-breaker mounting holes 5 5 GSIS006 Internal side of compartment door 6/6
195 Mounting parts for fixed circuit-breaker Template for drilling sheet metal support (Minimum thickness of sheet metal: mm) Template for drilling compartment door and fitting flange (Minimum thickness of sheet metal: < 2,5mm) N. 8 Ø 9 N. 8 Ø 9 POL 4 POL Key Hole for rear terminals only 2 Minimum radius of rotation of compartment door Accessories External neutral 6 6/7
196 Overall dimensions Distances to be respected Insulation distances for installation in metal compartment with wall to chassis ground or wall to chassis ground protected with insulating plate Wall to chassis ground [mm] B A (U b 45V) A(*) (U b 440V) B C S S A S S S S I o S O off S (*) these distances are valid for operating voltages of > 440 V and for circuit-breakers with breaking capacity level L. A B C D E POL POL F C GSIS008 S S S4 S B E B F A - B - C Distances inside compartment walls D - E - F Distances outside compartment A Insulation distances for installation in insulated compartment Insulated wall [mm] A B C D 6 S S I O o off S S4 S C GSIS007 S6 S7 S The dimensions shown apply for operating voltages Ub of up to 690 V. The dimensions to be respected must be added to the maximum dimensions of the various different versions of the circuit-breakers, including the terminals. 6/8
197 Minimum distance between centres for two horizontally or vertically-installed circuit-breakers For horizontal or vertical installation, make sure that the connection busbars or cables don t reduce the air insulation distan ces. Minimum distance between centres for horizontallyinstalled circuit-breakers Circuit-breaker width [mm] POL 4 POL POL I [mm] 4 POL S /9 (*) 0/8 (*) S2 S /05 (*) 05/9 (*) 20/5 (*) 40 on off on off S /9 (*) 40 S5 S l S S (*) these are the distances to be respected for circuit-breakers fitted with a flange for the compartment door or side conductor outlets. The distances between centres are for the installation of fixed and plug in circuit-breakers. When installing withdrawable SACE S, S4, S5, S6, S7 circuit-breakers you should also take into account the dimensions of the metal supporting channel that needs to be fitted between the guides of the fixed parts of two adjacent circuit-breakers. Minimum distance between centres for verticallyinstalled circuit-breakers H [mm] S 60 S2 S S H H 2 H 6 S5 40 S6 S GSIS0040 S8 00 Connection not insulated 2 Insulated cable Cable terminals 6/9
198 6/40
199 Circuit-diagrams Index Operating status shown... 6/42 Duty releases... 6/44 Auxiliary contacts... 6/46 Position contacts... 6/48 Auxiliary circuits of electronic releases... 6/50 Motor operators... 6/5 Graphic symbols for circuit-diagrams (IEC 67 and CEI -4-26)... 6/54 Key and reference notes... 6/55 6 6/4
200 Circuit diagrams Operating status shown The circuit is shown in the following conditions: - fixed, plug in or withdrawable circuit-breaker (depending on type of circuit-breaker), open and racked in - circuits de-energised - releases not tripped - motor operator with springs loaded (for S6-S7 circuit-breakers) The circuit-breaker is only fitted with those accessories specified in the confirmation of order. Consult this catalogue for information on how to make out an order. SACE S-S2-S-S5-S6 Three-pole or four-pole circuit-breaker with thermomagnetic release SACE SD-S6D-S7D-S8D Three-pole or four-pole switch-disconnector GSIS0045 GSIS0046 SACE S-S2-S Four-pole fixed circuit-breaker with vertically-installed residual-current release SACE RC2 o RC22 Four-pole fixed circuit-breaker with horizontally-installed residual-current release SACE RC20, RC2 o RC22 6 RC2 RC22 GSIS0047 RC20 RC2 RC22 GSIS0048 6/42
201 SACE S4-S5-S6-S7 Three-pole or four-pole circuit-breaker with SACE PR2/P microprocessor-based release Three-pole or four-pole circuit-breaker with SACE PR22/P microprocessor-based release Three-pole circuit-breaker with SACE PR22/MP microprocessor-based release GSIS0049 GSIS0050 GSIS005 SACE S4-S5-S6-S7 Three-pole fixed circuit-breaker with current transformer on neutral conductor outside circuit-breaker Three-pole plug-in or withdrawable circuit-breaker with current transformer on neutral conductor outside circuit-breaker Circuit of current transformer on neutral conductor outside circuitbreaker (for withdrawable circuit-breaker) External circuit Term.5 GSIS0052 Internal circuit 6 N.B. If using a fixed circuit-breaker with a current transformer on the neutral conductor outside the circuitbreaker, you must short-circuit the terminals of the TI/N transformer when you want to remove the circuitbreaker. Term.5 External circuit GSIS005 6/4
202 Circuit diagrams Duty releases SACE S-S2 Opening release Opening solenoid of SACE RC2 residualcurrent release Opening solenoid of SACE RC22 residual-current release Instantaneous undervoltage release GSIS0054 SACE S 6 GSIS0055 External circuit Internal circuit External circuit Conn. Conn. Opening release Opening solenoid of SACE RC2 residualcurrent release Opening solenoid of SACE RC22 residual-current release Instantaneous undervoltage release Version of instantaneous undervoltage release for machine tools Undervoltage release with electronic time-lag device outside the circuit-breaker External circuit Internal circuit External circuit Term. V Term. V 6/44
203 SACE S4-S5 Opening release Instantaneous undervoltage release Version of instantaneous undervoltage release for machine tools Undervoltage release with electronic time-lag device outside the circuit-breaker Incompatibility The circuits indicated in the following figures cannot be powered simultaneously on the same circuit-breaker External circuit Availability Connectors and 2 are only supplied to order for circuit-breakers S - S2. Conn. Term. V Internal circuit Term. V Conn. External circuit GSIS0056 Notes (*A) The undervoltage release is powered from upstream of the circuit-breaker or by an independent power supply: closing of the circuit-breaker is only allowed when the release is energised (the closing lock is implemented mechanically). (*B) Contact S4 shown in Fig. 5 opens the circuit when the circuitbreaker is open and closes it again upon a manual closing command from the rotary handle, in conformity with the Standards governing machine tools (the circuitbreaker will not close, however, if the undervoltage release is not powered). SACE S6-S7 Opening release Instantaneous undervoltage release Undervoltage release with electronic time-lag device outside the circuit-breaker Term. V 6 External circuit GSIS0057 Internal circuit External circuit Conn. Term. V Conn. 6/45
204 Circuit diagrams Auxiliary contacts SACE S-S2 Two change-over contacts for electrical signalling of circuitbreaker open/closed One change-over contact for electrical signalling of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to tripping of thermomagnetic releases O, O, U (tripped position) Internal circuit External circuit Conn. 2 Conn. 2 6 External circuit SACE S-S4-S5-S6-S7 External circuit Conn. 2 Term. V Internal circuit Term. V Conn. 2 External circuit Two change-over contacts for electrical signalling of circuitbreaker open/closed One change-over contact for electrical signalling of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to tripping of thermomagnetic releases O, O, U (tripped position) GSIS0059 GSIS0058 6/46
205 SACE S6-S7 External circuit Conn. 2 Term. V Internal circuit One contact for electrical signalling of circuit-breaker open, one change-over contact for electrical signalling of circuit-breaker closed and one contact for electrical signalling of circuit-breaker not open due to tripping of thermomagnetic releases O, O, U (not tripped/tripped position) to be used, for example, for the enabling shown in Fig.8 Incompatibility The circuits indicated in the following figures cannot be powered simultaneously on the same circuit-breaker: Availability Connectors and 2 are only supplied to order for circuit-breakers S - S2. Notes (*C) The electrical signalling contact for the microprocessor-based overcurrent release, shown in Fig. 4, has the following electrical characteristics: rated voltage 25V AC / 0V DC breaking capacity (resistive load W/VA) maximum interrupted current 0.5 A Term. V Conn. 2 GSIS0080 SACE S4-S5-S6-S7 Contact for signalling release 0 tripped 6 GSIS0060 External circuit Term. 6 Term. 5 External circuit Internal circuit External circuit Term. 5 Term. 6 6/47
206 Circuit diagrams Position contacts SACE S2 First circuitbreaker position contact, for electrical signalling of inserted Second circuitbreaker position contact, for electrical signalling of inserted Third circuitbreaker position contact, for electrical signalling of inserted Term. V GSIS006 SACE S First circuitbreaker position contact, for electrical signalling of inserted Second circuitbreaker position contact, for electrical signalling of inserted First circuit-breaker position contact, for electrical signalling of racked out or removed 6 GSIS0062 External circuit Internal circuit External circuit Term. V Term. V External circuit Internal circuit External circuit Term. V 6/48
207 SACE S4-S5 First circuitbreaker position contact, for electrical signalling of inserted Second circuitbreaker position contact, for electrical signalling of inserted Third circuitbreaker position contact, for electrical signalling of inserted First circuit-breaker position contact, for electrical signalling of racked out or removed Second circuitbreaker position contact, for electrical signalling of racked out or removed Third circuit-breaker position contact, for electrical signalling of racked out or removed Term. V GSIS006 Internal circuit External circuit Term. V External circuit SACE S6-S7 Term. V Internal circuit First circuit-breaker position contact, for electrical signalling of inserted Second circuit-breaker position contact, for electrical signalling of inserted Third circuit-breaker position contact, for electrical signalling of inserted Fourth circuit-breaker position contact, for electrical signalling of inserted Fifth circuit-breaker position contact, for electrical signalling of inserted First circuit-breaker position contact, for electrical signalling of racked out Second circuit-breaker position contact, for electrical signalling of racked out Third circuit-breaker position contact, for electrical signalling of racked out Fourth circuit-breaker position contact, for electrical signalling of racked out Fifth circuit-breaker position contact, for electrical signalling of racked out Incompatibility The circuits indicated in the following figures cannot be powered simultaneously on the same circuitbreaker: Notes (*D) The circuitbreaker can be fitted with position contacts S75I and S75S in any combination up to a maximum of total of 2 contacts for S total of contacts for S4, S5 total of 5 contacts for S6, S7 6 Term. V GSIS0064 6/49
208 Circuit diagrams Auxiliary circuits of SACE PR22/P electronic releases SACE S4-S5-S6-S7 SACE PR22/P release connected to the dialogue unit SACE PR22/D and actuator unit SACE PR22/T GSIS06 SACE S4-S5-S6-S7 SACE PR22/P release connected to the dialogue unit SACE PR22/D, signalling unit SACE PR00/K and actuator unit SACE PR22/T 6 GSIS062 6/50
209 Circuit diagrams Auxiliary circuits of SACE PR22/MP electronic releases for motor protection SACE S4-S5-S6-S7 SACE PR22/MP release connected to the dialogue unit SACE PR22/D-L and actuator unit SACE PR22/T SACE S4-S5-S6-S7 SACE PR22/MP release connected to the dialogue unit SACE PR22/D-L, actuator unit SACE PR22/T and contactor operator unit SACE PR22/CI GSIS06 GSIS /5
210 Circuit diagrams Auxiliary circuits of SACE PR22/MP electronic releases for motor protection SACE S4-S5-S6-S7 SACE PR22/MP release connected to the signalling unit SACE PR00/K and contactor operator unit SACE PR22/CI GSSC08 SACE S4-S5-S6-S7 6 GSSC09 GSIS066 GSIS065 SACE PR22/MP release connected to the dialogue unit SACE PR22/D-L, actuator unit SACE PR22/T, signalling unit SACE PR00/K and contactor operator unit SACE PR22/CI 6/52
211 SACE S4-S5-S6-S7 SACE PR22/MP release connected to the dialogue unit SACE PR22/D-L and actuator unit SACE PR22/T GSIS /5
212 Circuit diagrams Motor operators SACE S-S2 Solenoid operator SACE S-S4-S5 Direct action motor operator Conn. 2 Term. V Conn. 2 GSIS008 GSIS0065 SACE S6-S7 Stored-energy motor operator 6 GSIS0066 External circuit Internal circuit Term. V Term. V Internal circuit External circuit Conn. 2 Term. V Conn. 2 External circuit External circuit Conn. 2 External circuit Internal circuit External circuit Conn. 2 6/54
213 Circuit diagrams Graphic symbols for circuit diagrams (Standards IEC 67 and CEI ) Thermal effect Terminal or clamp Make contact with held position Electromagnetic effect Socket (female) or pole of a socket Make position contact (limit contact) Time delay Socket and plug (female and male) Opening position contact (limit contact) Mechanical connection Temperature dependent resistor Change-over position contact with temporary interruption (limit contact) Manual mechanical control (general case) Resistor (general symbol) Switch-disconnector Pushbutton actuator Induction motor, threephase, squirrel cage Contactor (closing contact) Key control Motor (general symbol) Circuit-breaker with automatic release Cam control Brush Control coil (general symbol) Earth (general symbol) Motor energised in series Instantaneous overcurrent relay Equipotentiality Current transformer with primary formed by 4 through conductors and wound secondary, with socket Overcurrent relay with adjustable short time-delay trip Galvanically separated converter Current transformer Overcurrent relay with short inverse time-delay trip Shielded cable conductors (example: two conductors) Make contact Overcurrent relay with inverse long time delay 6 Conductors or stranded cables (example: two conductors) Break contact Earth fault overcurrent relay with inverse short time-delay trip Connection of conductors Change-over contact with temporary interruption Residual current relay 6/55
214 Circuit diagrams Key and notes 6 Figure number of diagram * See the note indicated by the letter A Applications of the circuit-breaker A2 Applications of the motor operators A4 Example switchgear and connections for control and signalling, outside the circuit-breaker A PR22/D-L dialogue unit, for connection to a centralised control system A2 PR22/T actuator unit, with auxiliary relays for executing commands from the dialogue unit A2/KC Actuator unit closing control A2/KO Actuator unit opening control A PR00/K signalling unit with auxiliary relays for electrical signalling of the protection functions of the microprocessor-based overcurrent release A4 Interface unit with SACE PR22/CI operator unit D Electronic time-lag device of undervoltage release (outside the circuit-breaker) K5 PR2, PR22/P or PR22/MP microprocessor-based overcurrent release with the following protection functions: - L overload protection with inverse long time-delay trip - S short-circuit protection with inverse or definite short time-delay trip (only available with PR22/P release) - I short-circuit protection with instantaneous trip - G earth fault protection with inverse short time-delay trip (only available with PR22/P release) K5/ Electrical signalling of alarm for internal communication fault K5/ Electrical signalling of alarm for protection function G in tripping zone K5/ Electrical signalling of alarm for protection function I in tripping zone K5/ Electrical signalling of alarm for protection function L in tripping zone K5/ Electrical signalling for protection function L in pre-alarm zone K5/ Electrical signalling of alarm for protection function S in tripping zone K5/ Electrical signalling of alarm for release O tripped due to overcurrent or trip test (Fig. 4) K87 RC2-RC22 residual-current release (for circuitbreakers S-S2-S) or RC20 (for circuit-breaker S) KO For S - S4 - S5: auxiliary opening relay. For S6 - S7: opening and spring-loading relay with heldposition make contact, released by a cam of the motor operator when the circuit-breaker reaches its open position and the closing springs have been loaded M For S - S4 - S5: motor with energising in series for opening and closing of the circuit-breaker. For S6 - S7: motor for opening the circuit-breaker and loading the closing springs of the circuit-breaker M Three-phase asinchronous motor Q Main switch Q/ Auxiliary contacts of the circuit-breaker R S S2 S S4 S75I/...5 Resistor outside the circuit-breaker, supplied for motor power supply voltages of more than 220 V For S - S4 - S5: position contact operated by a circuitbreaker cam For S6 - S7: contact controlled by the motor operator cam: closes when the circuit-breaker reaches its closed position and opens when the circuitbreaker reaches its open position (doesn t switch when the circuit-breaker goes into its tripped position) For S - S4 - S5: safety contact operated by: - key lock (if fitted) - padlock device - manual control selector. For S6 - S7: contact controlled by the motor operator cam: opens when the circuit-breaker reaches its closed position and closes when the circuit-breaker reaches its open position (doesn t switch when the circuit-breaker goes into its tripped position).the contact is also operated by the key lock device (if present) Contact controlled by the motor operator cam: opens after contact KO has closed and closes when the circuit-breaker reaches its open position (doesn t switch when the circuit-breaker goes into its tripped position) Contact operated by the circuit-breaker rotary handle Contacts for electrical signalling of circuit-breaker in inserted position (only for plug in or withdrawable circuit-breakers) S75S/...5 Contacts for electrical signalling of circuit-breaker in SC SO removed or racked-out position (only for plug in or withdrawable circuit-breakers) Pushbutton or contact for closing the circuit-breaker or for motor start. For circuit-breakers S - S4 - S5, the operating mechanism must have a time of not less than 00ms Pushbutton or contact for opening the circuit-breaker or for motor stop SO, S02 Pushbuttons or contacts for opening the circuit-breaker. For circuit-breakers S - S4 - S5, the operating mechanism must have a time of not less than 00 ms (see Instructions for resetting the circuit-breaker after the releases have tripped ) S Contact for electrical signalling of circuit-breaker open due to tripping of thermomagnetic releases, O, O, U (tripped position) TI Toroidal current transformer TI/L Current transformer located on phase L TI/L2 Current transformer located on phase L2 TI/L Current transformer located on phase L TI/N Current transformer located on neutral 6/56
215 Circuit diagrams Graphic symbols for circuit diagrams (Standards IEC 67 and CEI ) W Serial interface with monitoring system (EIA RS485 interface), 2 Connectors for the auxiliary circuits of the circuit-breaker. For circuit-breakers S - S2 supplied to order only., 4 Connectors for the circuits of the microprocessor-based overcurrent release (with plug in or withdrawable circuit-breakers, the connectors are pulled out at the same time as the circuit-breaker) 5, 6 Terminal delivery block for microprocessor-based overcurrent release circuits O Connector for the opening solenoid O V Terminal blocks for accessories C Closing release O Opening release O Opening solenoid of the RC2 or RC22 residual current release (for S - S2 - S) and of the overcurrent release (for S4... S8) U Undervoltage release ) Electrical resetting always enabled The electrical opening control (contact SO2) is connected in series directly to relay KO for S - S4 - S5 or connected directly to pole A of connector 2 (for S6 - S7) and is therefore always enabled. Example of use: automatic resetting of the circuit-breaker immediately after the releases have been tripped N.B. If an overcurrent release is fitted, it will be necessary to identify the causes that brought it to its tripped position in order to prevent it from closing again in short-circuit conditions. Manual resetting is always allowed in each of these examples. Instructions for resetting the circuit-breaker after the releases have tripped The circuit-breaker can open both through the action of the motor operator and due to the following releases tripping: overcurrent undervoltage opening with consequent opening of contact S (if fitted) in series with relay KO. A reset operation involving manual or electric opening will have to be carried out in order to close the circuit-breaker again after tripping. Contact S closes again at the end of the operation. The type of resetting should be chosen to suit the design requirements and duty conditions. A number of possible solutions are suggested below: External circuit Conn. Term.V Internal circuit ) Manual resetting only The electrical opening control (contact SO) must be connected in series with contact S. Opening (for S - S4 - S5 using the auxiliary relay KO) is therefore prevented until the circuit-breaker is in its tripped position. To reset the circuit-breaker one needs to operate the related lever until the circuit-breaker is in its open position and the closing springs are fully loaded. 2) Electrical resetting, responsibility of the operator The normal electric opening control (contact SO) must be connected in series with contact S. Another opening control is provided (contact SO2), connected in series directly to relay KO for S - S4 - S5 or connected directly to pole A of connector 2 for S6 - S7. This control must be protected by, for example, a pushbutton keyswitch. It should only be used if the information relayed to the control station manager allows one to rule out the possibility of the tripping having been caused by a short circuit, or if the causes of the short circuit have been removed. Term.V Conn. External circuit GSIS /57
216 6/58
217 Order codes Index General information... 7/2 Circuit-breakers for power distribution SACE Isomax S... 7/ SACE Isomax S2... 7/6 SACE Isomax S... 7/ SACE Isomax S4... 7/26 SACE Isomax S5... 7/2 SACE Isomax S6... 7/4 SACE Isomax S7... 7/47 SACE Isomax S8... 7/5 Current-limiting circuit-breakers SACE Isomax S /52 SACE Isomax S... 7/5 SACE Isomax S4... 7/56 SACE Isomax S6... 7/58 Circuit-breakers for motor protection SACE Isomax S /60 SACE Isomax S... 7/6 SACE Isomax S4... 7/62 SACE Isomax S5... 7/6 SACE Isomax S6... 7/6 SACE Isomax S7... 7/6 SACE Isomax S-S4-S6... 7/64 Circuit-breakers for applications up to 000 V... 7/65 Switch-disconnectors SACE Isomax S2D... 7/67 SACE Isomax SD... 7/68 SACE Isomax S6D... 7/70 SACE Isomax S7D... 7/7 SACE Isomax S8D... 7/72 Accessories... 7/7 7 7/
218 Order codes General information Interpretation of abbreviations used for article description F Front terminals FC Cu Front terminals for copper cables RC Rear terminals for cables EF Extended front terminals FC CuAl Front terminals for copper / aluminium cables VR Vertical flat-bar rear terminals ES Spreaded extended front terminals R Threaded rear terminals HR Horizontal flat-bar rear terminals Im Im Ith Magnetic trip current PR2 P Microprocessorbased electronic release SACE PR2/P (functions I - LI) DC Direct current circuit-breakers for applications up to 000V Im 5 Ith Im 0 Ith Im Ith PR22 P PR22 MP Microprocessorbased electronic release SACE PR22/P (functions LSI - LSIG) Microprocessorbased electronic release for motor protection SACE PR22/MP (functions LRIU) Iu In AC ~ Alternate current circuit-breakers for applications up to 000V Rated uninterrupted current of the circuitbreaker Rated current of electronic release Ith Rated current of thermomagnetic release Icw Rated short-time withstand current Icu Rated ultimate short-circuit breaking capacity 7 Icm Rated duty shortcircuit making capacity (peak value) 7/2
219 Order codes SACE Isomax S circuit-breaker F FIED SB 25 Iu (40 C) 25 A Icu (45 V) 6 ka PSIS960 Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles FC Cu Front terminals for copper cables SB 25 F FC Cu R 0 60A A SB 25 F FC Cu R A A SB 25 F FC Cu R 6 60A A SB 25 F FC Cu R A A SB 25 F FC Cu R A A SB 25 F FC Cu R 2 200A A SB 25 F FC Cu R A A SB 25 F FC Cu R A A SB 25 F FC Cu R 6 20A A SB 25 F FC Cu R A A SB 25 F FC Cu R A A SB 25 F FC Cu R 25 60A A R Terminali posteriori filettati SB 25 F R R 0 60A A SB 25 F R R A A SB 25 F R R 6 60A A SB 25 F R R A A SB 25 F R R A A SB 25 F R R 2 200A A SB 25 F R R A A SB 25 F R R A A SB 25 F R R 6 20A A SB 25 F R R A A SB 25 F R R A A SB 25 F R R 25 60A A /
220 Order codes SACE Isomax S circuit-breaker F FIED PSIS960 SN 25 Iu (40 C) 25 A Icu (45 V) 25 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles FC Cu Front terminals for copper cables SN 25 F FC Cu R 0 60A A SN 25 F FC Cu R A A SN 25 F FC Cu R 6 60A A SN 25 F FC Cu R A A SN 25 F FC Cu R A A SN 25 F FC Cu R 2 200A A SN 25 F FC Cu R A A SN 25 F FC Cu R A A SN 25 F FC Cu R 6 20A A SN 25 F FC Cu R A A SN 25 F FC Cu R A A SN 25 F FC Cu R 25 60A A R Threaded rear terminals SN 25 F R R 0 60A A SN 25 F R R A A SN 25 F R R 6 60A A SN 25 F R R A A SN 25 F R R A A SN 25 F R R 2 200A A SN 25 F R R A A SN 25 F R R A A SN 25 F R R 6 20A A SN 25 F R R A A SN 25 F R R A A SN 25 F R R 25 60A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles FC Cu Front terminals for copper cables SN 25 F FC Cu In 6A 60A SN 25 F FC Cu In 40A 200A SN 25 F FC Cu In 50A 250A A SN 25 F FC Cu In 6A 20A A SN 25 F FC Cu In 80A 400A A SN 25 F FC Cu In 00A 000A SN 25 F FC Cu In 25A 250A R Threaded rear terminals SN 25 F R In 6A 60A SN 25 F R In 40A 200A SN 25 F R In 50A 250A A SN 25 F R In 6A 20A A SN 25 F R In 80A 400A A SN 25 F R In 00A 000A SN 25 F R In 25A 250A SN 25 Curva D Iu (40 C) 25 A Icu (45 V) 25 ka Thermomagnetic release Im 0 Ith code SDA R 4 poles FC Cu Front terminals for copper cables SN 25 F FC Cu R 6A 250A SN 25 F FC Cu R 80A 250A SN 25 F FC Cu R 00A 400A SN 25 F FC Cu R 25A 500A 4509 R Threaded rear terminals SN 25 F R R 6A 250A 4509 SN 25 F R R 80A 250A SN 25 F R R 00A 400A SN 25 F R R 25A 500A /4
221 Order codes SACE Isomax S circuit-breaker P PLUG-IN PSIS960 Moving part SB 25 Iu (40 C) 25 A Icu (45 V) 6 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SB 25 P MP R 0 60A A SB 25 P MP R A A SB 25 P MP R 6 60A A SB 25 P MP R A A SB 25 P MP R A A SB 25 P MP R 2 200A A SB 25 P MP R A A SB 25 P MP R A A SB 25 P MP R 6 20A A SB 25 P MP R A A SB 25 P MP R A A SB 25 P MP R 25 60A A SN 25 Iu (40 C) 25 A Icu (45 V) 25 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 25 P MP R 0 60A A SN 25 P MP R A A SN 25 P MP R 6 60A A SN 25 P MP R A A SN 25 P MP R A A SN 25 P MP R 2 200A A SN 25 P MP R A A SN 25 P MP R A A SN 25 P MP R 6 20A A SN 25 P MP R A A SN 25 P MP R A A SN 25 P MP R 25 60A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 25 P MP In 6A 60A SN 25 P MP In 40A 200A SN 25 P MP In 50A 250A A SN 25 P MP In 6A 20A A SN 25 P MP In 80A 400A A SN 25 P MP In 00A 000A SN 25 P MP In 25A 250A SN 25 Curva D Iu (40 C) 25 A Icu (45 V) 25 ka Thermomagnetic release Im 0 Ith code SDA R 4 poles FC Cu Front terminals for copper cables SN 25 P MP R 6A 250A 450 SN 25 P MP R 80A 250A 450 SN 25 P MP R 00A 400A 4505 SN 25 P MP R 25A 500A /5
222 Order codes SACE Isomax S2 circuit-breaker F FIED PSIS9604 S2B 60 Iu (40 C) 60 A Icu (45 V) 6 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles EF Extended front terminals S2B 60 F EF R A A S2B 60 F EF R 6 60A A S2B 60 F EF R A A S2B 60 F EF R A A S2B 60 F EF R 2 200A A S2B 60 F EF R A A S2B 60 F EF R A A S2B 60 F EF R 6 20A A S2B 60 F EF R A A S2B 60 F EF R A A S2B 60 F EF R 25 60A A S2B 60 F EF R A A FC Cu Front terminals for copper cables S2B 60 F FC Cu R A A S2B 60 F FC Cu R 6 60A A S2B 60 F FC Cu R A A S2B 60 F FC Cu R A A S2B 60 F FC Cu R 2 200A A S2B 60 F FC Cu R A A S2B 60 F FC Cu R A A S2B 60 F FC Cu R 6 20A A S2B 60 F FC Cu R A A S2B 60 F FC Cu R A A S2B 60 F FC Cu R 25 60A A S2B 60 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R 6 60A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R 2 200A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R 6 20A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl* R 25 60A A S2B 60 F FC CuAl* R A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R 6 60A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R 2 200A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R 6 20A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R A A S2B 60 F FC CuAl** R 25 60A A S2B 60 F FC CuAl** R A A R Threaded rear terminals S2B 60 F R R A A S2B 60 F R R 6 60A A S2B 60 F R R A A S2B 60 F R R A A S2B 60 F R R 2 200A A S2B 60 F R R A A S2B 60 F R R A A S2B 60 F R R 6 20A A S2B 60 F R R A A S2B 60 F R R A A S2B 60 F R R 25 60A A S2B 60 F R R A A /6 * Cable section x mm 2 ** Cable section x mm 2
223 Order codes SACE Isomax S2 circuit-breaker F FIED PSIS9604 S2N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles EF Extended front terminals S2N 60 F EF R A A S2N 60 F EF R 6 60A A S2N 60 F EF R A A S2N 60 F EF R A A S2N 60 F EF R 2 200A A S2N 60 F EF R A A S2N 60 F EF R A A S2N 60 F EF R 6 20A A S2N 60 F EF R A A S2N 60 F EF R A A S2N 60 F EF R 25 60A A S2N 60 F EF R A A FC Cu Front terminals for copper cables S2N 60 F FC Cu R A A S2N 60 F FC Cu R 6 60A A S2N 60 F FC Cu R A A S2N 60 F FC Cu R A A S2N 60 F FC Cu R 2 200A A S2N 60 F FC Cu R A A S2N 60 F FC Cu R A A S2N 60 F FC Cu R 6 20A A S2N 60 F FC Cu R A A S2N 60 F FC Cu R A A S2N 60 F FC Cu R 25 60A A S2N 60 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R 6 60A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R 2 200A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R 6 20A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl* R 25 60A A S2N 60 F FC CuAl* R A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R 6 60A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R 2 200A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R 6 20A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R A A S2N 60 F FC CuAl** R 25 60A A S2N 60 F FC CuAl** R A A R Threaded rear terminals S2N 60 F R R A A S2N 60 F R R 6 60A A S2N 60 F R R A A S2N 60 F R R A A S2N 60 F R R 2 200A A S2N 60 F R R A A S2N 60 F R R A A S2N 60 F R R 6 20A A S2N 60 F R R A A S2N 60 F R R A A S2N 60 F R R 25 60A A S2N 60 F R R A A * Cable section x mm 2 ** Cable section x mm 2 7/7
224 Order codes SACE Isomax S2 circuit-breaker F FIED PSIS9604 Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles EF Extended front terminals S2N 60 F EF In 6A 60A S2N 60 F EF In 40A 200A S2N 60 F EF In 50A 250A A S2N 60 F EF In 6A 20A A S2N 60 F EF In 80A 400A A S2N 60 F EF In 00A 000A S2N 60 F EF In 25A 250A S2N 60 F EF In 60A 600A FC Cu Front terminals for copper cables S2N 60 F FC Cu In 6A 60A S2N 60 F FC Cu In 40A 200A S2N 60 F FC Cu In 50A 250A A S2N 60 F FC Cu In 6A 20A A S2N 60 F FC Cu In 80A 400A A S2N 60 F FC Cu In 00A 000A S2N 60 F FC Cu In 25A 250A S2N 60 F FC Cu In 60A 600A FC CuAl Front terminals for copper/aluminium cables S2N 60 F FC CuAl* In 6A 60A S2N 60 F FC CuAl* In 40A 200A S2N 60 F FC CuAl* In 50A 250A A S2N 60 F FC CuAl* In 6A 20A A S2N 60 F FC CuAl* In 80A 400A A S2N 60 F FC CuAl* In 00A 000A S2N 60 F FC CuAl* In 25A 250A S2N 60 F FC CuAl* In 60A 600A S2N 60 F FC CuAl** In 6A 60A S2N 60 F FC CuAl** In 40A 200A S2N 60 F FC CuAl** In 50A 250A A S2N 60 F FC CuAl** In 6A 20A A S2N 60 F FC CuAl** In 80A 400A A S2N 60 F FC CuAl** In 00A 000A S2N 60 F FC CuAl** In 25A 250A S2N 60 F FC CuAl** In 60A 600A R Threaded rear terminals S2N 60 F R In 6A 60A S2N 60 F R In 40A 200A S2N 60 F R In 50A 250A A S2N 60 F R In 6A 20A A S2N 60 F R In 80A 400A A S2N 60 F R In 00A 000A S2N 60 F R In 25A 250A S2N 60 F R In 60A 600A * Cable section x mm 2 ** Cable section x mm 2 7 7/8
225 Order codes SACE Isomax S2 circuit-breaker F FIED PSIS9604 S2S 60 Iu (40 C) 60 A Icu (45 V) 50 ka Thermomagnetic Im 0 Ith code SDA R release poles 4 poles EF Extended front terminals S2S 60 F EF R A S2S 60 F EF R 6 500A S2S 60 F EF R A S2S 60 F EF R A S2S 60 F EF R 2 500A S2S 60 F EF R A S2S 60 F EF R A S2S 60 F EF R 6 60A S2S 60 F EF R A S2S 60 F EF R A S2S 60 F EF R A S2S 60 F EF R A FC Cu Front terminals for copper cables S2S 60 F FC Cu R A S2S 60 F FC Cu R 6 500A S2S 60 F FC Cu R A S2S 60 F FC Cu R A S2S 60 F FC Cu R 2 500A S2S 60 F FC Cu R A S2S 60 F FC Cu R A S2S 60 F FC Cu R 6 60A S2S 60 F FC Cu R A S2S 60 F FC Cu R A S2S 60 F FC Cu R A S2S 60 F FC Cu R A FC CuAl Front terminals for copper/aluminium cables S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R 6 500A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R 2 500A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R 6 60A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl* R A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R 6 500A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R 2 500A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R 6 60A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R A S2S 60 F FC CuAl** R A R Threaded rear terminals S2S 60 F R R A S2S 60 F R R 6 500A S2S 60 F R R A S2S 60 F R R A S2S 60 F R R 2 500A S2S 60 F R R A S2S 60 F R R A S2S 60 F R R 6 60A S2S 60 F R R A S2S 60 F R R A S2S 60 F R R A S2S 60 F R R A * Cable section x mm 2 ** Cable section x mm 2 7/9
226 Order codes SACE Isomax S2 circuit-breaker F FIED PSIS9604 Magnetic Im 0 Ith code SDA R release poles 4 poles EF Extended front terminals S2S 60 F EF In 50A 500A S2S 60 F EF In 6A 60A S2S 60 F EF In 80A 800A S2S 60 F EF In 00A 000A S2S 60 F EF In 25A 250A S2S 60 F EF In 60A 600A FC Cu Front terminals for copper cables S2S 60 F FC Cu In 50A 500A S2S 60 F FC Cu In 6A 60A S2S 60 F FC Cu In 80A 800A S2S 60 F FC Cu In 00A 000A S2S 60 F FC Cu In 25A 250A S2S 60 F FC Cu In 60A 600A FC CuAl Front terminals for copper/aluminium cables S2S 60 F FC CuAl* In 50A 500A S2S 60 F FC CuAl* In 6A 60A S2S 60 F FC CuAl* In 80A 800A S2S 60 F FC CuAl* In 00A 000A S2S 60 F FC CuAl* In 25A 250A S2S 60 F FC CuAl* In 60A 600A S2S 60 F FC CuAl** In 50A 500A S2S 60 F FC CuAl** In 6A 60A S2S 60 F FC CuAl** In 80A 800A S2S 60 F FC CuAl** In 00A 000A S2S 60 F FC CuAl** In 25A 250A S2S 60 F FC CuAl** In 60A 600A R Threaded rear terminals S2S 60 F R In 50A 500A S2S 60 F R In 6A 60A S2S 60 F R In 80A 800A S2S 60 F R In 00A 000A S2S 60 F R In 25A 250A S2S 60 F R In 60A 600A * Cable section x mm 2 ** Cable section x mm 2 7 7/0
227 Order codes SACE Isomax S2 circuit-breaker P PLUG-IN PSIS9604 Moving part S2B 60 Iu (40 C) 60 A Icu (45 V) 6 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles S2B 60 P MP R A A S2B 60 P MP R 6 60A A S2B 60 P MP R A A S2B 60 P MP R A A S2B 60 P MP R 2 200A A S2B 60 P MP R A A S2B 60 P MP R A A S2B 60 P MP R 6 20A A S2B 60 P MP R A A S2B 60 P MP R A A S2B 60 P MP R 25 60A A S2B 60 P MP R A A S2N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles S2N 60 P MP R A A S2N 60 P MP R 6 60A A S2N 60 P MP R A A S2N 60 P MP R A A S2N 60 P MP R 2 200A A S2N 60 P MP R A A S2N 60 P MP R A A S2N 60 P MP R 6 20A A S2N 60 P MP R A A S2N 60 P MP R A A S2N 60 P MP R 25 60A A S2N 60 P MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles S2N 60 P MP In 6A 60A S2N 60 P MP In 40A 200A S2N 60 P MP In 50A 250A A S2N 60 P MP In 6A 20A A S2N 60 P MP In 80A 400A A S2N 60 P MP In 00A 000A S2N 60 P MP In 25A 250A S2N 60 P MP In 50A 600A /
228 Order codes SACE Isomax S2 circuit-breaker P PLUG-IN PSIS9604 Moving part S2S 60 Iu (40 C) 60 A Icu (45 V) 50 ka Thermomagnetic I m 5 I th Im 0 Ith code SDA R release poles 4 poles S2S 60 P MP R A S2S 60 P MP R 6 500A S2S 60 P MP R A S2S 60 P MP R A S2S 60 P MP R 2 500A S2S 60 P MP R A S2S 60 P MP R A S2S 60 P MP R 6 60A S2S 60 P MP R A S2S 60 P MP R A S2S 60 P MP R A S2S 60 P MP R A Magnetic code SDA R release poles 4 poles S2S 60 P MP In 50A 500A S2S 60 P MP In 6A 60A S2S 60 P MP In 80A 800A S2S 60 P MP In 00A 000A S2S 60 P MP In 25A 250A S2S 60 P MP In 50A 600A /2
229 Order codes SACE Isomax S2 circuit-breaker F FIED PSIS9607 SN 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im Ith code SDA R release poles 4 poles F Front terminals SN 60 F F R 00 00A SN 60 F F R 25 75A SN 60 F F R 60 I480A SN 60 F F (N50%) R 60 I480A Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles F Front terminals SN 60 F F R 2 250A A 46 7 SN 60 F F R A A 48 7 SN 60 F F R A A SN 60 F F R A A SN 60 F F R A A SN 60 F F R A A 56 8 EF Extended front terminals SN 60 F EF R 2 250A A SN 60 F EF R A A SN 60 F EF R A A SN 60 F EF R A A SN 60 F EF R A A SN 60 F EF R A A FC Cu Front terminals for copper cables SN 60 F FC Cu R 2 250A A SN 60 F FC Cu R A A SN 60 F FC Cu R A A SN 60 F FC Cu R A A SN 60 F FC Cu R A A SN 60 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables SN 60 F FC CuAl R 2 250A A SN 60 F FC CuAl R A A SN 60 F FC CuAl R A A SN 60 F FC CuAl R A A SN 60 F FC CuAl R A A SN 60 F FC CuAl R A A R Threaded rear terminals SN 60 F R R 2 250A A SN 60 F R R A A SN 60 F R R A A SN 60 F R R A A SN 60 F R R A A SN 60 F R R A A RC Rear terminals for cables SN 60 F RC R 2 250A A SN 60 F RC R A A SN 60 F RC R A A SN 60 F RC R A A SN 60 F RC R A A SN 60 F RC R A A R Res. Cur Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker SN 60 F R Res. Cur R 2 250A A SN 60 F R Res. Cur R A A SN 60 F R Res. Cur R A A 2545 SN 60 F R Res. Cur R A A SN 60 F R Res. Cur R A A SN 60 F R Res. Cur R A A /
230 Order codes SACE Isomax S2 circuit-breaker F FIED Im 5 Ith Im 0 Ith PSIS9607 Magnetic code SDA R code SDA R release poles 4 poles poles 4 poles F Front terminals SN 60 F F In 50A 250A A SN 60 F F In 80A 400A A SN 60 F F In 00A 000A SN 60 F F In 25A 625A A SN 60 F F In 60A 600A EF Extended front terminals SN 60 F EF In 50A 250A A SN 60 F EF In 80A 400A A SN 60 F EF In 00A 000A SN 60 F EF In 25A 625A A SN 60 F EF In 60A 600A FC Cu Front terminals for copper cables SN 60 F FC Cu In 50A 250A A SN 60 F FC Cu In 80A 400A A SN 60 F FC Cu In 00A 000A SN 60 F FC Cu In 25A 625A A SN 60 F FC Cu In 60A 600A FC CuAl Front terminals for copper/aluminium cables SN 60 F FC CuAl In 50A 250A A SN 60 F FC CuAl In 80A 400A A SN 60 F FC CuAl In 00A 000A SN 60 F FC CuAl In 25A 625A A SN 60 F FC CuAl In 60A 600A R Threaded rear terminals SN 60 F R In 50A 250A A SN 60 F R In 80A 400A A SN 60 F R In 00A 000A SN 60 F R In 25A 625A A SN 60 F R In 60A 600A RC Rear terminals for cables SN 60 F RC In 50A 250A A SN 60 F RC In 80A 400A A SN 60 F RC In 00A 000A SN 60 F RC In 25A 625A A SN 60 F RC In 60A 600A /4
231 Order codes SACE Isomax S circuit-breaker F FIED PSIS9607 SH 60 Iu (40 C) 60 A Icu (45 V) 65 ka Thermomagnetic Im Ith code SDA R release poles 4 poles F Front terminals SH 60 F F R 00 00A SH 60 F F R 25 75A SH 60 F F R A SH 60 F F (N50%) R A Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles F Front terminals SH 60 F F R 2 250A A SH 60 F F R A A SH 60 F F R A A SH 60 F F R A A SH 60 F F R A A SH 60 F F R A A EF Extended front terminals SH 60 F EF R 2 250A A SH 60 F EF R A A SH 60 F EF R A A SH 60 F EF R A A SH 60 F EF R A A SH 60 F EF R A A FC Cu Front terminals for copper cables SH 60 F FC Cu R 2 250A A SH 60 F FC Cu R A A SH 60 F FC Cu R A A SH 60 F FC Cu R A A SH 60 F FC Cu R A A SH 60 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables SH 60 F FC CuAl R 2 250A A SH 60 F FC CuAl R A A SH 60 F FC CuAl R A A SH 60 F FC CuAl R A A SH 60 F FC CuAl R A A SH 60 F FC CuAl R A A R Threaded rear terminals SH 60 F R R 2 250A A SH 60 F R R A A SH 60 F R R A A SH 60 F R R A A SH 60 F R R A A SH 60 F R R A A RC Rear terminals for cables SH 60 F RC R 2 250A A SH 60 F RC R A A SH 60 F RC R A A SH 60 F RC R A A SH 60 F RC R A A SH 60 F RC R A A R Res. Cur Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker SH 60 F R Res. Cur R 2 250A A 2547 SH 60 F R Res. Cur R A A 2547 SH 60 F R Res. Cur R A A SH 60 F R Res. Cur R A A SH 60 F R Res. Cur R A A SH 60 F R Res. Cur R A A /5
232 Order codes SACE Isomax S circuit-breaker F FIED Im 5 Ith Im 0 Ith PSIS9607 Magnetic code SDA R code SDA R release poles 4 poles poles 4 poles F Front terminals SH 60 F F In 50A 250A A SH 60 F F In 80A 400A A SH 60 F F In 00A 000A SH 60 F F In 25A 625A A SH 60 F F In 60A 600A EF Extended front terminals SH 60 F EF In 50A 250A A SH 60 F EF In 80A 400A A SH 60 F EF In 00A 000A SH 60 F EF In 25A 625A A SH 60 F EF In 60A 600A FC Cu Front terminals for copper cables SH 60 F FC Cu In 50A 250A A SH 60 F FC Cu In 80A 400A A SH 60 F FC Cu In 00A 000A SH 60 F FC Cu In 25A 625A A SH 60 F FC Cu In 60A 600A FC CuAl Front terminals for copper/aluminium cables SH 60 F FC CuAl In 50A 250A A SH 60 F FC CuAl In 80A 400A A SH 60 F FC CuAl In 00A 000A SH 60 F FC CuAl In 25A 625A A SH 60 F FC CuAl In 60A 600A R Threaded rear terminals SH 60 F R In 50A 250A A SH 60 F R In 80A 400A A SH 60 F R In 00A 000A SH 60 F R In 25A 625A A SH 60 F R In 60A 600A RC Rear terminals for cables SH 60 F RC In 50A 250A A SH 60 F RC In 80A 400A A SH 60 F RC In 00A 000A SH 60 F RC In 25A 625A A SH 60 F RC In 60A 600A /6
233 Order codes SACE Isomax S circuit-breaker F FIED PSIS9607 SL 60 Iu (40 C) 60 A Icu (45 V) 85 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles F Front terminals SL 60 F F R 2 250A A SL 60 F F R A A SL 60 F F R A A SL 60 F F R A A SL 60 F F R A A SL 60 F F R A A EF Extended front terminals SL 60 F EF R 2 250A A SL 60 F EF R A A SL 60 F EF R A A SL 60 F EF R A A SL 60 F EF R A A SL 60 F EF R A A FC Cu Front terminals for copper cables SL 60 F FC Cu R 2 250A A SL 60 F FC Cu R A A SL 60 F FC Cu R A A SL 60 F FC Cu R A A SL 60 F FC Cu R A A SL 60 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables SL 60 F FC CuAl R 2 250A A SL 60 F FC CuAl R A A SL 60 F FC CuAl R A A SL 60 F FC CuAl R A A SL 60 F FC CuAl R A A SL 60 F FC CuAl R A A R Threaded rear terminals SL 60 F R R 2 250A A SL 60 F R R A A SL 60 F R R A A SL 60 F R R A A SL 60 F R R A A SL 60 F R R A A RC Rear terminals for cables SL 60 F RC R 2 250A A SL 60 F RC R A A SL 60 F RC R A A SL 60 F RC R A A SL 60 F RC R A A SL 60 F RC R A A R Res. Cur Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker SL 60 F R Res. Cur R 2 250A A SL 60 F R Res. Cur R A A SL 60 F R Res. Cur R A A SL 60 F R Res. Cur R A A 2550 SL 60 F R Res. Cur R A A 2550 SL 60 F R Res. Cur R A A /7
234 Order codes SACE Isomax S circuit-breaker F FIED Im 5 Ith Im 0 Ith PSIS9607 Magnetic code SDA R code SDA R release poles 4 poles poles 4 poles F Front terminals SL 60 F F In 50A 250A A SL 60 F F In 80A 400A A SL 60 F F In 00A 000A SL 60 F F In 25A 625A A SL 60 F F In 60A 600A EF Extended front terminals SL 60 F EF In 50A 250A A SL 60 F EF In 80A 400A A SL 60 F EF In 00A 000A SL 60 F EF In 25A 625A A SL 60 F EF In 60A 600A FC Cu Front terminals for copper cables SL 60 F FC Cu In 50A 250A A SL 60 F FC Cu In 80A 400A A SL 60 F FC Cu In 00A 000A SL 60 F FC Cu In 25A 625A A SL 60 F FC Cu In 60A 600A FC CuAl Front terminals for copper/aluminium cables SL 60 F FC CuAl In 50A 250A A SL 60 F FC CuAl In 80A 400A A SL 60 F FC CuAl In 00A 000A SL 60 F FC CuAl In 25A 625A A SL 60 F FC CuAl In 60A 600A R Threaded rear terminals SL 60 F R In 50A 250A A SL 60 F R In 80A 400A A SL 60 F R In 00A 000A SL 60 F R In 25A 625A A SL 60 F R In 60A 600A RC Rear terminals for cables SL 60 F RC In 50A 250A A SL 60 F RC In 80A 400A A SL 60 F RC In 00A 000A SL 60 F RC In 25A 625A A SL 60 F RC In 60A 600A /8
235 Order codes SACE Isomax S circuit-breaker P PLUG-IN PSIS9607 Moving part SN 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 60 P MP R 2 250A A SN 60 P MP R A A SN 60 P MP R A A SN 60 P MP R A A SN 60 P MP R A A SN 60 P MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 60 P MP In 50A 250A A SN 60 P MP In 80A 400A A SN 60 P MP In 00A 000A SN 60 P MP In 25A 625A A SN 60 P MP In 60A 600A SH 60 Iu (40 C) 60 A Icu (45 V) 65 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SH 60 P MP R 2 250A A SH 60 P MP R A A SH 60 P MP R A A SH 60 P MP R A A SH 60 P MP R A A SH 60 P MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SH 60 P MP In 50A 250A A SH 60 P MP In 80A 400A A SH 60 P MP In 00A 000A SH 60 P MP In 25A 625A A SH 60 P MP In 60A 600A SL 60 Iu (40 C) 60 A Icu (45 V) 85 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SL 60 P MP R 2 250A A SL 60 P MP R A A SL 60 P MP R A A SL 60 P MP R A A SL 60 P MP R A A SL 60 P MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SL 60 P MP In 50A 250A A SL 60 P MP In 80A 400A A SL 60 P MP In 00A 000A SL 60 P MP In 25A 625A A SL 60 P MP In 60A 600A /9
236 Order codes SACE Isomax S circuit-breaker W WITHDRAWABLE PSIS9607 Moving part SN 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 60 W MP R 2 250A A SN 60 W MP R A A SN 60 W MP R A A SN 60 W MP R A A SN 60 W MP R A A SN 60 W MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 60 W MP In 50A 250A A SN 60 W MP In 80A 400A A SN 60 W MP In 00A 000A SN 60 W MP In 25A 625A A SN 60 W MP In 60A 600A SH 60 Iu (40 C) 60 A Icu (45 V) 65 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SH 60 W MP R 2 250A A SH 60 W MP R A A SH 60 W MP R A A SH 60 W MP R A A SH 60 W MP R A A SH 60 W MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SH 60 W MP In 50A 250A A SH 60 W MP In 80A 400A A SH 60 W MP In 00A 000A SH 60 W MP In 25A 625A A SH 60 W MP In 60A 600A SL 60 Iu (40 C) 60 A Icu (45 V) 85 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SL 60 W MP R 2 250A A SL 60 W MP R A A SL 60 W MP R A A SL 60 W MP R A A SL 60 W MP R A A SL 60 W MP R A A Magnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SL 60 W MP In 50A 250A A SL 60 W MP In 80A 400A A SL 60 W MP In 00A 000A SL 60 W MP In 25A 625A A SL 60 W MP In 60A 600A /20
237 Order codes SACE Isomax S circuit-breaker F FIED PSIS9607 SN 250 Iu (40 C) 250 A Icu (45 V) 5 ka Thermomagnetic Im Ith code SDA R release poles 4 poles F Front terminals SN 250 F F R A SN 250 F F R A SN 250 F F (N50%) R A 4856 SN 250 F F (N50%) R A Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles F Front terminals SN 250 F F R A A SN 250 F F R A A EF Extended front terminals SN 250 F EF R A A SN 250 F EF R A A FC Cu Front terminals for copper cables SN 250 F FC Cu R A A SN 250 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables SN 250 F FC CuAl R A A SN 250 F FC CuAl R A A R Threaded rear terminals SN 250 F R R A A SN 250 F R R A A RC Rear terminals for cables SN 250 F RC R A A SN 250 F RC R A A R Res. Cur Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker SN 250 F R Res. Cur R A A 2559 SN 250 F R Res. Cur R A A 2552 Magnetic Im 0 Ith code SDA R release poles 4 poles F Front terminals SN 250 F F In 200A 2000A SN 250 F F In 250A 2500A EF Extended front terminals SN 250 F EF In 200A 2000A SN 250 F EF In 250A 2500A FC Cu Front terminals for copper cables SN 250 F FC Cu In 200A 2000A SN 250 F FC Cu In 250A 2500A FC CuAl Front terminals for copper/aluminium cables SN 250 F FC CuAl In 200A 2000A SN 250 F FC CuAl In 250A 2500A R Threaded rear terminals SN 250 F R In 200A 2000A SN 250 F R In 250A 2500A RC Rear terminals for cables SN 250 F RC In 200A 2000A SN 250 F RC In 250A 2500A /2
238 Order codes SACE Isomax S circuit-breaker F FIED PSIS9607 SH 250 Iu (40 C) 250 A Icu (45 V) 65 ka Thermomagnetic Im Ith code SDA R release poles 4 poles F Front terminals SH 250 F F R A SH 250 F F R A SH 250 F F (N50%) R A 4856 SH 250 F F (N50%) R A Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles F Front terminals SH 250 F F R A A SH 250 F F R A A EF Extended front terminals SH 250 F EF R A A SH 250 F EF R A A FC Cu Front terminals for copper cables SH 250 F FC Cu R A A SH 250 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables SH 250 F FC CuAl R A A SH 250 F FC CuAl R A A R Threaded rear terminals SH 250 F R R A A SH 250 F R R A A RC Rear terminals for cables SH 250 F RC R A A SH 250 F RC R A A R Res. Cur Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker SH 250 F R Res. Cur R A A SH 250 F R Res. Cur R A A Magnetic Im 0 Ith code SDA R release poles 4 poles F Front terminals SH 250 F F In 200A 2000A SH 250 F F In 250A 2500A EF Extended front terminals SH 250 F EF In 200A 2000A SH 250 F EF In 250A 2500A FC Cu Front terminals for copper cables SH 250 F FC Cu In 200A 2000A SH 250 F FC Cu In 250A 2500A FC CuAl Front terminals for copper/aluminium cables SH 250 F FC CuAl In 200A 2000A SH 250 F FC CuAl In 250A 2500A R Threaded rear terminals SH 250 F R In 200A 2000A SH 250 F R In 250A 2500A RC Rear terminals for cables SH 250 F RC In 200A 2000A SH 250 F RC In 250A 2500A /22
239 Order codes SACE Isomax S circuit-breaker F FIED PSIS9607 SL 250 Iu (40 C) 250 A Icu (45 V) 85 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles F Front terminals SL 250 F F R A A 52 5 SL 250 F F R A A EF Extended front terminals SL 250 F EF R A A SL 250 F EF R A A FC Cu Front terminals for copper cables SL 250 F FC Cu R A A SL 250 F FC Cu R A A FC CuAl Front terminals for copper/aluminium cables SL 250 F FC CuAl R A A SL 250 F FC CuAl R A A R Threaded rear terminals SL 250 F R R A A SL 250 F R R A A RC Rear terminals for cables SL 250 F RC R A A SL 250 F RC R A A R Res. Cur Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker SL 250 F R Res. Cur R A A 2555 SL 250 F R Res. Cur R A A 2557 Magnetic Im 0 Ith code SDA R release poles 4 poles F Front terminals SL 250 F F In 200A 2000A SL 250 F F In 250A 2500A EF Extended front terminals SL 250 F EF In 200A 2000A SL 250 F EF In 250A 2500A FC Cu Front terminals for copper cables SL 250 F FC Cu In 200A 2000A SL 250 F FC Cu In 250A 2500A FC CuAl Front terminals for copper/aluminium cables SL 250 F FC CuAl In 200A 2000A SL 250 F FC CuAl In 250A 2500A R Threaded rear terminals SL 250 F R In 200A 2000A SL 250 F R In 250A 2500A RC Rear terminals for cables SL 250 F RC In 200A 2000A SL 250 F RC In 250A 2500A /2
240 Order codes SACE Isomax S circuit-breaker P PLUG-IN PSIS9607 Moving part SN 250 Iu (40 C) 250 A Icu (45 V) 5 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 250 P MP R A A SN 250 P MP R A A Magnetic Im 0 Ith code SDA R release poles 4 poles SN 250 P MP In 200A 2000A SN 250 P MP In 250A 2500A SH 250 Iu (40 C) 250 A Icu (45 V) 65 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SH 250 P MP R A A SH 250 P MP R A A Magnetic Im 0 Ith code SDA R release poles 4 poles SH 250 P MP In 200A 2000A SH 250 P MP In 250A 2500A SL 250 Iu (40 C) 250 A Icu (45 V) 85 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SL 250 P MP R A A SL 250 P MP R A A Magnetic Im 0 Ith code SDA R release poles 4 poles SL 250 P MP In 200A 2000A SL 250 P MP In 250A 2500A /24
241 Order codes SACE Isomax S circuit-breaker W WITHDRAWABLE PSIS9607 Moving part SN 250 Iu (40 C) 250 A Icu (45 V) 5 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SN 250 W MP R A A SN 250 W MP R A A Magnetic Im 0 Ith code SDA R release poles 4 poles SN 250 W MP In 200A 2000A SN 250 W MP In 250A 2500A SH 250 Iu (40 C) 250 A Icu (45 V) 65 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SH 250 W MP R A A SH 250 W MP R A A Magnetic Im 0 Ith code SDA R release poles 4 poles SH 250 W MP In 200A 2000A SH 250 W MP In 250A 2500A SL 250 Iu (40 C) 250 A Icu (45 V) 85 ka Thermomagnetic Im 5 Ith code SDA R Im 0 Ith code SDA R release poles 4 poles poles 4 poles SL 250 W MP R A A SL 250 W MP R A A Magnetic Im 0 Ith code SDA R release poles 4 poles SL 250 W MP In 200A 2000A SL 250 W MP In 250A 2500A /25
242 Order codes SACE Isomax S4 circuit-breaker F FIED PSIS960 S4N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4N 60 F F In 00 A I LSI LI LSIG S4N 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S4N 60 F EF In 00 A I LSI LI LSIG S4N 60 F EF In 60 A I LSI LI LSIG FC Cu Front terminals for copper cables S4N 60 F FC Cu In 00 A I LSI LI LSIG S4N 60 F FC Cu In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4N 60 F FC CuAl In 00 A I LSI LI LSIG S4N 60 F FC CuAl In 60 A I LSI LI LSIG R Threaded rear terminals S4N 60 F R In 00 A I LSI LI 58 6 LSIG S4N 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S4N 60 F RC In 00 A I LSI LI LSIG S4N 60 F RC In 60 A I LSI LI LSIG S4H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4H 60 F F In 00 A I LSI LI LSIG S4H 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S4H 60 F EF In 00 A I LSI LI LSIG S4H 60 F EF In 60 A I LSI LI LSIG FC Cu Front terminals for copper cables S4H 60 F FC Cu In 00 A I LSI LI LSIG S4H 60 F FC Cu In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4H 60 F FC CuAl In 00 A I LSI LI LSIG S4H 60 F FC CuAl In 60 A I LSI LI LSIG /26
243 Order codes SACE Isomax S4 circuit-breaker F FIED PSIS960 Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles R Threaded rear terminals S4H 60 F R In 00 A I LSI LI LSIG S4H 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S4H 60 F RC In 00 A I LSI LI LSIG S4H 60 F RC In 60 A I LSI LI LSIG S4L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4L 60 F F In 00 A I LSI LI LSIG S4L 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S4L 60 F EF In 00 A I LSI LI LSIG S4L 60 F EF In 60 A I LSI LI LSIG FC Cu Front terminals for copper cables S4L 60 F FC Cu In 00 A I LSI LI LSIG S4L 60 F FC Cu In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4L 60 F FC CuAl In 00 A I LSI LI LSIG S4L 60 F FC CuAl In 60 A I LSI LI LSIG R Threaded rear terminals S4L 60 F R In 00 A I LSI LI LSIG S4L 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S4L 60 F RC In 00 A I LSI LI LSIG S4L 60 F RC In 60 A I LSI LI LSIG /27
244 Order codes SACE Isomax S4 circuit-breaker P PLUG-IN PSIS960 Moving part S4N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S4N 60 P MP In 00 A I LSI 62 6 LI 69 6 LSIG S4N 60 P MP In 60 A I LSI LI LSIG S4H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4H 60 P MP In 00 A I LSI LI LSIG S4H 60 P MP In 60 A I LSI LI LSIG S4L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4L 60 P MP In 00 A I LSI LI LSIG S4L 60 P MP In 60 A I LSI LI LSIG W WITHDRAWABLE PSIS960 Moving part S4N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S4N 60 W MP In 00 A I LSI LI LSIG S4N 60 W MP In 60 A I LSI LI LSIG S4H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S4H 60 W MP In 00 A I LSI LI LSIG S4H 60 W MP In 60 A I LSI LI LSIG S4L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4L 60 W MP In 00 A I LSI LI 70 7 LSIG S4L 60 W MP In 60 A I LSI LI LSIG /28
245 Order codes SACE Isomax S4 circuit-breaker F FIED PSIS960 S4N 250 Iu (40 C) 250 A Icu (45 V) 5 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4N 250 F F In 250 A I LSI LI LSIG EF Extended front terminals S4N 250 F EF In 250 A I LSI LI LSIG FC Cu Front terminals for copper cables S4N 250 F FC Cu In 250 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4N 250 F FC CuAl In 250 A I LSI LI LSIG R Threaded rear terminals S4N 250 F R In 250 A I LSI LI LSIG RC Rear terminals for cables S4N 250 F RC In 250 A I LSI LI LSIG S4H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4H 250 F F In 250 A I LSI LI LSIG EF Extended front terminals S4H 250 F EF In 250 A I LSI LI LSIG FC Cu Front terminals for copper cables S4H 250 F FC Cu In 250 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4H 250 F FC CuAl In 250 A I LSI LI LSIG R Threaded rear terminals S4H 250 F R In 250 A I LSI LI LSIG RC Rear terminals for cables S4H 250 F RC In 250 A I LSI LI LSIG /29
246 Order codes SACE Isomax S4 circuit-breaker F FIED PSIS960 S4L 250 Iu (40 C) 250 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4L 250 F F In 250 A I LSI LI LSIG EF Extended front terminals S4L 250 F EF In 250 A I LSI LI LSIG FC Cu Front terminals for copper cables S4L 250 F FC Cu In 250 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4L 250 F FC CuAl In 250 A I LSI LI LSIG R Threaded rear terminals S4L 250 F R In 250 A I LSI LI LSIG RC Rear terminals for cables S4L 250 F RC In 250 A I LSI LI LSIG /0
247 Order codes SACE Isomax S4 circuit-breaker P PLUG-IN Moving part S4N 250 Iu (40 C) 250 A Icu (45 V) 5 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S4N 250 P MP In 250 A I LSI LI LSIG PSIS960 S4H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S4H 250 P MP In 250 A I LSI LI LSIG S4L 250 Iu (40 C) 250 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S4L 250 P MP In 250 A I LSI LI LSIG W WITHDRAWABLE Moving part S4N 250 Iu (40 C) 250 A Icu (45 V) 5 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4N 250 W MP In 250 A I LSI LI LSIG PSIS960 S4H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4H 250 W MP In 250 A I LSI LI LSIG S4L 250 Iu (40 C) 250 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4L 250 W MP In 250 A I LSI LI LSIG /
248 Order codes SACE Isomax S5 circuit-breaker F FIED PSIS96 S5N 400 Iu (40 C) 400 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R release Ith poles 4 poles F Front terminals S5N 400 F F R A S5N 400 F F R A EF Extended front terminals S5N 400 F EF R A S5N 400 F EF R A FC Cu Front terminals for copper cables S5N 400 F FC Cu R A S5N 400 F FC Cu R A FC CuAl Front terminals for copper/aluminium cables S5N 400 F FC CuAl* R A S5N 400 F FC CuAl* R A S5N 400 F FC CuAl** R A S5N 400 F FC CuAl** R A R Threaded rear terminals S5N 400 F R R A S5N 400 F R R A RC Rear terminals for cables S5N 400 F RC R A S5N 400 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S5N 400 F F In 20 A I LSI LI LSIG S5N 400 F F In 400 A I LSI LI LSIG EF Extended front terminals S5N 400 F EF In 20 A I LSI LI LSIG S5N 400 F EF In 400 A I LSI LI LSIG FC Cu Front terminals for copper cables S5N 400 F FC Cu In 20 A I LSI LI LSIG S5N 400 F FC Cu In 400 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S5N 400 F FC CuAl* In 20 A I LSI LI LSIG S5N 400 F FC CuAl* In 400 A I LSI LI LSIG S5N 400 F FC CuAl** In 20 A I LSI LI LSIG S5N 400 F FC CuAl** In 400 A I LSI LI LSIG R Threaded rear terminals S5N 400 F R In 20 A I LSI LI LSIG S5N 400 F R In 400 A I LSI LI LSIG RC Rear terminals for cables S5N 400 F RC In 20 A I LSI LI LSIG S5N 400 F RC In 400 A I LSI LI LSIG * Cable section x 240 mm 2 ** Cable section 2 x 20 mm 2 7/2
249 Order codes SACE Isomax S5 circuit-breaker F FIED PSIS96 S5H 400 Iu (40 C) 400 A Icu (45 V) 65 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S5H 400 F F R A S5H 400 F F R A EF Extended front terminals S5H 400 F EF R A S5H 400 F EF R A FC Cu Front terminals for copper cables S5H 400 F FC Cu R A S5H 400 F FC Cu R A FC CuAl Front terminals for copper/aluminium cables S5H 400 F FC CuAl* R A S5H 400 F FC CuAl* R A S5H 400 F FC CuAl** R A S5H 400 F FC CuAl** R A R Threaded rear terminals S5H 400 F R R A S5H 400 F R R A RC Rear terminals for cables S5H 400 F RC R A S5H 400 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S5H 400 F F In 20 A I LSI LI LSIG S5H 400 F F In 400 A I LSI LI LSIG EF Extended front terminals S5H 400 F EF In 20 A I LSI LI LSIG S5H 400 F EF In 400 A I LSI LI LSIG FC Cu Front terminals for copper cables S5H 400 F FC Cu In 20 A I LSI LI LSIG S5H 400 F FC Cu In 400 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S5H 400 F FC CuAl* In 20 A I LSI LI LSIG S5H 400 F FC CuAl* In 400 A I LSI LI LSIG S5H 400 F FC CuAl** In 20 A I LSI LI LSIG S5H 400 F FC CuAl** In 400 A I LSI LI LSIG R Threaded rear terminals S5H 400 F R In 20 A I LSI LI LSIG S5H 400 F R In 400 A I LSI LI LSIG RC Rear terminals for cables S5H 400 F RC In 20 A I LSI LI LSIG S5H 400 F RC In 400 A I LSI LI LSIG * Cable section x 240 mm 2 ** Cable section 2 x 20 mm 2 7 7/
250 Order codes SACE Isomax S5 circuit-breaker F FIED PSIS96 S5L 400 Iu (40 C) 400 A Icu (45 V) 00 ka Thermomagnetic Im code SDA R release Ith poles 4 poles F Front terminals S5L 400 F F R A S5L 400 F F R A EF Extended front terminals S5L 400 F EF R A S5L 400 F EF R A FC Cu Front terminals for copper cables S5L 400 F FC Cu R A S5L 400 F FC Cu R A FC CuAl Front terminals for copper/aluminium cables S5L 400 F FC CuAl* R A S5L 400 F FC CuAl* R A S5L 400 F FC CuAl** R A S5L 400 F FC CuAl** R A R Threaded rear terminals S5L 400 F R R A S5L 400 F R R A RC Rear terminals for cables S5L 400 F RC R A S5L 400 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S5L 400 F F In 20 A I LSI LI LSIG S5L 400 F F In 400 A I LSI LI LSIG EF Extended front terminals S5L 400 F EF In 20 A I LSI LI LSIG S5L 400 F EF In 400 A I LSI LI LSIG FC Cu Front terminals for copper cables S5L 400 F FC Cu In 20 A I LSI LI LSIG S5L 400 F FC Cu In 400 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S5L 400 F FC CuAl* In 20 A I LSI LI LSIG S5L 400 F FC CuAl* In 400 A I LSI LI LSIG S5L 400 F FC CuAl** In 20 A I LSI LI LSIG S5L 400 F FC CuAl** In 400 A I LSI LI LSIG R Threaded rear terminals S5L 400 F R In 20 A I LSI LI LSIG S5L 400 F R In 400 A I LSI LI LSIG RC Rear terminals for cables S5L 400 F RC In 20 A I LSI LI LSIG S5L 400 F RC In 400 A I LSI LI LSIG * Cable section x 240 mm 2 ** Cable section 2 x 20 mm 2 7/4
251 Order codes SACE Isomax S5 circuit-breaker P PLUG-IN Moving part S5N 400 Iu (40 C) 400 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5N 400 P MP R A S5N 400 P MP R A PSIS96 Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5N 400 P MP In 20 A I LSI LI LSIG S5N 400 P MP In 400 A I LSI LI LSIG S5H 400 Iu (40 C) 400 A Icu (45 V) 65 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S5H 400 P MP R A S5H 400 P MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5H 400 P MP In 20 A I LSI LI LSIG S5H 400 P MP In 400 A I LSI LI LSIG S5L 400 Iu (40 C) 400 A Icu (45 V) 00 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5L 400 P MP R A S5L 400 P MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5L 400 P MP In 20 A I LSI LI LSIG S5L 400 P MP In 400 A I LSI LI LSIG /5
252 Order codes SACE Isomax S5 circuit-breaker W WITHDRAWABLE Moving part S5N 400 Iu (40 C) 400 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5N 400 W MP R A S5N 400 W MP R A PSIS96 Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5N 400 W MP In 20 A I LSI LI LSIG S5N 400 W MP In 400 A I LSI LI LSIG S5H 400 Iu (40 C) 400 A Icu (45 V) 65 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5H 400 W MP R A S5H 400 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S5H 400 W MP In 20 A I LSI LI LSIG S5H 400 W MP In 400 A I LSI LI LSIG S5L 400 Iu (40 C) 400 A Icu (45 V) 00 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S5L 400 W MP R A S5L 400 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5L 400 W MP In 20 A I LSI LI LSIG S5L 400 W MP In 400 A I LSI LI LSIG /6
253 Order codes SACE Isomax S5 circuit-breaker W WITHDRAWABLE Moving part () S5N 400 Iu (40 C) 400 A Icu (45 V) 5 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S5N 400 W MP R A S5N 400 W MP R A PSIS96 Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S5N 400 W MP In 20 A I LSI LI LSIG S5N 400 W MP In 400 A I LSI LI LSIG S5H 400 Iu (40 C) 400 A Icu (45 V) 65 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S5H 400 W MP R A S5H 400 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5H 400 W MP In 20 A I LSI LI LSIG S5H 400 W MP In 400 A I LSI LI LSIG S5L 400 Iu (40 C) 400 A Icu (45 V) 00 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S5L 400 W MP R A S5L 400 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S5L 400 W MP In 20 A I LSI LI LSIG S5L 400 W MP In 400 A I LSI LI LSIG () The S5 400 mobile parts indicated on this page can be used in conjunction with S5 60 W FP fixed parts. Two different fixed parts are available for circuit-breakers S5 400 and S5 60. Fixed circuit-breaker S5 400: converted into the mobile part of a withdrawable circuit-breaker using kit SDA0 78 R (three-pole), SDA0 79 R (four-pole) can be used in conjunction with the fixed part for S5 400 (see codes on pages 7/8). converted into the mobile part of a withdrawable circuit-breaker using kit SDA R (three-pole), SDA R (four-pole) can be used in conjunction with the fixed part for S5 60. This page shows the codes for the mobile parts of withdrawable circuit-breakers which have already been converted and can be used in conjunction with the fixed parts for S5 60. Circuit-breaker S5 60 can be converted into the mobile part of a withdrawable circuit-breaker using kit SDA R (three-pole), SDA R (four-pole) and used in conjunction exclusively with the fixed parts for S5 60 (see codes on page 7/8). 7 7/7
254 Order codes SACE Isomax S5 circuit-breaker F FIED PSIS96 S5N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S5N 60 F F R A ES Spreaded extended front terminals S5N 60 F ES R A FC Cu Front terminals for copper cables S5N 60 F FC Cu R A R Threaded rear terminals S5N 60 F R R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S5N 60 F F In 60 A I LSI LI LSIG ES Spreaded extended front terminals S5N 60 F ES In 60 A I LSI LI LSIG FC Cu Front terminals for copper cables S5N 60 F FC Cu In 60 A I LSI LI LSIG R Threaded rear terminals S5N 60 F R In 60 A I LSI LI LSIG S5H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Im Thermomagnetic code SDA R Ith release poles 4 poles F Front terminals S5H 60 F F R A ES Spreaded extended front terminals S5H 60 F ES R A FC Cu Front terminals for copper cables S5H 60 F FC Cu R A R Threaded rear terminals S5H 60 F R R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S5H 60 F F In 60 A I LSI LI LSIG ES Spreaded extended front terminals S5H 60 F ES In 60 A I LSI LI LSIG FC Cu Front terminals for copper cables S5H 60 F FC Cu In 60 A I LSI LI LSIG R Threaded rear terminals S5H 60 F R In 60 A I LSI LI LSIG /8
255 Order codes SACE Isomax S5 circuit-breaker F FIED PSIS96 S5L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S5L 60 F F R A ES Spreaded extended front terminals S5L 60 F ES R A FC Cu Front terminals for copper cables S5L 60 F FC Cu R A R Threaded rear terminals S5L 60 F R R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S5L 60 F F In 60 A I LSI LI LSIG ES Spreaded extended front terminals S5L 60 F ES In 60 A I LSI LI LSIG FC Cu Front terminals for copper cables S5L 60 F FC Cu In 60 A I LSI LI LSIG R Threaded rear terminals S5L 60 F R In 60 A I LSI LI LSIG /9
256 Order codes SACE Isomax S5 circuit-breaker W WITHDRAWABLE Moving part S5N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5N 60 W MP R A PSIS96 Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5N 60 W MP In 60 A I LSI LI LSIG S5H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5H 60 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5H 60 W MP In 60 A I LSI LI LSIG S5L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S5L 60 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S5L 60 W MP In 60 A I LSI LI LSIG /40
257 Order codes SACE Isomax S6 circuit-breaker F FIED PSIS966 S6N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6N 60 F F R A EF Extended front terminals S6N 60 F EF R A FC CuAl Front terminals for copper/aluminium cables S6N 60 F FC CuAl* R A R Threaded rear terminals S6N 60 F R R A RC Rear terminals for cables S6N 60 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6N 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S6N 60 F EF In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6N 60 F FC CuAl* In 60 A I LSI LI LSIG R Threaded rear terminals S6N 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S6N 60 F RC In 60 A I LSI LI LSIG S6S 60 Iu (40 C) 60 A Icu (45 V) 50 ka Im Thermomagnetic code SDA R Ith release poles 4 poles F Front terminals S6S 60 F F R A EF Extended front terminals S6S 60 F EF R A FC CuAl Front terminals for copper/aluminium cables S6S 60 F FC CuAl* R A R Threaded rear terminals S6S 60 F R R A RC Rear terminals for cables S6S 60 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6S 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S6S 60 F EF In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6S 60 F FC CuAl* In 60 A I LSI LI LSIG R Threaded rear terminals S6S 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S6S 60 F RC In 60 A I LSI LI LSIG * Cable section x 240 mm 2 7/4
258 Order codes SACE Isomax S6 circuit-breaker F FIED PSIS966 S6H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6H 60 F F R A EF Extended front terminals S6H 60 F EF R A FC CuAl Front terminals for copper/aluminium cables S6H 60 F FC CuAl* R A R Threaded rear terminals S6H 60 F R R A RC Rear terminals for cables S6H 60 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6H 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S6H 60 F EF In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6H 60 F FC CuAl* In 60 A I LSI LI LSIG R Threaded rear terminals S6H 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S6H 60 F RC In 60 A I LSI LI LSIG S6L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6L 60 F F R A EF Extended front terminals S6L 60 F EF R A FC CuAl Front terminals for copper/aluminium cables S6L 60 F FC CuAl* R A R Threaded rear terminals S6L 60 F R R A RC Rear terminals for cables S6L 60 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6L 60 F F In 60 A I LSI LI LSIG EF Extended front terminals S6L 60 F EF In 60 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6L 60 F FC CuAl* In 60 A I LSI LI LSIG R Threaded rear terminals S6L 60 F R In 60 A I LSI LI LSIG RC Rear terminals for cables S6L 60 F RC In 60 A I LSI LI LSIG * Cable section 2 x 240 mm 2 7/42
259 Order codes SACE Isomax S6 circuit-breaker W WITHDRAWABLE Moving part S6N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S6N 60 W MP R A PSIS966 Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S6N 60 W MP In 60 A I LSI LI LSIG S6S 60 Iu (40 C) 60 A Icu (45 V) 50 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S6S 60 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S6S 60 W MP In 60 A I LSI LI LSIG S6H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S6H 60 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S6H 60 W MP In 60 A I LSI LI LSIG S6L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S6L 60 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6L 60 W MP In 60 A I LSI LI LSIG /4
260 Order codes SACE Isomax S6 circuit-breaker F FIED PSIS966 S6N 800 Iu (40 C) 800 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6N 800 F F R A EF Extended front terminals S6N 800 F EF R A FC CuAl Front terminals for copper/aluminium cables S6N 800 F FC CuAl* R A R Threaded rear terminals S6N 800 F R R A RC Rear terminals for cables S6N 60 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S6N 800 F F In 800 A I LSI LI LSIG EF Extended front terminals S6N 800 F EF In 800 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6N 800 F FC CuAl* In 800 A I LSI LI LSIG R Threaded rear terminals S6N 800 F R In 800 A I LSI LI LSIG RC Rear terminals for cables S6N 800 F RC In 800 A I LSI LI LSIG S6S 800 Iu (40 C) 800 A Icu (45 V) 50 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6S 800 F F R A EF Extended front terminals S6S 800 F EF R A FC CuAl Front terminals for copper/aluminium cables S6S 800 F FC CuAl* R A R Threaded rear terminals S6S 800 F R R A RC Rear terminals for cables S6S 800 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6S 800 F F In 800 A I LSI LI LSIG EF Extended front terminals S6S 800 F EF In 800 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6S 800 F FC CuAl* In 800 A I LSI LI LSIG R Threaded rear terminals S6S 800 F R In 800 A I LSI LI LSIG RC Rear terminals for cables S6S 800 F RC In 800 A I LSI LI LSIG /44 * Cable section x 85 mm 2
261 Order codes SACE Isomax S6 circuit-breaker F FIED PSIS966 S6H 800 Iu (40 C) 800 A Icu (45 V) 65 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6H 800 F F R A EF Extended front terminals S6H 800 F EF R A FC CuAl Front terminals for copper/aluminium cables S6H 800 F FC CuAl* R A R Threaded rear terminals S6H 800 F R R A RC Rear terminals for cables S6H 800 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6H 800 F F In 800 A I LSI LI LSIG EF Extended front terminals S6H 800 F EF In 800 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6H 800 F FC CuAl* In 800 A I LSIG LI LSIG R Threaded rear terminals S6H 800 F R In 800 A I 4 20 LSIG 6 22 LI 5 2 LSIG 9 25 RC Rear terminals for cables S6H 800 F RC In 800 A I LSI LI LSIG S6L 800 Iu (40 C) 800 A Icu (45 V) 00 ka Thermomagnetic Im code SDA R Ith release poles 4 poles F Front terminals S6L 800 F F R A EF Extended front terminals S6L 800 F EF R A FC CuAl Front terminals for copper/aluminium cables S6L 800 F FC CuAl* R A R Threaded rear terminals S6L 800 F R R A RC Rear terminals for cables S6L 800 F RC R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6L 800 F F In 800 A I LSI LI LSIG EF Extended front terminals S6L 800 F EF In 800 A I LSI LI LSIG 2 29 FC CuAl Front terminals for copper/aluminium cables S6L 800 F FC CuAl* In 800 A I LSI LI LSIG R Threaded rear terminals S6L 800 F R In 800 A I 8 44 LSI LI 9 45 LSIG 2 49 RC Rear terminals for cables S6L 800 F RC In 800 A I LSI LI LSIG * Cable section x 85 mm 2 7/45
262 Order codes SACE Isomax S6 circuit-breaker W WITHDRAWABLE Moving part S6N 800 Iu (40 C) 800 A Icu (45 V) 5 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S6N 800 W MP R A PSIS966 Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6N 800 W MP In 800 A I LSI LI LSIG S6S 800 Iu (40 C) 800 A Icu (45 V) 50 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S6S 800 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6S 800 W MP In 800 A I LSI LI 0 09 LSIG S6H 800 Iu (40 C) 800 A Icu (45 V) 65 ka Thermomagnetic Im code SDA R Ith release poles 4 poles S6H 800 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6H 800 W MP In 800 A I LSI LI LSIG S6L 800 Iu (40 C) 800 A Icu (45 V) 00 ka Im Thermomagnetic code SDA R Ith release poles 4 poles S6L 800 W MP R A Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6L 800 W MP In 800 A I LSI LI LSIG /46
263 Order codes SACE Isomax S7 circuit-breaker F FIED PSIS9620 S7S 250 Iu (40 C) 250 A Icu (45 V) 50 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S7S 250 F F In 000 A I LSI LI LSIG S7S 250 F F In 250 A I LSI LI LSIG EF Extended front terminals S7S 250 F EF In 000 A I LSI LI LSIG S7S 250 F EF In 250 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S7S 250 F FC CuAl In 000 A I LSI LI LSIG S7S 250 F FC CuAl In 250 A I LSI LI LSIG VR Vertical flat-bar rear terminals S7S 250 F VR In 000 A I LSI LI LSIG S7S 250 F VR In 250 A I LSI LI LSIG HR Horizontal flat-bar rear terminals S7S 250 F HR In 000 A I LSI LI LSIG S7S 250 F HR In 250 A I LSI LI LSIG S7H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S7H 250 F F In 000 A I LSI LI LSIG S7H 250 F F In 250 A I LSI LI LSIG EF Extended front terminals S7H 250 F EF In 000 A I LSI LI LSIG S7H 250 F EF In 250 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S7H 250 F FC CuAl In 000 A I LSI LI LSIG S7H 250 F FC CuAl In 250 A I LSI LI LSIG 9 20 VR Vertical flat-bar rear terminals S7H 250 F VR In 000 A I LSI LI LSIG S7H 250 F VR In 250 A I LSI LI LSIG HR Horizontal flat-bar rear terminals S7H 250 F HR In 000 A I LSI LI LSIG S7H 250 F HR In 250 A I LSI LI LSIG /47
264 Order codes SACE Isomax S7 circuit-breaker F FIED PSIS9620 S7L 250 Iu (40 C) 250 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S7L 250 F F In 000 A I LSI LI LSIG S7L 250 F F In 250 A I LSI LI LSIG EF Extended front terminals S7L 250 F EF In 000 A I LSI LI LSIG S7L 250 F EF In 250 A I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S7L 250 F FC CuAl In 000 A I LSI LI LSIG S7L 250 F FC CuAl In 250 A I LSI LI LSIG VR Vertical flat-bar rear terminals S7L 250 F VR In 000 A I LSI LI LSIG S7L 250 F VR In 250 A I LSI LI LSIG HR Horizontal flat-bar rear terminals S7L 250 F HR In 000 A I LSI LI LSIG S7L 250 F HR In 250 A I LSI LI LSIG W WITHDRAWABLE Moving part S7S 250 Iu (40 C) 250 A Icu (45 V) 50 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S7S 250 W MP In 000 A I LSI LI LSIG S7S 250 W MP In 250 A I LSI 82 8 LI 89 8 LSIG PSIS9620 S7H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S7H 250 W MP In 000 A I LSI LI LSIG S7H 250 W MP In 250 A I LSI LI LSIG S7L 250 Iu (40 C) 250 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S7L 250 W MP In 000 A I LSI LI LSIG S7L 250 W MP In 250 A I LSI LI LSIG /48
265 Order codes SACE Isomax S7 circuit-breaker F FIED PSIS9620 S7S 600 Iu (40 C) 600 A Icu (45 V) 50 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S7S 600 F F In 600 A I LSI LI LSIG EF Extended front terminals S7S 600 F EF In 600 A I LSI LI LSIG VR Vertical flat-bar rear terminals S7S 600 F VR In 600 A I LSI LI LSIG HR Horizontal flat-bar rear terminals S7S 600 F HR In 600 A I LSI LI LSIG S7H 600 Iu (40 C) 600 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S7H 600 F F In 600 A I LSI LI LSIG EF Extended front terminals S7H 600 F EF In 600 A I LSI LI LSIG VR Vertical flat-bar rear terminals S7H 600 F VR In 600 A I LSI LI LSIG HR Horizontal flat-bar rear terminals S7H 600 F HR In 600 A I LSI LI LSIG S7L 600 Iu (40 C) 600 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S7L 600 F F In 600 A I LSI LI LSIG EF Extended front terminals S7L 600 F EF In 600 A I LSI LI LSIG VR Vertical flat-bar rear terminals S7L 600 F VR In 600 A I LSI LI LSIG HR Horizontal flat-bar rear terminals S7L 600 F HR In 600 A I LSI LI LSIG /49
266 Order codes SACE Isomax S7 circuit-breaker W WITHDRAWABLE Moving part S7S 600 Iu (40 C) 600 A Icu (45 V) 50 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S7S 600 W MP In 600 A I LSI LI LSIG PSIS9620 S7H 600 Iu (40 C) 600 A Icu (45 V) 65 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S7H 600 W MP In 600 A I LSI LI LSIG S7L 600 Iu (40 C) 600 A Icu (45 V) 00 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S7L 600 W MP In 600 A I LSI LI LSIG /50
267 Order codes SACE Isomax S8 circuit-breaker F FIED GSIS908 S8H 2000 Iu (40 C) 2000 A Icu (45 V) 85 ka Microprocessor-based PR22 code SDA R release P poles 4 poles F Front terminals S8H 2000 F F In 600 A LSI LSIG S8H 2000 F F In 2000 A LSI LSIG VR Vertical flat-bar rear terminals S8H 2000 F VR In 600 A LSI LSIG S8H 2000 F VR In 2000 A LSI LSIG S8V 2000 Iu (40 C) 2000 A Icu (45 V) 20 ka Microprocessor-based PR22 code SDA R release P poles 4 poles F Front terminals S8V 2000 F F In 600 A LSI LSIG S8V 2000 F F In 2000 A LSI LSIG VR Vertical flat-bar rear terminals S8V 2000 F VR In 600 A LSI LSIG S8V 2000 F VR In 2000 A LSI LSIG S8H 2500 Iu (40 C) 2500 A Icu (45 V) 85 ka Microprocessor-based PR22 code SDA R release P poles 4 poles F Front terminals S8H 2500 F F In 2500 A LSI LSIG VR Vertical flat-bar rear terminals S8H 2500 F VR In 2500 A LSI LSIG S8V 2500 Iu (40 C) 2500 A Icu (45 V) 20 ka Microprocessor-based PR22 code SDA R release P poles 4 poles F Front terminals S8V 2500 F F In 2500 A LSI LSIG VR Vertical flat-bar rear terminals S8V 2500 F VR In 2500 A LSI LSIG S8H 200 Iu (40 C) 200 A Icu (45 V) 85 ka Microprocessor-based PR22 code SDA R release P poles 4 poles VR Vertical flat-bar rear terminals S8H 200 F VR In 200 A LSI LSIG S8V 200 Iu (40 C) 200 A Icu (45 V) 20 ka Microprocessor-based PR22 code SDA R release P poles 4 poles VR Vertical flat-bar rear terminals S8V 200 F VR In 200 A LSI LSIG /5
268 Order codes SACE Isomax S2 00 current-limiting circuit-breaker F FIED GSIS950 S2 00 Iu (40 C) 00 A Icu (45 V) 70 ka Thermomagnetic release FC Cu Front terminals for copper cables S2 00 F FC Cu R 0A 5007 S2 00 F FC Cu R.6 6A 5008 S2 00 F FC Cu R A 5009 S2 00 F FC Cu R 4 40A 500 S2 00 F FC Cu R 6. 6A 50 S2 00 F FC Cu R 0 00A 502 S2 00 F FC Cu R A 50 S2 00 F FC Cu R 6 60A 504 S2 00 F FC Cu R A 505 S2 00 F FC Cu R A 506 S2 00 F FC Cu R 2 20A 507 S2 00 F FC Cu R A 508 S2 00 F FC Cu R A 509 S2 00 F FC Cu R 6 60A 5020 S2 00 F FC Cu R A 502 S2 00 F FC Cu R A 5022 R Threaded rear terminals S2 00 F R R 0A 509 S2 00 F R R.6 6A 5040 S2 00 F R R A 504 S2 00 F R R 4 40A 5042 S2 00 F R R 6. 6A 504 S2 00 F R R 0 00A 5044 S2 00 F R R A 5045 S2 00 F R R 6 60A 5046 S2 00 F R R A 5047 S2 00 F R R A 5048 S2 00 F R R 2 20A 5049 S2 00 F R R A 5050 S2 00 F R R A 505 S2 00 F R R 6 60A 5052 S2 00 F R R A 505 S2 00 F R R A 5054 I m code SDA R poles 7 P PLUG-IN GSIS950 Moving part S2 00 Iu (40 C) 00 A Icu (45 V) 70 ka Thermomagnetic release S2 00 P MP R 0A 507 S2 00 P MP R.6 6A 5072 S2 00 P MP R A 507 S2 00 P MP R 4 40A 5074 S2 00 P MP R 6. 6A 5075 S2 00 P MP R 0 00A 5076 S2 00 P MP R A 5077 S2 00 P MP R 6 60A 5078 S2 00 P MP R A 5079 S2 00 P MP R A 5080 S2 00 P MP R 2 20A 508 S2 00 P MP R A 5082 S2 00 P MP R A 508 S2 00 P MP R 6 60A 5084 S2 00 P MP R A 5085 S2 00 P MP R A 5086 I m code SDA R poles 7/52
269 Order codes SACE Isomax S current-limiting circuit-breaker F FIED GSIS95 S 25 Iu (40 C) 25 A Icu (45 V) 200 ka Thermomagnetic I m code SDA R release poles 4 poles F Front terminals S 25 F F R 2 500A S 25 F F R A S 25 F F R A S 25 F F R A S 25 F F R A EF Extended front terminals S 25 F EF R 2 500A S 25 F EF R A S 25 F EF R A S 25 F EF R A S 25 F EF R A FC Cu Front terminals for copper cables S 25 F FC Cu R 2 500A S 25 F FC Cu R A S 25 F FC Cu R A S 25 F FC Cu R A S 25 F FC Cu R A FC CuAl Front terminals for copper/aluminium cables S 25 F FC CuAl R 2 500A S 25 F FC CuAl R A S 25 F FC CuAl R A S 25 F FC CuAl R A S 25 F FC CuAl R A R Threaded rear terminals S 25 F R R 2 500A S 25 F R R A S 25 F R R A S 25 F R R A S 25 F R R A RC Rear terminals for cables S 25 F RC R 2 500A S 25 F RC R A S 25 F RC R A S 25 F RC R A S 25 F RC R A /5
270 Order codes SACE Isomax S current-limiting circuit-breaker F FIED GSIS95 S 200 Iu (40 C) 200 A Icu (45 V) 200 ka Thermomagnetic Im code SDA R release poles 4 poles F Front terminals S 200 F F R A S 200 F F R A S 200 F F R A EF Extended front terminals S 200 F EF R A S 200 F EF R A S 200 F EF R A FC Cu Front terminals for copper cables S 200 F FC Cu R A S 200 F FC Cu R A S 200 F FC Cu R A FC CuAl Front terminals for copper/aluminium cables S 200 F FC CuAl R A S 200 F FC CuAl R A S 200 F FC CuAl R A R Threaded rear terminals S 200 F R R A S 200 F R R A S 200 F R R A RC Rear terminals for cables S 200 F RC R A S 200 F RC R A S 200 F RC R A P PLUG-IN GSIS95 Moving part S 25 Iu (40 C) 25 A Icu (45 V) 200 ka Thermomagnetic code SDA R release poles 4 poles S 25 P MP R 2 500A S 25 P MP R A S 25 P MP R A S 25 P MP R A S 25 P MP R A S 200 Iu (40 C) 200 A Icu (45 V) 200 ka Thermomagnetic code SDA R release poles 4 poles S 200 P MP R A S 200 P MP R A S 200 P MP R A I m I m 7 7/54
271 Order codes SACE Isomax S current-limiting circuit-breaker W WITHDRAWABLE GSIS95 Moving part S 25 Iu (40 C) 25 A Icu (45 V) 200 ka Thermomagnetic Im code SDA R release poles 4 poles S 25 W MP R 2 500A S 25 W MP R A S 25 W MP R A S 25 W MP R A S 25 W MP R A S 200 Iu (40 C) 200 A Icu (45 V) 200 ka Thermomagnetic code SDA R release poles 4 poles S 200 W MP R A S 200 W MP R A S 200 W MP R A I m 7 7/55
272 Order codes SACE Isomax S4 current-limiting circuit-breaker F FIED GSIS952 S4 250 Iu (40 C) 250 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S4 250 F F In00 I LSI LI LSIG S4 250 F F In60 I LSI LI LSIG S4 250 F F In250 I LSI LI LSIG EF Extended front terminals S4 250 F EF In00 I LSI LI LSIG S4 250 F EF In60 I LSI LI LSIG S4 250 F EF In250 I LSI LI LSIG FC Cu Front terminals for copper cables S4 250 F FC Cu In00 I LSI LI LSIG S4 250 F FC Cu In60 I LSI LI LSIG S4 250 F FC Cu In250 I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S4 250 F FC CuAl In00 I LSI LI LSIG S4 250 F FC CuAl In60 I LSI LI LSIG S4 250 F FC CuAl In250 I LSI LI LSIG R Threaded rear terminals S4 250 F R In00 I LSI LI LSIG S4 250 F R In60 I LSI LI LSIG S4 250 F R In250 I LSI LI LSIG RC Rear terminals for cables S4 250 F RC In00 I LSI LI LSIG S4 250 F RC In60 I LSI LI LSIG S4 250 F RC In250 I LSI LI LSIG /56
273 Order codes SACE Isomax S4 current-limiting circuit-breaker P PLUG-IN Moving part S4 250 Iu (40 C) 250 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4 250 P MP In00 I LSI LI LSIG S4 250 P MP In60 I LSI LI LSIG S4 250 P MP In250 I LSI LI LSIG GSIS952 GSIS952 W WITHDRAWABLE Moving part S4 250 Iu (40 C) 250 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles S4 250 W MP In00 I LSI LI LSIG S4 250 W MP In60 I LSI LI LSIG S4 250 W MP In250 I LSI LI LSIG /57
274 Order codes SACE Isomax S6 current-limiting circuit-breaker F FIED GSIS95 S6 400 Iu (40 C) 400 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles 4 poles P poles 4 poles F Front terminals S6 400 F F In20 I LSI LI LSIG S6 400 F F In400 I LSI LI LSIG EF Extended front terminals S6 400 F EF In20 I LSI LI LSIG S6 400 F EF In400 I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6 400 F FC CuAl In20 I LSI LI LSIG S6 400 F FC CuAl In400 I LSI LI LSIG R Threaded rear terminals S6 400 F R In20 I LSI LI LSIG S6 400 F R In400 I LSI LI LSIG RC Rear terminals for cables S6 400 F RC In20 I LSI LI LSIG S6 400 F RC In400 I LSI LI LSIG S6 60 Iu (40 C) 60 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles F Front terminals S6 60 F F In60 I LSI LI LSIG EF Extended front terminals S6 60 F EF In60 I LSI LI LSIG FC CuAl Front terminals for copper/aluminium cables S6 60 F FC CuAl In60 I LSI LI LSIG R Threaded rear terminals S6 60 F R In60 I LSI LI LSIG RC Rear terminals for cables S6 60 F RC In60 I LSI LI LSIG /58
275 Order codes SACE Isomax S6 current-limiting circuit-breaker W WITHDRAWABLE Moving part S6 400 Iu (40 C) 400 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6 400 W MP In20 I LSI LI LSIG S6 400 W MP In400 I LSI LI LSIG GSIS95 S6 60 Iu (40 C) 60 A Icu (45 V) 200 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles 4 poles poles 4 poles S6 60 W MP In60 I LSI LI LSIG /59
276 Order codes SACE Isomax S2 80 circuit-breaker for motor protection F FIED GSIS954 S2 80 Iu (40 C) 80 A Icu (45 V) 70 ka Magnetic only release FC Cu Front terminals for copper cables S2 80 F FC Cu R A 502 S2 80 F FC Cu R.6 2A 5022 S2 80 F FC Cu R 2 26A 502 S2 80 F FC Cu R 2.5 2A 5024 S2 80 F FC Cu R.2 42A 5025 S2 80 F FC Cu R 4 52A 5026 S2 80 F FC Cu R 5 65A 5027 S2 80 F FC Cu R A 5028 S2 80 F FC Cu R 8.5 0A 5029 S2 80 F FC Cu R 45A S2 80 F FC Cu R 2.5 6A 5024 S2 80 F FC Cu R 6 20A S2 80 F FC Cu R A 5024 S2 80 F FC Cu R 25 25A S2 80 F FC Cu R 2 45A S2 80 F FC Cu R A S2 80 F FC Cu R A S2 80 F FC Cu R 6 820A S2 80 F FC Cu R A R Threaded rear terminals S2 80 F R R A S2 80 F R R.6 2A 5025 S2 80 F R R 2 26A S2 80 F R R 2.5 2A 5025 S2 80 F R R.2 42A S2 80 F R R 4 52A S2 80 F R R 5 65A S2 80 F R R A S2 80 F R R 8.5 0A S2 80 F R R 45A S2 80 F R R 2.5 6A S2 80 F R R 6 20A 5026 S2 80 F R R A S2 80 F R R 25 25A 5026 S2 80 F R R 2 45A S2 80 F R R A S2 80 F R R A S2 80 F R R 6 820A S2 80 F R R A Im code SDA R poles 7 P PLUG-IN GSIS954 Moving part S2 80 Iu (40 C) 80 A Icu (45 V) 70 ka Magnetic only release S2 80 P MP R A S2 80 P MP R.6 2A S2 80 P MP R 2 26A 5027 S2 80 P MP R 2.5 2A S2 80 P MP R.2 4A 5027 S2 80 P MP R 4 52A S2 80 P MP R 5 65A S2 80 P MP R A S2 80 P MP R 8.5 0A S2 80 P MP R 45A S2 80 P MP R 2.5 6A S2 80 P MP R 6 20A S2 80 P MP R A 5028 S2 80 P MP R 25 25A S2 80 P MP R 2 45A 5028 S2 80 P MP R A S2 80 P MP R A S2 80 P MP R 6 820A S2 80 P MP R A I m code SDA R poles 7/60
277 Order codes SACE Isomax S circuit-breaker for motor protection F FIED PSIS9607 SN 60 Iu (40 C) 60 A Icu (45 V) 5 ka Magnetic only release code SDA R poles F Front terminals SN 60 F F R A SN 60 F F R A 4778 SN 60 F F R A SN 60 F F R A SN 60 F F R A SN 60 F F R A SN 60 F F R A SN 60 F F R A Im SH 60 Iu (40 C) 60 A Icu (45 V) 65 ka Magnetic only release code SDA R poles F Front terminals SH 60 F F R A 4585 SH 60 F F R A 4586 SH 60 F F R A 4587 SH 60 F F R A 4588 SL 60 Iu (40 C) 60 A Icu (45 V) 85 ka Magnetic only release code SDA R poles F Front terminals SL 60 F F R A SL 60 F F R A SL 60 F F R A SL 60 F F R A SN 250 Iu (40 C) 250 A Icu (45 V) 5 ka Magnetic only release code SDA R poles F Front terminals SN 250 F F R A 4865 SN 250 F F R A SH 250 Iu (40 C) 250 A Icu (45 V) 65 ka Magnetic only release code SDA R poles F Front terminals SH 250 F F R A SH 250 F F R A I m Im Im I m SL 250 Iu (40 C) 250 A Icu (45 V) 85 ka Magnetic only release code SDA R poles F Front terminals SL 250 F F R A SL 250 F F R A I m 7 Note Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80. 7/6
278 Order codes SACE Isomax S4 circuit-breaker for motor protection F FIED S4N 60 Iu (40 C) 60 A Icu (45 V) 5 ka Microprocessor-based release PR22 MP F Front terminals S4N 60 F F In 00A LRIU 509 S4N 60 F F In 60A LRIU 5040 code SDA R poles PSIS960 S4H 60 Iu (40 C) 60 A Icu (45 V) 65 ka Microprocessor-based release PR22 MP F Front terminals S4H 60 F F In 00A LRIU S4H 60 F F In 60A LRIU code SDA R poles S4L 60 Iu (40 C) 60 A Icu (45 V) 00 ka Microprocessor-based release F Front terminals S4L 60 F F In 00A LRIU S4L 60 F F In 60A LRIU 5055 S4N 250 Iu (40 C) 250 A Icu (45 V) 5 ka Microprocessor-based release F Front terminals S4N 250 F F In 200A LRIU 504 S4H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based release F Front terminals S4H 250 F F In 200A LRIU S4L 250 Iu (40 C) 250 A Icu (45 V) 00 ka Microprocessor-based release PR22 MP PR22 MP PR22 MP PR22 MP F Front terminals S4L 250 F F In 200A LRIU code SDA R poles code SDA R poles code SDA R poles code SDA R poles 7 Note Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80. 7/62
279 Order codes SACE Isomax S5-S6-S7 circuit-breakers for motor protection F FIED S5N 400 Iu (40 C) 400 A Icu (45 V) 5 ka Microprocessor-based release PR22 MP F Front terminals S5N 400 F F In 20A LRIU 5042 code SDA R poles PSIS96 S5H 400 Iu (40 C) 400 A Icu (45 V) 65 ka Microprocessor-based release PR22 MP F Front terminals S5H 400 F F In 20A LRIU 4505 code SDA R poles S5L 400 Iu (40 C) 400 A Icu (45 V) 00 ka Microprocessor-based release F Front terminals S5L 400 F F In 20A LRIU 5055 S6N 800 Iu (40 C) 800 A Icu (45 V) 5 ka Microprocessor-based release PR22 MP PR22 MP F Front terminals S6N 800 F F In 60A LRIU 504 code SDA R poles code SDA R poles PSIS966 S6H 800 Iu (40 C) 800 A Icu (45 V) 65 ka Microprocessor-based release PR22 MP F Front terminals S6H 800 F F In 60A LRIU code SDA R poles S6L 800 Iu (40 C) 800 A Icu (45 V) 00 ka Microprocessor-based release F Front terminals S6L 800 F F In 60A LRIU S7S 250 Iu (40 C) 250 A Icu (45 V) 50 ka Microprocessor-based release PR22 MP PR22 MP F Front terminals S7S 250 F F In 000A LRIU 5044 code SDA R poles code SDA R poles S7H 250 Iu (40 C) 250 A Icu (45 V) 65 ka Microprocessor-based release PR22 MP F Front terminals S7H 250 F F In 000A LRIU 4505 code SDA R poles 7 PSIS9620 Note Withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80. 7/6
280 Order codes SACE Isomax S-S4-S6 current-limiting circuit-breakers for motor protection F FIED S 25 Iu (40 C) 25 A Icu (45 V) 200 ka Magnetic only release code SDA R poles F Front terminals S 25 F F R A 4587 S 25 F F R A 4588 S 25 F F R A 4589 S 25 F F R A 4590 Im GSIS95 S 200 Iu (40 C) 200 A Icu (45 V) 200 ka Magnetic only release code SDA R poles F Front terminals S 200 F F R A 465 S 200 F F R A S 200 F F R A I m S4 250 Iu (40 C) 250 A Icu (45 V) 200 ka Microprocessor-based release PR22 MP code SDA R poles F Front terminals S4 250 F F In 00A LRIU S4 250 F F In 60A LRIU 4659 S4 250 F F In 200A LRIU 4866 GSIS952 S6 400 Iu (40 C) 400 A Icu (45 V) 200 ka Microprocessor-based release GSIS95 code SDA R poles F Front terminals S6 400 F F In 20A LRIU S6 60 Iu (40 C) 60 A Icu (45 V) 200 ka Microprocessor-based release PR22 MP PR22 MP code SDA R poles F Front terminals S6 60 F F In 400A LRIU 4778 S6 60 F F In 60A LRIU Note Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80. 7/64
281 Order codes SACE Isomax S circuit-breakers for applications up to 000V F FIED PSIS9607 SL 60 Iu (40 C) 60 A Icu (000 V) 6 ka Thermomagnetic release AC ~ F Front terminals SL 60 F F R 2 Im 500A 5046 SL 60 F F R 50 Im 500A 5047 SL 60 F F R 80 Im 800A 5048 SL 60 F F R 00 Im 000A 5049 SL 60 F F R 25 Im 250A 5044 SL 60 F F R 60 Im 600A code SDA R poles SL 60 Iu (40 C) 60 A Icu (000 V) 40 ka Thermomagnetic release code SDA R 4 poles F Front terminals SL 60 F F (N00%) R 2 Im 500A 5044 SL 60 F F (N00%) R 50 Im 500A SL 60 F F (N00%) R 80 Im 800A SL 60 F F (N00%) R 00 Im 000A SL 60 F F (N00%) R 25 Im 250A SL 60 F F (N00%) R 60 Im 600A SL 250 Iu (40 C) 250 A Icu (000 V) 40 ka Thermomagnetic release code SDA R 4 poles F Front terminals SL 250 F F (N00%) R 200 Im 2000A SL 250 F F (N00%) R 250 Im 2500A S 25 Iu (40 C) 25 A Icu (000 V) 0 ka Thermomagnetic release F Front terminals S 25 F F R 2 Im 500A 5045 S 60 F F R 50 Im 500A S 60 F F R 80 Im 800A 5045 S 60 F F R 00 Im 000A S 60 F F R 25 Im 250A S4L 60 Iu (40 C) 60 A Icu (000 V) 8 ka code SDA R poles Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles P poles DC DC AC ~ F Front terminals S4L 60 F F In 00 A LI LSI LSIG PSIS960 S4L 250 Iu (40 C) 250 A Icu (000 V) 8 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles P poles F Front terminals S4L 250 F F In 250 A LI LSI 5046 LSIG S4 250 Iu (40 C) 250 A Icu (000 V) 0 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles P poles F Front terminals S4 250 F F In 250 A LI 5046 LSI LSIG /65
282 Order codes SACE Isomax S circuit-breakers for applications up to 000V F FIED S5L 400 Iu (40 C) 400 A Icu (000 V) 40 ka Thermomagnetic release code SDA R 4 poles F Front terminals S5L 400 F F (N00%) R 400 Im 4000A DC PSIS96 S6L 60 Iu (40 C) 60 A Icu (000 V) 40 ka Thermomagnetic release code SDA R 4 poles F Front terminals S6L 60 F F (N00%) R 60 Im 600A DC S6L 800 Iu (40 C) 800 A Icu (000 V) 50 ka Thermomagnetic release code SDA R 4 poles F Front terminals S6L 800 F F (N00%) R 800 Im 8000A DC PSIS966 S5L 400 Iu (40 C) 400 A Icu (000 V) 8 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles P poles S5L 400 F F In 400 A LI LSI 5058 LSIG PSIS955 GSIS95 S6L 60 Iu (40 C) 60 A Icu (000 V) 2 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles P poles S6L 60 F F In 60 A LI LSI LSIG 5047 S6L 800 Iu (40 C) 800 A Icu (000 V) 2 ka Microprocessor-based PR2 code SDA R PR22 code SDA R release P poles P poles F Front terminals S6L 800 F F In 800 A LI 5054 LSI 5055 LSIG 5056 S6 60 Iu (40 C) 60 A Icu (000 V) 0 ka Microprocessor-based PR2 code SDA R PR22 code SDA R P P release poles poles F Front terminals S4 60 F F In 60 A LI LSI 5047 LSIG SD/S6D/S7D Iu (40 C) 20/800/600 A Switch-disconnector F Front terminals SD 20 F F S6D 800 F F S7D 600 F F code SDA R poles 7/66
283 Order codes SACE Isomax S2D switch-disconnectors F FIED S2D 25 Iu (40 C) 25 A Icw (s) 2.2 ka Icm (45 V). ka PSIS9604 Switch-disconnector code SDA R poles 4 poles FC Cu Front terminals for copper cables S2D 25 F FC Cu FC CuAl Front terminals for copper/aluminium cables S2D 25 F FC CuAl* S2D 25 F FC CuAl** EF Extended front terminals S2D 25 F EF R Threaded rear terminals S2D 25 F R S2D 60 Iu (40 C) 60 A Icw (s) 2.2 ka Icm (45 V). ka Switch-disconnector code SDA R poles 4 poles FC Cu Front terminals for copper cables S2D 60 F FC Cu FC CuAl Front terminals for copper/aluminium cables S2D 60 F FC CuAl* S2D 60 F FC CuAl** EF Extended front terminals S2D 60 F EF R Threaded rear terminals S2D 60 F R P PLUG-IN Moving part S2D 25 Iu (40 C) 25 A Icw (s) 2.2 ka Icm (45 V). ka PSIS9604 Switch-disconnector code SDA R poles 4 poles S2D 25 P MP S2D 60 Iu (40 C) 60 A Icw (s) 2.2 ka Icm (45 V). ka Switch-disconnector code SDA R poles 4 poles S2D 60 P MP * Cable section x mm 2 ** Cable section x mm 2 7 7/67
284 Order codes SACE Isomax SD switch-disconnectors F FIED SD 00 Iu (40 C) 00 A Icw (s) 6.5 ka Icm (45 V) 0 ka PSIS9607 Switch-disconnector code SDA R poles 4 poles F Front terminals SD 00 F F EF Extended front terminals SD 00 F EF FC Cu Front terminals for copper cables SD 00 F FC Cu FC CuAl Front terminals for copper/aluminium cables SD 00 F FC CuAl R Threaded rear terminals SD 00 F R RC Rear terminals for cables SD 00 F RC SD 60 Iu (40 C) 60 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles F Front terminals SD 60 F F EF Extended front terminals SD 60 F EF FC Cu Front terminals for copper cables SD 60 F FC Cu FC CuAl Front terminals for copper/aluminium cables SD 60 F FC CuAl R Threaded rear terminals SD 60 F R RC Rear terminals for cables SD 60 F RC P PLUG-IN SD 00 Iu (40 C) 00 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 00 P MP PSIS9607 SD 60 Iu (40 C) 60 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 60 P MP W WITHDRAWABLE SD 00 Iu (40 C) 00 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 00 W MP PSIS9607 SD 60 Iu (40 C) 60 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 60 W MP /68
285 Order codes SACE Isomax SD switch-disconnectors F FIED SD 250 Iu (40 C) 250 A Icw (s) 6.5 ka Icm (45 V) 0 ka PSIS9607 Switch-disconnector code SDA R poles 4 poles F Front terminals SD 250 F F EF Extended front terminals SD 250 F EF FC Cu Front terminals for copper cables SD 250 F FC Cu FC CuAl Front terminals for copper/aluminium cables SD 250 F FC CuAl R Threaded rear terminals SD 250 F R RC Rear terminals for cables SD 250 F RC SD 20 Iu (40 C) 20 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles F Front terminals SD 20 F F EF Extended front terminals SD 20 F EF FC Cu Front terminals for copper cables SD 20 F FC Cu FC CuAl Front terminals for copper/aluminium cables SD 20 F FC CuAl R Threaded rear terminals SD 20 F R RC Rear terminals for cables SD 20 F RC P PLUG-IN SD 250 Iu (40 C) 250 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 250 P MP PSIS9607 SD 20 Iu (40 C) 20 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 20 P MP W WITHDRAWABLE SD 250 Iu (40 C) 250 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 250 W MP PSIS9607 SD 20 Iu (40 C) 20 A Icw (s) 6.5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles SD 20 W MP /69
286 Order codes SACE Isomax S6D switch-disconnectors F FIED S6D 400 Iu (40 C) 400 A Icw (s) 5 ka Icm (45 V) 0 ka GSIS956 Switch-disconnector code SDA R poles 4 poles F Front terminals S6D 400 F F EF Extended front terminals S6D 400 F EF FC CuAl Front terminals for copper/aluminium cables S6D 400 F FC CuAl R Threaded rear terminals S6D 400 F R RC Rear terminals for cables S6D 400 F RC S6D 60 Iu (40 C) 60 A Icw (s) 5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles F Front terminals S6D 60 F F EF Extended front terminals S6D 60 F EF FC CuAl Front terminals for copper/aluminium cables S6D 60 F FC CuAl R Threaded rear terminals S6D 60 F R RC Rear terminals for cables S6D 60 F RC S6D 800 Iu (40 C) 800 A Icw (s) 5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles F Front terminals S6D 800 F F EF Extended front terminals S6D 800 F EF FC CuAl Front terminals for copper/aluminium cables S6D 800 F FC CuAl R Threaded rear terminals S6D 800 F R RC Rear terminals for cables S6D 800 F RC W WITHDRAWABLE S6D 400 Iu (40 C) 400 A Icw (s) 5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles S6D 400 W MP GSIS956 S6D 60 Iu (40 C) 60 A Icw (s) 5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles S6D 60 W MP S6D 800 Iu (40 C) 800 A Icw (s) 5 ka Icm (45 V) 0 ka Switch-disconnector code SDA R poles 4 poles S6D 800 W MP /70
287 Order codes SACE Isomax S7D switch-disconnectors F FIED S7D 000 Iu (40 C) 000 A Icw (s) 25 ka Icm (45 V) 52.5 ka Switch-disconnector code SDA R poles 4 poles F Front terminals S7D 000 F F EF Extended front terminals S7D 000 F EF FC CuAl Front terminals for copper/aluminium cables S7D 000 F FC CuAl VR Vertical flat-bar rear terminals S7D 000 F VR HR Horizontal flat-bar rear terminals S7D 000 F HR PSIS9625 S7D 250 Iu (40 C) 250 A Icw (s) 25 ka Icm (45 V) 52.5 ka Switch-disconnector code SDA R poles 4 poles F Front terminals S7D 250 F F EF Extended front terminals S7D 250 F EF FC CuAl Front terminals for copper/aluminium cables S7D 250 F FC CuAl VR Vertical flat-bar rear terminals S7D 250 F VR HR Horizontal flat-bar rear terminals S7D 250 F HR S7D 600 Iu (40 C) 600 A Icw (s) 25 ka Icm (45 V) 52.5 ka Switch-disconnector code SDA R poles 4 poles F Front terminals S7D 600 F F EF Extended front terminals S7D 600 F EF VR Vertical flat-bar rear terminals S7D 600 F VR HR Horizontal flat-bar rear terminals S7D 600 F HR W WITHDRAWABLE S7D 000 Iu (40 C) 000 A Icw (s) 25 ka Icm (45 V) 52.5 ka Switch-disconnector code SDA R poles 4 poles S7D 000 W MP PSIS9625 S7D 250 Iu (40 C) 250 A Icw (s) 25 ka Icm (45 V) 52.5 ka Switch-disconnector code SDA R poles 4 poles S7D 60 W MP S7D 600 Iu (40 C) 600 A Icw (s) 25 ka Icm (45 V) 52.5 ka Switch-disconnector code SDA R poles 4 poles S7D 600 W MP /7
288 Order codes SACE Isomax S8D switch-disconnectors F FIED S8D 2000 Iu (40 C) 2000 A Icw (s) 40 ka Icm (45 V) 85 ka Switch-disconnector code SDA R poles 4 poles F Front terminals S8D 2000 F F VR Vertical flat-bar rear terminals S8D 2000 F VR S8D 2500 Iu (40 C) 2500 A Icw (s) 40 ka Icm (45 V) 85 ka GSIS949 Switch-disconnector code SDA R poles 4 poles F Front terminals S8D 2500 F F VR Vertical flat-bar rear terminals S8D 2500 F VR S8D 200 Iu (40 C) 200 A Icw (s) 40 ka Icm (45 V) 85 ka Switch-disconnector code SDA R poles 4 poles VR Vertical flat-bar rear terminals S8D 200 F VR /72
289 Order codes SACE Isomax S accessories Duty releases GSIS900 Shunt opening releases Type code SDA R S-S2 S-S4-S5 S6-S7 S V AC 48 V AC - 60 V DC V AC V AC V AC 4 2 V DC V DC V DC 05 0 V DC V DC V DC 0 2 V DC V AC / DC V AC / DC V AC / DC V AC / V DC V AC V DC V AC V DC V AC V AC V DC V DC - 24 V AC V AC / DC V DC V DC / AC V AC V DC / V AC V DC / V AC V AC GSIS900 Shunt closing releases Type code SDA R S8 24 V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 60 Hz V AC 60 Hz V AC 60 Hz V AC 60 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V DC V DC V DC V DC V DC V DC V DC /7
290 Order codes SACE Isomax S accessories Undervoltage releases GSIS9002 Type code SDA R S-S2 S-S4-S5 S6-S7 S8 24 V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC 50 Hz V AC 60 Hz V AC V AC V AC V AC 60 Hz V AC V AC 60 Hz V AC 60 Hz V AC V AC 60 Hz V AC 60 Hz V AC V AC V DC V DC V DC V DC V DC V DC V DC V DC Undervoltage releases + time-lag device GSIS9042 Type code SDA R S-S4-S5 S6-S7 S V AC V AC/DC V AC/DC V AC/DC V AC/DC /25 V AC/DC /250 V AC/DC GSIS90 Connectors for duty releases Type code SDA R S-S2 S-S4-S5-S6 S7 for fixed circuit-breakers - Lm 865 for fixed circuit-breakers - L2m 752 for fixed circuit-breakers - Lm 4209 for fixed circuit-breakers - L2m for plug-in or withdrawable circuit-breakers - Lm 866 for withdrawable circuit-breakers - Lm 420 for withdrawable circuit-breakers - L2m flying 9-pole socket-plug - L0,6m extension for testing auxiliary circuits with the circuit-breaker racked out /74
291 Order codes SACE Isomax S accessories Electrical signalling GSIS9004 Auxiliary contacts Type code SDA R S-S2 S-S4-S5 S6-S7 S8 2 open/closed change-over contacts open/closed change-over contacts and release tripped signal NO, NC and release not tripped signal 2577 NO, NC and release tripped signal open/closed change-over contacts 4756 Auxiliary contacts for digital signals Type code SDA R S-S2 S-S4-S5 S6-S7 S8 2 open/closed change-over contacts open/closed change-over contacts and release tripped signal NO, NC and release not tripped signal Early making contacts and connectors Type code SDA R S-S2 S-S4-S5-S6 S7 S8 early making contact and connector for undervoltage release GSIS905 Connectors for auxiliary contacts Type code SDA R S-S2 S-S4-S5-S6 S7 S8 for fixed circuit-breakers - Lm 86 for fixed circuit-breakers - L2m 7522 for fixed circuit-breakers - Lm 4207 for fixed circuit-breakers - L2m 4475 for plug-in or withdrawable circuit-breakers - Lm 864 for withdrawable circuit-breakers - Lm 4208 for withdrawable circuit-breakers - L2m flying 9-pole socket-plug - L0,6m 29 extension for testing auxiliary circuits with the circuit-breaker racked out Signally contacts Type code SDA R S8 contact for signalling closing springs charged /75
292 Order codes SACE Isomax S accessories Motor operating mechanisms GSIS902 GSIS9022 Solenoid operator Type code SDA R S-S2 at the side of the circuit-breaker 48 V DC V DC - 0 V AC V DC V AC V DC on the front of the circuit-breaker 48 V DC V DC - 0 V AC V DC V AC V DC 4808 GSIS902 Direct action motor operating mechanism Type code SDA R S-S4-S5 24 V DC V DC V AC V DC V AC V DC V AC V AC 4545 GSIS9020 Stored energy motor operating mechanism Type code SDA R S6 S7 24 V DC V DC V DC V AC / DC V AC / DC V AC / DC V AC GSIS9007 Geared motor for automatic charging of closing springs Type code SDA R S8 24/0 V DC /60 V DC V DC V DC GSIS904 Connectors for motor operating mechanism and auxiliary contacts Type code SDA R S-S2 S-S4-S5-S6 S7 for fixed circuit-breakers - Lm 857 for fixed circuit-breakers - L2m 7524 for fixed circuit-breakers - Lm 420 for fixed circuit-breakers - L2m for plug-in or withdrawable circuit-breakers - Lm 858 for withdrawable circuit-breakers - Lm 4204 for withdrawable circuit-breakers - L2m flying 9-pole socket-plug - L0,6m 29 extension for testing auxiliary circuits with the circuit-breaker racked out /76
293 Order codes SACE Isomax S accessories Operating mechanism and locks Direct-mounted rotary handle operating mechanism GSIS9025 Type code SDA R S-S2 S-S4-S5 S6 S7 for fixed/plug-in circuit breakers for withdrawable circuit breakers emergency for fixed or plug-in circuit-breakers Rotary handle operating mechanism with transmission rod GSIS9024 Type code SDA R S-S2 S-S4-S5 S6 S7 compartment door, fixed depth for fixed or plug-in circuit-breakers (L 9,5 mm) 26 compartment door, adjustable depth (Lmax00 mm) for fixed or plug-in 869 compartment door, adjustable depth (Lmax00 mm) for withdrawable 5074 compartment door, adjustable depth (Lmax500 mm) for fixed compartment door, adjustable depth (Lmax500 mm) for withdrawable compartment door, emergency, fixed depth for fixed or plug-in circuit-breakers (Lmax 9.5 mm) compartment door, emergency, adjustable depth for fixed or plug-in circuit-breakers (Lmax 00 mm) 87 compartment door, emergency, adjustable depth for fixed circuit-breakers (Lmax 500 mm) remote transmission rod with adj. depth (Lmax 80 mm) 2546 remote transmission rod with adj. depth (Lmax 500 mm) Front flange GSIS9026 Type code SDA R S...S5 S6 S7 S8 front flange for operating lever mechanism for fixed or plug-in front flange for operating lever mechanism for withdrawable flange for compartment door 4502 Key lock for open position GSIS9008 Type code SDA R S...S5 S6-S7 S8 for motor operating mechanism - a different key for each cb for motor operating mechanism - the same key for sets of cbs for motor operating mechanism against manual operation - the same key for each circuit-breaker 6245 for front flange / rotary handle - a different key for each circuit-breaker for front flange / rotary handle - the same key for sets of circuit-breakers for front flange key lock type RONIS GSIS900 GSIS905 Locks Type Size code SDA R compartment door lock for front flange for locks /crank handle operating mechanism S-S4-S5-S6-S7 880 padlock device for operating lever S-S2 2 padlock device on the front of the circuit-breaker S tamper-proof lock for thermal release S2 696 tamper-proof lock for thermal release S /77
294 Order codes SACE Isomax S accessories Mechanical interlock across two circuit-breakers PSIS9640 Type code SDA R horizontal vertical S 20 2 S S S S5400/ S S S-S4-S5-S6-S7 (circuit-breaker/fixed part for interlocking) Connection terminals Type code SDA R pieces 4 pieces 6 pieces 8 pieces 7 PSIS966 PSIS964 PSIS9642 PSIS964 EFExtended front terminals S S-S S S S S ESSpreaded extended front terminals S-S S S6 (/2 upper kit) S6 (/2 lower kit) S S7 (/2 upper kit) S7 (/2 lowerkit) S FC CuFront terminals for copper cables S-S S S FC CuAlFront terminals for copper/aluminium cables S2 (2,5-50 mm 2 ) (*) S2 (5-95 mm 2 ) (*) SD S 60 - S4 60 (x95 mm 2 ) S S4 250 (x50 mm 2 ) S5 400 (2x20 mm 2 ) S5 400 (x240 mm 2 ) S6 60 (2x240 mm 2 ) S6 800 (x85 mm 2 ) S7 250 (4x240 mm 2 ) RThreaded rear terminals S S S-S S S S R Res.Cur.Threaded rear terminals for reasidual current-release mounted below S 2554 HR/VRHorizontal or vertical flat-bar rear terminals S S RC Rear terminals for copper/aluminium cables S-S4 (x20 mm 2 ) S5 400 (x240 mm 2 ) S6 60 (2x50 mm 2 ) S6 800 (x240 mm 2 ) (*) Order also the relevant EF extended front terminals 7/78
295 Order codes SACE Isomax S accessories Insulating terminal covers PSIS9644 PSIS968 Type code SDA R poles 4 poles high for fixed S S S-S S S low for fixed and for moving part of plug-in or withdrawable circuit-breakers S S S-S S S S Screws for sealing terminal covers Type code SDA R S-S2 44 S-S4-S5-S6-S7 699 Accessories for electronic releases GSIS904 GSIS904 GSIS90 GSIS9045 GSIS9005 Type Model code SDA R Signalling unit SACE PR00/K S4-S5-S6-S Signalling unit SACE PR22/K S Dialogue unit SACE PR22/D-M Modbus + actuator unit SACE PR22/T for SACE PR22/P (LSI - LSIG) S4-S5-S6-S Dialogue unit SACE PR22/D-M Modbus + actuator unit SACE PR22/T for SACE PR22/MP (LRIU) S4-S5-S6-S Dialogue unit SACE PR22/D-L Lon + actuator unit SACE PR22/T for SACE PR22/P (LSI - LSIG) S4-S5-S6-S Dialogue unit SACE PR22/D-L Lon + actuator unit SACE PR22/T for SACE PR22/MP (LRIU) S4-S5-S6-S Dialogue unit SACE PR22/D + Actuator unit SACE PR22/T S Test unit SACE TT S4-S5-S6-S7 72 Test and configuration unit SACE PR00/T S4-S5-S6-S SACE PR22/CI contactor operating unit (with PR22/MP) S4-S5-S6-S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S Current transformer for neutral conductor outside circuit-breaker S connector for relay tripped signal and neutral protection for fixed circuit-breaker with PR2/P, PR22/P - LSI S4-S5-S6-S7 702, 4 connectors for relay tripped signal and neutral protection for fixed circuit-breaker with PR22/P - LSIG S4-S5-S6-S7 704 connector for relay tripped signal and neutral protection for plug-in or withdrawable circuit-breaker with PR2/P, PR22/P - LSI S4-S5-S6-S7 70, 4 connectors for relay tripped signal and neutral protection for plug-in or withdrawable circuit-breaker with PR22/P - LSIG S4-S5-S6-S7 705 electrical/mechanical signalling and lock for PR22/P tripped S /79
296 Order codes SACE Isomax S accessories Conversion kits from fixed circuit-breaker to moving part of plug-in circuit-breaker GSIS906 Type code SDA R poles 4 poles S S S-S S S S from fixed circuit-breaker to moving part of withdrawable circuitbreaker GSIS907 Type code SDA R poles 4 poles S-S S S S S S6 60 / S S from plug-in circuit-breaker to withdrawable circuit-breaker GSIS9047 Type Size code SDA R Guide for preparing the fixed part of a plug-in circuit-breaker for use as the fixed part of a withdrawable circuit-breaker S-S4 692 Guide for preparing the fixed part of a plug-in circuit-breaker for use as the fixed part of a withdrawable circuit-breaker S /80
297 Order codes SACE Isomax S accessories Fixed parts GSIS92 Plug-in circuit-breaker Type code SDA R poles 4 poles EF Extended front terminals S P FP EF S4 P FP EF S5 400 P FP EF FC Front terminals for copper cables S P FP FC S2 P FP FC S P FP FC S4 P FP FC S5 400 P FP FC R Threaded rear terminals S P FP R S2 P FP R S P FP R S4 P FP R S5 400 P FP R Withdrawable circuit-breaker GSIS924 Type code SDA R poles 4 poles EF Extended front terminals S W FP EF S4 W FP EF S5 400 W FP EF S6 W FP EF S7 W FP EF ES Spreaded extended front terminals S5 60 W FP ES FC Front terminals for copper cables S W FP FC S4 W FP FC S5 400 W FP FC R Threaded rear terminals S W FP R S4 W FP R S5 400 W FP R S5 60 W FP R VR Vertical flat-bar rear terminals S5 60 W FP VR S6 W FP VR S7 W FP VR HR Horizontal flat-bar rear terminals S6 W FP HR S7 W FP HR /8
298 Order codes SACE Isomax S accessories Accessories for fixed part of plug-in or withdrawable circuit-breakers Terminals for the fixed parts of plug-in or withdrawable circuit-breakers PSIS965 PSIS9655 PSIS9654 Type code SDA R poles 4 poles EF Extended front terminals S-S S S S6 (with terminals mounted below for S6) S FC Cu/Al Front terminals for copper / aluminium cables S-S S R Threaded rear terminals S-S S S HR Horizontal flat-bar rear terminals S S VR Vertical flat-bar rear terminals S S S PSIS9646 Insulating covers for fixed parts Type code SDA R poles 4 poles S-S S Position contacts GSIS9006 Type Model code SDA R contacts for signalling circuit-breaker racked out S-S4-S5-S6-S7 859 contacts for signalling circuit-breaker racked out for digital signals S-S4-S5-S6-S contacts for signalling circuit-breaker racked in S-S4-S5-S6-S7 860 contacts for signalling circuit-breaker racked in for digital signals S-S4-S5-S6-S Lock for fixed part of withdrawable circuit-breakers GSIS9009 Type Model code SDA R key lock for locking in racked in / out position - different key for each cb. S-S4-S5-S6-S key lock for locking in racked in / out position - same key for sets of cb. S-S4-S5-S6-S padlock device S-S4-S5-S6-S /82
299 Order codes SACE Isomax S accessories Installation accessories Bracket for mounting on DIN rail Type Model code SDA R GSIS90 DIN EN S 228 DIN EN S2 229 DIN EN (for solenoid operator) S 4852 DIN EN (for solenoid operator) S DIN EN 5002 (complete with DIN front flange H45 mm) S - poles 576 DIN EN 5002 (complete with DIN front flange H45 mm) S - 4 poles 577 DIN EN 5002 (complete with DIN front flange H45 mm) S4 - poles 700 DIN EN 5002 (complete with DIN front flange H45 mm) S4-4 poles 70 DIN EN 5002 (complete with DIN front flange H45 mm) S5 - poles 90 DIN EN 5002 (complete with DIN front flange H45 mm) S5-4 poles 902 IP54 protection Type Model code SDA R PSIS9657 for fixed-depth rotary handle operating mechanism on door S-S2 9 for adjustable-depth rotary handle operating mechanism on door S-S4-S5-S6-S7 89 Residual-current releases SACE RC20, RC2, SACE RC22 GSIS9027 Type code SDA R side by side below RC20/ for S (In6 A - I n0, A) RC20/ for S (In6 A - I n0,5 A) RC20/ for S (In6 A - I n0, A) RC20/ for S (In6 A - I n0,5 A) RC2/ for S RC2/2 for S RC2/ for S RC22/ for S RC22/2 for S RC22/ for S PSIS9665 SACE RCQ Type code SDA R GSIS9046 release and closed toroid - diameter 60 mm 788 release and closed toroid - diameter 0 mm 789 release and closed toroid - diameter 85 mm release and opening toroid - diameter 0 mm 790 release and opening toroid - diameter 80 mm 79 release and opening toroid - diameter 20 mm 792 release only 79 closed toroid only - diameter 60 mm 794 closed toroid only - diameter 0 mm 795 closed toroid only - diameter 85 mm 5054 opening toroid only - diameter 0 mm 796 opening toroid only - diameter 80 mm 797 opening toroid only - diameter 20 mm /8
300 7/84
301 7/85
302 7/86
303 7/87
304 7/88
305 7/89
306 7/90
307
308 Due to possible developments of standards as well as of materials, the characteristics and dimensions specified in the present catalogue may only be considered binding after confirmation by /02 en Printed in Italy Tipografia S.p.A. L.V. Breakers Division Via Baioni, Bergamo - Italy Tel.: Telefax:
Tmax. Technical catalogue. Low voltage moulded-case circuit-breakers up to 630 A 1SDC210004D0204
Technical catalogue Tmax Low voltage moulded-case circuit-breakers up to 630 A 1SDC210004D0204 VERVIEW MAIN CHARACTERISTICS THE RANGES ACCESSORIES CHARACTERISTIC CURVES AND TECHNICAL INFORMATION WIRING
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of
General information Circuit breakers for power distribution T1 T3
Circuit breakers for power distribution T1 T3 T1 T2 T3 T1 1P T1 T2 T3 UL 489 CSA C22.2 Frame size A 100 100 100 225 Number of poles Nr 1 3, 4 3, 4 3, 4 Rated voltage AC (50-60 Hz) V 277 600Y / 347V 480
Technical catalogue - Ordering Codes. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated
Technical catalogue - Ordering Codes SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated New SACE Tmax XT. Simply XTraordinary. Today a highly advanced range of circuit-breakers
Tmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
Technical catalogue. Low voltage air circuit-breakers. SACE Emax. 604019/011 en March '99. 690 V 800-6300 A 40-150 ka (380/415 V) ABB SACE L.V.
Technical catalogue 604019/011 en March '99 Low voltage air circuit-breakers SACE Emax 690 V 800-6300 A 40-150 ka (380/415 V) ABB SACE L.V. GENERAL INDEX Introduction Technology and innovation for advanced
Technical catalogue - 2015.10. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A
Technical catalogue - 2015.10 SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A Construction Characteristics 1 The SACE Tmax XT Ranges 2 Accessories 3 Characteristic Curves and Technical
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Spare parts Catalogue
Technical catalogue Spare parts Catalogue Low voltage circuit-breakers Product support ABB SACE SDC0000D00 Not every original spare parts are really original spare parts. Availability of spare parts for
Brochure April 2012. Moulded-case circuit-breakers overview SACE Tmax
Brochure April 0 Moulded-case circuit-breakers overview SACE Tmax A single family of moulded-case circuit-breakers up to 00 A Tmax moulded-case circuit-breakers guarantee an extremely high performance
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Circuit Breakers. Next Generation of Protection Capabilities
Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many
IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
SENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager
Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager SACE Emax 2 From Circuit-Breaker to Power Manager Our customers need more efficient solutions, to Increase
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
Technical catalog. FORMULA UL New low voltage molded case circuit breakers up to 250A. Power and productivity for a better world TM
Technical catalog FORMULA UL New low voltage molded case circuit breakers up to 2A Power and productivity for a better world TM Index Main characteristics 1 Circuit breakers for power distribution 2 Accessories
Thermal-Magnetic Circuit Breaker 3120-...-M1-..
Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
Medium Voltage Products. PR512 Microprocessor-based self-supplied protection relays
Medium Voltage Products PR512 Microprocessor-based self-supplied protection relays DESCRIPTION CHARACTERISTICS AND ORDERING CODES PR512/P (50-51) UNIT PR512/P (50-51-50N-51N) UNIT PR512/PD (50-51-50N-51N
Breaking and protection devices
Breaking and protection devices 05 POWER GUIDE 2009 / BOOK 05 INTRO The purpose of selecting a protection device is to perform two essential functions: to protect people and to protect trunking, while
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
P System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
Catalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Emax DC. Annex to the technical catalogue. Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications
Annex to the technical catalogue Emax DC Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications 1SDC200012D0201 Index SACE Emax DC automatic circuit-breakers...
High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.
The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved
LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil
Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Molded case circuit breakers
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product technology. Never before has the industry seen such high
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.
ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. Ensuring operational continuity To ensure the operational continuity of an electrical
Manual Motor Starter MS 116 up to 16 A Technical Data
Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates
NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
White paper. ABB solutions for switching and protection of low speed wind turbines
White paper ABB solutions for switching and protection of low speed wind turbines ABB solutions for switching and protection of low speed wind turbines Index 1 Introduction...2 2 Full converter configuration...4
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
The easy way to build switchgear and controlgear assemblies in compliance with the regulations
The easy way to build switchgear and controlgear assemblies in compliance with the regulations A guide for partially type-tested switchgear and controlgear assemblies in compliance with EN 60 439 What
Environmental Product Declaration. Registration number: S-P-00047. Rev. 0 11/06/03. Tmax T1. Low voltage circuit breaker.
Environmental Product Declaration Registration number: S-P-00047 Rev. 0 11/06/03 Tmax T1 Low voltage circuit breaker ABB SACE SpA Information about the company and the product This document aims to provide
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
Technical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com
Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,
STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD
Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: 200137 Tel: 86-21-5012789 Fax: 86-21-58675966 E-mail: [email protected] LINE 1 LINE 3 LINE 5
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
The complete range of consumer switchboards and switchgear
Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Nothing s BetterThan the Original MODAN Power Distribution Systems
MODAN www.eaton.com Nothing s BetterThan the Original MODAN Power Distribution Systems Modan Modular switchboard system Controlling and Distributing Power Safely Thinking further. Questioning the well-established
RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
A sophisticated design for a demanding field. prima series
A sophisticated design for a demanding field prima series 2 nd edition 2003 prima compact horizontal interlocked sockets carefully studied A size for all versions with or without fuses. Extends horizontally
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Manual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
ABLOY DOOR AUTOMATICS Easy access for all types of swing doors
ABLOY DOOR AUTOMATICS Easy access for all types of swing doors Automatic door operators bring additional convenience in situations where the doors opening manually would be inconvenient or laborious. Recommended
Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
Index. 17 - Molded case circuit breakers. Molded case circuit breakers. Tmax UL489B Photovoltaic circuit breakers...17.67-17.70
Molded case circuit breakers Index Molded case circuit breakers - Molded case circuit breakers Formula...1 -.10 General information Introduction...1 Circuit breakers for power distribution...2 explanation...3
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
Products and solutions for lifting systems
Products and solutions for lifting systems 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric headquarters founded
GE Power Controls. MiniFORM Switchboards
GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules
White Paper - July 2012. ATS021-ATS022 Automatic transfer switching
White Paper - July 202 02-022 Automatic transfer switching 02-022 Automatic transfer switching Index. Introduction...2 2. Description of... Switching logics...6 Transformer for the main and generator
Safety automation solutions
Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
Current and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)
Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic
Type: DILM9 10(24VDC) Article No.: 276705
Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50
ELR: ABB range of front panel residual current relays Protection device according to IEC/EN 60947-2 Annex M
ELR: ABB range of front panel residual current relays Protection device according to IEC/EN 60947-2 Annex M Tested, certified, reliable Network monitoring and protection The electronic residual current
MNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
Tmax. Molded case circuit breakers. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]. Tmax.
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
IEC 61439-1 & 2 standard. The reference for safe and reliable LV switchboards
IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC
IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors
IZM ACB/Circuit-breakers Robust safety Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors t [s] 0.1 0.05 0.04 0.03 0.02 0.01 20 1230DIA-125 (70C1043) 30 40 50 60 80 100
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
Technical catalog - Edition 2015. SACE Tmax PV Adaptability, versatility and complete freedom continue
Technical catalog - Edition 205 SCE Tmax PV daptability, versatility and complete freedom continue SCE Tmax PV automatic molded case circuit-breakers and molded case switch-disconnectors The Tmax PV line
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of