S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv)
|
|
|
- Eleanor Elliott
- 9 years ago
- Views:
Transcription
1 Outdoor Distribution (14.4 kv and 25 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The pad-mounted gear shall be in accordance with the single-line diagram, and shall conform to the following specification The pad-mounted gear shall consist of a single self-supporting enclosure, containing interrupter switches and power fuses with the necessary accessory components, all completely factoryassembled and operationally checked. The interrupter switches and fuses shall be enclosed within an inner grounded steel compartment for electrical isolation and for protection from contamination. Switch terminals shall be equipped with bushings rated 600 amperes continuous, and fuse terminals and bus terminals shall be equipped with bushing wells rated 200 amperes continuous to provide for elbow connection. Bushings and bushing wells shall be mounted on the walls of the inner compartment and shall extend into termination compartments. A termination compartment shall be provided for each three-phase switch, each three-phase set of fuses, and each three-phase set of bus terminals Ratings The ratings for the integrated pad-mounted gear shall be as designated below. (Select values from the table on page 2.) Nominal Voltage, kv... Maximum Voltage, kv BIL Voltage, kv Short-Circuit Peak Withstand Current, Amperes, Peak... One-Second Short-Time Withstand Current, Amperes, RMS, Symmetrical... MVA, Three-Phase Symmetrical, at Rated Nominal Voltage Main Bus Continuous Current, Amperes Peak Withstand Current, Amperes, Peak... One-Second Short-Time Withstand Current, Amperes, RMS, Symmetrical... Three-Pole Interrupter Switches Continuous Current, Amperes Load Dropping Current, Amperes Peak Withstand Current, Amperes, Peak... One-Second Short-Time Withstand Current, Amperes, RMS, Symmetrical... Three-Time Duty-Cycle Fault-Closing Current, Amperes, RMS, Symmetrical... Three-Time Duty-Cycle Fault-Closing Current, Amperes, Peak Fuses Maximum Current, Amperes... The short-circuit and three-time duty-cycle fault-closing ratings of switches, short-circuit rating of bus, and interrupting ratings of fuses shall equal or exceed the short-circuit ratings of the pad-mounted gear. November 9, 2009 S&C Electric Company Information Sheet
2 SELECTION OF 60-HERTZ RATINGS Nominal Voltage, kv Maximum Voltage, kv BIL Voltage, kv Peak Withstand Current, Amperes, Peak Short-Circuit One-Second Short-Time Withstand Current, Amperes, RMS, Symmetrical MVA, Three-Phase Symmetrical, at Rated Nominal Voltage Continuous Current, Amperes Main Bus Peak Withstand Current, Amperes, Peak One-Second Short-Time Withstand Current, Amperes, RMS, Symmetrical Continuous Current, Amperes Load Dropping Current, Amperes Three-Pole Interrupter Switches Peak Withstand Current, Amperes, Peak One-Second Short-Time Withstand Current, Amperes, RMS, Symmetrical Three-Time Duty-Cycle Fault-Closing Current, Amperes, Peak Fuses Maximum Current, Amperes 200, 200E, or 200K 200, 200E, or 200K Short-circuit rating of complete pad-mounted gear may be limited by ratings of bushing inserts, elbows, T-bodies, fuses, and cables used kV gear, when furnished with switches only (and no fuses), has the following ratings: 17.5 kv maximum voltage; 65,000 amperes, peak, short-circuit peak withstand current; 25,000 amperes, RMS, symmetrical, short-circuit one-second shorttime withstand current; 620 MVA, three-phase symmetrical, at rated nominal voltage kV gear, when furnished with fuses utilizing refill-unit-and-holder construction, has the following ratings: 32,500 amperes, peak, short-circuit peak withstand current; 12,500 amperes, RMS, symmetrical, short-circuit one-second shorttime withstand current; 310 MVA, three-phase symmetrical, at rated nominal voltage kV gear, when furnished with current-limiting fuses having a rated maximum interrupting current of at least of 25,000 amperes, RMS, symmetrical, and limiting the instantaneous peak let-through current to less than 36,000 amperes, has the following ratings: 65,000 amperes, peak, short-circuit peak withstand current; 25,000 amperes, RMS, symmetrical, short-circuit one-second shorttime withstand current; 620 MVA, three-phase symmetrical, at rated nominal voltage. Applicable to four-compartment models. Two-compartment models have the following ratings: 36,400 amperes, peak, short-circuit peak withstand current; 14,000 amperes, RMS, symmetrical, short-circuit one-second shorttime withstand current Certification of Ratings (a) The manufacturer of the pad-mounted gear shall be completely and solely responsible for the performance of the basic switch and fuse components as well as the complete integrated assembly as rated. The manufacturer shall furnish, upon request, certification of ratings of the basic switch and fuse components and/or the integrated pad-mounted gear assembly consisting of the switch and fuse components in combination with the enclosure. 2 S&C Information Sheet
3 1.05 Compliance with Standards and Codes The pad-mounted gear shall conform to or exceed the applicable requirements of the following standards and codes: (a) All portions of ANSI C , covering enclosure integrity for pad-mounted equipment. Article (e) in the National Electrical Code, which specifies that the interrupter switches in combination with power fuses shall safely withstand the effects of closing, carrying, and interrupting all possible currents up to the assigned maximum short-circuit rating. All portions of ANSI, IEEE, and NEMA standards applicable to the basic switch and fuse components. The following optional feature should be specified as required: UL Listing Enclosure Design (a) To ensure a completely coordinated design, the pad-mounted gear shall be constructed in accordance with the minimum construction specifications of the fuse and/or switch manufacturer to provide adequate electrical clearances. In establishing the requirements for the enclosure design, consideration shall be given to all relevant factors such as controlled access, tamper resistance, corrosion resistance, and resistance to entry of foliage, animals, and airborne contaminants. 2.0 CONSTRUCTION Insulators, High-Voltage Bus, Provisions for Grounding, Bushings and Bushing Wells, and Termination Compartments 2.01 Insulators The interrupter-switch and fuse-mounting insulators shall be of a cycloaliphatic epoxy resin system with characteristics and restrictions as follows: (a) Operating experience of at least 25 years under similar conditions. (e) Adequate leakage distance established by test per IEC Publication 507, Artificial Pollution Test on High Voltage Insulators to be Used on AC Systems. Adequate strength for short-circuit stress established by test. Conformance with applicable ANSI standards. Homogeneity of the cycloaliphatic epoxy resin throughout each insulator to provide maximum resistance to power arcs. Ablation due to high temperatures from power arcs shall continuously expose more material of the same composition and properties so that no change in mechanical or electrical characteristics takes place because of arc-induced ablation. Furthermore, any surface damage to insulators during installation or maintenance of the pad-mounted gear shall expose material of the same composition and properties so that insulators with minor surface damage need not be replaced. S&C Information Sheet
4 2.02 High-Voltage Bus (a) (e) Bus and interconnections shall consist of aluminum bar of 56% IACS conductivity. Bus and interconnections shall withstand the stresses associated with short-circuit currents up through the maximum rating of the pad-mounted gear. Bolted aluminum-to-aluminum connections shall be made with a suitable number of galvanized steel bolts, with two Belleville spring washers per bolt, one under the bolt head and one under the nut. Bolts shall be tightened to 50 foot-pounds torque. Before installation of the bus, all electrical contact surfaces shall first be prepared by machine-abrading to remove any aluminum-oxide film. Immediately after this operation, the electrical contact surfaces shall be coated with a uniform coating of an oxide inhibitor and sealant. Tie bus, where furnished, shall consist of continuous, one-piece sections of aluminum bar with no intermediate splices. Flexible braid or cable shall not be used Provisions for Grounding (a) A ground-connection pad shall be provided in each termination compartment of the pad-mounted gear. (e) The ground-connection pad shall be constructed of steel no less than 3/8-in. thick. It shall be nickel plated and welded to the enclosure, and shall have a short-circuit rating equal to that of the pad-mounted gear. Ground-connection pads shall be coated with a uniform coating of an oxide inhibitor and sealant prior to shipment. A copper rod, connected to the ground-connection pad, shall be provided in each termination compartment for switches and bus. The rod shall have a diameter no less than 3/8-in. and extend across the full width of the compartment to allow convenient grounding of cable concentric neutrals and accessories, and shall have a short-circuit rating equal to that of the pad-mounted gear. Continuous copper ground bus shall be provided across the full width of each termination compartment for fuses. For each fuse mounting, there shall be a ground ring made of 3/8 in.-diameter copper rod bolted to the ground bus and placed to allow convenient grounding of cable concentric neutrals and accessories. Ground rings and bus shall have a short-circuit rating equal to that of the padmounted gear. 4 S&C Information Sheet
5 2.04 Bushings and Bushing Wells (a) Bushings and bushing wells shall conform to ANSI/IEEE Standard 386. Bushings and bushing wells shall be of a cycloaliphatic epoxy resin system with characteristics and restrictions as follows: (1) Operating experience of at least 15 years under similar conditions. (2) Adequate leakage distance for in-air application established by test per IEC Publication 507, Artificial Pollution Test on High Voltage Insulators to be Used on AC Systems. (3) Adequate strength for short-circuit stress established by test. (4) Conformance with applicable ANSI standards. (5) Homogeneity of the cycloaliphatic epoxy resin throughout each bushing or bushing well to provide maximum resistance to power arcs. Ablation due to high temperatures from power arcs shall continuously expose more material of the same composition and properties so that no change in mechanical or electrical characteristics takes place because of arcinduced ablation. Bushings and bushing wells shall be mounted in such a way that the semiconductive coating is solidly grounded to the enclosure. Bushings rated 600 amperes continuous shall have a removable threaded stud so that the bushings are compatible with all 600-ampere elbow systems those requiring a threaded stud as well as those that do not. S&C Information Sheet
6 2.05 Termination Compartments (a) Termination compartments for switches shall have bushings, and termination compartments for fuses shall have bushing wells to permit connection of elbows. The bushings and bushing wells shall be mounted on the interior walls at a minimum height of 33 inches above the enclosure base. (e) (f) (g) Termination compartments for bus shall have bushing wells to permit connection of elbows. The bushing wells shall be mounted on the interior walls at a minimum height of 25 inches above the enclosure base. Termination compartments for bushings rated 600 amperes continuous shall be of an adequate depth to accommodate two 600-ampere elbows mounted piggyback, encapsulated surge arresters or grounding elbows mounted on 600-ampere elbows having 200-ampere interfaces, or other similar accessory combinations without the need for an enclosure extension. Termination compartments for bushing wells rated 200 amperes continuous shall be of an adequate depth to accommodate 200-ampere elbows mounted on portable feedthrus or standoff insulators, or other similar accessory combinations without the need for an enclosure extension. Termination compartments shall be provided with one parking stand for each bushing or bushing well. The parking stand shall be located immediately adjacent to the associated bushing or bushing well and shall accommodate standard feedthrus and standoff insulators, and other similar accessories. Each termination compartment for a switch shall be equipped with a viewing window to allow visual inspection of interrupter switch blades to allow positive verification of switch position. Each termination compartment for a set of fuses shall be equipped with a set of viewing windows to allow visual inspection of blown-fuse indicators. 3.0 CONSTRUCTION Enclosure, Doors, Roof, and Finish 3.01 Enclosure (a) The pad-mounted gear enclosure shall be of unitized monocoque (not structuralframe-and-bolted-sheet) construction to maximize strength, minimize weight, and inhibit corrosion. (e) The basic material shall be 11-gauge hot-rolled, pickled and oiled steel sheet. All structural joints and butt joints shall be welded, and the external seams shall be ground flush and smooth. The gas-metal-arc welding process shall be employed to eliminate alkaline residues and to minimize distortion and spatter. To guard against unauthorized or inadvertent entry, enclosure construction shall not utilize any externally accessible hardware. The base shall consist of continuous 90-degree flanges, turned inward and welded at the corners, for bolting to the concrete pad. 6 S&C Information Sheet
7 (f) The door openings shall have 90-degree flanges, facing outward, that shall provide strength and rigidity as well as deep overlapping between doors and door openings to guard against water entry. (g) (h) (i) (j) (k) (l) Gasketing between the roof and the enclosure shall guard against entry of water and airborne contaminants and shall discourage tampering or insertion of foreign objects. An internal steel-enclosed compartment shall encase the interrupter switches and fuses for electrical isolation and protection from contamination. The compartment shall have a galvanized steel sheet floor to exclude foliage and animals. The floor shall have screened drain vents to allow drainage if the enclosure is flooded. The top of this compartment shall be gasketed to provide sealing with the enclosure roof. Insulating barriers of NEMA GPO3-grade fiberglass-reinforced polyester shall be provided for each interrupter switch where required to achieve BIL ratings. Additional insulating barriers of the same material shall isolate the tie bus (where furnished). Full-length steel barriers shall separate adjoining termination compartments. Lifting tabs shall be removable. Sockets for the lifting-tab bolts shall be blindtapped. A resilient material shall be placed between the lifting tabs and the enclosure to help prevent corrosion by protecting the finish against scratching by the tabs. To further preclude corrosion, this material shall be closed-cell to prevent moisture from being absorbed and held between the tabs and the enclosure in the event that lifting tabs are not removed. The enclosure shall be provided with an instruction manual holder. The following optional feature should be specified as required: (m) To guard against corrosion due to extremely harsh environmental conditions, the entire exterior of the enclosure shall be fabricated from 11-gauge Type 304 stainless steel. S&C Information Sheet
8 3.02 Doors 3.03 Roof (a) (e) (f) (g) (a) (e) Doors shall be constructed of 11-gauge hot-rolled, pickled and oiled steel sheet. Door-edge flanges shall overlap with door-opening flanges to discourage tampering or insertion of foreign objects. Doors shall have a minimum of two extruded-aluminum hinges with stainless-steel hinge pins, and interlocking extruded-aluminum hinge supports for the full length of the door to provide strength, security, and corrosion resistance. Mounting hardware shall be stainless steel or zinc-nickel-plated steel, and shall not be externally accessible to guard against tampering. Doors shall be hinged at the sides to swing open with minimum effort. Doors hinged at the top requiring significant effort to lift open shall not be allowed. In consideration of controlled access and tamper resistance, each door (or set of double doors) shall be equipped with an automatic three-point latching mechanism. (1) The latching mechanism shall be spring-loaded, and shall latch automatically when the door is closed. All latch points shall latch at the same time to preclude partial latching. (2) A pentahead socket wrench or tool shall be required to actuate the mechanism to unlatch the door and, in the same motion, recharge the spring for the next closing operation. (3) The latching mechanism shall have provisions for padlocking that incorporate a means to protect the padlock shackle from tampering and that shall be coordinated with the latches such that: (i) It shall not be possible to unlatch the mechanism until the padlock is removed, and (ii) It shall not be possible to insert the padlock until the mechanism is completely latched closed. Doors providing access to solid-material power fuses shall have provisions to store spare fuse units or refill units. Each door shall be provided with a zinc-nickel-plated steel door holder located above the door opening. The holder shall be hidden from view when the door is closed, and it shall not be possible for the holder to swing inside the enclosure. The roof shall be constructed of 11-gauge hot-rolled, pickled and oiled steel sheet. A heavy coat of insulating no-drip compound shall be applied to the inside surface of the center roof section to minimize condensation of the moisture thereon. Roof sections over termination compartments shall be liftable and hinged to allow room for cable pulling during installation. Each roof section shall require minimal effort to open and close and shall have a retainer to hold it in the open position. A mechanical interlock shall be provided to ensure that the roof sections over the termination compartments are closed and secured before allowing full engagement of the door latching mechanism described in Section 3.02(e). Roof sections over high-voltage compartments shall be bolted to the enclosure with no exposed fasteners. 8 S&C Information Sheet
9 3.04 Finish (a) Full coverage at joints and blind areas shall be achieved by processing enclosures independently of components such as doors and roofs before assembly into the unitized structures. All exterior seams shall be filled and sanded smooth for neat appearance. To remove oils and dirt, to form a chemically and anodically neutral conversion coating to improve the finish-to-metal bond, and to retard underfilm propagation of corrosion, all surfaces shall undergo a thorough pretreatment process comprised of a fully automated system of cleaning, rinsing, phosphatizing, sealing, drying, and cooling before any protective coatings are applied. By utilizing an automated pretreatment process, the enclosure shall receive a highly consistent thorough treatment, eliminating fluctuations in reaction time, reaction temperature, and chemical concentrations. After pretreatment, protective coatings shall be applied that shall help resist corrosion and protect the steel enclosure. To establish the capability to resist corrosion and protect the enclosure, representative test specimens coated by the enclosure manufacturer s finishing system shall satisfactorily pass the following tests: (1) 4000 hours of exposure to salt-spray testing per ASTM B 117 with: (i) Underfilm corrosion not to extend more than 1/32 in. from the scribe, as evaluated per ASTM D 1645, Procedure A, Method 2 (scraping); and (ii) Loss of adhesion from bare metal not to extend more than 1/8 in. from the scribe. (2) 1000 hours of humidity testing per ASTM D 4585 using the Cleveland Condensing Type Humidity Cabinet, with no blistering as evaluated per ASTM D 714. (3) 500 hours of accelerated weathering testing per ASTM G 53 using lamp UVB-313, with no chalking as evaluated per ASTM D 659, and no more than 10% reduction of gloss as evaluated per ASTM D 523. (4) Crosshatch-adhesion testing per ASTM D 3359 Method B, with no loss of finish. (5) 160-inch-pound impact, followed by adhesion testing per ASTM D 2794, with no chipping or cracking. (6) 3000 cycles of abrasion testing per ASTM 4060, with no penetration to the substrate. Certified test abstracts substantiating the above capabilities shall be furnished upon request. S&C Information Sheet
10 (e) After the finishing system has been properly applied and cured, welds along the enclosure bottom flange shall be coated with a wax-based anticorrosion moisture barrier to give these areas added corrosion resistance. (f) (g) (h) A resilient closed-cell material, such as PVC gasket, shall be applied to the entire underside of the enclosure bottom flange to protect the finish on this surface from scratching during handling and installation. This material shall isolate the bottom flange from the alkalinity of a concrete foundation to help protect against corrosive attack. After the enclosure is completely assembled and the components (switches, fuses, bus, etc.) are installed, the finish shall be inspected for scuffs and scratches. Blemishes shall be touched up by hand to restore the protective integrity of the finish. The finish shall be olive green, Munsell 7GY3.29/1.5. The following optional feature should be specified as required: (i) The finish shall be outdoor light gray, satisfying the requirements of ANSI Standard Z55.1 for No To guard against corrosion, all hardware (including door fittings, fasteners, etc.), all operatingmechanism parts, and other parts subject to abrasive action from mechanical motion shall be of either nonferrous materials, or galvanized or zinc-nickel-plated ferrous materials. Cadmiumplated ferrous parts shall not be used. 4.0 BASIC COMPONENTS 4.01 Interrupter Switches (a) Interrupter switches shall be enclosed in an inner steel compartment and shall be provided with bushings rated 600 amperes continuous to permit connection of elbows external to the switch compartment. Interrupter switches shall have a three-time duty-cycle fault-closing rating equal to or exceeding the short-circuit rating of the pad-mounted gear. These ratings define the ability to close the interrupter switch three times against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and interrupt rated current. Tests substantiating these ratings shall be performed at maximum voltage with current applied for at least 10 cycles. Certified test abstracts establishing such ratings shall be furnished upon request. 10 S&C Information Sheet
11 Interrupter switches shall be operated by means of an externally accessible 3/4-in. hex switch-operating hub. The switch-operating hub shall be located within a recessed stainless-steel pocket mounted on the side of the pad-mounted gear enclosure and shall accommodate a 3/4-in.deep-socket wrench or a 3/4-in. shallowsocket wrench with extension. The switch-operating-hub pocket shall include a padlockable stainless-steel access cover that shall incorporate a hood to protect the padlock shackle from tampering. Stops shall be provided on the switchoperating hub to prevent overtravel and thereby guard against damage to the interrupter switch quick-make quick-break mechanism. Labels to indicate switch position shall be provided in the switch-operating-hub pocket. (e) (f) (g) (h) (i) Each interrupter switch shall be provided with a folding switch-operating handle. The switch-operating handle shall be secured to the inside of the switch-operatinghub pocket by a brass chain. The folded handle shall be stored behind the closed switch-operating-hub access cover. Interrupter switches shall utilize a quick-make quick-break mechanism installed by the switch manufacturer. The quick-make quick-break mechanism shall be integrally mounted on the switch frame, and shall swiftly and positively open and close the interrupter switch independent of the switch-operating-hub speed. Each interrupter switch shall be completely assembled and adjusted by the switch manufacturer on a single rigid mounting frame. The frame shall be of welded steel construction such that the frame intercepts the leakage path which parallels the open gap of the interrupter switch to positively isolate the load circuit when the interrupter switch is in the open position. Interrupter switch contacts shall be backed up by stainless-steel springs to provide constant high contact pressure. Interrupter switches shall be provided with a single blade per phase for circuit closing, including fault closing, continuous current carrying, and circuit interrupting. Spring-loaded auxiliary blades shall not be permitted. Interrupter switch blade supports shall be permanently molded in place in a unified insulated shaft constructed of the same cycloaliphatic epoxy resin as the insulators. Circuit interruption shall be accomplished by use of an interrupter which is positively and inherently sequenced with the blade position. It shall not be possible for the blade and interrupter to get out of sequence. Circuit interruption shall take place completely within the interrupter, with no external arc or flame. Any exhaust shall be vented in a controlled manner through a deionizing vent. S&C Information Sheet
12 The following optional features should be specified as required: (j) (k) (l) (m) Key interlocks shall be provided to prevent paralleling the two source interrupter switches. Key interlocks shall be provided to guard against opening the door(s) of fusetermination compartment(s) unless all switches are locked open. Mounting provisions shall be provided to accommodate one three-phase fault indicator with three single-phase sensors in each switch-termination compartment. Interrupter switch bushings rated 600 amperes continuous shall be provided without studs Fuses (Select either solid-material power fuses or electronic power fuses.) (a) Solid-Material Power Fuses (1) Solid-material power fuses shall utilize refill-unit-and-holder or fuse-unitand-end-fitting construction. The refill unit or fuse unit shall be readily replaceable and low in cost. (2) Fusible elements shall be nonaging and nondamageable so it is unnecessary to replace unblown companion fuses following a fuse operation. (3) Fusible elements for refill units or fuse units, rated 10 amperes or larger, shall be helically coiled to avoid mechanical damage due to stresses from current surges. (4) Fusible elements that carry continuous current shall be supported in air to help prevent damage from current surges. (5) Refill units and fuse units shall have a single fusible element to eliminate the possibility of unequal current sharing in parallel current paths. (6) Solid-material power fuses shall have melting time-current characteristics that are permanently accurate to within a maximum total tolerance of 10% in terms of current. Time-current characteristics shall be available which permit coordination with source-side and load-side protective relays, automatic circuit reclosers, and other fuses. (7) Solid-material power fuses shall be capable of detecting and interrupting all faults, whether large, medium, or small (down to minimum melting current); under all realistic conditions of circuitry; and with line-to-line or line-to-ground voltage across the fuse. They shall be capable of handling the full range of transient recovery voltage severity associated with these faults. (8) All arcing accompanying solid-material power fuse operation shall be contained within the fuse, and all arc products and gases evolved shall be effectively contained within the exhaust control device during fuse operation. (9) Solid-material power fuses shall be equipped with a blown-fuse indicator that shall provide visible evidence of fuse operation while installed in the fuse mounting. 12 S&C Information Sheet
13 Electronic Power Fuses (1) Electronic power fuses shall utilize an expendable interrupting module and a reusable control module. (i) The interrupting module shall consist of a main-current section and a fault-interrupting section. These sections shall be arranged coaxially and contained within the same housing. (ii) The main-current section shall carry current under normal operating conditions. (iii) The fault-interrupting section shall operate only under fault conditions. It shall not carry current continuously and shall not determine the minimum operating time-current characteristic curve shape. (iv) The current-limiting-section fusible element shall not be subject to damage due to current surges. (v) All arcing accompanying operation of the electronic power fuse shall be contained within the interrupting module and fuse operation shall be silent, without any exhaust. (vi) The control module shall continuously monitor the line current through an electronic sensing circuit. (vii) The electronic components shall be located within a cylindrical cast-aluminum housing that shall serve as both a path for continuous current and as a shield to protect the electronic components against interference from external electric fields. (iix) To prevent damage to the control-module circuits by surges (such as due to lightning or inrush currents), the control module shall be free of external control wiring and connections to ground, and shall incorporate a device that acts as a buffer to isolate the electronic components at a level of current well below their surge-withstand capability. (ix) The control module shall be factory-sealed to assure a dry, contaminant-free environment for the electronic components. (x) The control module shall be self-powered with the capability to supply power for operating the sensing logic circuits and to actuate the interrupting module when a fault occurs. (xi) The control module shall include one or more integrally mounted current transformers to provide both the sensing signal and the control power. (xii) The current transformer used to provide control power shall be designed to act as a buffer against surges in the line by saturating at a level of current well below the surge-withstand capability of the electronic components. (xiii) No leads (including coaxial leads) between the current transformers and the electronic components shall be exposed. S&C Information Sheet
14 (2) To ensure the integrity of the electrical connection between the interrupting and control modules is independent of the mechanical force with which the modules are joined, the connection shall be through a louvered ring-type sliding contact. (3) Electronic power fuses shall be equipped with a blown-fuse indicator that shall provide visible evidence of fuse operation while installed in the fuse mounting. (4) It shall not be necessary to replace unblown companion interrupting modules following operation of an electronic power fuse. (5) Electronic power fuses shall have time-current characteristics that are permanently accurate. Time-current characteristics shall be available which permit coordination with source-side and load-side protective relays, automatic circuit reclosers, and other fuses. (6) Mountings for electronic power fuses shall also accommodate current-limiting fuses. Fuse mountings shall be enclosed in an inner steel compartment and shall be provided with bushing wells rated 200 amperes continuous for elbow connection. (1) Each fuse mounting shall be an integral part of a fuse handling mechanism that does not allow access to the fuse until the elbow for that fuse has been disconnected. To access a fuse it shall be necessary to: (i) Disconnect the elbow for that fuse and move it to the appropriate parking stand. (ii) Actuate a mechanical interlock to unlock the fuse-access panel. It shall not be possible to disengage this interlock before the elbow is moved. (iii) Unlatch and then pivot the fuse-access panel to electrically isolate the fuse so that it can be removed from the fuse mounting with a shotgun stick. (2) The opening into the component compartment shall be covered by the fuse-access panel in both the open and closed positions to help prevent inadvertent access to high voltage. (3) To protect the fuse-handling mechanism from corrosion, all mechanism parts shall be painted or made of corrosion-resistant materials, or otherwise be protected from corrosion. All latches and pivots shall be stainless steel or zinc-nickel-plated steel with nylon or plastic bushings. (4) Cable guides shall be provided in each termination compartment for a set of fuses, to prevent cables from interfering with rotation of the fuse-access panel. The following optional feature should be specified as required: A fuse-storage feature shall be provided in (one, two) source interrupter-switch compartment(s). Each fuse-storage feature shall provide space for storing three spare fuse holders or fuse units with end fittings for solid-material power fuses, or two spare electronic power fuse holders. 14 S&C Information Sheet
15 5.0 LABELING 5.01 Hazard-Alerting Signs (a) All external doors shall be provided with Warning Keep Out Hazardous Voltage Inside Can Shock, Burn, or Cause Death signs. The inside of each door shall be provided with a Danger Hazardous Voltage Failure to Follow These Instructions Will Likely Cause Shock, Burns, or Death sign. The text shall further indicate that operating personnel must know and obey the employer s work rules, know the hazards involved, and use proper protective equipment and tools to work on this equipment. Termination compartments shall be provided with Danger Keep Away Hazardous Voltage Will Shock, Burn, or Cause Death signs Nameplates, Ratings Labels, and Connection Diagrams (a) The outside of each door (or set of double doors) shall be provided with a nameplate indicating the manufacturer s name, catalog number, model number, date of manufacture, and serial number. The inside of each door (or set of double doors) shall be provided with a ratings label indicating the following: (1) Overall pad-mounted gear ratings: nominal voltage, kv; maximum voltage, kv; BIL voltage, kv; power frequency, Hz; short-circuit peak withstand current, amperes, peak; short-circuit one-second short-time withstand current, amperes, RMS, symmetrical; and short-circuit MVA, three-phase symmetrical, at rated nominal voltage. (2) Main bus ratings: continuous current, amperes; peak withstand current, amperes, peak; and one-second short-time withstand current, amperes, RMS symmetrical. (3) Switch ratings: continuous current, amperes; load splitting current, amperes; load dropping current, amperes; peak withstand current, amperes, peak; one-second short-time withstand current, amperes, RMS, symmetrical; and three-time duty-cycle fault-closing current, amperes, RMS symmetrical and amperes, peak. (4) Fuse type and ratings: maximum current, amperes and interrupting current, amperes, RMS, symmetrical. A three-line connection diagram showing interrupter switches, fuses, and bus along with the manufacturer s model number shall be provided on the inside of each door (or set of double doors), and on the inside of each switch-operating-hub access cover. S&C Information Sheet
16 6.0 ACCESSORIES (Specify as required.) 6.01 End fittings and fuse unit, holder and refill unit, or interrupting module and control module shall be furnished for each fuse mounting. In addition, one spare fuse unit, refill unit, or interrupting module shall be furnished A voltage tester with audio-visual signal capability shall be provided, along with batteries, shotgun clamp-stick adapter, and storage case A shotgun clamp stick (6 ft. 5 1/2 in., 8 ft. 5 1/2 in.) in length shall be provided complete with canvas storage bag. 7.0 ANALYTICAL SERVICES The following analytical services should be specified as required: 7.01 Short-Circuit Analysis (a) The manufacturer shall provide a short-circuit analysis to determine the currents flowing in the electrical system under faulted conditions. Since expansion of an electrical system can result in increased available short-circuit current, the momentary and interrupting ratings of new and existing equipment on the system shall be checked to determine if the equipment can withstand the short-circuit energy. Fault contributions from utility sources, motors, and generators shall be taken into consideration. If applicable, results of the analysis shall be used to coordinate overcurrent protective devices and prepare an arc-flash hazard analysis of the system. Data used in the short-circuit analysis shall be presented in tabular format, and shall include the following information: (1) Equipment identifications. (2) Equipment ratings. (3) Protective devices. (4) Operating voltages. (5) Calculated short-circuit currents. (6) X/R ratios. A single-line diagram model of the system shall be prepared, and shall include the following information: (1) Identification of each bus. (2) Voltage at each bus. (3) Maximum available fault current, in ka symmetrical, on the utility source side of the incoming feeder or first upstream device. (4) Data for each transformer (i) (ii) (iii) (iv) (v) Three-phase kva rating Percent impedance Temperature rise, 65 C and 55/65 C Primary voltage Primary connection 16 S&C Information Sheet
17 (vi) Secondary voltage (vii) (iix) (ix) Secondary connection X/R ratio Tap settings and available settings The manufacturer shall use commercially available PC-based computer software such as Power System Analysis Framework (PSAF Fault) from CYME International, CYMDIST, and/or SKM Power Tools for Windows with the PTW Dapper Module to calculate three-phase, phase-to-phase, and phase-to-ground fault currents at relevant locations in the electrical system, in accordance with ANSI Standards C37.010, C37.5, and C If applicable, an ANSI closing-and-latching duty analysis shall also be performed to calculate the maximum currents following fault inception Overcurrent Protective Device Coordination Analysis (a) The manufacturer shall provide an overcurrent protective device coordination analysis to verify that electrical equipment is protected against damage from short-circuit currents. Analysis results shall be used to select appropriately rated protective devices and settings that minimize the impact of short-circuits in the electrical system, by isolating faults as quickly as possible while maintaining power to the rest of the system. (e) As applicable, the analysis shall take into account pre-load and ambienttemperature adjustments to fuse minimum-melting curves, transformer magnetizing-inrush current, full-load current, hot-load and cold-load pick-up, coordination time intervals for series-connected protective devices, and the type of reclosers and their reclosing sequences. Locked-rotor motor starting curves and thermal and mechanical damage curves shall be plotted with the protective-device time-current characteristic curves, as applicable. Differing per-unit fault currents on the primary and secondary sides of transformers (attributable to winding connections) shall be taken into consideration in determining the required ratings or settings of the protective devices. The time separation between series-connected protective devices, including the upstream (source-side) device and largest downstream (load-side) device, shall be graphically illustrated on log-log paper of standard size. The time-current characteristics of each protective device shall be plotted such that all upstream devices shall be clearly depicted on one sheet. The manufacturer shall furnish coordination curves indicating the required ratings or settings of protective devices to demonstrate, to the extent possible, selective coordination. The following information shall be presented on each coordination curve, as applicable: (1) Device identifications. (2) Voltage and current ratios. (3) Transformer through-fault withstand duration curves. (4) Minimum-melting, adjusted, and total-clearing fuse curves. (5) Cable damage curves. S&C Information Sheet
18 (6) Transformer inrush points. (7) Maximum available fault current, in ka symmetrical, on the utility source side of the incoming feeder or first upstream device. (8) Single-line diagram of the feeder branch under study. (9) A table summarizing the ratings or settings of the protective devices, including: (f) (g) (i) (ii) (iii) (iv) (v) Device identification. Relay current-transformer ratios, and tap, time-dial, and instantaneous-pickup settings. Circuit-breaker sensor ratings; long-time, short-time, and instantaneous settings; and time bands. Fuse type and rating. Ground fault pickup and time delay. The manufacturer shall use commercially available PC-based computer software such as CYMTCC from CYME International and/or SKM Captor to create the timecurrent characteristic curves for all protective devices on each feeder. As applicable, a technical evaluation shall be prepared for areas of the electrical system with inadequate overcurrent protective device coordination, with recommendations for improving coordination Arc-Flash Hazard Analysis (a) The manufacturer shall provide an arc-flash hazard analysis to verify that electrical equipment on the system is electrically safe for personnel to work on while energized. An arc flash is a flashover of electric current in air from one phase conductor to another phase conductor, or from one phase conductor to ground that can heat the air to 35,000 F. It can vaporize metal and cause severe burns to unprotected workers from direct heat exposure and ignition of improper clothing. And the arc blast resulting from release of the concentrated radiant energy can damage hearing and knock down personnel, causing trauma injuries. The arc-flash hazard analysis shall include the following: (1) Identification of equipment locations where an arc-flash hazard analysis is required. (2) Collection of pertinent data at each equipment location, including: (i) Transformer kva ratings, including voltage, current, percent impedance, winding ratio, and X/R ratio, plus wiring connections. (ii) Protective device ratings, including current, time-current characteristics, settings, and time delays. (iii) Switchgear data, including conductor phase spacing, type of grounding, and appropriate working distances. (3) Preparation of a single-line diagram model of the system. 18 S&C Information Sheet
19 (4) Preparation of a short-circuit study to determine the three-phase bolted fault current at each location. (5) Preparation of arc-flash calculations in accordance with NFPA 70E and IEEE 1584, including: (i) Calculation of arc current in accordance with applicable guidelines. (ii) Determination of protective device total-clearing times based upon the time-current characteristics. (iii) Calculation of arc-flash incident energy level based on the protective device total-clearing times and appropriate working distance. (6) Determination of appropriate personal protective equipment in accordance with risk levels defined in NFPA 70E. (7) Calculation of the arc-flash protection boundary distance. (8) Documentation of the results of the analysis, including: (i) (ii) (iii) Preparation of a written report. Preparation of single-line diagrams. Preparation of arc-flash hazard labels to be affixed to the equipment. (9) The manufacturer shall use commercially available PC-based computer software such as the arc-flash module in SKM Power Tools for Windows to calculate the incident energy category levels, in accordance with IEEE Analytical Service Site Visits (a) The manufacturer shall perform a site walk-down to gather: (1) Transformer ratings, including voltage, current, power, percent impedance, winding ratio, and X/R ratio, plus wiring connections. (2) Protective device ratings, including current, time-current characteristics, settings, and time delays. (3) Switchgear data, including conductor phase spacing, type of grounding, and appropriate working distances. S&C Information Sheet
20 Printed in U.S.A.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Specifications. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv)
Outdoor Distribution (14.4 kv and 25 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)
1.0 GENERAL S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.1 This specification covers the electrical and mechanical characteristics of Three-Phase,
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
LIVE-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV
Manual Live-Front TYPE PSI/II MANUAL LIVE-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV The PSI/II is Federal Pacific's line of live-front pad-mounted switchgear (available as UL Listed) built to IEEE C37.74
SPECIFICATIONS. S&C Switch Operators Type PM SPECIFICATION BULLETIN 669-31. For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear
S&C Switch Operators Type PM Outdoor Distribution For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters
S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
Specifications. S&C Manual Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv)
Outdoor Distribution ( kv through kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Vista
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.
S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.
Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
MCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
TERMINATION ENCLOSURE OPTIONS
TERMINATION ENCLOSURE OPTIONS Add suffix: R - Reverse Stagger the Bus Bars (to run cable in from the top) CU - Copper NEMA Mount Bus Bars C - Plastisol Covers for Bus Bars DF - Dead Fronts T - Tin Plated
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
Safety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
5800 Temperature Sensor Cable Assembly
5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the
Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)
August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
Low Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
Learning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: [email protected] Cleaveland/Price Type TP-C2 Motor Operator
01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
Autobody/Collision and Repair Technology/Technician CIP 47.0603 Task Grid
1 Secondary Task List 100 ORIENTATION 101 Identify opportunities in the auto body field. 102 Identify basic auto body construction. 103 Identify program rules and policies. 104 Identify government agencies
Instructions for Secondary Unit Substation Transformers 150-3000 KVA, Three Phase
ABB Inc. Instruction Booklet Distribution Transformers Jefferson City, MO ISO 9001 Certified I.B. 46-060-1, Section E ILUJ000004-BLE Effective: January, 2008 Instructions for Secondary Unit Substation
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
Customer Substation Manual 08/05/02
Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
Installation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
Type 1, 3, & 3R Enclosures
Junction oxes Type 1 Screw over....................................................................... 50-53 Junction oxes Type 1 Hinge over........................................................................
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
Installation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
16300 MEDIUM VOLTAGE DISTRIBUTION
16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served
DYNA RIDER FOOTBOARD KIT
-J0 REV. 0-0-0 DYNA RIDER FOOTBOARD KIT GENERAL Kit Number 000 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Instructions For SF 6 Refill Kit
S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
S&C TripSaver Dropout Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing S&C s new TripSaver Dropout Recloser: A better solution for overhead lateral circuit protection at
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and