DOCUMENT TITLE : ELEMEC plus PUBLIC ADDRESS AND GENERAL ALARM (PA/GA) SYSTEM SPECIFICATION PROJECT : Rev 3 25/2/04
|
|
|
- Trevor Fisher
- 9 years ago
- Views:
Transcription
1 DOCUMENT TITLE : ELEMEC plus PUBLIC ADDRESS AND GENERAL ALARM (PA/GA) SYSTEM SPECIFICATION PROJECT : Rev 3 25/2/04
2 TABLE OF CONTENTS 1. GENERAL SCOPE SCOPE OF WORK REFERENCES SUBMITTALS QUALITY ASSURANCE REGULATORY REQUIREMENTS SYSTEM DESCRIPTION ARCHITECTURE EQUIPMENT CHARACTERISTICS CENTRAL EQUIPMENT MAIN SYSTEM FEATURES ACCESS PANELS DUPLICATION OPTIONAL SYSTEM FEATURES SYSTEM OPERATION GENERAL PUBLIC ADDRESS ANNOUNCEMENTS EMERGENCY NOTIFICATION SUPERVISION PAGING PRIORITIES PLANT TELEPHONE ACCESS PRODUCTS AND MATERIALS CENTRAL EQUIPMENT System Cabinet Basic Components Power Amplifier Power Supply Interfaces FIELD EQUIPMENT Access Panels Loudspeakers Auxiliary Warning Beacons Uninterruptible Power Supply of 24
3 Auxiliary External Equipment EXECUTION INSTALLATION ELECTRICAL PROTECTION ENVIRONMENTAL CONDITIONS TESTING COMMISSIONING AND TRAINING WARRANTY MEAN TIME TO REPAIR (MTTR) of 24
4 1. GENERAL This specification describes the minimum requirements for the design, manufacture and application of the Public Address and General Alarm (PA/GA) System. The PA/GA application is a critical system with respect to personnel safety and shall, during an emergency situation, be fully operational to allow safe evacuation of the facility, therefore a field proven design shall be provided. The ELEMEC plus System architecture and operation exceeds the requirements for a reliable, life safety PA/GA system. The PA/GA System shall be fully compliant to this specification. The ELEMEC plus System shall distribute alarm tones, pre-recorded messages, emergency voice messages and routine voice messages to all or selected areas of the facility, in a reliable and safe manner, by the use of loudspeakers. In areas with a high ambient noise level, flashing lights shall complement voice messages and audible alarms Alarms shall be initiated either manually from any one of the dedicated access panels or automatically from the Fire and Gas Detection System or Emergency Shutdown System main panel via dedicated hardwired interfaces between the two systems. Voice messages shall be generated either from the microphones at dedicated access panels or from telephones in the facility SCOPE The purpose of this specification is to ensure consistency in selection, design and application of the Public Address and Alarm System. This specification defines the requirements of the Public Address System equipment utilised, to allow broadcasts of speech and alarms. Minimum hardware and application software requirements of these systems are defined. All labour, materials, equipment and services necessary and required to furnish and install a complete and operating Public Address and Alarm system are provided. Any material not specifically mentioned in this specification or shown on the applicable drawings, but required for proper performance and operation shall be included SCOPE OF WORK PA/GA system, including controls (central and remote), access stations, amplifiers, loudspeakers, wiring and all specified and/or required appurtenances and accessories REFERENCES The following categories list the standard bodies referenced in the design of the system: A. Alarm Systems 3 of 24
5 International Electro-technical Commission (IEC) UKOOA Guidelines for Telecommunications Systems International Maritime Organisation (IMO) SOLAS DNV Safety Principles and Arrangements B. Equipment for use in Hazardous Locations Comite European de Normalisation Electro-technique (CENELEC) International Electro-technical Commission (IEC) IEC 79 Electrical apparatus for explosive gas atmosphere IEC 331 Fire resisting characteristics of electric cables IEC 529 Classification of degrees of protection provided by enclosures IEC 801 Electromagnetic compatibility for industrial-process measurement and control equipment C. Equipment Safety Comite European de Normalisation Electro-technique (CENELEC) CE Mark International Electro-technical Commission (IEC) 1.4. SUBMITTALS Based on customer detailed requirements the following shall be supplied: A. Equipment general arrangement drawings. B. Equipment termination drawings. C. Certificates of conformity. D. Catalogue data on all furnished standard equipment, including, but not limited to: - 1. Central equipment and all internal modules and devices. 2. Access panels. 3. Field access panels. 4. Loudspeakers. 5. Beacons. E. Technical manuals which contain mounting details and dimensions, installation and connection instructions, operating and maintenance instructions, spare parts list and equipment specifications. F. As-built equipment drawings after construction. 4 of 24
6 1.5. QUALITY ASSURANCE A. All work shall be performed in accordance with this specification, applicable drawings and the best modern practices in design, manufacture and fabrication. B. The system equipment manufacturer shall be ISO 9001 registered for the design, manufacture, contract installation management and service of industrial communication and emergency notification systems. The system manufacturer shall be an experienced firm having 10 years documented experience in the manufacture of similar systems currently demonstrating satisfactory service. C. The system equipment manufacturer shall have in effect at all times a quality system which shall fully satisfy all the elements of ISO , "Quality Systems-Model for Quality Assurance in Design/Development, Production, Installation and Servicing" and ISO , "Quality Management and Quality System Elements- Guidelines". The quality system shall provide for the planned and systematic control of all quality-related activities performed during design. Implementation of the system shall be in accordance with the system equipment manufacturer s Quality Manual. The Quality system shall clearly establish the authority and responsibility of those responsible for the quality system. Persons performing quality functions shall have sufficient and welldefined authority to enforce quality requirements, initiate, identify, recommend and provide solutions to quality problems and verify the effectiveness of the corrective action REGULATORY REQUIREMENTS A. The PA/GA system shall be designed and installed in complete conformance designated by the customer requirements. B. All hazardous locations shall be equipped with certified equipment. Equipment certification shall be through recognised testing laboratories. Equipment shall be labelled according to the appropriate regulations. 5 of 24
7 2. SYSTEM DESCRIPTION 2.1. ARCHITECTURE The PA/GA system shall be divided into one or more zones (up to a maximum of 8 zones) which can be accessed independently for announcement or alarm broadcasts. Zones can be designated as to function, such as: work areas or accommodations. Physically, loudspeakers or beacon circuits shall support zones where one or more circuits can be partitioned into a zone. Each loudspeaker or beacon circuit shall be connected to the central equipment for amplification and control/monitor functions. Paging announcements shall be broadcast through loudspeakers installed in the various areas and locations throughout the facility. The system shall allow calls between it and any existing public address system. The system shall be modular in design and shall be easily expandable. The area coverage will be such that calls will be clearly audible in the paged operating areas and their surrounding space. Final distribution of loudspeakers over the zones will be determined during detailed design. Each zone shall be split into loops, where each loop is physically connected to a different amplifier. This configuration ensures that a loss of a single amplifier does not adversely affect paging broadcasts within a zone. The distribution of loudspeakers will be related to area configuration and other operational objectives. Cable distribution throughout the plant area will be designed such that all loops relevant to the same zone are laid up separately following different paths, in order to ensure that cable cuts or shorts will cause a minimum effect on the zone broadcast. Suitable speech amplifiers shall drive the loudspeaker lines. The system shall provide facilities for automatic insertion of a hot standby amplifier(s) in the event of a single/multiple amplifier failure. Access panels shall support operator voice announcement and alarm control operations. Announcements are classified as routine or emergency, where an emergency announcement shall take precedence over all other audio broadcasts. The system shall be expandable to provide inputs for up to 16 fully fitted microphone panels. Announcements shall be pre-configured to broadcast in designated zones. A zone selection feature shall enable users to direct routine announcements to selected zones. Alarm operations shall initiate the broadcast of alarm tones or pre-recorded messages to pre-configured designated zones. Access panels shall be connected to the central equipment and accorded an access priority for announcements. Alarms shall be accorded a broadcast priority that gives the most critical alarm precedence. Each access panel shall be able to: - Address a call to one or multiple zones. (maximum 8) 6 of 24
8 Address a call to one or multiple groups of zones, by activating the selected groups of zones. Transmit a general call to the whole area activating all zones simultaneously. The speech messages shall be announced by an automatically generated preannouncement attention signal. The access panels shall be interlocked to prevent interference on the call in progress for the same zone or group of zones from lower priority panels. In addition, all audio signals to be broadcast shall be able to be configured with different levels of priority in order to allow each signal to override the others where appropriate and where specified in accordance with specific site requirements. The central equipment shall support external interfaces for telephone or other audio source interconnection for routine broadcast to designated zones. A digital storage and replay feature shall eliminate any acoustic feedback between audio source and nearby loudspeaker. Each external interface shall be accorded an access priority for announcements. Additional interfaces shall support connectivity to external alarm or monitor systems to facilitate the remote control of alarm operations. Alarms shall be accorded a broadcast priority that gives the most critical alarm precedence. It shall be possible to initiate a routine paging broadcasts via authorised telephones. In normal operation the user will ring into the system, record a message and then trigger its playback over related zones. Automatic repeating of the message can be configured. DTMF tones are used to control the recording and playback of the messages. If the access to the PA System is denied due to priority configuration, the PA System shall return a busy signal to the telephone caller. The plant radio sets equipped with DTMF keypad shall be interfaced with the plant telephone PABX, and consequently they shall be allowed to access the PA system in the same manner as the telephones. Integrated test equipment shall be incorporated into the central equipment to identify faults on the external loudspeaker loops EQUIPMENT CHARACTERISTICS The system shall provide facilities for the control and management of a high integrity Public Address and Alarm System specially designed for industrial environments where advanced technology coupled with very high system availability is demanded. The materials used shall have characteristics suitable for the installation site and for the service required. The equipment shall be fully solid state type, multimicroprocessor based and programmable. The system shall be software program controlled to enable easy system configuration and self- diagnostics, as well as future software upgrade. 7 of 24
9 Configuration of the system shall be achieved by software for maximum flexibility. A user friendly set-up and checking routine shall provide system management and programming through LCD displays and Personal Computers, which enables an operator using a system controller to implement quick commissioning and fault finding functions. The use of these methods shall allow adjustments to be easily made after the system is installed without resulting in modifications to the system wiring. The access panels shall be microprocessor based and connected to the central control cabinets using three individually twisted and shielded pairs. Facilities to indicate the status of the main system units shall be provided. Such indications shall show any faulty unit for easy replacement. The system shall be provided with standard serial interface RS 232 for local or remote access for supervision and maintenance activities (such as diagnostics with a mimic panel, status and logging of events) CENTRAL EQUIPMENT The central equipment shall comprise a single 42U X 19 cabinet. The cabinet shall house all amplification, control and monitoring equipment necessary for the reliable operation of the PA/GA system. An additional amplifier cabinet can be accommodated where greater broadcast power is a requirement. External connections shall be provided for loudspeaker and beacon circuits and external interfaces shall be supported within the central equipment cabinet. The central equipment shall support integral facilities to test the system and provide status information to facilitate repair or replacement of possible failed circuits. Cable entry to the central equipment cabinet will be via top and/or bottom gland plates, which will be provided less drilling MAIN SYSTEM FEATURES A. Configuration of Alarm Tones and Priorities Alarm tones and priorities shall be configured to each customer s requirement so that particular tones are generated under different conditions. Higher priority alarms shall be programmed to override those of a lower priority. The customer shall specify alarm tone frequencies, types, durations, external contact specifications and alarm conditions during the detail design phase. B. Configuration of Announcement Priorities Announcements from different sources shall be configured to override others. C. Pre-Announcement Tones Single chime or double chime as pre-announcement tones shall be generated under software control, with the possibility to associate these different chimes to different sources and activation types. For example, typically a single chime 8 of 24
10 precedes a routine announcement and a double chime precedes a telephone access. D. Zone Selection of Announcement and Alarms Real time and pre-recorded voice messages and Emergency Alarm signals may be diverted to pre-determined groups of amplifiers/loudspeakers. The access priority regime will determine which announcement has priority of access and is broadcast. The configurations of groups of zones shall be changed via software without the need to alter wiring of audio inputs or the speaker loops. E. Gain Control of Alarms and Announcements Alarms and announcements shall be individually configurable to different volume levels to allow for clearly audible emergency broadcasts. An alarm in progress can be attenuated (up to 12 db) or fully muted while an emergency broadcast is made and then increased back to its original level afterwards. F. Pre-recorded Digital Tones and Important Messages The microprocessor shall control the generation of alarm tones, as well as prerecorded chimes and digital speech messages. The system shall be provided with alarm and test tones, as well as the facility for bilingual or multilingual pre-recorded announcements Emergency notification alarms can be broadcast manually or automatically. Each alarm is fully configurable and initiated by either a direct command from an access panel or by contact closures from within other system equipment. (Such as fire and gas detection systems) in accordance with the customers requirements. Prerecorded messages of up to 256 seconds in length can be initiated manually from any operator access panel. For security reasons it shall only be possible to reprogram either the important message or the alarm tones by removing the controller unit lid and replacing the storage device (EPROM). G. System Recovery The control unit incorporates a hardwired watchdog circuit. This circuit must be continually refreshed from the microcontroller to prevent it from generating a hardware reset. The circuit also monitors the power supply to generate resets if brown-outs occur. The 'crash mode' relays are also controlled by this circuit to ensure that they revert to fault condition if the processor stops running. H. Power Amplifiers Industry standard 300 Watt power amplifiers shall be provided with the following minimum features: low idle current, LCD indicators for output level (V.U), built-in thermal protection, overload and short circuit protection. The short circuit protection shall shut off the power amplifier for a 5-second period, repeating until the fault is rectified. Power amplifiers shall be provided with built-in supply capability from AC mains or 48VDC or 24V DC (250W). 9 of 24
11 I. Network Connection Facility Data links between remote units shall be provided through standard serial interface RS 232/RS 485. The maximum distance for RS 485 shall be 1km. Audio links between remote units shall be provided through individually shielded, twisted pairs. The maximum distance shall be 1 km. For distances greater than 1 km, it shall be necessary to use an alternative transmission system, for example a fibre optic link may be used. J. Multiple Sources of Speech Announcements shall be able to be made from a variety of sources, such as engineer test panel, operator access panels, telephones via PABX interface, radio (through the PABX) or digitally recorded messages. K. System Redundancy The system is designed for full 100% redundancy of equipment. Each operator access panel is provided with duplicate (A+B) circuitry. To further increase system availability hot standby amplification shall be offered. System power supplies may be provided such that each control cabinet shall contain a power supply of substantial capacity to provide power to the Controller Unit and Microphone Panels. L. Built-in Self Diagnostics Each piece of system equipment shall have a comprehensive built in diagnostic test feature so that at all times the status of the system can be monitored. Faults shall be reported to an operator or engineer via remote or local access panel. Circuit failures shall be reported on the LCD display of the Controller Unit and on the operator s control sets, and reported remotely through dry contacts and/or serial lines. The system monitoring functions shall include: - Management System alarms, power amplifier alarms, power supply alarms, speaker loop alarms and communication alarms between the various system equipment. M. Speaker Loop Monitoring The system shall provide the facility for monitoring speaker loop status. Automatic setting procedures shall be able to be programmed in order to check all output line conditions. Speaker loop monitoring shall utilize two-wires, using the same 100V or 70.7V speaker line, which provides real time (or scheduled) trouble-shooting of the individual speaker loops. The system shall provide facility for detection of speaker line earth leakage and for detection of speaker line impedance deviation, utilising an ultrasonic signal (open or short circuit detection or alteration from the defined typical value). 10 of 24
12 2.5. ACCESS PANELS Multiple access panel formats shall be supported. Standard formats shall include rack-mount, desktop and bulkhead versions. Each panel type can be offered in safe area or I.S. approved versions for use in Zone 1, Gas Group IIB/C, Temperature Class T4 locations. Custom formats can be provided if packaging deviations do not void unit certifications. Connection to the Central Equipment shall be via a 3 pair individually screened cable. Access panels shall support facilities for an operator to execute routine or emergency announcements, and initiate and terminate prioritized alarms. Panels shall provide status information on panel and external operations, and system health. Operator facilities shall be selected from a features list to meet a customer s specific operational requirements. The unit may be used with a single system or provide galvanic isolated circuits for use with fully redundant A+B systems. The front fascia panel allows user access to: - Panel microphone:fist or gooseneck (safe area or I. S.) Panel switches: Up to 30 pushbuttons can be fitted Sounder: Confidence beep tone emitted on any pushbutton press (safe area panels only) Switch LEDs: Lights to confirm control equipment acceptance of push button press Status LEDs: Indicators provided for typical, healthy, fault, alarm actuation, system in use DUPLICATION The system design shall support a complete duplication of critical components, i.e. central equipment, access panels, loudspeakers and beacon components. The desired redundancy format shall be stipulated by the customer requirements. Critical component redundancy shall support duplication (2N) or hot standby (N+1) formats. Components available for duplicated service shall be, but are not limited to tone generators and pre-recorded audio units. Components available for hot standby shall be, but are not limited to amplifiers and power supplies. Complete duplication of the PA/GA system shall be of a design such that in the event of a serious failure of the alarm circuits in the primary central equipment cabinet, the secondary cabinet is given control of the power amplifiers and beacon outputs. In case of complete cabinet failure, alarm and emergency announcements shall still be audible in all areas from all microphone panels, but at a reduced volume level. 11 of 24
13 2.7. OPTIONAL SYSTEM FEATURES A. Audio Recording The calls originated from telephone or microphone consoles shall be automatically recorded through a suitable digital audio recorder, with a removable storage media. During an incident or emergency, it shall be possible to record voice traffic on the system for future replay. A transformer isolated 600 ohm output is provided for this purpose. B. Alarm Attenuation Attenuation of alarms while a broadcast is being made shall be provided. The alarm audio level shall be reduced up to 12 db from the broadcast level. C. Audio Path Monitoring The system shall provide full audio path test from microphone panels to loud speakers with ultrasonic audio signal for true dynamic checks. The ultrasonic test signal shall be a true sinusoidal low distortion signal. The system shall provide signal wire integrity monitoring throughout the internal cabinet wiring and over all access panels to cabinet wiring (open or short circuit, unbalancing for balanced lines and ground leakage). D. Background Music Broadcast The system shall be able to provide broadcasts of background music from various music sources such as CD players, cassette recorders or tuners. The Customer shall specify music sources during the detailed design phase. E. Page /Party Access A facility is provided whereby the page line output of a GAI-Tronics Page/Party system can access the Elemec Plus equipment to make paging broadcasts. Dependent upon the input configuration, either real time or voice storage and replay options are available. F. PABX Access A priority telephone interface unit can be installed at each equipment cabinet. Upon receipt of a valid access code (e.g., 333) a confirmation tone is returned to the call originator and the message to be broadcast is recorded. During message playback system A has control and sends the announcement via the A/B inter-link to both A and B broadcast amplifiers. G. Auxiliary Warning Beacons The system shall provide for auxiliary warning beacon activation or other relaycontrolled outputs (up to 16 maximum), for alarm indication and local muting facilities. 12 of 24
14 3. SYSTEM OPERATION 3.1. GENERAL The PA/GA system shall provide basic functions for: Announcements The capability to support prioritized one-way voice audio broadcasts to one or more zones from access panels and external audio interfaces. Emergency Notification The capability to support prioritized alarm responses that include audio and/or visual notification when initiated from access panels or external interfaces. Supervision The capability to continually monitor all critical audio paths and circuits so that any failure can be brought to the attention of the system operators or maintenance personnel for corrective action PUBLIC ADDRESS ANNOUNCEMENTS The PA/GA system shall provide one-way voice audio broadcast primarily utilising access panels located throughout the facility in accordance with customer requirements. Additional broadcast services shall be provided through interfaces for telephone or intercom systems as specified by customer requirements. Alarm audio notification shall employ circuitry integral to voice audio broadcast so as to facilitate prioritisation. Access panel, external audio interface and alarm audio sources shall be prioritised by content to allocate access to the most critical broadcast information. Where multiple microphone panels are used, these shall be prioritised in order of importance. TABLE 3-1 TYPICAL ANNOUNCEMENT PRIORITISATION MESSAGE CONTENT PRIORITY LEVEL DEFAULT DESTINATION Emergency Announcements from Access Panels 1 st Priority All Areas (Programmable) Including accommodation Alarms 2 nd Priority All Areas (Programmable) Routine Announcements from Access Panels External Announcement (eg PABX) 3 rd Priority All normally occupied work areas, zone selectable except accommodations 4 th Priority All Areas, zone selectable 13 of 24
15 A facility to combine both zone selection and announcement initiation shall be supported. This facility shall allow an operator to select one momentary switch to launch a routine announcement to one pre-configured zone. Zone selection is automatically terminated after an announcement. Status facilities shall be provided to display system information regarding active or non-active announcement information on access panel indicators. This status serves to sequence equal access announcements EMERGENCY NOTIFICATION The PA/GA system shall support eight alarms that consist of distinctive tones and/or pre-recorded messages broadcast to predetermined destinations. Visual notification shall be supported for alarms and emergency announcements to supplement audio notification in areas where noise levels typically exceed 85dBA or in accordance with customer requirements. Visual notification shall be through color coded beacons that indicate the severity of the alarm or emergency announcement. Each alarm may be initiated through an access panel or external voltage free contact interface. The standard manual format for alarm operations from an access panel shall be through switches for each alarm activation. The external interface shall support configurable normally open or normally closed, maintained or momentary voltage-free contacts for each automatic alarm activation. Audio notification shall be prioritised to assure the broadcast of the most critical alarms as identified in Section 3.2. Customization of the system design can provide for additional alarms. Status facilities may be provided to display system information regarding active or non-active alarm information on access panel indicators. This status serves to provide a visual interpretation to access panel operators SUPERVISION The central equipment shall incorporate configurable automatic monitoring facilities. These facilities shall be selected during system design in accordance with the customer requirements. The standard set of monitoring facilities shall interrogate: Controller unit with built-in message/tone generator. Power amplifiers. Loudspeaker loops. Digital communication paths between the various system equipment. The interrogation of supplemental circuits shall be supported as required. The standard system design shall ensure that all critical audio paths and operation of the PA/GA system are continuously monitored so faults are immediately identified. The Controller Unit located in the central equipment cabinet shall assist 14 of 24
16 in fault location and diagnosis during a failure condition. Voltage free relay contacts shall be provided to enunciate equipment failure conditions to external systems. Facilities shall be provided to display system information regarding health or fault information on access panel indicators PAGING PRIORITIES Paging priorities can be assigned for each page audio source and can be altered through software programming PLANT TELEPHONE ACCESS The following steps are completed to make an all zone page announcement from a plant telephone: Dial the PA Access number the system will auto-answer if the line is not already engaged; otherwise a busy notification will be returned. As an alternative it is possible to provide zone selection from PABX access by keying the appropriate zone once a seize condition has been registered. Make announcement then through the use of the page delay feature to eliminate feedback, the system broadcasts the user s voice to all zones if no other higher or equal priority broadcast is active. Access to plant telephones or radios are similar except for the number dialled. Note: Based on the project specification, the approach for radio access assumes that DTMF keypad equipped hand-held radios are employed, and interfaced with the plant telephone PABX, and consequently allowed to access the PA system in the same manner as the telephones. 15 of 24
17 4. PRODUCTS AND MATERIALS 4.1. CENTRAL EQUIPMENT The central equipment shall consist of: Single board Controller Unit with integral fault monitoring circuitry Audio Power Amplifiers Power Supplies System Cabinet The control sub-system, amplifiers and their ancillary devices shall be housed in a 19 standard rack mounted 42U system cabinet with all control, power circuits and necessary amplifiers. Wiring from the modules shall be via ribbon cables and via screw terminals. Connections external to the control rack shall also be made via screw terminals. All wiring shall be clearly identified by numbered sleeves and terminal markers where appropriate. Cabinet(s) shall contain all panels that are part of the central system equipment. Cabinets shall have front glazed and plain rear access doors. Panel(s) shall be removable from the front, and disconnected from the rear before removing. The cable entries shall be via top or bottom gland plates sealed. Low power signals among cabinets shall be extended with interconnecting cables connected via IDC terminals. All the connectors shall be mechanically lockable. Cooling fans external to the power amplifiers, shall not be used. Terminal strips shall be provided at each side of the cabinet(s) for external circuit s connection. All terminals shall be progressively numbered. Terminals shall have adequate size for accepting cables with up to 2.5mm² cross section. Dirty and clean earth bars shall also be provided to earth all the metallic parts of the cabinet(s) and incoming field cables. Unless otherwise specified in the requisition, or agreed by the principal, the colorcoding of wires shall be as follows: Power Positive Negative Live Neutral Low Level Input signals Low Level Output signals 100V Power Output Signals Safety earth Signal earth RED BLACK BROWN LIGHT BLUE TBA GREY/ORANGE TBA GREEN/YELLOW GREEN 16 of 24
18 Basic Components Controller Unit The control unit provides the heart of the PAGA system controlling audio routing from access panels, alarm generation, contacts inputs and outputs, power amplifier control, and visual-audible indication of system status. For ease of rack wiring all connections to the unit are made via ribbon cables. The unit is microprocessor controlled with a hardware fallback circuit, which is capable of alarm generation and emergency speech in the event of processor failure. Three PCBs are used within the unit one main PCB containing all the audio routing and microprocessor components, a front panel PCB containing the LCD, LEDs, and switches, and a rear PCB for the ribbon cable connectors. The software is designed to be as flexible as possible by making extensive use of configurable options to meet customer needs. The system is configured via an RS232 port with appropriate software. The system is designed for use in safety critical installations and as such contains several high integrity features. Emergency fall back operation Dual system A/B inter-link for operational status checking Fully duplicated A/B operation Hardware watchdog circuitry Hot standby amplification Fault-event logging Power Amplifier The power amplifiers support speaker loops. Each amplifier produces 300W RMS from a 0dB, 600 ohm-input signal. The line output is 100 or 70V with a frequency response of 100 to 18,000 Hz and with less than 1% THD. The power amplifier shall be capable of operation from 115/230 VAC or 48 VDC or 24VDC (250W) with a supply tolerance of ± 10% and shall be capable of operating in an ambient temperature ranging from -10 C to +40 C. Separate Amplifier power supplies and separate fan cooling shall not be used. Power consumption at full power is 500W and quiescent power consumption is 25W. The amplifier is monitored for fuse failure, overtemperature, overload, and output short circuit. Alarm levels shall be capable of being broadcast at full line output level continuously. 17 of 24
19 The power amplifier shall provide the following features: On/Off Switch Internal overload and shutdown protection Temperature controlled, cross flow forced cooling Soft-start power up (AC mains), preventing initial current surges Comprehensive front panel status LCD display indicating: a) High Temperature operation b) Output Overload c) Power On d) Internal DC Fuse Failure e) LCD output level bar graph f) Tri-state LED fault indication g) Zone allocation h) Amplifier Enable/Disable i) Amplifier Shutdown The unit shall be composed of a welded steel tray with vented lid. Connections shall be supplied for audio and supply input, line output and standby line input. The unit shall be 19 rack mountable with 2U height. The supply and line voltages shall be selected in accordance with customer requirements Power Supply The power supply shall operate from VAC (+10%) 50/60 Hz, in a temperature ranging from -10 C to +40 C. Power consumption at full power is 150VA max. The power supply shall be protected against short circuit on each output Interfaces The central cabinet shall provide customised interfaces in accordance to customer requirements. These interfaces support, but are not limited to, the following applications: Telephone Announcement - Supports telephone dial-in announcement facility; will incorporate feedback elimination. Facility Control System - Supports alarm inputs and status reporting for an external system, up to a maximum of 16 inputs. Fire and Gas Emergency Supports alarm inputs and status reporting for an external system, up to a maximum of 16 inputs. 18 of 24
20 Interfaces that support announcement facilities employ access panel and central equipment cards to inject and control audio for subsequent broadcast to preconfigured areas. Typically these interfaces are at a lower priority than access panel or system alarm announcements. Connection to external systems shall be through contact inputs and outputs. The inputs (up to 16 max) typically are implemented through a normally open relay contact wherein the external system energises the relay for the normal state. A deenergised or open circuit condition on the line triggers the alarm response. Outputs are also supported by relays wherein either state can be supplied to the external system. The outputs typically are used to provide PA/GA system status information FIELD EQUIPMENT The field equipment shall consist of: Access Panels Loudspeakers Auxiliary Warning Beacons UPS Auxiliary external equipment Access Panels Access panels shall be custom designed to support system specific announcement and alarm operations in accordance with customer requirements. While each panel is unique in terms of configuration up to 30 pushbuttons, the design shall incorporate standard components and packaging formats. Connection between each panel and the central equipment cabinets shall be through 3 pair individually screened/shielded conductor cable Loudspeakers The loudspeakers shall be indoor, weatherproof for all outdoor locations, and/or explosion proof type (if required), depending upon the location in which they will be installed. The nominal power is intended as the power of a sinusoidal signal continuously applied without damage. All speakers of the same type shall have the same rated power and shall be adjusted to provide the required coverage. The secondary winding of the loudspeaker transformer shall be tapped so that the loudspeakers will absorb from the line 100%, or a smaller percentage of its power, according to the tap used Auxiliary Warning Beacons 19 of 24
21 Proprietary Xenon beacons shall be employed with either indoor, weather-proof outdoor and or explosion proof type (if required) depending upon the location in which they will be installed. High output power 10-joule units are preferred Uninterruptible Power Supply The system will be powered from an Uninterruptible Power System at 220 V, single phase, 50 Hz. Range of UPS voltage deviations are limited to ± 2%; bypass source deviations may be up to ± 10%. The UPS shall be able to feed the entire equipment load and allow 20% future growth. It shall be fitted with the suitable optical indication of correct working condition Auxiliary External Equipment Auxiliary external equipment could include a PABX, Page/Party Interface, or other similar equipment. 20 of 24
22 5. EXECUTION 5.1. INSTALLATION A. Locate and install components as indicated on the applicable drawings and in accordance with the manufacturer s recommendations. Access panels shall be mounted with sufficient clearance for observation and testing. All junction boxes shall be clearly marked for easy identification. All wiring shall be in conduit or other approved means. All devices, conduit, junction boxes, etc. shall be securely hung and fastened with appropriate fittings to ensure positive grounding throughout the entire system. B. All wiring shall be checked and tested to ensure that there are no grounds, opens or shorts, on all the control, power and audio conductors. C. The equipment manufacturer shall provide technical guidance during and/or following construction to perform a checkout of the system. At such time, a factory-trained technician shall apply system power and make all necessary adjustments and instruct operating and maintenance personnel on the proper use and care of the system ELECTRICAL PROTECTION All field mounted electrical equipment shall be of the weatherproof type IP65 and/or of explosion-proof type Ex d certified to CENELEC/IEC for hazardous area classified Zone 1, IIB or IIC, T4, IP65 as required ENVIRONMENTAL CONDITIONS The equipment shall, in all respects, be suitable for operation in service conditions typical of the facility environment. The following parameters further define the environmental conditions: Indoor Conditions: Ambient temperature : 25 C, ± 2 C Humidity : 40% to 60% Pressurization: 6.5 mm WG min. 21 of 24
23 Outdoor conditions: Air temperature: min/max. 5 / 50 C Relative humidity: min/ max. 6 / 100% Rain: min/max. 0 / 100 mm per year Maximum: wind velocity :160 Km/hr Altitude not exceeding: m AMSL 5.4. TESTING A. The installed system shall be performance tested in accordance with the manufacturer s recommendations and in accordance with the applicable requirements. Tests shall demonstrate the proper operation of all components, interlocks, etc. B. The Owner and Engineer reserve the right to witness the tests and approve all portions of the system prior to acceptance COMMISSIONING AND TRAINING The System Equipment Manufacturer shall perform on-site commissioning and start-up of all system components in order to provide a fully functional system. The System Equipment Manufacturer shall provide a training course on site for Customer s personnel on the operation and maintenance of the system as follows: Operation: 1 day Maintenance and programming 2 days The System Equipment Manufacturer shall provide any and all special test equipment required for system check-out/start-up and/or training functions WARRANTY A. The Installer shall warrant all equipment and systems for a period of one-year following shipment. B. The manufacturer shall offer an annual test and maintenance agreement, consisting of the following: 1. Regularly and systematically examine, test and adjust all system components. 22 of 24
24 2. Submit test reports, which certify that all components have been tested and that the system is in proper working order and functions in accordance with this specification MEAN TIME TO REPAIR (MTTR) The design and construction of the Public Address and General Alarm system shall ensure high reliability and availability. The Public Address and General Alarm system shall employ modular constructional techniques in its design, allowing a first line maintenance philosophy of module replacement to be implemented. The average module replacement time for the system is less than 1 hour as long as the correct spares holding is maintained as recommended by the manufacturer. 23 of 24
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
PS 29M DUAL CHANNEL BELTPACK IN METAL CASE
PS 29M DUAL CHANNEL BELTPACK IN METAL CASE USER MANUAL October 2013 This product is designed and manufactured by: ASL Intercom BV Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax:
Kit 106. 50 Watt Audio Amplifier
Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications
LOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
EN54-16 Voice Alarm System PRODUCT DATASHEETS
EN54-16 Voice Alarm System PRODUCT DATASHEETS WayGuard This page is intentionally left blank Pagina 2 di 16 WayGuard Revision history Rel. Data Autore Modifiche 1.00 25/02/15 First emission Pagina 3 di
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
Installation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
1 All safety instructions, warnings and operating instructions must be read first.
ONYX USER MANUAL 2 Dateq ONYX Manual Safety instructions EN Safety instructions 1 All safety instructions, warnings and operating instructions must be read first. 2 All warnings on the equipment must be
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX
ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX INSTALLATION INSTRUCTIONS Step 1. Determine the position for the Hands-free phone in the elevator phone
PagePac PAGEPAL V-5335700
PagePac Issue 3 by PAGEPAL V-5335700 INTRODUCTION The PagePal unit interfaces most telephone systems (PBX, KTS, Centrex) to virtually any public address audio system. In addition, PagePal furnishes inputs
USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.
USER GUIDE Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator Version 1.3 DM Engineering 2174 Chandler St. Camarillo, CA 91345-4611 805-987-7881 800-249-0487
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
FIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
PowerGem Pro Uninterruptible Power Supply
Uninterruptible Power Supply User-friendly Intelligent Ultra reliable Range The Most Intelligent On-Line Double Conversion Power Protection System The range achieves higher reliability and greater immunity
Praesideo - Digital Public Address and Emergency Sound System
Praesideo - Digital Public Address and Emergency Sound System Praesideo - Digital Public Address and Emergency Sound System 2 Praesideo - Digital Public Address and Emergency Sound System Praesideo - Digital
CX Zoner Installation & User Guide
CX Zoner Installation & User Guide Cloud Electronics Limited 140 Staniforth Road, Sheffield, S9 3HF England Tel +44 (0)114 244 7051 Fax +44 (0)114 242 5462 e-mail [email protected] web site http://www.cloud.co.uk
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
Back-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
Repeaters and Mimics Data Sheet
Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
Applied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
User manual Rev 1.3 Contents
User manual Rev 1.3 Contents 1. Introduction...4 2. System specifications...5 2.1.. General overview...5 2.2. Maximum capacity...6 2.3. Electrical specifications...6 2.4. Mechanical specifications...6
TrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
SECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines
PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,
GSM Alarm System User Manual
GSM Alarm System User Manual For a better understanding of this product, please read this user manual thoroughly before using it. Quick Guider After getting this alarm system, you need to do the following
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
TOTALLY SOLID STATE NON-DIRECTIONAL RADIO BEACONS 190-535 khz
TOTALLY SOLID STATE NON-DIRECTIONAL RADIO S 190-535 khz This family of radio transmitters has been developed as extremely efficient, highly reliable Non Directional Beacons. ND2000A/4000A» MODULAR CONSTRUCTION»
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
PAGE/PARTY. Solutions. GAI-Tronics Page/Party. communication systems. provide paging and. party-line capabilities... two important plant
GAI-TRONICS A Hubbell Company PAGE/PARTY Solutions GAI-Tronics Page/Party communication systems provide paging and party-line capabilities... two important plant communication functions in one durable,
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1000RT2U Highlights 1kVA / 1000VA / 900W line-interactive 2U rack/tower UPS, Sine
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
How To Use A 1232 On A 1236 On A Computer Or A Cell Phone
12-36-1000 Autodialler and Relay Telephone Interface 1.0 INTRODUCTION 12-36-1000 I/O Telephone Interface with AutoDialer The 12-36-1000 is a autodialer and telephone interface that can be used autonomously
Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation
Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT
TELIKOU Intercom System. MS-500(4+1 channel) Main Station Instruction Manual
TELIKOU Intercom System MS-500(4+1 channel) Main Station Instruction Manual TELIKOU Systems All Rights Reserved While TELIKOU makes every attempt to maintain the accuracy of the information contained in
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Architectural and Engineering Specification for a Perimeter Intrusion Detection System. FiberPatrol-ZR
Architectural and Engineering Specification for a Perimeter Intrusion Detection System FiberPatrol-ZR Sept 3, 2014 Page 1 of 13 FLR1DA0315-001 Rev A This document is intended to provide performance specifications
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
GSM Autodialer Professional GJD700 Speech & Text Autodialer
Text Edit message GSM Autodialer Professional GJD700 Speech & Text Autodialer Introduction The GSM Autodialer Professional works in conjunction with standard alarm systems and makes use of your preferred
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
INTRUSION DETECTION SYSTEM Section 281600
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
Memcom Emergency Telephone
Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming
Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM
Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
TELIKOU Intercom System. TM-200 Main Station. Instruction Manual
Intercom System TM-200 Main Station Instruction Manual TELIKOU Systems All Rights Reserved I. Introduction Thank you for choosing TELIKOU intercom product. TM-200 main station is suitable for television
OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder
P R O D U C T G R O U P OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder Manual # 600-0901 November 30, 1999 Rev. D - 99068 DESCRIPTION The ST-888 Mobilecall Display Decoder is a desktop
CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual
CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CGWTS-M001A Version 1, Release 1, December 2004 NOTICE
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
Operation Manual for Users
Operation Manual for Users Model No.: FLTAMFMRCD!!!!!!!!!! ATTENTION!!!!!!!!!! THE RESET BUTTON MUST BE PRESSED TO ENSURE PROPER OPERATION. SEE INSTRUCTION MANUAL Table of Contents Table of Contents ---------------------------------------------------------------------------------------------
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
user guide Meridian 558 Multi Channel Power Amplifier
user guide Meridian 558 Multi Channel Power Amplifier Meridian 558 Multi Channel Power Amplifier User Guide ipreface Sales and service in the UK Meridian Audio Ltd Stonehill Stukeley Meadows Cambs PE18
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
B. Equipment shall be furnished and installed as specified. No substitutions will be allowed.
CLASSROOM SOUNDFIELD DISTRIBUTION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
CB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
ZMR 80 STEREO MODULAR ZONER USERS MANUAL
ZMR 80 STEREO MODULAR ZONER USERS MANUAL Lime Technologies http://limetechnologies.co.uk Tel: 08712 233127 ZMR80 Stereo Modular Zoner Mixer Introduction The modular construction of the ZMR80 allows it
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
Brio-Rmanual:Cursamanual.qxd 08/04/2011 09:25 Page1
- Brio-Rmanual:Cursamanual.qxd 08/04/2011 09:25 Page1 Brio-Rmanual:Cursamanual.qxd 08/04/2011 09:25 Page2 CONTENTS INTRODUCTION, FEATURES AND TECHNOLOGY 1-3 INSTALLATION 3 CONNECTIVITY 4-6 LOUDSPEAKER
ENGINEERING SPECIFICATIONS SENSAPHONE IMS-4000
ENGINEERING SPECIFICATIONS SENSAPHONE IMS-4000 I. General A. Summary The monitoring system shall be an expandable, self-contained microprocessor-controlled IMS-4000 Host unit (hereafter referred to as
Operation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
9452/9453 Installation and User Guide
9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
TMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
Model #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: [email protected] Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
Power Feeding Equipment for Optical Submarine Cable Systems
Power Feeding Equipment for Optical Submarine Cable Systems KANEKO Tomoyuki, CHIBA Yoshinori, KUNIMI Kaneaki, NAKAMURA Tomotaka Abstract A submarine cable system is fed power from power feeding equipment
Features, Benefits, and Operation
Features, Benefits, and Operation 2014 Decibel Eleven Contents Introduction... 2 Features... 2 Rear Panel... 3 Connections... 3 Power... 3 MIDI... 3 Pedal Loops... 4 Example Connection Diagrams... 5,6
AARC-EVAC Portable Hand Held or Fixed Transmitter with SOS assist - ATX43E25 SAFETY ALERT SYSTEMS
Wireless - Emergency Alert Systems Easy installation - Wireless Radio System no wires or wiring required Evacuation, Alert & Lockdown all in one system S.O.S Assist - up to 6 unique SOS assistance zone
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
eela-audio EA916 Journalist Unit USB Audio module with Telephone Hybrid User manual
eela-audio EA916 Journalist Unit USB Audio module with Telephone Hybrid User manual EA Broadcast / Eela Audio, Het Riet 8 A, 5431NM Cuijk, The Netherlands http://www.eela-audio.com e-mail: [email protected]
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
Manufactures of: All. Dallas Delta Corporation Pty.Ltd. Pty.Ltd. 102 Albert St. East Brunswick, 3057 Vic. Tel: 613 93877388 Fax: 613 93873128
Dallas Delta Corporation Pty.Ltd. 102 Albert St. East Brunswick, 3057 Vic. Tel: 613 93877388 Fax: 613 93873128 Email: [email protected] www.dallasdelta.com.au LP GUARD DOORSTATION MK II G UARD Doorstation
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Public Address and Voice Alarm
Training Presentation Public Address and Voice Alarm Slide 1 Contents Introduction What is Voice Alarm? What are the benefits? What standards apply? Intelligibility requirements Issues when designing VA
EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.
ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual
TS510 & TS500. Installation & User Guide. Compatible Equipment
Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
Emergency Voice Communication Systems EVCS Network 8 Data Sheet
Emergency Voice Communication Systems EVCS Network 8 Data Sheet The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT