1 The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers
2 Table of Contents Introduction... 1 Intention... 2 Authority and responsibility letter... 3 Organizational relationship chart... 4 Boiler room repair progression chart... 5 P.M. outline schedules Daily... 6 Weekly... 7 Monthly... 8 Semiannual... 9 Annual...10 Diagrams and Fault-free analysis...11 Exhibits Boiler log...12 Repair log...13 Monitoring system form Certification/re-certification form...16 Record of revisions...17
3 INTRODUCTION Preventative maintenance of boiler components is required to maintain them in good working condition and to assure safety. The primary objective of any PM System is to provide for managing maintenance and maintenance support in a manner, which will ensure maximum equipment readiness. The intermediate objectives of the PM System is as follows: a) Documenting information relating to maintenance and maintenance support actions. b) Improvement of maintainability and reliability of systems and equipment by provision of documented maintenance information for analysis. c) Provide the means to schedule, plan, manage, and track maintenance. d) Provide data on which to base improvements in system. Adequate precautions should be taken while maintenance is being performed to protect personnel (performing the work), building occupants, and the equipment.
4 Intention It is not intended that this manual serve as operating instructions for any specific plant. Due to the wide variety of types and makes of equipment used, this guide should be supplemented with manufacturer's recommendations concerning the maintenance and care of your system. Specific written operating and maintenance instructions should be supplied.
5 City of Milwaukee Boiler Inspection Division Sample Letterhead Corporate Authority Letter Date: (today) Our company has been furnished a copy of the city of Milwaukee code for boiler Electronic Monitoring systems. We have read the code and assume responsibility for complying with it and its preventative maintenance requirements. The boiler preventative maintenance is an integrated maintenance management system which operates under the guidance of ( enter name ), which has been assigned overall responsibility for the development, coordination, and maintenance of said system. Refer to the documents "Organizational Relationship - Chain of Responsibility" and "Boiler room repair progression" Boilers are located at: Company Name Company Address State Registration Number The personnel listed below are responsible for the duties indicated. Engineering manager; is responsible for the overall boiler preventative maintenance program and ensuring that an analysis program is carried out.(list duties) Maintenance supervisor; is responsible for implementing the boiler preventative maintenance and analysis programs.(list duties) Boiler operator; is responsible for performing log readings and preventative maintenance checks. (List duties) Approved by: (signature and title of a corporate officer)
6 Organizational Relationships Chain of Responsibilit y for boilers at : President Exec Vice President of Operations Over all Responsibility for program Engineering Manager Responsible for implementing program Maintenance Supervisor Operator #1 Operator #2 Operator #3 Operator #4 Operator #5 Operator #6 Responsible for performing log readings & P.M. checks
7 Fireman Review Start PM Outline Here Fireman Perform PM Enter problem in boiler log Notify Maintenance Supervisor Ye Is problem minor repair No Is A problem Discovere d Yes Fireman Repair Maintenance Supervisor Review No Enter status in boiler Enter solution In repair log Yes Is Maintenanc e Qualified No Maintenance Supervisor Review Engineering Review (PE) Yes Is Problem a System Modification Hire qualified Contractor Is Engineering Qualified To do work No Yes No Notify Boiler inspector As required Hire boiler Consultant Boiler Room Repair Progression
8 Daily Checklist Blow down and test low water cut-offs Blow down gage glasses Blow down boiler Check boiler and system for leaks Check burner flame Note: The above checklist should be referenced to specific written procedures. In all cases the equipment manufacturer s recommendations should be followed. This check off list uses ASME section VI and ASME CSD-1 for it s specific written instructions.
9 Weekly Checklist Check flame signal strength for both pilot and main flame Check pilot and main fuel shutoff valves closing Check igniter and burner operation Check level in chemical treatment tank Note: The above checklist should be referenced to specific written procedures. In all cases the equipment manufacturer s recommendations should be followed. This check off list uses ASME section VI and ASME CSD-1 for it s specific written instructions.
10 Monthly Checklist Check boiler water treatment test results and adjust as necessary Lubricate motors and equipment bearings Test fan and air pressure interlocks Check main burner fuel safety shutoff valves for leakage Check low fire start interlock Check high pressure / temperature interlocks Check high and low pressure interlocks on gas train Manually lift safety valve by hand Note: The above checklist should be referenced to specific written procedures. In all cases the equipment manufacturer s recommendations should be followed. This check off list uses ASME section VI and ASME CSD-1 for it s specific written instructions.
11 Semiannually Checklist Inspect burner components Check flame failure system components Check piping and wiring of all interlocks and shutoff valves Recalibrate all instruments, indicating and recording gages Perform a slow drain test for low water cut-off Check combustion control system Check oil atomizers and strainers Test boiler safety valves according to ASME Note: The above checklist should be referenced to specific written procedures. In all cases the equipment manufacturer s recommendations should be followed. This check off list uses ASME section VI and ASME CSD-1 for it s specific written instructions.
12 Annual Checklist Perform the semiannual Check all equipment coils and diaphragms Perform a pilot turndown test Recondition or replace low water cut-off Check gas drip leg and gas strainer Clean boiler firesides Drain boiler, open manholes, handholes, and clean water sides Have boiler inspected by a commissioned inspector Clean burner and fans Replace gaskets Leak test all fuel valves Test operation of all controls and safety devices Adjust combustion Test and re-certify boiler monitoring system Note: The above checklist should be referenced to specific written procedures. In all cases the equipment manufacturer s recommendations should be followed. This check off list uses ASME section VI and ASME CSD-1 for it s specific written instructions.
13
14
15 Mechanical repair log Date Boiler/Fireman Approved by Person doing work Employed by Description of work (Be precise)
16 BOILER MONITORING SYSTEMS Location of Installation Name Address City State Zip Code Area Code Telephone Number Person to Contact TYPE OF MONITORING SYSTEM Low Pressure High Pressure ITEMS TO BE MONITORED ON BOILER Low Water With Alarm Manual Reset Visually Verified High Pressure With Alarm Manual Reset Visually Verified Flame Failure With Alarm Manual Reset Visually Verified Power Failure With Alarm Manual Reset Visually Verified Low Pressure or Temperature Visually Verified Dual Shut-Off Fuel Valves Visually Verified Remote Shut-Off Capabilities Visually Verified LOCATION OF WIRING DIAGRAMS OF SYSTEM AND FAULT-FREE ANALYSIS OF SYSTEM: Do not write below this line DATE OF INSPECTION: PERMIT NUMBER: NUMBER OF BOILERS MONITORED BY SYSTEM: COMMENTS: INSPECTION AGENCY SIGNATURE INS CODE CERT NUMBER
17 BOILER MONITORING SYSTEMS NAMES OF BOILER OPERATORS OR NAME OF RESPONDING COMPANY (1) (2) (3) (4) NAMES OF COMPANIES INSTALLING OR HOOKING UP MONITORING SYSTEM (1) (2) (3) LOCATION OF WIRING DIAGRAMS OF SYSTEM AND FAULT-FREE ANALYSIS OF SYSTEM: HOW WILL EMERGENCY CALLS BE HANDLED?
18 ELECTRONIC MONITORING SYSTEM OF BOILERS CERTIFICATION--RECERTIFICATION FORM TO: Commissioner of Building Inspection Boiler Division, Room N Broadway Milwaukee, WI Inspection Date Expiration Date of Certification SUBJECT: CERTIFICATION--RECERTIFICATION (CIRCLE ONE) OF INSTALLATION AT: Address Wisconsin Boiler Registration Number(s) (If Installing) I HEREBY CERTIFY THAT THE ELECTRONIC MONITORING SYSTEM(S) AT THE SUBJECT PREMISES IS INSTALLED AND OPERATING IN ACCORDANCE WITH THE CITY OF MILWAUKEE BUILDING CODE REQUIREMENTS FOR BOILERS AND ELECTRONIC MONITORING AS PER CHAPTER 223. Installing Company Name Certifying Company Name Address Address City State Zip City State Zip Area Code Telephone Number Area Code Telephone Number Person to Contact Person to Contact Installer Signature Professional Engineer s Signature and Seal (If Re-certifying) I HEREBY CERTIFY THAT I PERFORMED THE REQUIRED ANNUAL TESTING OF THE BOILER ELECTRONIC MONITORING SYSTEM IN ACCORDANCE WITH SECTION 223 AND FOUND THE SYSTEM OPERATING PROPERLY. Certifying Company Name Address City State Zip Area Code Telephone Number Person to Contact Certifying Company Signature Professional Engineer s Signature and Seal
19 Record of Revisions Revision Number Section number(s) revised and description Date Issued A current copy of this document will be kept with: engineering manager, maintenance supervisor, boiler room, and city of Milwaukee.
PACKAGED FIRE TUBE BOILER
SAMPLE PREVENTIVE MAINTENANCE MANUAL PACKAGED FIRE TUBE BOILER 1 CONTENTS Introduction 1 Intention 2 Organisational setup 3 Boiler Fault reporting & Repair progression 4 Preventive Maintenance Schedules
GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90
GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90 Department of Labor and Workforce Development Labor Standards & Safety Enforcement Division of Public Safety and Occupational Safety
C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
SECTION A... 3 SECTION B... 7
BRITISH COLUMBIA SAFETY AUTHORITY Manual for Owners and Operators of Special Status Plants Risk Assessed and General Supervision Date: March 12, 2012 Controlled Document: MAN -4000-03 I TABLE OF CONTENTS
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
Boiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00
RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls
Boiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
PLP - TERMS AND CONDITIONS
PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia
Routine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Commercial Gas Water Heaters
POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Boiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
SMITH PLUMBING & HEATING 2012 Home Care SERVICE PLAN AGREEMENT. A. Silver Plan
SMITH PLUMBING & HEATING 2012 Home Care SERVICE PLAN A. Silver Plan AGREEMENT Priority Emergency Plumbing / Heating Repair Service: All service labor will be billed at our prevailing labor rate with no
Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement.
Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement. The benefits of a Home Service Agreement Provides peace of mind Regularly scheduled maintenance will keep
Backup Fuel Oil System Decommissioning & Restoration Plan
Backup Fuel Oil System Page 1 of 19 Overview of Physical Fuel Oil System and Decommissioning Steps The fuel oil system at Milford Power consists of a number of subsystems. These include the following:
D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD
DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD JOB DESCRIPTION POSITION TITLE: Air Conditioning Mechanic DEPARTMENT: Plant TITLE OF IMMEDIATE SUPERVISOR: Supervisor, Maintenance Services Position Summary
Chicago Stationary Engineer Licensure Examination Information
Chicago Stationary Engineer Licensure Examination Information This candidate guide should help you prepare for the Chicago Stationary Engineer licensure examination. Part I contains general information
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
Action Plan Template HVAC Page 1
Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
Essentials Welding QA/QC Plan Sample
Essentials Welding QA/QC Plan Sample Good for smaller projects and bid qualifications Has All the Essential Elements of a well-founded Quality Control Plan Contact: Ed Caldeira 410-451-8006 Pat [Pick the
Bradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
DRAFT 2015 SEATTLE BOILER CODE
DRAFT 2015 SEATTLE BOILER CODE Comments may be addressed to Larry Leet, [email protected] no later than November 25, 2015. October 26, 2015 Contents Section 1 Administrative... 5 1.1 Title... 5 1.2
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Attachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 October 15, 2008 BOILER PLANT OPERATIONS
CORRECTED COPY Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 BOILER PLANT OPERATIONS 1. PURPOSE: This Veterans Health Administration (VHA) Directive
1 RCNY 101-07 CHAPTER 100
1 RCNY 101-07 CHAPTER 100 Subchapter A Administration 101-07 Approved Agencies. (a) Definitions. For the purposes of this section, all terms used herein shall have the same meanings as set forth in the
Owner-User Pressure Equipment Integrity Management Requirements
the pressure equipment safety authority Owner-User Pressure Equipment Integrity Management Requirements AB-512 Edition 2, Revision 0 Issued 2015-06-25 Owner-user Pressure Equipment Integrity Management
REQUEST FOR QUOTATIONS
Metropolitan Washington Airports Authority Materials Management, MA-133 Terminal A, Room 278 Washington, DC 20001-4901 REQUEST FOR QUOTATIONS 1. FOR INFORMATION CONTACT NAME: Regina Leigh 2. REQUEST FOR
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Rules for construction of heating boilers, Boiler and Pressure Vessel Code, Section IV-2007
Boilers Introduction How Boilers Work Types of Boilers Key Components of Boilers Safety Issues Best Practices for Efficient Operation Best Practices for Maintenance References Introduction Boilers are
COMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
LICENSE CATEGORIES. (2) A demolition contractor class II may demolish any building not more than three stories in height.
CONTRACTOR LICENSING & CERTIFICATION REQUIREMENTS INFORMATION BULLETIN NO. 118 -- June 2, 1997 (Revised May 1, 2012) City of Kansas City, Missouri http://www.kcmo.org/codes/ CONTRACTOR LICENSING & CERTIFICATION
Control Device Requirements Charts For Oil and Gas Handling and Production Facilities
Device Charts For Oil and Gas Handling and Production Facilities Purpose/Scope: The purpose of this document is to provide standardized guidance for use by the regulated community and air permit reviewers,
On-Site Risk Management Audit Checklist for Program Level 3 Process
On-Site Risk Management Audit Checklist for Program Level 3 Process Auditor name: Date: I. Facility Information: Facility name: Facility location: County: Contact name: RMP Facility I.D. Phone Number:
OBSERVING BOILER SAFETY RULES
OBSERVING BOILER SAFETY RULES The rules that follow are brief reminders of the possible consequences in a boiler plant of inappropriate operator response or questionable action in maintaining the boiler
Trouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
Section 1. The title of Section 101-07 of Subchapter A of Chapter 100 of Title 1 of the Rules of the City of New York is amended to read as follows:
Section 1. The title of Section 101-07 of Subchapter A of Chapter 100 of Title 1 of the Rules of the City of New York is amended to read as follows: 101-07 [Inspections and] [a] Approved [a] Agencies.
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN XXXX FARM (CITY OR COUNTY), MICHIGAN CONTACT (NAME), OWNER CERTIFICATION: I hereby certify that I have examined the facility, and being familiar with the
APPLICATION FOR LIQUEFIED PETROLEUM GAS PERMIT TYPE OR PRINT LEGIBLY
LIQUEFIED PETROLEUM GAS COMMISSION DEPARTMENT OF PUBLIC SAFETY AND CORRECTION Public Safety Services Bobby Jindal Governor John W. Alario Executive Director APPLICATION FOR LIQUEFIED PETROLEUM GAS PERMIT
MODEL FLX PACKAGED BOILER
MODEL FLX PACKAGED BOILER 1,500,000 to 12,000,000 Btu/hr Hot Water and Steam Fuel: Light Oil, Gas or Combination Manual Part No. 750-177 R5 10/2009 MODEL FLX PACKAGED BOILER Operation, Service, and Parts
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to March 1, 2014. It is intended for information and reference purposes only.
Powered Industrial Truck Safety Program
Powered Industrial Truck Safety Program TABLE OF CONTENTS Forklift Safety Program 1.0 Overview... 3 2.0 Policy.....3 3.0 Requirements 3 4.0 Purpose. 3 5.0 Scope......4 6.0 Forklift Procedures 4 6.0 Responsibilities.....6
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
ABOVE-GROUND STORAGE TANKS
ABOVE-GROUND STORAGE TANKS Above-ground storage tanks in Georgia are regulated by the State Fire Marshall and by the EPA. Above-ground tanks containing 1,100 gallons or less do not require any secondary
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Spill Control Prevention Plan (SCPP)
Spill Control Prevention Plan (SCPP) FACILITY INFORMATION PLEASE PRINT Facility Name: Mailing Address: Physical address if different: Owner Name: Owner Address: Primary Contact Name: Work Phone Number:
MECHANICAL ADMINISTRATOR LICENSE APPLICATION
STATE OF ALASKA CONTRACTOR LICENSING SECTION 333 WILLOUGHBY AVENUE, 9TH FLOOR, JUNEAU, ALASKA 99801 P.O. BOX 110806, JUNEAU, ALASKA 99811-0806 PHONE: 907-465-8443 WEBSITE: www.commerce.alaska.gov/occ/
Annual Service Agreement
Annual Service Agreement 462 Main Street P.O. Box 130 Royersford, PA 19468 610-948-7220 www.plottsenergy.com GAS OIL HEAT PUMP AIR CONDITIONING A family owned and operated business since 1949. We are here
610-6-MURPHY 610-461-6502 PRIORITY SERVICE AGREEMENTS. 610-461-6502 PLUMBING HEATING COOLING DUCT CLEANING BATHS TILE Thank You. Richard G.
Contractor License PA#022799 PA#022799 PLUMBING, HEATING & AIR CONDITIONING 610-6-MURPHY OR 610-461-6502 PRIORITY SERVICE AGREEMENTS A staff of professionals waiting to serve you 24 hours a day 365 days
Features and Benefits
SPC 1000 Single Point Control ABC-1000 Retropak Section: F100 Bulletin: 100.2 Date: 03/09 Supercedes: 5/01 Features and Benefits Design pressure to 450 WSP Meets ASME, CSD-1 Requirements LED Monitoring
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
Waste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
Plan Number. 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020. www.charlottemechanical.com. Simplified Service Plan. Air Conditioning.
Plan Number 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020 www.charlottemechanical.com Simplified Service Plan Air Conditioning And Heating System PARTS, LABOR, & EMERGENCY REPAIR Effective Date:
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
Preventing Overheated Boiler Incidents
Preventing Overheated Boiler Incidents PSE&G Appliance Service October 2012 Runaway Boiler Explosion Review Items Hazard Background Past Incidents PSE&G Emergency Response Future Process Improvements What
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
Contingency Plan. Facility Name
Contingency Plan Facility Name This plan is reviewed annually and amended whenever changes occur that will significantly affect the ability of this facility to respond to an emergency situation. This includes
COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23
COMMERCIAL REPORT / STOCK CONDITION SURVEY For Sydenham Hill Estate Sydenham Hill London SE 23 Submission Prepared by Gas Advisory Services Limited Date: 4 th June 2013 Gas Advisory Services Limited Phoenix
MANAGEMENT AND USE OF WORK EQUIPMENT: PRESSURE SYSTEMS
Health & Safety Services Unit name goes here Safety Code of Practice 46, Part 2 1st Edition, November 2009 MANAGEMENT AND USE OF WORK EQUIPMENT: PRESSURE SYSTEMS University of Reading 2015 Page 1 Contents
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and
A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
Preventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances.
Preventative Maintenance Plan Guide The Simple, Smart Way To Properly Care For Home Systems And Appliances. Protect. Prevent. Preserve. Prolong. What AHS Preventative Maintenance Plans Can Do For Your
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
Operation & Maintenance Manual SYSTEM NAME
Operation & Maintenance Manual and Maintenance Log FOR SYSTEM NAME FLORIDA RURAL WATER ASSOCIATION 2970 Wellington Circle ~ Tallahassee FL 32309 Telephone: 850-668-2746 ~ Fax: 850-893-4581 E-mail: [email protected]
Vectren Energy Delivery of Indiana Natural Gas Business Rebate Program Application
Thank you for participating in Vectren Energy Delivery of Indiana s Natural Gas Business Rebate Program! Refer to the information below to ensure you are eligible for program rebates and your application
Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
BOILER ROOM GUIDE. Reference Guide
BOILER ROOM GUIDE Reference Guide Cleaver-Brooks FOREWORD This guide is provided to assist supervisory, operating and maintenance personnel in understanding the operation of boiler room equipment, and
GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS
Company Name: Address: The City of Attleboro s Rules and Regulations for the use of Wastewater Facilities require each user to provide protection from accidental discharge of prohibited materials and substances
How to Prevent Liquid Damage Property Losses
1. The leading cause of property losses is from liquid damage. A review of Zurich North America claims data highlights the problem. 2. Water damage originates from a number of sources: Domestic water lines
TECHNICAL ADVISORY BULLETIN
RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are
TABLE OF CONTENTS THE WATERTUBE BOILER...1-2 REGULATORY CODES...1-5 ECONOMIZERS...1-7 BLOWDOWN SEPARATOR...1-8
Boiler Room Guide FOREWORD This guide is provided to assist supervisory, operating and maintenance personnel in understanding the operation of boiler room equipment, and to provide guidance to achieve
FIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
Safety Manual Title: Spill Prevention & Response Review Date: 6/1/2014
Operation s Purpose The purpose of this plan is to document spill prevention and response requirements. Each Elkhorn Construction, Inc. jobsite will develop a spill prevention and response plan based on
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant Health and Safety Safe management of industrial steam and
BWC Division of Safety and Hygiene
BWC Division of Safety and Hygiene A SAMPLE LOCKOUT/TAGOUT PROCEDURE A good Lockout/Tagout Procedure, at a minimum, should contain the following elements: 1. All maintenance personnel shall be provided
ASME B31.3 Process Piping. Scope of B31.3 Course
ASME B31.3 Process Piping Charles Becht IV, PhD, PE Don Frikken, PE Instructors BECHT ENGINEERING COMPANY, INC. Introduction -1 Scope of B31.3 Course This course covers piping as typically used in process
INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9
TABLE OF CONTENTS Description Page Number SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 Indeck Keystone Energy, LLC. 5451 Merwin Lane, Suite 100 Erie,