OBSERVING BOILER SAFETY RULES
|
|
|
- Roderick Leonard
- 9 years ago
- Views:
Transcription
1 OBSERVING BOILER SAFETY RULES The rules that follow are brief reminders of the possible consequences in a boiler plant of inappropriate operator response or questionable action in maintaining the boiler plant. In all cases, follow the published or oral safety rules of your employer, jurisdiction, and the Federal OSHA safety regulations to avoid possible disciplinary actions. In addition, study the safety guidelines of the manufacturer of your boiler. NEVER NEVER fail to anticipate emergencies. Do not wait until something happens to start thinking. NEVER start work in a strange plant without tracing every pipeline and learning the location and purpose of every valve. Know your job. NEVER allow sediment to accumulate in gaugeglass or water-column connections. A false water level may fool you and make you sorry. NEVER give verbal orders for important operations or report such operations verbally with no record. Have something to back you up when needed. NEVER light a fire under a boiler without a double check on the water level. Many boilers have been ruined and many jobs lost this way. NEVER light a fire under a boiler without checking all valves. Why take a chance? NEVER open a value under pressure quickly. The sudden change in pressure, or resulting water hammer may cause piping failure. NEVER cut a boiler in on the line unless its pressure is within a few pounds of header pressure. Sudden stressing of a boiler under pressure is dangerous. NEVER bring a boiler up to pressure without trying the safety valve. A boiler with its safety valve stuck is nearly as safe as playing with dynamite. NEVER take it for granted that the safety valves are in proper condition. The power plant is no place for guesswork. NEVER increase the setting of a safety valve without authority. Serious accidents have occurred from failure to observe this rule. NEVER change adjustments of a safety valve more than 10 percent. Proper operation depends on the proper spring. NEVER tighten a nut, bolt, or pipe thread under steam or air pressure. Many have died doing this. NEVER strike any object under steam or air ALWAYS ALWAYS study every conceivable emergency and know exactly what moves to make. ALWAYS proceed to proper valves or switches rapidly but without confusion in time of emergency. You can think better walking than running. ALWAYS blow out each gauge-glass and watercolumn connection at least once a day. Forming good habits may mean longer life for you. ALWAYS accompany orders for important operations with a written memorandum. Use a logbook to record every important fact or unusual occurrence. ALWAYS have at least one gauge of water before lighting off. The level should be checked with the gauge cocks. You will not be fired for being too careful. ALWAYS be sure blow down valves are closed and proper vents, water-column valves, and pressure-gauge cock are open. ALWAYS use the bypass if one is provided. Crack the valve from its seat slightly and await pressure equalization. Then open it slowly. ALWAYS watch the steam gauge closely and be prepared to cut the boiler in, opening the stop valve only when the pressures are nearly equal. ALWAYS lift the valve from its seat by the hand lever when the pressure reaches about threequarters of popping pressure. ALWAYS raise the valve from its seat with the lifting level periodically while the boiler is under pressure. Test by raising to popping pressure at least once per year. ALWAYS consult an authorized boiler inspector and accept his or her recommendations before increasing the safety-valve pressure setting. ALWAYS have the valve fitted with a new spring and re-stamped by the manufacture for changes over 10 percent. ALWAYS play safe on this rule. The one that is going to break does not have a special warning sign. ALWAYS play safe on this rule. You cannot tell
2 pressure. This is another sure path to the undertaker. which straw might break the camel s back.
3 NEVER allow unauthorized persons to tamper with any steam-plant equipment. If they do not injure themselves, they may cause injury to you. NEVER leave an open blow down valve unattended when a boiler is under pressure or has a fire in it. Play safe; memory can fail. NEVER allow anyone to enter a drum of a boiler without following OSHA rules for entering a confined space. NEVER allow major repairs to a boiler without authorization. If you do not break a law, you may break your neck. NEVER try to light a second burner from the flames of the first on-line burner. You might be inviting a serious puff back. NEVER attempt to light a burner without venting the furnace until clear. Burns are painful. NEVER fail to report unusual behavior of a boiler or other equipment. It may be a warning of danger. ALWAYS keep out loiterers and place plant operation in the hands of qualified persons. A boiler room is not a place for a club meeting. ALWAYS check the water level before blowing down and have a second person watch the water gauge level while you blow down the boiler. Close the blow down valve, and then recheck the water level. You will avoid dry-firing the boiler this way. ALWAYS make sure the boiler is cool to enter, has enough oxygen per OSHA rules, has a sign by the entrance stating Worker Inside, has an emergency person at the entrance, and that all valves going to and from the boiler are locked and closed. ALWAYS consult an authorized boiler inspector before proceeding with boiler repairs. ALWAYS follow the starting sequence of the manufacturer on multi-burner boilers, including ignition and main flame proving by installed burner controls, and you will avoid a furnace explosion. ALWAYS allow draft to clear furnace of gas and dust for prescribed purge period. Change draft conditions slowly. ALWAYS consult someone in authority. Two heads are better than one.
4 STANDARD OPERATIONAL SEQUENCES AND PROCEDURES Note: This Publication is to be viewed only as a guide. 1. PRE-OPERATION CHECKLIST Pre-operational checks should be completed before lighting-up any boiler. Necessary to ensure the boiler plant is in a safe and efficient condition. g. Chemical Cleaning / Boil Out For new or existing boilers with excessive deposits. Should be done under supervision of experienced personnel / contractors familiar with the hazards of such an operation. h. Safety Checklist Prior To Inspection Before entering any boiler : Lock out and tag all equipment items with movable parts connected to the boiler and fuel system and place a sign at the operating controls indicating that a workman is in the boiler. Make sure it is properly isolated at ALL fuel, flue gas, steam and water sources; make sure it is properly vented and obtain an air sample to check for breathing quality. Use low voltage lights or explosion proof flashlights inside the boiler. Notify the person in charge at the site when beginning and upon completion of the inspection. Inspect with another person. Always be aware of the nearest escape routes. Before closing drum manholes and furnace doors, it is essential to ensure that all personnel are out of the boiler. i. Before Closing The Boiler Thoroughly inspect all available parts of the boiler s interior, both the waterside and the fireside. Ensure no tools, rags or other debris are left lying around inside the boiler that could cause problems. Tubes and other areas that are not easily visible should be checked using other suitable methods i.e. push rods, mirrors, etc. All loose tubes and debris should be swept into a dustpan being careful not to sweep into tubes, drains, or blow-down connections. Check all internal piping, hangers, brackets, etc. to be sure they not been damaged during maintenance work. All sealing surfaces should be given a final check for dents, scratches and gouges. Critical water or steam joints under pressure must be scraped then dressed off flat with a carborundum block, or similar abrasive surface if they were damaged. Replace all gaskets on the waterside and steam connections. The cost is minor compared with the headaches from leakages later on. Use a graphite paste or other suitable paste to prevent sticking. Gas side gasket joints are not as critical, but require close inspection and cleaning and replacement if necessary.
5 j. Testing The Gas Side For Leakage For a forced draught unit, the draft fan may be used to place the furnace under high enough pressure by closing off the outlet damper. Passing a lighted candle along all the joints to be tested, tests the furnace attachments, furnace seals and smoke-box seals. The effects upon the flame will detect any leaks of air from the positive pressure furnace to the atmosphere. Another method is to use a soap test, which must be thoroughly dried after the test. NOTE: For the first test, a manometer could be installed to give the head pressure the fan can deliver against the closed damper operating at normal speed. This data should be recorded for future reference or fan testing. - For an induced draft boiler, the same procedure may be followed, but this case calls for the flame behaving differently i.e. the inward suction of air will pull the flame into the leak. k. Water And Steam Systems Visual survey all the areas of the plant to check for damage and ensure no unauthorized persons tampered with the plant. Do NOT refill a boiler while it is hot. Treated warm water should be used. The boiler should be vented to permit air to escape. Check the water level in the gauge glass (mid point) and all the gauge glass valves are open. Test true water level by opening the test cocks, starting with the uppermost. Open all the feed water supply valves. If water level was low, use the manual bypass valve to raise the water level to slightly below the midpoint of the gauge glass )i.e. head pressure from the hot well). Check the make-up water supply system to the hot well and whether it shall function automatically i.e. check float condition and operation. Start the feed water pump. Check the water treatment plant is in full operating condition. Boiler vent valve and any steam line vents should be opened to bleed air out as steam is raised. Open the main steam valve bypass. When distribution manifold is up to temperature and pressure, bypass valve is closed and main steam valve is opened. Open all steam drains, including steam trap bypasses, when the bypass valve was opened. l. Fuel Systems Covers fuel oil and fuel gas supply to a boiler. Check furnace internals for obvious signs of fuel leaks due to failure of the fuel valves to shut off (oil). Check the gas supply pressure is greater than the minimum permissible. Check the fuel oil temperatures (for heavy fuel oil). Check all the fuel valves are in final position for light-up sequence. The vent valves between the gas shut-off valve should be closed.
6 Check all burner control panel lights are Ready. If not, check and rectify the faulty condition. Safety devices are worthless if they are not kept in operating condition and checked regularly. The fuel safety shut-off valves are no exception. To test the tightness of the safety shutoff valves, a general procedure should be followed. It may slightly vary for different burner suppliers. 1. Ensure the draft fan is operating and close the safety shut-off valves. 2. Open the main manual gas supply valve and the vent valve. 3. Note the pressure gauge reading between the gas pressure regulator and the first safety shut-off valve. It should stabilize at the lock-up pressure if the regulator is a tight shut off design. 4. Open the gas cock. 5. Connect the rubber hose with the test valve to the first nipple. 6. Close the vent valve and place the lower end of the test hose in a cup of water. 7. Observe if any bubbles are emanating from the hose end, which would indicate the first shut-off valve is leaking. 8. Move the hose to the second nipple and cap off first nipple. 9. Place the hose end in the cup of water and close the gas cock. 10. Open the first shut-off valve and close the gas cock. If bubbles are observed, then the second (downstream) shut-off valve is leaking. 11. Close the first shut off valve and the gas cock. The pressure gauge after the second shut-off valve should read (kpa). Cap off second nipple and ensure all lines have been vented and closed. g. Air Systems Covers the combustion air system and the instrument air system and/or plant air for oil atomizer: Check the intake air dampers are open and clear of any debris or obstructions. Check both the primary and secondary air dampers are set and ready for automatic operation. Check the damper control system is ready to operate. Check the flue dampers for readiness to operate. Check the draft fans are clear, run free and ready to operate. Check the instrument air supply lines are clear of water and pressure is correct. If atomizing air is being used for the fuel oil, clear the line of all condensed water by draining and check its pressure.
Boiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9
TABLE OF CONTENTS Description Page Number SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 Indeck Keystone Energy, LLC. 5451 Merwin Lane, Suite 100 Erie,
Routine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
PROCEDURES PREVENTION OF ACCIDENTAL IGNITION
Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
Boiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap
1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Boiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
Oxy-Fuel Gas Welding. Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to:
I. Competencies Oxy-Fuel Gas Welding Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to: A. Identify the major parts of the oxy-fuel gas unit. B. Pass
NITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
Your Boiler Room: A Time Bomb?
Your Boiler Room: A Time Bomb? Is you boiler room a potential Time Bomb? A few basics you need to know to work safely in the boiler room: Two potentials for explosions in a boiler room: Water/steam side
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
San josé OWNER S MANUAL
San josé OWNER S MANUAL Assembling & operating manual San josé 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
Chapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 [email protected] www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 October 15, 2008 BOILER PLANT OPERATIONS
CORRECTED COPY Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 BOILER PLANT OPERATIONS 1. PURPOSE: This Veterans Health Administration (VHA) Directive
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant Health and Safety Safe management of industrial steam and
Pressure Testing (Hydrostatic / Pneumatic) Safety Guidelines
The INGAA Foundation, Inc. 1.0 ACTIVITY DESCRIPTION 1.1 This document provides basic safety guidelines for the safety of all personnel and the general public during pressure (e.g., hydrostatic, pneumatic)
The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers
The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers Table of Contents Introduction... 1 Intention... 2 Authority and responsibility letter... 3 Organizational
C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES. Leader s Guide. 2005, CLMI Training
C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES Leader s Guide 2005, CLMI Training LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES This easy-to-use Leader s Guide is provided to assist in conducting a successful
COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.
Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute
Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems. 20.A General... 20-1. 20.B Compressed Air and Gas Systems... 20-4
Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems Section: Page 20.A General... 20-1 20.B Compressed Air and Gas Systems... 20-4 20.C Boilers and Systems... 20-7 20.D Compressed Gas Cylinders...
Compressed Gas Cylinder Safety
Compressed Gas Cylinder Safety I. Background. Due to the nature of gas cylinders, special storage and handling precautions are necessary. The hazards associated with compressed gases include oxygen displacement,
PACKAGED FIRE TUBE BOILER
SAMPLE PREVENTIVE MAINTENANCE MANUAL PACKAGED FIRE TUBE BOILER 1 CONTENTS Introduction 1 Intention 2 Organisational setup 3 Boiler Fault reporting & Repair progression 4 Preventive Maintenance Schedules
Class 5 to 7 Truck and Bus Hydraulic Brake System
Class 5 to 7 Truck and Bus Hydraulic Brake System Diagnostic Guide 1st Edition * 5+0 Important Service tes The information in this publication was current at the time of printing. The information presented
Operating instructions
6300 9681 02/2006 GB For the user Operating instructions Logano GE315 Boiler for oil-/gas-fired pressure jet burners Please read thoroughly before use. Operating instructions Logano GE315 Dear Customer,
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)
ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS
National- Spencer Inc.
9-27-2010 National- Spencer Inc. 19.2V HEAVY DUTY GREASE GUN PRODUCT SPECIFICATION Charger Input Power 110 VAC Battery Output Power 19.2V Battery Capacity 1500 MAH Battery Pack Charge Time 1 Hour Maximum
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
Voltmaster Trash Pumps Model TSP2, TSP3 and TSP4
Model TSP2, TSP3 and TSP4 Owner s Manual July 2010 Table of Contents 1 Introduction...................................................... 1 1.1 Read before using..............................................
Gas-Fired, Residential Storage Type Water Heaters
Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors
WARNING: IMPROPER SERVICING AND START-UP OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND TO OPERATORS OR PERSONS IN THE BUILDING.
START-UP AND OPERATION WATER BOILERS WARNING: IMPROPER SERVICING AND START-UP OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND TO OPERATORS OR PERSONS IN THE BUILDING. SERVICING AND START-UP
Trouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
orlando OWNER S MANUAL
orlando OWNER S MANUAL 2 Assembling & operating manual Orlando 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.
3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: [email protected] Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION
NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION Fire and Life-Safety Group (FLS) I. EMERGENCY PROCEDURES The emergency procedures for natural gas emergencies are similar to that for fire emergencies.
Bradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en
8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................
Basic Safety Examination instructions
Name of candidate: This VCA mock examination is only intended for training purposes and is aimed at familiarising candidates with the examination methods. The questions are checked every year for accuracy
Section 7 Adjustment, Repair and Replacement
Section 7 Adjustment, Repair, and Replacement Page 7-1 Section 7 Adjustment, Repair and Replacement Section Contents Page Overview...7-5 Belts Belt Guard Removal/Installation...7-7 Belt Removal/Installation...7-11
Some Criteria for Choosing a Steam Boiler for a Microbrewery
Some Criteria for Choosing a Steam Boiler for a Microbrewery Jack Coe Rite Engineering and Manufacturing Corporation Breweries rely on steam heating for a number of functions, primarily to heat the brew
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
Northern Region. Underground Storage Tank
California CUPA Northern Region Presents Underground Storage Tank Designated Operators Workshop Workshop Agenda Definitions Tank Construction Corrosion Protection Spill Prevention Overfill Prevention Piping
WEEKLY SAFETY MEETING All Euramax Subsidiaries LOCKOUT / TAGOUT. Safety Meeting Contents. Meeting Notice. Leaders Guide.
Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read
Action Plan Template HVAC Page 1
Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation
3088 Lockout-Tagout Training Program Course Outline
3088 Lockout-Tagout Training Program Course Outline The following outline summarizes the major points of information presented in the course. The outline can be used to review the course before conducting
ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
Tankless Water Heater
Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not
Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
Preventing Overheated Boiler Incidents
Preventing Overheated Boiler Incidents PSE&G Appliance Service October 2012 Runaway Boiler Explosion Review Items Hazard Background Past Incidents PSE&G Emergency Response Future Process Improvements What
Flame Conductivity VS Flame Rectification Systems
Flame Conductivity VS Flame Rectification Systems There are two basic principles in flame rod detection systems-flame conductivity and flame rectification. Conductivity systems are, for the most part no
Energy Saving Fact Sheet Boilers
Energy Saving Fact Sheet Boilers Turn a burning issue into real energy savings You need a boiler to heat your premises and provide hot water or to generate steam for use in industrial processes. Unfortunately,
How To Fix A Car With A Carbide Engine
Section 12 Adjustment, Repair, and Replacement Page 12-1 Section 12 Adjustment, Repair and Replacement Section Contents Page Overview...12-5 Belts Belt Guard Removal/Installation...12-7 Belt Removal/Installation...12-11
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil
HOW TO SELECT A LOW VOLUME (L.V ) BOILER
HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Having a gas appliance installed or serviced? Doing home improvements?
Keeping you safe Having a gas appliance installed or serviced? Think Safety. Think RGI. In your home, safety comes first. If you are having a gas appliance installed, serviced or repaired, always use a
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
15GAL STEEL OIL DRAIN WITH 110V PUMP
15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety
Chicago Stationary Engineer Licensure Examination Information
Chicago Stationary Engineer Licensure Examination Information This candidate guide should help you prepare for the Chicago Stationary Engineer licensure examination. Part I contains general information
Emergency procedures instructions to farm staff
Emergency procedures instructions to farm staff The first priority in the event of an emergency is for the safety of all people present. Emergency phone numbers Dial 111 for Fire/Police/Ambulance 1. Tell
Cooling system components, removing and installing
Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,
Department of Environmental Health & Safety. Lock Out/Tag Out Program. Date Effective: November 2010
Department of Environmental Health & Safety Lock Out/Tag Out Program Issued by: Jeff Campbell Date Effective: November 2010 Date Revised: April 2014 General Policy Ohio University Lockout/Tagout Policy
TYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
Compressed Gas Cylinder Program
Department of Environmental Health & Safety Procedures Compressed Gas Cylinder Program March 2010 Compressed Gas Cylinder Program Page 1 of 8 Table of Contents I. Introduction II. III. IV. Policy Scope
GAS CYLINDER SAFETY. 2. GRADES OF GASES BOC have divided the gases that they supply into 3 grades.
GAS CYLINDER SAFETY Contents 1. INTRODUCTION 2. GRADES OF GASES 3. PRESSURES 4. TYPES OF REGULATORS 5. CYLINDER TRANSPORT 6. STORAGE 7. KEEPING THE SYSTEM SAFE 8. PROBLEM REGULATORS OR ATTACHMENTS 9. FURTHER
Millersville University - Office Of Environmental Health & Safety Scope & Application
Confined Space Entry Millersville University - Office Of Environmental Health & Safety Scope & Application The Confined Space Entry (CSE) program applies to the safe working practices for entering and
USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
American Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems
American Fireglass Outdoor Fire pit kit information General instructions/warnings for outdoor gas pan and burner systems We strongly recommend that our burner products be installed by a licensed and certified
Reduced Pressure Principle Assembly 3 Valve Procedure
Reduced Pressure Principle Assembly 3 Valve Procedure A. Initial Setup 1. Flush test cocks by: a. opening test cock #4 to establish flow through the unit. (Leave this test cock open until others are flushed)
EXPRESS STILL WARNING It is legal in New Zealand to own and operate a still for the purpose of producing alcohol for your own consumption.
THE EXPRESS STILL This still represents the next generation in home distillation equipment. It eliminates the problem of having to spend all day processing a 25 litre wash. Taking 1 hour to heat up, then
AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller
January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:
Diesel Fuel Systems. Injection Nozzles
Diesel Fuel Systems Injection Nozzles Unit Terms Injection nozzle Nozzle, nozzle holder, valve, spring assembly Nozzle assembly Valve, body, and spray valve Orifice Small hole Pintle Valve which the end
THREE. Heating and Cooling
THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
Operation & Maintenance Manual
Manual # OMAV2-SUMP1 High Performance Air & Dirt Separators Manual # 9636-1230 Rev. A Operation & Maintenance Manual 340 West 8 th Street Peru, IN 46970 PH: 765 472 3351 FX: 765 472 3968 www.thrushco.com
BELLMAN CXE-25/27 INSTRUCTIONS
IMPORTANT SAFEGUARDS BELLMAN CXE-25/27 INSTRUCTIONS 1. READ ALL INSTRUCTIONS. 2. WARNING: SCALDING MAY OCCUR IF TOP IS NOT TIGHTENED DOWN COMPLETELY OR IF TOP IS TAKEN OFF BEFORE MACHINE IS COOL AND ALL
MODEL T200-F18 MODEL T125-F18 Finish Nailers
P MODEL T200-F18 MODEL T125-F18 Finish Nailers IMPORTANT! DO NOT DESTROY It is the customer s responsibility to have all operators and service personnel read and understand this manual. OPERATING MANUAL
Home Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
Steam System Efficiency. Bill Lumsden Leidos Engineering
Steam System Efficiency Bill Lumsden Leidos Engineering Steam System Efficiency Steam System Efficiency Key Take-aways: Review of the properties of ice, water, and steam Learn the basics of steam trap