SECTION HVAC AND PLUMBING INSULATION
|
|
|
- Laura Andrea Lindsey
- 10 years ago
- Views:
Transcription
1 SECTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. HVAC and plumbing piping insulation, jackets and accessories. 2. HVAC and plumbing equipment insulation, jackets and accessories. 3. Pipe insulation jackets. 4. Equipment insulation jackets. 5. Insulation accessories including vapor retarders and accessories 6. HVAC ductwork insulation, jackets and accessories. 7. Insulation accessories including vapor retarders and accessories. B. Related Sections: 1.02 REFERENCES 1. Division07 - Firestopping: Product requirements for firestopping for placement by this section. 2. Division09 - Painting and Coating: Execution requirements for painting insulation jackets and covering specified by this section. 3. Division23 Hangers and Supports for HVAC and Plumbing Piping and Equipment: Product and Execution requirements for inserts at hanger locations. 4. Division23 Identification for HVAC and Plumbing Piping and Equipment: Product requirements for HVAC piping and equipment identification. A. ASTM International: 1. ASTM A167 - Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip. 2. ASTM B209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate. 3. ASTM C195 - Standard Specification for Mineral Fiber Thermal Insulating Cement. 4. ASTM C449/C449M - Standard Specification for Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement. 5. ASTM C450 - Standard Practice for Prefabrication and Field Fabrication of Thermal Insulating Fitting Covers for NPS Piping, Vessel Lagging, and Dished Head Segments. 6. ASTM C533 - Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation. 7. ASTM C534 - Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form. 8. ASTM C547 - Standard Specification for Mineral Fiber Pipe Insulation. 9. ASTM C553 - Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications. 10. ASTM C578 - Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation. 11. ASTM C585 - Standard Practice for Inner and Outer Diameters of Rigid Thermal Insulation for Nominal Sizes of Pipe and Tubing (NPS System). 12. ASTM C591 - Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation. 13. ASTM C612 - Standard Specification for Mineral Fiber Block and Board Thermal Insulation. 14. ASTM C795 - Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel. 15. ASTM C921 - Standard Practice for Determining the Properties of Jacketing Materials for Thermal Insulation. Tenant Build Out - August
2 16. ASTM C Standard Specification for Thermal and Acoustical Insulation (Glass Fiber, Duct Lining Material). 17. ASTM C Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation. 18. ASTM C Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts. 19. ASTM D Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds. 20. ASTM D Standard Specification for EPDM Sheet Used in Single-Ply Roof Membrane. 21. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials. 22. ASTM E96 - Standard Test Methods for Water Vapor Transmission of Materials. 23. ASTM E162 - Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source. B. Sheet Metal and Air Conditioning Contractors : 1. SMACNA - HVAC Duct Construction Standard - Metal and Flexible. C. National Fire Protection Association: 1. NFPA Standard Method of Test of Surface Burning Characteristics of Building Materials. D. Underwriters Laboratories Inc.: 1.03 SUBMITTALS 1. UL Tests for Surface Burning Characteristics of Building Materials. 2. UL Standard for Safety for Grease Ducts. A. Division01 - Submittal Procedures: Submittal procedures. B. Product Data: Submit product description, thermal characteristics and list of materials, R value, finished accessories and thickness for each service, and location. C. Manufacturer's Installation Instructions: Submit manufacturers published literature indicating proper installation procedures. D. Manufacturer's Certificate: Certify products meet or exceed specified requirements QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience. B. Applicator: Company specializing in performing work of this section with minimum three years documented experience, approved by manufacturer QUALITY ASSURANCE A. Test pipe insulation for maximum flame spread index of 25 and maximum smoke developed index of not exceeding 50 in accordance with ASTM E84, UL 723, and NFPA 255. B. Pipe insulation manufactured in accordance with ASTM C585 for inner and outer diameters. C. Factory fabricated fitting covers manufactured in accordance with ASTM C450. Tenant Build Out - August
3 D. Flame/Smoke Ratings: Provide composite mechanical insulation (insulation, jackets, coverings, sealers, mastics and adhesives) with flame spread index of 25 or less, and smoke developed index of 50 or less, in accordance with UBC standard No except where more stringent requirements are noted. E. Insulation materials shall be tested by Underwriters Laboratories, Inc. (UL). Tests shall include insulation, jackets, fittings, adhesives, coatings and accessories. Composite products shall meet the fire hazard requirements of NFPA 90A. F. Furnish affidavit from manufacturer that products delivered to project meet requirements specified G. Maintain one copy of each document on site PRE-INSTALLATION MEETINGS A. Division01 - Administrative Requirements: Pre-installation meeting. B. Convene minimum one week prior to commencing work of this section DELIVERY, STORAGE, AND HANDLING A. Division01 - Product Requirements: Requirements for transporting, handling, storing, and protecting products. B. Accept materials on site in original factory packaging, labeled with manufacturer's identification, including product density, thickness and fire hazard indexes of products. C. Protect insulation from weather and construction traffic, dirt, water, chemical, and damage, by storing in original wrapping. Do not install damaged or wet insulation, remove from project site ENVIRONMENTAL REQUIREMENTS A. Division01 - Product Requirements: Environmental conditions affecting products on site. B. Install insulation only when ambient temperature and humidity conditions are within range recommended by manufacturer. C. Maintain temperature before, during, and after installation for minimum period of 24 hours FIELD MEASUREMENTS A. Verify field measurements prior to fabrication WARRANTY A. Division01 - Execution and Closeout Requirements: Product warranties and product bonds. B. Furnish five year manufacturer warranty for man made fiber. PART 2 PRODUCTS 2.01 ACCEPTABLE MANUFACTURER A. Manufacturer: Subject to compliance with requirements, provide products of one of the following: 1. Owens Corning Fiberglass Corp. 2. Armstrong World Industries, Inc. Tenant Build Out - August
4 3. Certainteed Corp. 4. Knauf Fiber Glass GmbH. 5. Rubatex Corp PIPING INSULATION MATERIALS A. Fiberglass (Mineral Fiber) Piping Insulation: ASTM C547, Class 1 unless otherwise indicated. Owens Corning Fiberglass Corp., ASJ/SL-II, Manville Products Corp. Micro-Lok, or equivalent. B. Calcium silicate piping insulation: ASTM C533, Type I. Kaylo asbestos free" or equivalent. C. Jackets for Piping Insulation: ASTM C921, Type I (Vapor Barrier) for piping with temperatures below ambient. Type I insulation may be used for all piping at the installer's option. 1. All insulated pipes and fittings in the boiler rooms, chiller rooms, pump rooms, mechanical rooms and exposed piping in the interior areas shall be covered with PVC covers, except chilled water systems insulated with Owens Corning Vaporwick. Fitting shall have one-piece remolded PVC covers, fastened as per manufacturer s recommendations. Zeston PVC insulation covers, Fiberglass, Inc. or equal. 2. Encase exterior piping insulation with aluminum jacket with weatherproof construction. Unjacketed fiberglass insulation meeting ASTM C-547, Class I, may be used at Developer Design/Builder's option. D. Staples, Bands, Wires, and Cement: As recommended by insulation manufacturer for applications indicated. E. Adhesives, Sealers, and Protective Finishes: As recommended by insulation manufacturer for applications indicated DUCTWORK INSULATION MATERIALS A. Rigid Fiberglass Ductwork Insulation: ASTM C612, Class 1, 3-5 lbs/ft3. B. Flexible Fiberglass Ductwork Insulation: ASTM C1290, with ASTM C1136 Type II vapor barrier jacket. Owens-Corning Fiberglass All Service Wrap Insulation, Type 75 or equivalent R-value: 1. R8 minimum installed insulation for all supply and return ducts. Applies to ducts located in unconditioned spaces, such as outdoors, spaces between roof and insulated ceiling, space directly under roof, unconditioned crawl space. 2. R4.2 minimum installed insulation for all supply ducts for all other spaces not listed above (i.e., conditioned space). 3. Additions, alternations, and repairs (all climate zones) a. R8 minimum installed insulation for all supply and return ducts (unconditioned spaces see above) and R4.2 installed insulation for all supply ducts (conditioned spaces see above) whenever: 1) Ducts are to be extended to serve a new addition. 2) New ducts are installed or existing ducts replaced with new ducts in an existing building. 3) Density of 0.75 pcf (Type 75) and thicknesses below shall be used to provide installed R-value as follows: 4. Nominal 1 inch thickness or equivalent to provide installed R-value as follows: a. Type /2 Thick R = 4.2 b. Type 75 3 " Thick R = 8.3 Tenant Build Out - August
5 C. Ductwork Insulation Accessories: Provide staples, bands, wires, tape, anchors, corner angles and similar accessories as recommended by insulation manufacturer for applications indicated. D. Ductwork Insulation Compounds: Provide cements, adhesives, coatings, sealers, protective finishes and similar compounds as recommended by insulation manufacturer for applications indicated EQUIPMENT INSULATION MATERIALS A. Flexible Fiberglass Equipment Insulation: ASTM C553, Type II, Class F-1, Owens-Corning Fiberglass, Inc., Type 702, 2.3 lbs./ft3. B. Calcium Silicate Equipment Insulation: ASTM C533, Type I, Block; Owens-Corning Fiberglass, Inc., Kaylo Asbestos Free, U-Grooved block insulation. C. Jacketing Material for Equipment Insulation: Provide Zeston heavy gauge insulated PVC material to cover the equipment. D. Equipment Insulation Compounds: Provide adhesives, cements, sealers, mastics, and protective finishes as recommended by insulation manufacturer for applications indicated. E. Equipment Insulation Accessories: Provide staples, bands, wire, wire netting, tape corner angles, anchors and stud piping as recommended by insulation manufacturer for applications indicated FIRE-RATED INSULATION SYSTEMS A. Fire-Rated Board: 1. Manufacturers: a. Johns Manville; Super Firetemp M, or equal 2. Structural grade, press molded, xonolite calcium silicate, fireproofing board suitable for operating temperatures up to 1,700 degrees F. Comply with ASTM C656, Type II, Grade 6. Ul tested and certified to provide 2 hour fire rating. B. Fire-Rated Blanket: High-temperature, flexible, blanket insulation with FSK jacket that is UL tested and certified to provide a 2-hour fire rating. 1. Manufacturers: 2.06 FIELD-APPLIED JACKETS a. Certainteed Corp.; Flame Check b. Johns Manville; Super Firetemp Wrap c. Nelson Firestop Products: Nelson FSB Flameshield Blanket. d. 3M; Fire Barrier Wrap Products. e. Unifrax Corp.; Fyre Wrap f. Or equal. A. General: ASTM C 921, Type 1. B. Aluminum Jacket: Stucco-embossed finish sheets manufactured from aluminum alloy complying with ASTM B 209, and having an integrally bonded moisture barrier over entire surface in contact with insulation. Metal thickness shall be.024 for outdoor applications. 1. Moisture Barrier: 3-mil- thick, heat-bonded polyethylene or Kraft paper. Tenant Build Out - August
6 C. Stainless Steel Jacket: Deep corrugated sheets of stainless steel complying with ASTM A666, Type 304 or 316, 0.16 inch thick, and roll stock ready for shop or field cutting and forming to indicated sizes ALUMINUM PIPE JACKET 1. Moisture Barrier: 3 mil thick, heat bonded polyethylene and kraft paper. 2. Jacket Bands: Stainless steel, Type 304, 3/4 inch wide. A. ASTM B209, inch thick sheet. B. Finish: Embossed C. Joining: Longitudinal slip joints and 2 inch laps D. Fittings inch thick die shaped fitting covers with factory attached protective liner. E. Metal Jacket Bands: 3/8 inch wide, inch thick aluminum STAINLESS STEEL PIPE JACKET A. ASTM A167 Type 302, 304, or 316 stainless steel. B. Thickness inch thick C. Finish: Corrugated. D. Metal Jacket Bands 3/8 inch wide, inch thick stainless steel INSULATING CEMENTS (DUCTWORK AND EQUIPMENT) A. Mineral Fiber Insulating Cement: Comply with ASTM C Manufacturers: a. Insulco, Division of MFS, Inc.: Triple I. b. P.K. Insulation Mfg. Co., Inc.: Super-Stik c. Or equal. B. Mineral Fiber Hydraulic-Setting Insulating and Finishing Cement: Comply with ASTM C Manufacturers: a. Insulco, Division of MFS, Inc.: SmoothKote. b. P.K. Insulation Mfg. Co., Inc.: P.K. No. 127 and Quick-Cote c. Rock Wool Manufacturing Co.; Delta One Shot d. Or equal ADHESIVES (DUCTWORK) A. Manufacturers: 1. Childers Products, Division of ITW; CP Foster Products Corporation, H. B. Fuller Company; ITW TACC, Division of Illinois Tool Works; S-90/80 4. Marathon Industries, Inc.; 225 Tenant Build Out - August
7 5. Mon-Eco Industries, Inc.; Or equal B. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated. C. Mineral-Fiber Adhesive: Comply with MIL-A-3316C, Class 2, Grade A MASTICS (DUCTWORK) A. Manufacturers: 1. Childers Products, Division of ITW; CP Foster Products Corporation, H. B. Fuller Company; ITW TACC, Division of Illinois Tool Works; CB Marathon Industries, Inc.; Mon-Eco Industries, Inc.; Vimasco Corp.; Or equal B. Materials shall be compatible with insulation materials, jackets, and substrates; comply with MIL-C-19565C, Type II. C. Vapor-Barrier Mastic: Water based; suitable for indoor and outdoor use on below ambient services. D. Water-Vapor Permeance: ASTM E 96, Procedure B, perm at 43-mil dry film thickness. E. Service Temperature Range: Minus 20 to plus 180 degrees F. F. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight. G. Color: White SEALANTS A. FSK and Metal Jacket: 1. Manufacturers: a. Childers Products, Division of ITW; CP-76-8 b. Foster Products Corp. H.B. Fuller Co.; c. Marathon Industries, Inc., 405 d. Mon-Eco Industries, Inc.; e. Vimasco Corp; 750 f. Or equal. 2. Materials shall be compatible with insulation materials, jackets, and substrates. 3. Fire- and water-resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F. 5. Color: Aluminum. B. ASJ Flashing Sealants (Ductwork) 1. Manufacturer: Childers Products, Division of TTW; CP Materials shall be compatible with insulation materials, jackets, and substrates. 3. Fire and water resistant, flexible, elastomeric sealant. Tenant Build Out - August
8 4. Service Temperature Range: Minus 40 to plus 250 degrees F. 5. Color: White 2.13 ACCESSORIES AND ATTACHMENTS (DUCTWORK) A. Weld-Attached Anchor Pins and Washers: Copper-coated steel pin for capacitor-discharge welding and galvanized speed washer. Pin length sufficient for insulation thickness indicated. 1. Welded Pin Holding Capacity: 20 lb for direct pull perpendicular to the attached surface. B. Adhesive-Attached Anchor Pins and Speed Washers: Galvanized steel plate, pin, and washer manufactured for attachment to duct and plenum with adhesive. Pin length sufficient for insulation thickness indicated. May be used for heating and hot water systems. 1. Adhesive: Recommended by the anchor pin manufacturer as appropriate for surface temperatures of ducts, plenums, and breechings; and to achieve a holding capacity of 20 lb for direct pull perpendicular to the adhered surface. C. Bands: Minimum 1/2 inch wide, in one of the following materials compatible with jacket: 1. Stainless Steel: ASTM A666, Type 304; inch thick. 2. Aluminum inch thick. D. Wire: inch, nickel copper alloy, inch soft annealed stainless steel, or inch soft annealed galvanized steel. E. Weld Attached Anchor Pins and Washers for Chilled Water System: Copper coated steel pin for capacitor discharge welding and galvanized speed washer. Pin length sufficient for insulation thickness indicated. 1. Welded Pin Holding Capacity: 20 lbs for direct pull perpendicular to the attached surface. PART 3 EXECUTION 3.01 INSPECTION A. Examine areas and conditions under which mechanical insulation is to be installed. Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to installer PLUMBING PIPING SYSTEM INSULATION. A. Insulation Omitted: Omit insulation on chrome plated exposed piping (except for handicapped fixtures), air chambers, unions, strainers check valves, balance cocks, flow regulators, drain lines from water coolers, drainage piping located in crawl spaces or tunnels, buried piping, fire protection piping, and pre-insulated equipment. B. Cold Piping: 1. Application requirements: Insulate the following cold plumbing piping systems: a. Plumbing drains carrying cold condensate. 2. Insulate each piping system specified above with one of the following types and thicknesses of insulation: a. Fiberglass: 1 inch thickness. Tenant Build Out - August
9 C. Hot Piping: 1. Application Requirements: Insulate the following hot plumbing piping system. a. Potable hot water piping. b. Potable hot water recirculating piping. c. Hot drain piping. d. Handicapped fixtures. 2. Insulate each piping system specified above with one of the following types and thickness of insulation HVAC PIPING SYSTEM INSULATION a. Fiberglass: 1 inch thick for pipe sizes up to and including 2 inch, 1-1/2 inch thick for pipe sizes over 2-1/2 inch. b. Provide "Armaflex" insulation over the hot water supply and angle stop and "Trap Cap" insulation on the trap. A. Insulation Omitted: Omit insulation on hot unions, flanges, strainers, flexible connections and expansion joints. B. Cold/Chilled Piping 1. Application Requirements: Insulate the cold HVAC piping systems for HVAC chilled water supply and return piping. 2. Insulate each piping system specified above with the following types and thicknesses of insulation: Fiberglass with wicking technology: : 1 inch thick for pipe sizes up to and including 4 inch, 1-1/2 inch thick for pipe sizes and over 4 inch. C. Hot Water and Steam Piping: 1. Application Requirements: Insulate the following hot water and steam HVAC piping systems. a. HVAC heating water supply and return piping. b. Low pressure steam and condensate piping. c. Hot gas refrigerant piping. d. Medium and high pressure steam and condensate piping. 2. Insulate each piping system specified above (item a, b and c) with one of the following types and thicknesses of the insulation: a. Fiberglass: 1-1/2 inch thick for pipe sizes up to 1-1/2 inch; 2 inch thick for piping over 2 inch. 3. Insulate medium and high pressure steam and condensate piping with fiberglass 2.5" thick for pipe up to 2 inch and 3 inch thick pipe up to 4 inch and 4 inch thick for pipe over 5 inch. 4. Insulation is not required for automatic relief steam vents where the steam is only discharge or vent out periodically to relief the pressure of the steam system. 5. Insulation is required for steam vents that steam is relief continuously. Insulate with fiberglass 1.5 thick DUCTWORK SYSTEM INSULATION: A. Insulation Omitted: Do not insulate lined ductwork. Tenant Build Out - August
10 B. Hot/Cold Ductwork: 3.05 EQUIPMENT INSULATION 1. Application Requirements: Insulate the following ductwork: a. Outdoor air intake ductwork between air entrance and fan inlet or HVAC unit inlet, insulate to R-8, b. HVAC supply ductwork, unconditioned space R-8, above ceiling grid indirectly conditioned space R-4.2. c. HVAC return ductwork, unconditioned space R-8, above ceiling grid indirectly conditioned space R-4.2. d. HVAC plenums and unit housings not pre-insulated at factory to geographical R-value requirements based on California Title 24, R-4.2, R-6 or R Insulate each ductwork system specified above with one of the following types and thickness of insulation as indicated: a. Rigid Fiberglass: 2 inch thick, (Owens Corning 703 FRK R-8), in machine, fan and equipment rooms. b. Flexible Fiberglass: Type 75 (0.75 pcf), 1-1/2 inch thick in conditioned space (R4.2) or 3 inch thick in unconditioned space (R-8),, application limited to concealed locations. A. Cold Equipment (Below Ambient Temperature): 1. Application requirements: Insulate the following cold equipment: a. Drip pans under chilled equipment. b. Chilled water pumps: Enclosed fixed section of pump in a fixed box fabricated of insulation sections cemented and skewered together. Fill voids with loose fill glass fiber. Secure box with loose fill glass fiber. Secure box with wire ties at 3 inch on center. Similarly enclose removable section of pump with a removal box. Install 22 gage sheet metal parting gasket to fit flush with finish. Apply metal mesh and lace edges, apply 1/2 inch thick insulating cement, trowel smooth and allow to dry. 1) Cover with 8 oz canvas cemented in place, apply smoothly, and finish by sizing with lagging adhesive. 2) Seal boxes together with vapor barrier tape. Arrange for removal by peeling off tape. Reinstall by application of new tape. c. Expansion tanks 2. Insulate each item of equipment specified above with one of the following types and thicknesses of insulation: a. Fiberglass: 2 inch thick for cold surfaces above 35 degrees F and 3 inch thick for surfaces 35 degrees F and lower. Acceptable materials include: Owens Corning Fiberglass Flexwrap with PSK jacketing or equivalent, or Owens Corning Fiberglas Pipe & Tank Wrap or equivalent. B. Hot Equipment (Above Ambient Temperature): 1. Application Requirements: Insulate the following hot equipment: a. Condensate pumps. b. Heat exchangers Tenant Build Out - August
11 c. Expansion tank d. Air separator 2. Insulate each item of equipment specified above with one of the following types and thicknesses of insulation INSTALLATION OF PIPING INSULATION a. Fiberglass: 2 inch thick, except 3 inch for steam jacketed heat exchangers, emergency generator muffler and connection. A. General: Install insulation products in accordance with manufacturer's written instructions, and in accordance with recognized industry practices to ensure that insulation serves its intended purpose. B. Install insulation on pipe systems subsequent to installation of heat tracing, painting, testing and acceptance of tests. C. Install insulation materials with smooth and even surfaces. Insulate each continuous run of piping with fulllength units of insulation, with a single cut piece to complete run. Do not use cut pieces or scraps abutting each other. D. Clean and dry pipe surfaces prior to insulating. Butt insulation joints firmly together to ensure a complete and tight fit over surfaces to be covered. E. Maintain integrity of vapor barrier jackets on pipe insulation, and protect to prevent puncture or other damage. F. Cover valves, fittings and similar items in each piping system with equivalent thickness and composition of insulation as applied to adjoining pipe run. Install factory molded, precut or job fabricated units (at Installer's option) except where specific form or type is indicated. G. Extend piping insulation without interruption through walls, floors and similar piping penetrations, except where otherwise indicated. H. Butt piping insulation against pipe hanger insulation inserts. For hot pipes, apply 3" wide vapor barrier tape or band over the butt joints. For chilled water piping apply insulation with wicking technology with 3 inch wide paperless tape over the butt joints. I. Pipe exposed to weather: Encase exterior piping with aluminum jacket with weather proof construction. J. Pipes in mechanical rooms (Pump rooms, Fan rooms, mechanical rooms and equipment rooms). Use pipe insulation with paperless polymer jacketing or encase piping with PVC cover. K. Saddles and Shields: Except as otherwise indicated, provide saddles or shields under piping hangers and supports, factory fabricated, for all insulated piping. Size saddles and shields for exact fit to mate with pipe insulation. Provide high density insulation of same thickness where saddles or protection shields all located. In case where insulation with wicking technology is used, cover evaporation grid holes with paperless tape under length of saddles or shields INSTALLATION OF DUCTWORK INSULATION A. General: Install insulation products in accordance with manufacturer's written instructions, and in accordance with recognized industry practices to ensure that insulation serves its intended purpose. B. Install insulation materials with smooth and even surfaces. Tenant Build Out - August
12 C. Clean and dry ductwork prior to insulating. Butt insulation joints firmly together to ensure complete and tight fit over surfaces to be covered. D. Maintain integrity of vapor barrier on ductwork insulation, and protect it to prevent puncture and other damage. E. Extend ductwork insulation without interruption through walls, floors and similar ductwork penetrations, except where otherwise indicated. F. Lined ductwork: Except as otherwise indicated, omit external insulation on ductwork where internal insulation or sound absorbing linings have been installed. G. Ductwork Exposed to Weather: Cover exposed to weather duct insulation with 26 gauge galvanized sheet metal, sides, top and bottom with standing seams. Pitch for drainage. H. Ductwork and sheet metal plenums exposed to view (Ductwork in the mechanical rooms): Insulate to California Title 24 requirements. If space is unconditioned provide 3 inch thick, 3/4 pounds per cubic foot density FRK faced glass fiber blanket. If space is indirectly conditioned, provide 1-1/2 inch thick 3/4 pounds per cubic foot density FRK faced glass fiber blanket. Tightly butt joints. Secure with 18 gauge tie wire. Corner angles shall overlap at least two sheet metal screws at each side INSTALLATION OF EQUIPMENT INSULATION A. General: Install equipment thermal insulation products in accordance with manufacturer's written instructions, and in compliance with recognized industry practices to ensure that insulation serves intended purpose. B. Install insulation materials with smooth and even surfaces and on clean and dry surfaces. Redo poorly fitted joints. Do not use mastic or joint sealer as filler for gaping joints and excessive voids resulting from poor workmanship. C. Maintain integrity of vapor barrier on equipment insulation and protect it to prevent puncture and other damage. D. Do not apply insulation to equipment, breechings, or stacks while hot. E. Apply insulation using the staggered joint method for both single and double layer construction, where feasible. Apply each layer of insulation separately. F. Coat insulated surfaces with layer of insulating cement, troweled in workmanlike manner, leaving a smooth continuous surface. Fill in scored block, seams, chipped edges and depressions, and cover over wire netting and joints with cement of sufficient thickness to remove surface irregularities. G. Cover insulated surfaces with PVC jacketing neatly fitted and firmly secured. Lap seams at least 2 inches. Apply over vapor barrier where applicable, except for emergency generator muffler, cover with aluminum jacket. H. Do not insulate boiler manholes, handholes, cleanouts, ASME stamp, and manufacturer's nameplate. Provide neatly beveled edge at interruptions of insulation. I. Provide removable insulation sections to cover parts of equipment which must be opened periodically for maintenance; include metal vessel covers, fasteners, flanges, frames and accessories. J. Equipment exposed to Weather: Protect outdoor insulation from weather by installation of weather barrier mastic protective finish, or jacketing, as recommended by the manufacturer. Tenant Build Out - August
13 3.09 PROTECTION AND REPLACEMENT A. Replace damaged insulation that cannot be repaired satisfactorily, including units with vapor barrier damage and moisture saturated units. B. Protection: Insulation Installer shall advise Developer Design/Builder of required protection for insulation work during remainder of construction period, to avoid damaged and deterioration. END OF SECTION Tenant Build Out - August
B. Types of mechanical insulation specified in this section include the following:
SECTION 23 0700 HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Extent of mechanical insulation required by this section is indicated on drawings and schedules, and by requirements of this section. B.
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
SECTION 23 0700 HVAC INSULATION
PART 1 GENERAL 1.01 QUALITY ASSURANCE SECTION 23 0700 HVAC INSULATION A. FIRE-TEST-RESPONSE CHARACTERISTICS: FLAME-SPREAD INDEX OF 25, AND SMOKE- DEVELOPED INDEX OF 50 FOR INSULATION INSTALLED INDOORS
Guide Specification SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY
SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC piping insulation, jackets and accessories. 2. HVAC ductwork insulation, jackets, and accessories. 3. Equipment
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15250 MECHANICAL INSULATION
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Minimum insulation thicknesses shall comply with ASHRAE Standard 90A. B. Provide saddles and shields under pipe hangers. C. If more than one type
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
SECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION
PROJECT ARCHITECT RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems
Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016
Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.
SUMMARY 1.1. 3. Heating REFERENCES 1.2. Thermal Insulation. 222 07 19-1
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunctionn with good construction practice and professional judgment.
GUIDELINE SPECIFICATIONS
GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Fire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
FIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES
SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES 4121 N.W. 37 th Street, Lincoln, NE 68524 Telephone (402) 470-2627 Fax (404) 470-2410 www.gtexhaust.com
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 31 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
DIVISION 7 - THERMAL AND MOISTURE PROTECTION Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s Contract Documents. SECTION 07 1000
All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS
Perry Fiberglass Products, Inc. FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS PERRY FIBERGLASS Perry Fiberglass Products, Inc. is a leading manufacturer of high
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
Preformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA
Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,
Acumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023
Specifications Preformed Metal Wall and Roof Panels Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Section 07410 Preformed Metal Wall and Roof Panels Structural
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
Guide Specifications for Maple Flooring Systems
Guide Specifications for Maple Flooring Systems MFMA Guide Specification for Resilient Pre-Engineered Fixed Panel System Purpose This Guide Specification is designed to assist in the production of actual
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING
APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING Appendix C Moisture Guidelines Determining moisture content is an essential part of quality control within the flooring installation process. Flooring
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
HVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
Refrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL. 23 21 13.19 Pre-Insulated Piping 4-8-13
TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL 23 21 13.19 Pre-Insulated Piping 4-8-13 MATERIAL SUBMITTAL JOB NAME: TEXAS A&M SAN ANTONIO CENTRAL ACADEMIC BUILDING & PATRIOTS CASA CONTRACTOR:
HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS The LOGIX wall assembly has no need for an additional vapor barrier, the solid concrete core covered with the low permeance EPS (Type II) foam
2.1 DEFINITION OF INSULATION 1 2.2 GENERIC TYPES AND FORMS OF INSULATION 1 2.3 PROPERTIES OF INSULATION 2 2.4 MAJOR INSULATION MATERIALS 4
SECTION 2: 2.1 DEFINITION OF INSULATION 1 2.2 GENERIC TYPES AND FORMS OF INSULATION 1 2.3 PROPERTIES OF INSULATION 2 2.4 MAJOR INSULATION MATERIALS 4 2.5 PROTECTIVE COVERINGS AND FINISHES 5 2.6 PROPERTIES
Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013
Master Guide Specification (CAVITYROCK DD) Page 1 ROXUL GUIDE NOTE: This master specification section is based on ROXUL INC., CAVITYROCK DD. Standard application: Cavity wall. ROXUL GUIDE NOTE: This master
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
FIRING RANGE PHASE 1 DESIGN 224500-1
FIRING RANGE PHASE 1 DESIGN 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping
BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
A. This Section includes the following for soil, waste, and vent piping inside the building:
June 2014, Draft 01 22 1316 Sanitary and Waste Vent Piping PART 1. GENERAL 1.01 Summary A. This Section includes the following for soil, waste, and vent piping inside the building: 1. Pipe, tube, and fittings.
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
FINAL December 2012 SECTION 233100 DUCTWORK
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed
Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders
INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
Foundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
Mastics, Coatings, Adhesives & Sealants
Guide to Mastics, Coatings, Adhesives & Sealants for the Thermal Insulation Industry Selection Guide to Products Mastics, Coatings, Adhesives and Sealants Weather Barrier Coatings Breather type for above
The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A
TechSpecs A builder s blueprint for construction technologies January 2013 The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A C B A E D H G F A. Wood Floor Framing - p. 2 B. Foundation
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved
Bafl-Sorb Sound Absorbing Ceiling Baffles
Bafl-Sorb Sound Absorbing Ceiling Baffles INC offers a complete line of Sound Absorbing Ceiling Baffles to compliment any environment. Our ceiling baffles are among the most cost-effective method of adding
MECHANICAL INSULATION BEST PRACTICES GUIDE TABLE OF CONTENTS
MECHANICAL INSULATION BEST PRACTICES GUIDE TABLE OF CONTENTS SECTION PAGE SECTION 1: INTRODUCTION 1 SECTION 2: INSULATION MATERIALS AND PROPERTIES MP-0 SECTION 3: SYSTEMS DESIGN SD-0 SECTION 4: PRODUCTS
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
SECTION 07320 ROOFING TILE
SECTION 07320 ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Vitrified clay roofing tiles. 2. Tile accessories. 3. Felt underlayment. 4. Self-adhering sheet underlayment. 5. Snow guards.
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
H-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION The Condensation Process Condensation occurs when warmer moist air comes in contact with cold surfaces such as framing members, windows
GENERAL RUBBER LINING PRINCIPLES
GENERAL RUBBER LINING PRINCIPLES I. METAL PREREQUISITES Metal to be lined should meet the requirements as stated in section 8 Metal Fabrication and section 12 Blasting and Cementing Procedures. The surface
GigaCrete Specification PlasterMax
GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION