1 MINNESOTA ENERGY CODE COMPLIANCE COLLABORATIVE 2015 Minnesota Residential Energy Code (MR 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY (July 15, 2015 Update) Note: The following information contains simplified explanations of significant changes to the 2012 International Energy Conservation Code (Residential Provisions) adopted with Minnesota Amendments on February 14, 2015, along with commentary explaining the intent of selected sections for clear understanding of the code. The commentary is advisory only. R103 Construction Documents. Include the following: A. Insulation materials and R values B. Fenestration U factors and SHGCs C. Area-weighted U factor and SHGC calculations D. Mechanical system design criteria E. Mechanical and service water heating system and equipment types, sizes and efficiencies. F. Equipment and system control G. Fan motor horsepower and controls H. Duct sealing, and the location and insulation of ducts and pipes I. Lighting fixture schedule with wattage and control narrative J. Air sealing details R202 Building thermal envelope (definition). The basement walls, exterior walls, floor, roof and any other building elements that enclose conditioned space or provides a boundary between conditioned space and exempt or unconditioned space. R202 COMMENTARY: The boundary is typically considered to be the interior air barrier, such as gypsum board used for a wall or ceiling. R202 High-efficacy lamps (definition). Lamps with a minimum efficacy of: lumens per watt for lamps over 40 watts; lumens per watt for lamps over 15 watts to 40 watts; lumens per watt for lamps 15 watts or less. R302.1 Interior design conditions. The interior design temperatures used for heating and cooling load calculations shall be a maximum of 72 F for heating and minimum of 75 F for cooling. R303.1 Building thermal envelope insulation. The insulation installer shall provide a certification listing the type, manufacturer and R-value of insulation installed, including sprayed polyurethane foam (SPF) insulation. The insulation installer shall sign, date and post the certification in a conspicuous location on the job site. R401.3 Certificate. Include the following on or in the electrical distribution panel: A. Date the certificate is installed B. Dwelling address C. Residential contractor name and contractor license number D. Homeowner name, if acting as the general contractor E. Predominant installed R-values and location F. Type of insulation installed in or on ceiling/roof, walls, rim/band joist, foundation, slab, basement wall, crawl space wall or floor, and ducts outside conditioned spaces G. U-factors for fenestration and the solar heat gain coefficient (SHGC) of fenestration H. Results of any required duct system and building envelope air leakage testing I. Types, input ratings, manufacturers, model numbers and efficiencies of heating, cooling and service water heating equipment J. Structure s calculated heat loss, cooling load and heat gain K. Mechanical ventilation type, location and capacity L. Buildings designated continuous and total ventilation rates M. Type, size and location of any make-up air system N. Location or future location of radon fan 1
2 Table R Insulation and Fenestration Requirements by Component. Insulation and fenestration requirements for Climate Zone 6 (southern zone): Window maximum U factor: 0.32 Wood frame wall insulation: R-20 Attic ceiling: R-49 Wood frame wall option: R-13 with R-5 continuous Attic vaulted ceiling: R-38 (if R-49 not possible) Basement wall insulation: R-15 Floor insulation: R-30 Crawl space insulation: R-15 Slab insulation (on foundation wall): R-10 Rim joist insulation: R-20 Table R Insulation and Fenestration Requirements by Component. Insulation and fenestration requirements for Climate Zone 7 (northern zone): Window maximum U factor: 0.32 Wood frame wall insulation: R-21 Attic ceiling minimum R value: R-49 Mass wall: R-19/21 (See Table R for info) Attic vaulted ceiling: R-38 (if R-49 not possible) Basement wall insulation: R-15 Floor insulation: R-38 Crawl space insulation: R-15 Slab insulation (on foundation wall): R-10 Rim joist insulation: R-21 R Insulation, waterproofing and fenestration. Concrete and block foundation walls shall be waterproofed according to the following when required by Section R406.2 of the MN Residential Code, MR 1309: 1. Waterproofing shall extend from the top interior wall edge, across the top of the wall, and down the exterior wall face to the top of the footing. 2. If walls are exposed to the exterior environment, the waterproofing system shall have a rigid, opaque, and weather-resistant protective covering that shall extend a minimum of 6 inches below grade. R COMMENTARY: Waterproofing shall be installed when required by Section R406.2 of the MN Residential Code and dampproofing is no longer allowed. R through R Specific requirements for basement wall insulation similar to the previous residential energy code. R Basement walls. An alternative to the minimum basement wall insulation of R-15 allows a minimum exterior insulation of R-10 if the tested air leakage rate required in R does not exceed 2.6 air changes per hour and the total square feet between the finished grade and the top of each foundation wall does not exceed 1.5 multiplied by the total lineal feet of each foundation wall that encloses conditioned space. R Installation. The components of the building thermal envelope shall be installed according to Table R Air Barrier and Insulation Installation. R COMMENTARY: The sealing methods between dissimilar materials shall allow for differential expansion and contraction. The building thermal envelope shall also include a Class I or II vapor retarder on the interior side of a frame wall cavity per Section R702.7 of the MN Residential Code. Sheet polyethylene is Class I and kraft-faced fiberglass batt is Class II. Class of other materials shall be based on the manufacturer s certified testing or a tested assembly. 2
3 R Building thermal envelope testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 3 air changes per hour. Testing shall be conducted with a blower door at a pressure of 50 Pascals (0.2 inches w.g.) Where required by the code official, testing shall be conducted by an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed. 2. Dampers shall be closed. 3. Interior doors shall be open. 4. Exterior doors for HRVs and ERVs shall be closed. 5. Heating and cooling systems shall be turned off. 6. Supply and return registers shall be fully open. R COMMENTARY: Blower door testing should follow the RESNET Standard for Performance Testing, found in Chapter 8, Section 802 of the RESNET Mortgage Industry National Home Energy Rating System Standards. Recommended training and certification for the party conducting the testing to include one of the following: RESNET Home Energy Raters (HERS) Certificate Building Performance Institute (BPI) Building Analyst, Energy Auditor, Infiltration and Duct Leakage Certificate, Quality Control Inspector Interstate Renewable Energy Council (IREC) Energy Auditor Southface Institute Duct and Envelope Tester (DET) Certificate Dunwoody Residential Energy Auditor R Programmable thermostat. Where the primary heating system is a forced-air furnace, a programmable thermostat is required. R Duct sealing. Ducts, air handlers, and filter boxes shall be sealed. Joints and seams shall comply with Section of the IMC. Exception: Air-impermeable spray foam products shall be permitted to be applied without additional joint seals. R COMMENTARY: Although this exception infers that duct joints, seams and connections are not required to be sealed, as a practical issue they shall be sealed per IMC to ensure that dissimilar materials allow for differential expansion and contraction. In addition, a thermal barrier per Section R316.4 of the MN Residential Code and Section of the MN Building Code is required so that an ignition barrier is provided between the foam plastic and the interior of the building. Duct tightness testing should follow the RESNET Standard for Performance Testing, found in Chapter 8, Section 802 of the RESNET Mortgage Industry National Home Energy Rating System Standards. Recommended training and certification for the party conducting the testing to include one of the following: RESNET Home Energy Raters (HERS) Certificate Building Performance Institute (BPI) Energy Auditor, Infiltration and Duct Leakage Certificate, Quality Control Inspector Interstate Renewable Energy Council (IREC) Energy Auditor Southface Institute Duct and Envelope Tester (DET) Certificate 3
4 IMC Duct sealing. All joints, longitudinal and transverse seams and connections in ductwork shall be securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic-plus-embedded-fabric systems, liquid sealants or tapes. Closure systems used to seal ductwork listed and labeled in accordance with UL 181A shall be marked 181A-P for pressure-sensitive tape, 181A-M for mastic, or UL181A-H for heat-sensitive tape. Closure systems used to seal flexible air ducts and flexible air connectors shall comply with UL 181B and shall be marked 181B-FX for pressure-sensitive tape or 181B-M for mastic. Closure systems used to seal metal ductwork shall be installed in accordance with the manufacturer s installation instructions. Pressure-sensitive tape shall not be used as the primary sealant on ducts, unless it has been certified to comply with UL 181A or UL 181B by a nationally recognized testing laboratory. Unlisted duct tape is not permitted as a sealant on any duct. IMC COMMENTARY: Although a listed duct tape may comply with the sealing requirements of this section, in order to comply with the tightness tests specified in Section R , typically duct mastic listed to UL181A-M or UL181B-M will be required on all joints, seams and connections, and it shall be installed liberally with a minimum thickness of approximately 1/16 inch. For metal ducts that are not required to comply with the tightness test, pressure-sensitive tape listed to UL181A-P or UL181B-FX for cold weather applications will typically be allowed if it is installed according to commonly-accepted industry practices. R (#1) Duct tightness postconstruction test. Total leakage shall be less than or equal to 4 cfm per 100 square feet of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. across the entire system, including the air handler enclosure. All register boots shall be taped or sealed. R (#2) Duct tightness rough-in test. Total leakage shall be less than or equal to 4 cfm per 100 square feet of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. across the entire system, including the air handler enclosure. All register boots shall be taped or sealed. If the air handler is not installed at the time of test, total leakage shall be less than or equal to 3 cfm per 100 square feet of conditioned floor area. R Exception to duct tightness tests. The total leakage test is not required for ducts and air handlers located entirely within the building thermal envelope. R COMMENTARY ON DUCTS LOCATED ABOVE A GARAGE FOR A CONDITIONED BONUS ROOM/BEDROOM: Typically a supply duct serving a conditioned room above an attached garage would be considered to be located entirely within the building thermal envelope if it complies with the following: 1. Duct joints, seams and connections shall be sealed per IMC Duct shall be insulated with minimum R-8 duct insulation and have a vapor retarder (per IMC ) installed without respect to other building envelope insulation. 3. Duct shall be completely located above the floor insulation of minimum R HVAC register boots shall be sealed to the subfloor or drywall. 5a. If the space above the garage ceiling freely communicates with the ceiling cavity of the house, an air and vapor impermeable R-30 building thermal envelope insulation shall be used. 5b. If the space above the garage ceiling is sealed at the junction of the house wall and garage wall with a durable continuous air barrier, creating a sealed six-sided building cavity, then either an air and vapor impermeable, or an air and vapor permeable, R-30 building thermal envelope insulation can be used. However, if an air and vapor permeable R-30 building thermal envelope insulation is used (such as fiberglass or cellulose), the R-8 duct insulation shall be installed in contact with bottom of the floor sheathing and shall be encapsulated with a minimum 1 ½ inch thickness of air and vapor impermeable closed cell spray foam. In addition, all duct joints, seams and connections shall be sealed with duct mastic listed to UL 181A-M or UL181B-M installed liberally with a minimum thickness of approximately 1/16 inch. 4
5 R COMMENTARY ON METAL DUCTS LOCATED IN AN EXTERIOR WALL: Typically a metal supply duct serving an upper floor located in an exterior wall would be considered to be located entirely within the building thermal envelope if it complies with all of the following: 1. Duct joints, seams and connections shall be sealed with duct mastic listed to UL 181A-M or UL181B-M installed liberally with a minimum thickness of approximately 1/16 inch. 2. Duct shall be installed on the interior side of the frame wall. 3. Air and vapor impermeable insulation shall be installed on the exterior side of the duct with a minimum value of R-13 per Table R Continuous insulation or insulated siding shall be installed on the exterior of the frame wall with a minimum value of R-5 per Table R R Sealed air handler. Air handlers shall have a manufacturer s designation for an air leakage rate of not more than 2 percent of the design air flow rate. R Building cavities. Building framing cavities shall not be used as ducts or plenums. R403.3 Mechanical system piping insulation. Hydronic and refrigeration system piping fluid above 105 F or below 55 F shall be insulated to a minimum of R-3. R Hot water pipe insulation. Hot water pipe shall be insulated to a minimum of R-3 in most applications. R403.5 Mechanical ventilation. The building shall be provided with a balanced mechanical ventilation system that is +/-10% of the system s design capacity and complies with the continuous ventilation requirements (under low capacity) and total ventilation requirements (under high capacity) for dwelling unit ventilation. In addition, the ventilation system shall have the airflow capacity tested so that the air intake is within 10% of the exhaust output and meets the requirements of R Exception: The balanced system and HRV/ERV system may include exhaust fans to meet the intermittent ventilation rate. Surface mounted fans shall have a maximum 1.0 sone per HVI Standard 915. R403.5 COMMENTARY: Exhaust-only ventilation systems are no longer allowed for continuous or total ventilation, however intermittent exhaust-only systems may be used to provide supplemental ventilation with a balanced HRV/ERV system, according to the exception in Section R Typically a smaller HRV/ERV is installed to meet the continuous ventilation rate and an intermittent exhaust fan (with maximum 1.0 sone) is installed to provide supplemental ventilation, resulting in a total ventilation rate complying with Section R All of the installation requirements specified in Sections R through R shall be met when using this strategy. In addition, the pressure equalization requirements (protection against excessive depressurization) of Section of the MN Mechanical Code shall be included in the design of the balanced ventilation system. R Airflow verification. All mechanical ventilation system airflows greater than 30 cfm at the building intake and exhaust shall be tested and verified. R Climatic conditions. HVAC equipment shall be sized according to ACCA Manual S or an equivalent method based on ACCA Manual J. Oversizing of heating equipment shall not exceed 40% and oversizing of cooling equipment shall not exceed 15%. R404.1 Lighting equipment. A minimum of 75% of the lamps or lighting fixtures shall be high-efficacy (see R202 definition). 5
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
SIGNIFICANT CHANGES to the 2015 Minnesota Residential Codes (MR 1303, 1309 and 1322)
SIGNIFICANT CHANGES to the 2015 Minnesota Residential Codes (MR 1303, 1309 and 1322) The following information contains simplified explanations of significant changes to the 2015 Requirements for Radon
HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International
Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance
Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements
Residential Buildings Energy Code Summary
Residential Buildings Energy Code Summary Overview Iowa homebuyers appreciate the comfort and warmth of well-designed, energy-efficient houses. With the upgrade of Iowa s statewide energy code, home buyers
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center
http://www.energy.ca.gov/ FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center Relevant Standard The Residential Manual for Compliance with
Georgia State Supplements and Amendments to the International Energy Conservation Code
Georgia State Supplements and Amendments to the International Energy Conservation Code (2009 Edition) Georgia Department of Community Affairs Planning and Environmental Management Division 60 Executive
Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE
June 24, 2011 North Carolina Has a New Energy Conservation Code! By R. Christopher Mathis Executive Summary On Friday, June 24, 2011, Governor Beverly Perdue signed SB 708 into law and, with it, approved
Chapter 8. Duct Design and Sealing
Chapter 8 Duct Design and Sealing Duct Materials The three most common types of duct material used in home construction are metal, rigid fiberglass duct board, and flex-duct. Both metal and fiberglass
Residential Provisions of the 2012 International Energy Conservation Code July 2011
BUILDING ENERGY CODES UNIVERSITY Residential Provisions of the 2012 International Energy Conservation Code July 2011 PNNL-SA-82108 The Family of I-Codes International Building Code International Mechanical
Pennsylvania Housing Research/Resource Center The Pennsylvania State University 219 Sackett Building University Park, PA 16801 Phone: 814-865-2341
Pennsylvania Housing Research/Resource Center The Pennsylvania State University 219 Sackett Building University Park, PA 16801 Phone: 814-865-2341 Fax: 814-863-7304 E-mail: [email protected] www.engr.psu.edu/phrc
Category Measure Minimum Efficiency / Certification Requirements
ENERGYSMART and DENVER ENERGY CHALLENGE RESIDENTIAL LOAN ELIGIBLE MEASURES s! Please check https://www.elevationscu.com/energyloans/home-loans to ensure you are using the most up to date version of the
The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A
TechSpecs A builder s blueprint for construction technologies January 2013 The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A C B A E D H G F A. Wood Floor Framing - p. 2 B. Foundation
BPC Green Builders. Green building for new and existing homes. Health Comfort Energy
BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)
Analysis of 2009 International Energy Conservation Code Requirements for Residential Buildings in Kansas City, Missouri
PNNL-20699 Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 Analysis of 2009 International Energy Conservation Code Requirements for Residential Buildings in Kansas City, Missouri
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
Duct Construction Standards. Code Reference: 2013 Title 24, Part 6 Standards 150.0(m)1. UL Ratings
DUCTS - CONSTRUCTION DO YOU HAVE A PHOTO OF THIS? PLEASE SEND IT TO US! installation.feedback@ energycodeace.com R-H-DS1 Duct Construction Standards All air-distribution system ducts and plenums shall
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
Jesse Krivolavek Nebraska Native American Energy Auditors 20214 Veterans Dr Ste. 600, Omaha, NE 68022
Jesse Krivolavek Nebraska Native American Energy Auditors 20214 Veterans Dr Ste. 600, Omaha, NE 68022 HERS Rater HERS Instructor National HERS QA Delegate BPI Building Analyst Energy Star Verifier EPA
This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).
CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
CALCS-PLUS. 2010 Florida Building Code Energy Conservation Glitch Supplement
2010 Florida Building Code Energy Conservation Glitch Supplement Today's Discussion Overview of Recent Changes Prescriptive or Performance Compliance Methods? Mandatory Provisions Reading the Forms Overview
Indiana Energy and Cost Savings
BUILDING TECHNOLOGIES PROGRAM Indiana Energy and Cost Savings for New Single and Multifamily Homes: 2012 IECC as Compared to the 2009 IECC 1 2012 IECC AS COMPARED TO THE 2009 IECC Indiana Energy and Cost
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
Colorado Energy and Cost Savings
BUILDING TECHNOLOGIES PROGRAM Colorado Energy and Cost Savings for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC 1 2009 AND 2012 IECC AS COMPARED TO THE 2006 IECC Colorado
Tennessee. Energy and Cost Savings. for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC
BUILDING TECHNOLOGIES PROGRAM Tennessee Energy and Cost Savings for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC 1 2009 AND 2012 IECC AS COMPARED TO THE 2006 IECC Tennessee
ENERGY STAR Certified Homes, Version 3 Cost & Savings Estimates
November 1, 2013 Contents ENERGY STAR Certified Homes, Version 3 Section 1: Executive Summary... 3 Section 2: Detailed Incremental Cost Estimates... 6 Section 3: Incremental Cost & Savings of the Thermal
Residential Duct Systems for New and Retrofit Homes
Residential Duct Systems for New and Retrofit Homes Why it is important to properly design and install high quality, efficient ducted air systems? The efficiency of air distribution systems has been found
Mississippi. Energy and Cost Savings. for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC
BUILDING TECHNOLOGIES PROGRAM Mississippi Energy and Cost Savings for New Single and Multifamily Homes: 2009 and 2012 IECC as Compared to the 2006 IECC 1 2009 AND 2012 IECC AS COMPARED TO THE 2006 IECC
GUIDELINES for BUILDING ENERGY EFFICIENT NEW HOMES with the URA. November 3, 2010 - Version 2.0
GUIDELINES for BUILDING ENERGY EFFICIENT NEW HOMES with the URA November 3, 2010 - Version 2.0 Welcome The Urban Redevelopment Authority of Pittsburgh (URA) is the City of Pittsburgh s economic development
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Comment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to [email protected] by October 10 th, 2012 with the subject line
APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1
APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = The lower the Energy Performance Index, the more efficient
Foundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
MINNESOTA RULES, CHAPTER 1322 RESIDENTIAL ENERGY CODE
MINNESOTA RULES, CHAPTER 1322 RESIDENTIAL ENERGY CODE 1322.0010 DEFINITIONS. ACCESSIBLE. Signifies access that requires the removal of an access panel or similar removable obstruction. ACCESSIBLE, READILY.
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
Energy Efficiency for the Homeowner
Efficiency for the Homeowner How to Reduce Your Home s Bills October 2009 National Mall Washington, DC A Quick Test Using Efficient Products and Practices Can: A. Make your home more affordable B. Make
Building Performance Solutions HVAC Design Guide, 2007
Building Performance Solutions HVAC Design Guide, 2007 HVAC sizing, system design, layout, and installation shall be sized according to (Air Conditioning Contractor of America), ACCA manual J8, 8 th edition,
Contract for Weatherization Management Address City & State
I. Parties Contract for Weatherization Management Address City & State This contract is made and entered into on and specifies the terms of the agreement between Client Name, homeowner, and Sherlock Homes
CLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even
CLOSED CRAWLSPACES What s In the Crawlspace? Wet Sagging Fiberglass Improper Drainage Have you ever been in your crawlspace? If not, have you ever even opened the door to look inside and see what it looked
1 RCNY 5000-01 CHAPTER 5000. New York City Energy Conservation Code
1 RCNY 5000-01 CHAPTER 5000 New York City Energy Conservation Code 5000-01 Construction document approval requirements for compliance with the New York City Energy Conservation Code. (a) Purpose. This
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes
Energy Code Compliance With SIPs Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes Outline Overview of 2009 and 2012 energy codes Code compliance with SIPs Reducing air infiltration with SIP
Residential Building Plan Review Additions and New Home Construction
Residential Building Plan Review Additions and New Home Construction Submittal Requirements Documents to be Submitted A completed and signed permit application and signed cover sheet. Building Plans Provide
Basic B.S. (building science) insights for. Spray Foam, HVAC and Moisture
Basic B.S. (building science) insights for Spray Foam, HVAC and Moisture Claudette Hanks Reichel, Ed.D. Professor and Extension Housing Specialist Director, LaHouse Resource Center When the blind leads
LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS
SUBCHAPTER 9 LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS SECTION 150.2 ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS IN EXISTING BUILDINGS
City of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
Center for Energy Education Laboratory
Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and
CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM
CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete
DUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
ROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
Key energy-efficient features of your new home
Key energy-efficient features of your new home Your thermal envelope The thermal envelope, or shell, of your home (walls, roof and floor) is designed to keep you dry and comfortable. It protects you from
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses
2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
Heating, Ventilation and Air-Conditioning (HVAC)
Heating, Ventilation and Air-Conditioning () Energy Code Requirements The energy requirements of the building code that apply to installations (ECCCNYS Section 503) are in addition to any plumbing, mechanical,
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
DUCT SYSTEM DESIGN CONSIDERATIONS Part 1
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic
ECHO System for Basements
ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton
INDIANA COMMERCAL ENERGY CODE BASELINE STUDY
INDIANA COMMERCAL ENERGY CODE BASELINE STUDY March 21, 2005 Report Prepared for Indiana Department of Commerce, Energy and Recycling Division One North Capitol Avenue, Suite 700 Indianapolis, IN 46204
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
More Bang for Your Buck: Combining Thermal, Air and Water Barrier
More Bang for Your Buck: Combining Thermal, Air and Water Barrier Linda Jeng, Dow Building Solutions 2014 RESNET Atlanta, Jan. 29, 2014 Actual high: 30 F Actual low: 12 F Effect of polar vortex on Atlanta,
Chapter 2: Foundations
Chapter 2: Foundations Crawlspace [V502.1.2] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup under the floor.
Chapter Seven RESNET Standards
Chapter Seven RESNET Standards 700 RESNET NATIONAL STANDARD FOR HOME ENERGY AUDITS 701 GENERAL PROVISIONS 701.1 Purpose The provisions of this Standard are intended to define a framework for a home energy
Residential Weatherization Plus Program
Since 1982, Cowlitz PUD has been helping its customers reduce their monthly electric bills and make their homes more comfortable through our weatherization programs. Under the current program Residential
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
Zen House. A Case Study on Design, Construction and Cost/benefit Analysis of a High Performance Home. Presentation for Net Zero Networking & Exchange
Zen House A Case Study on Design, Construction and Cost/benefit Analysis of a High Performance Home Presentation for Net Zero Networking & Exchange CHBA Net Zero Energy Housing Council May 13, 2015 Ottawa
Home Performance with ENERGY STAR. Evaluation Report
Home Performance with ENERGY STAR Customer Information Evaluation Report Customer Name: Sample Report 2 Address of Building: 123 Johnson Street Mailing Address: Same City: Madison State: WI Zip: 53704
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon
New Homes EPS Modeling Frequently Asked Questions Developed by Energy Trust of Oregon 1 General Questions 3 REM/Rate questions 4 -Creating custom entries 4 -Modeling Heat Pumps 5 -Modeling HRV/ERV 7 -Modeling
HV AC CODE CHECKLISTS
The following text is informational only and shall serve as an informational guide for HV AC contractors, journeymen, and apprentices working in the Heating, Ventilation, and Air Conditioning industry.
First Time Home Buyers Energy Efficiency Workshop Guide
First Time Home Buyers Energy Efficiency Workshop Guide Why is efficiency important when buying a home? Affordability: lower utility bills Environmental responsibility: reduces your carbon footprint and
EPA WaterSense for New Homes Program DOE Zero Energy Ready Home Quality Management Guidelines
22 Harbor Ave Dunhill Companies LTD John S. Rodenhizer 10/28/2014 EPA WaterSense for New Homes Program DOE Zero Energy Ready Home Quality Management Guidelines -7 REM/Rate - Residential Energy Analysis
1995 Model Energy Code Version 2.0
US DEPARTMENT OF ENERGY BUILDING STANDARDS AND GUIDELINES PROGRAM 1995 Model Energy Code Version.0 December 1995 MECcheck TM was developed by the Building Standards and Guidelines Program at Pacific Northwest
Introduction to Energy Codes & Green Building Programs
Introduction to Energy Codes & Green Building Programs David Neiger B.S. Arch, LEED AP Homes, Certified HERS Rater Principal Populus Sustainable Design Consulting Why green homes? The Building Sector:
FLORIDA SOLAR ENERGY CENTER
FLORIDA SOLAR ENERGY CENTER Creating Energy Independence High Performance Existing Homes Partnerships and Research Janet McIlvaine Research Analyst, Florida Solar Energy Center A Research Institute of
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
ENERGY EFFICIENCY PLAN REVIEW CHECKLIST
GEORGE CHAVEZ, City Building Official DAVID YELTON, Building Inspection Manager NESTOR OTAZU, Community Preservation Manager BUILDING & SAFETY DIVISION 455 North Rexford Drive, 1 st Floor Beverly Hills,
HVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by