Airflow Utilization Efficiency (AUE) Can we cool today s servers with airflow?

Size: px
Start display at page:

Download "Airflow Utilization Efficiency (AUE) Can we cool today s servers with airflow?"

Transcription

1 AirflowUtilizationEfficiency(AUE) How to use River Cooling to reduce energy costs while improving server performance. By ThomasS.Weiss Sr.VicePresident TriadFloorsbyNxGen,LLC This paper offers insight into how airflow can be utilized and manipulated to cool servers in the data center. The analysis uncovers new revelations regarding how tiles perform while framing this performance in financial terms. In the end, this paperwillprovideamoredetailedunderstandingofthecapabilitiesandscienceof raised floor cooling, provide methods for testing tiles and provide a total cost of ownership example. This information has been created to enable Data Center Managers to make the most cost effective decision in determining how to keep coolingcostslowwhilereducinghotspotsandimprovingserverperformance. Canwecooltoday sserverswithairflow? CoolingintheDataCenterhasbeentheroleoftheraisedfloorforthelast40years. Airissentintotheunderfloorplenumwhileperforatedtilesareplacedinfrontof serverracks.thehopeisthattheairwillrisetotheserversandbepulledthrough theserversbytheserverfans.thissystemhasbeenrelativelyeffectiveasheatloads withintheservershavebeenverylow. Inthepastcoupleofyears,datacenterservershavebeenaskedtodomuchmore. With the use of virtualization products such as VMware, servers are now utilizing 60 80% of their capacity compared to 20 40% previously. This has added significantamountsofheattotheinternalprocessingoftheserver.coupledwiththe emergence of video, digital security, IP telephony and CRM/ ERP applications, we havebeguntoseepowerusagepushing7kwperrackwithmanylookingtoscaleto 12 25kwandbeyond. Higherheatloadswithintheserverrackhavebeguntohighlighttheinefficienciesof raisedfloorcoolingsystems.asheatloadsrise,hotspotsbegintoemergefollowed by sky rocketing energy costs. The inefficiencies of the airflow tile have made it impossible for the air to get to all the servers in the rack. The problem with conventionalairflowsystemsresultsfromtheinabilityfortheairflowtopenetrate theboundarylayersofheatonthefront,thesideandatthetopoftherack/cabinet. Asaresult,theDataCentermanagershavetolowerthesetpointofthedatacenter to keep the servers cool. Servers can function at an intake temperature of 80 degreesbutdatacentersaresetat72,68andsometimesaslowas65degrees.since every degree of movement in set point equates to a 4% impact on the energy bill, datacenterswerenowspendingupto60%oftheutilitybillonthecoolingsystems.

2 Whenanalyzingindetailwhathappenswhentheairflowsystemdoesnotpenetrate the boundary layers of heat, we first find a large discrepancy between the temperaturesatthebottomoftherackcomparedtothetopoftherack.sincethe topoftherackisthehottestpartoftheserverenvironment,theheatatthetopof therackdrivesthetemperatureofthewholedatacenter.highertemperaturesat thetopoftherackforceustolowerthetemperatureintheroomsowecankeepthe upper servers below 90 degrees. The reason there is such a discrepancy between thebottomandthetopistheaircomingoutofthefloorsitsinthecoldaisleinstead offlowingintothehotservers.thisinefficientsystemof leakingair intothecold aislemakestheserverfantheprimarycatalystforcoolingtheserver. Whenweanalyzetheentirerackwiththermalimaging,weseecoolingisprimarily presentwherethereisafan.thisleadstowarmertemperaturesattheperimeterof theserverscreatinghotspotsinthesidesofthecabinet,thetopofthecabinetand the bottom of the cabinet. In effect the tiles only cool a small portion of the boundarylayerofheatonthefrontsideofthecabinet.sincetheairdoesnotflowto theheatsource,theonlywaydatacentermanagerscankeeptheheatedareasofthe serverscoolistomaketheroomcolder.they,ineffect,havetomakethedatacenter arefrigerator. Thisinefficiencyoftheairflowsystemhasleadsomecompaniestomoveawayfrom raisedfloorcoolingformoreeffective,ifnotextremelyexpensive,solutions.these alternativesconsistofactivecoolingdevicesanddesignsthatusefans,liquidcooling and customized racking. Cooling is improved but the solution can cost as much as $500,000forasfewas12racks.Thesesystemsare10timesmoreexpensivethan theirpassivecounterparts. Sofromacapitaloutlayperspective,themostcosteffectivecoolingsystemwouldbe passive solution capable of supplying air to the front of the servers, starting at 8 inchesandstratifyingupto7feet.airneedstoflowtotheservers.thetileneedsto workfortheserver.theairinthecoldaisleshouldbemorethanpresent;itshould attacktheboundarylayerofheatonthefrontandtopoftherack.thiswouldallow ustokeepeveryserverintherackthesametemperatureandwouldblockthehot airfromcomingoverthetopoftherackandheatingtheupperservers. The end result of deploying an efficient airflow system would mean temperatures couldbeconsistentatthetopandbottomoftherackandsetpointscouldrisetothe temperatureoftheaircomingoutofthefloor.ifwewereabletouseairmovement effectively,datacentercoolingcostscouldbereducedbyasmuchas50%. Thetileistheentitythatdeliverstheairtotheserversbutitisonlyonepartofthe system. We have broken the airflow ecosystem into four components. These all play a part in the efficiency of the airflow system. Each of these components supportstheflowofairwhileminimizingwasteandlossofthermalintegrity.each andeverymoleculeofcool,movingair,shouldgothroughoracrossaserver.

3 Thesefourcomponentsare: 1. Theunderfloorspace 2. Theperforatedtile 3. Thecabinet/rack 4. Thereturnairsystem Thispaperisgoingtoprimarilyfocusononepartofthesystem;theperforatedtile as an airflow delivery device. Through a detailed analysis of perforated tile performance, in an open plenum environment, we have found the need for three distinctperformancecharacteristics. 1. The tile should be constructed in a way that it ensures positive flow out of everypartofthetile(noshortcycling). 2. Itshoulddiverttheairtotheserverssoitcanpenetratetheboundarylayer ofheatonthefrontsideofthecabinet/rack. 3. Itshouldbeableto stratify theairtothetopofthecoldaisle. Servers need a constant flow of air to keep them cool. All three of these performance parameters are necessary and lead to consistent temperatures and improvedcooling. When analyzing the performance of traditional perforated tiles by applying the stated requirements, we find meeting our performance criteria to be difficult. Traditionaltileshavebeentestedinaductandwerenevercreatedtodiverttheair. Whenwemeasuretheperformanceofthetileinanopenplenum,wefindthedesign of the tile to be flawed leading to mixing, no dispersion of the air into the servers andaninabilitytoflowtotheupperservers. Thisflawcomesfromthedesignofa flatbottom foundonmostperforatedtiles. The best way to illustrate the impact of this design flaw is to show you how flat bottomtilesarelikeacarwindowwhenacarismovingdowntheroad. Whenwithyourcarwindowsopen,youfindinconsistentflowcomingintothecar. Airgoingbythewindowofthecarpassesbypartofthe openarea ofthewindow, providingsomeairintothecarbutpullingairoutofthecaraswell.theonlywayto gettheairtoflowdirectlyintothecaristoangletheairintotheareaneedingthe air.thisanglingoftheairtowardstheheateditemcreateswindchillonthesurface oftheitemtobecooledanddissipatesheatbylettingtheairpassbytheitem.in otherwords,weneedaventwindowtodiverttheairtotheservers. Flatbottomtilesarelikeacarwindow.Airpassesbypartofthetile,whichleadsto mixing, less directed flow and a low stratification line.these flaws have lead to designconsiderationsthatreducetheimpactoftheflawfoundinthetilebutleadto a great deal of inefficient airflow utilization. These airflow system designs have focusedonpressureandopenspaceinsteadofvelocityandwindchill.

4 Intheirstudyofairflowinthedatacenter,Dr.BobF.SullivanandKennethG.Brillin their paper Cooling Techniques that meet 24 by forever Demands of Your Data Center estimatethatonly28%oftheairintheraisedfloorairflowsystemactually getstotheservers.thismeans72%oftheairiswastedandisonlypresentsoasto guide the other 28%. We, in effect, use air to divert air. Consequently, the same studyfindsthatwehave2.6timesmorecoolingcapacitythanisnecessary. Thehiddendrainofenergy FlatBottomShortCycling Foryearsperforatedtileshavebeenmadewithflatbottoms.Theairwassupposed tocomethroughthetilesbasedonthelevelofopenspaceinthetileandthestatic pressureintheunderfloorplenum.theassumptionwasthattheairwassittingstill (the lake) and would leak consistently through the holes in the tile. All testing of perforated tiles was done in a duct not in an open plenum so testing never contemplatedthereallifeenvironmentofthesetiles. When we analyze the performance of flat bottom tiles in an open plenum environment,welearnquicklythatiftheairismovingtoofast,airnotonlydoesnot gothroughthetile,itactuallypullsairintotheunderfloorplenum.thisiswhatis known of as a short cycle. It was thought that we could correct this problem by movingthetilefurtherawayfromthecracunit.oncewegettheairtoslowdown weareabletogetittomovethroughthetile.thereasonairdoesnotgothrougha tile and is pulled back into the under floor plenum is a direct result of what Isaac Newtontermedas TheLawofMotions orthe VenturiEffect. Airpassingbytheopenareaofthetilecreatesapullofairthatisequalinmagnitude andoppositeindirection.sowhenatileisclosetoacracunit,thevelocityofthe airoverridesthepressureunderthefloor,pullingtheairfromabovethefloor.this leadstolowerpressureatthefrontofthetile.thishappenswhenairpassesbyany partofthetile,itmustbehappeningalloverthedatacenter. Evenifaircomesoutofthebackofthetile,atcertainvelocities,airwillbepulled backintotheplenumatthefrontofthetile.thispullmakesitdifficulttogetairto disperse to the front of the server and pulls the air back down into the plenum creating a short cycle within the tile. This pull and the short cycle itself, has the unwanted effect of making it virtually impossible to get air to the upper servers, doesnotdirectairtothelowerserversandmixesthecoolairwiththewarmair.

5 Triadthermalimagecomparedtoaflatbottomtile. Note the pull at the front of the flat bottom tile on the right and note the lower temperatureoftheaircomingoutofthethreetriadtiles. AircomingoutoftheTriadtileis4degreescolderthantheaircomingoutof theflatbottomtile.(thankstoeuropeanbaseddaxtenforthistiletesting) TheHi PlumeFin In2003aglobalfortune100,computermanufacturer,begantoworkontheshort cycle issue with their vendor Triad Floors by NxGen, LLC. Triad analyzed the inefficiencies of the perforated tile and came to the conclusion that getting air to stratifytoover7 andtodisperseairintothefrontoftheservers,weremandatory performance qualifications of the perforated tile. As a direct result of this analysis andadetailedscientificstudyoffluiddynamics,garymeyer,founderandpresident oftriadfloors,createdthepatentedhi Plumefin. The fin is scientifically designed to not only create positive airflow through every holeinthetile;italsohasacurvedshapedesignedtocreateadispersedpatternof airflow out of the top of the tile. By altering the pressure under the tile, the Hi Plumefinusesthescienceoffluiddynamicsto,ineffect, bend theairoutwardlyso

6 itcanflowintotheserversandupto7. The end result of introducing the Hi plume fin design to the airflow cooling environmenthasbeentoimprovecoolingtemperatures,atthefrontoftheserver, thatare: 3 5degreescoolerinthebottomthirdoftherack, 5 10inthemiddlethirdand 10 20degreescoolerintheupperpartoftherack. BelowarethetestresultsfromacustomerwhodeployedTriad s65%hi Plumefin tile.pleasenotethereareonlythree65%openareatriadtilesinthisrowcompared tothesix,56%tilesthatweretherepreviously. Three tiles replacing 6, 56% tiles. Less air but better cooling from less air through directional airflow. Top Before Front Top After Front Difference Middle Before Front Middle After Front Difference Bottom Before Front Bottom After Front Difference Triad Tile Placement Solid tile XXXX Solid tile XXXX Solid tile XXXX 56% Tile Placement XX XX XX XX XX XX

7 The test results confirm that open space / CFM does not, necessarily, equate to improvedcooling.thetestresultsshowlowertemperatureswithlessairandless open space. Also note the consistent temperature at all levels of the rack. This means the flow of the air to the servers in the rack is consistent no matter the height. This customer was able to raise their set point by 8 degrees, enabling them to realizeacoolingcostsavingsof32%.thisconfirmsthatcfmisnotthesolecriteria formeasuringcoolingandconfirmswhyweseesomuchwasteofairintheairflow system. TheRiver andthelake DataCentermanagersarelearningabouttheinefficienciesofthetileandthecosts associated with adding more and more cooling capacity to the data center airflow system.asaresultoftheirpursuitofreducinghotspotsandimprovedcooling,they havedevelopedtwo,competing,designphilosophies.oneoftheseprovidesairata sufficient velocity to stratify to 7 while flowing into and over the front of the servers;theothercreatesalargepoolofverycoolair,leakingintothecoldaisle.we callthesetwomethodsthe River andthe Lake. Thelakeenvironmentreliesoncreatingalargepoolofcoldairunderthefloorand in the cold aisle. This pool, or lake of air, is pressurized under the floor. As the pressureisreleasedthroughthetile,itisexpectedtofillthecoldaisle.theservers are cooled by the internal fans pulling the cold air from the middle of the aisle throughtheserver. Theriver,ontheotherhand,isdesignedtousetheflowofairtocool.Itreliesonthe movement of air to provide a dissipative effect on the servers and through the serverfans.therivermethodtreatsthedatacenterasanecosystemofairflow.a molecule of cool air leaves the CRAC unit, moves through the under floor plenum, through the tile and directly into the front of the server, cooling the server then retreatingthroughthehotupperplenumbacktothecracunit. Whenyoucomparethesetwodesigns,youfindthelakeneedsairtobeagreatdeal coolerandtheplenumspaceneedstobedeep,tokeeptheaircoolandpressurized. Theairsitsinareasunderthefloorandsitsinapoolinthecoldaisle.Muchofthe airinthissystemisinplaceto contain theairsothereisflowoutofthetile.even withthislargepoolofair,wefinditdifficulttogettheairtotheserverboundary layers at the front and top of the rack. As a result, in a lake design, we are only utilizing28%oftheairtocooltheservers. Theriverontheotherhandreliesonthevelocityandmovementofairanddoesnot requiretheairtobeascool(lessenergyneededtocooltheriver).theriverismore

8 concernedwiththemovementofair(likeafan)andtheneedtogettheairtothe server.airisredirectedandconcentratedbydirectionalflowtotheservers.ifyou wantarivertowork,youneedtokeeptheairmovingtoandthroughtheserver. There are three benefits to the River system. First of all, by breaking down the boundarylayeratthefrontandtopoftherack,youareabletoimprovethecooling capabilitiesoftheairflowsystem.thesecondbenefitoftheriversystemisthatyou needlessairthanyoudoinalakesystem.theriversystemcontainstheairunder thefloor,focusestheairtotheserverbymanagingtheairoutofthetile,usesthe cabinet door to further channel the air to the servers and finally, supports an 18 degreedeltatinthehotaisletopulltheairfromthebackoftheservers. Awell designedriversystemcanreducetheneedforcrac/crahgeneratedairby upto50%andcanlowerupperservertemperaturesby10to20degrees.thiscan leadtoareductioninenergycostsbyasmuchas60%whilereducingtheneedfor 40% of the air handling devices. You get the best of both worlds, lower energy costsforaloweracquisitioncost.hereisanexample: Currentenvironment/LakeCooling 10,000sfdatacenter 15CRACunitsx$47,000perunit=$705,000 Utilitybill=$62,000permonthx12=$744,000annually RiverCooling 9CRACunitsx$47,000perunit=$423,000 Savings=$282,000 Utilitybill=$62,000x.5=$31,000forcoolingx.4=$7,440x12=$89,280annually Costoffloorsystemandimprovedtiles: Underfloorwalls $25,000 Tilereplacement $23,000 Totalcost $48,000 CRACsavings $282,000 Utilitysavings $89,280 Totalsavings $371,280 MinusRiverproducts $48,000 Totalsavings: $323,280

9 AirflowUtilizationEfficiency(AUE) Sincethetemperatureatthetopoftherackdrivesthecoolingstrategyforthewhole datacenter,creatingameasurementthatfactorsinthisreadingseemsonlylogical. And,sincethetemperaturesuppliedbytheCRACunitisourcoolingsource,creating ameasurementthatevaluatestheintegrityoftheairasitmovesthroughthefloor andtotheserverseemslogicalaswell. The Airflow Utilization Efficiency (AUE) calculation provides us with a way of evaluatingthethermallossinourairflowsystem.wecomparethetemperaturesat thetopoftheracktothesupplyairtemperature. Hereisanexample: 85degreestopofrack 55degreesupplyair AUE=30 83degreestopofrack 58degreesupplyair AUE=25 This is a simple way to determine if the cool air coming out of the CRAC unit experiences thermal loss leading to a low set point and higher energy usage. The smaller the AUE number, the more efficient your airflow system is working. In additiontothesupplyairtemperatures,wewouldofferthatthecracunit/supply air,shouldbeoptimizedtohaveairflowtemperaturesatthetopoftherackasclose to80aspossible.lastly,sincethedifferenceisshownintemperaturebydegree,you cancomparethedifferenceanddeterminethereductioninenergycosts. 1degree=4%reductioninenergycosts 12degrees=48%reductioninenergycosts RiversystemsquiteoftensupportanAUEnumberof10.Thatis: 80degreestopofrack 70degreessupplyair AUE=10 River systems can do this with half the CRAC units utilized in a lake system. Additionally,theimpactonenergyconsumptionisimprovedaswell.Intheend,the reduced impact on capital expense and recurring costs make the River Cooling

10 System anextremelycompellingsolutionforanydatacenter. Summary Raisedfloorcoolingcanbeacosteffectivesolutionforcoolingservers.The River CoolingSystem isthemostefficientwayofusingairtocool.whenlookingatthe choicebetweenrivercoolingenvironmentsandlakeenvironments,itisimperative to look at all the costs associated with the solution including installation costs, equipmentcostsandenergycosts. By factoring in all three cost elements, companies will be able to choose the best solutionfortheirspecificneeds.byimprovingairutilizationefficiencyandutilizing passivecooling,wecanlowercapitalcosts.aueisenhancedbygettingairoutofthe floor without loss of temperature and dispersing the flow into the front of the server.thiscanonlybedonewhentheairisdirectedthroughthetiletothefrontof the server. Flat bottom tiles cannot divert air to the server and do not stratify to sevenfeet.theyshortcycleandmixcoldaisleairwithunderfloorair.thisleadsto thermal loss and higher energy costs. Triad s High Plume fin improves AUE by gettingairtotheservers,inadispersedflow,whileprotectingunderfloorairfrom thewarmairabove. (For questions regarding this document, please feel free to contact Tom Weiss at [email protected])

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

Energy-efficient & scalable data center infrastructure design

Energy-efficient & scalable data center infrastructure design Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges

More information

Layer Zero. for the data center

Layer Zero. for the data center Layer Zero for the data center Preparefor the Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Small Data / Telecommunications Room on Slab Floor

Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure

More information

Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling

Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Student Intern Earth and Environmental Engineering,

More information

Thermal Optimisation in the Data Centre

Thermal Optimisation in the Data Centre Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Effect of Rack Server Population on Temperatures in Data Centers

Effect of Rack Server Population on Temperatures in Data Centers Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Server Room Thermal Assessment

Server Room Thermal Assessment PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

5 Reasons. Environment Sensors are used in all Modern Data Centers

5 Reasons. Environment Sensors are used in all Modern Data Centers 5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center

More information

Measure Server delta- T using AUDIT- BUDDY

Measure Server delta- T using AUDIT- BUDDY Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Layer Zero. for the data center

Layer Zero. for the data center Layer Zero for the data center PREPAREFOR THE Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected]

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected] Learning Objectives 1. Gain familiarity with Computational

More information

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if

More information

Office of the Government Chief Information Officer. Green Data Centre Practices

Office of the Government Chief Information Officer. Green Data Centre Practices Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain

More information

Extend the Life of Your Data Center By Ian Seaton Global Technology Manager [email protected]

Extend the Life of Your Data Center By Ian Seaton Global Technology Manager iseaton@chatsworth.com C P I C O N TA I N M E N T S O L U T I O N S WHITE PAPER Extend the Life of Your Data Center By Ian Seaton Global Technology Manager [email protected] Published August 2013 800-834-4969 [email protected]

More information

OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers

OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

RACKMOUNT SOLUTIONS. 1/7/2013 AcoustiQuiet /UCoustic User Guide. The AcoustiQuiet /UCoustic User Guide provides useful

RACKMOUNT SOLUTIONS. 1/7/2013 AcoustiQuiet /UCoustic User Guide. The AcoustiQuiet /UCoustic User Guide provides useful RACKMOUNT SOLUTIONS 1/7/2013 AcoustiQuiet /UCoustic User Guide The AcoustiQuiet /UCoustic User Guide provides useful hints, tips and advice to help maximize the thermal and acoustic properties of the cabinets.

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that

More information

Cabcon. Data Centre Solutions. www.cabcon.co.uk. an acal group company UK +44 (0)1189 122980 IRE (00353) 1 629 2640

Cabcon. Data Centre Solutions. www.cabcon.co.uk. an acal group company UK +44 (0)1189 122980 IRE (00353) 1 629 2640 Data Centre Solutions www.cabcon.co.uk UK +44 (0)1189 122980 IRE (00353) 1 629 2640 About Us are a specialist distributor of copper, fibre, power, security, active and cable management products for the

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

SERVER ROOM CABINET INSTALLATION CONCEPTS

SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

An Introduction to Cold Aisle Containment Systems in the Data Centre

An Introduction to Cold Aisle Containment Systems in the Data Centre An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems

More information

Cloud Computing Data Centers

Cloud Computing Data Centers Cloud Computing Data Centers Dr. Sanjay P. Ahuja, Ph.D. 2010-14 FIS Distinguished Professor of Computer Science School of Computing, UNF Warehouse-Scale Data Center (WSC) Design. Example: a data center

More information

Using CFD for optimal thermal management and cooling design in data centers

Using CFD for optimal thermal management and cooling design in data centers www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,

More information

Understanding How Cabinet Door Perforation Impacts Airflow by Travis North

Understanding How Cabinet Door Perforation Impacts Airflow by Travis North & design deployment The first step in determining the proper perforation for an application is to understand the airflow requirements of the equipment that will be used in the cabinet. Understanding How

More information

Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n

Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction How To Preserve Your Servers And Prevent Overheating Your high-performance, multiprocessor servers are working hard, computing tons

More information

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013 Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Application of CFD modelling to the Design of Modern Data Centres

Application of CFD modelling to the Design of Modern Data Centres Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of

More information

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically

More information

TecCrete. Data Center Flooring

TecCrete. Data Center Flooring TecCrete Data Center Flooring The TecCrete Data Center product is based on Haworth s proven TecCrete access flooring platform. For the last 30 years, it has been the leading choice for architects and developers

More information

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Access Server Rack Cabinet Compatibility Guide

Access Server Rack Cabinet Compatibility Guide Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY Rajat Ghosh, Pramod Kumar Vikneshan Sundaralingam Yogendra Joshi [email protected] G.W. Woodruff School

More information