2 Contents: 03 Editorial Correct values 04 Precise documentation and reliable production Measurement is best 06 Test stand measurements Precision measurement: Modern chamber test rig guarantees accurate values 08 Plug & Play solution The fan: Combination of impeller, motor and control system 10 Documentation Documentation and fan selection: Reliable data 14 Production Accurate means reproducible: Accuracy classes are a measure of manufacturing accuracy 16 Fan efficiency Comparison of fans: RadiPac values are real values 18 Partial load Operation geared to requirements: Fans in AHUs generally operate in the partial load range 22 New impeller Continuous enhancement: RadiPac now even more efficient 24 References Imprint ebm-papst Mulfi ngen GmbH & Co. KG Bachmühle 2 D Mulfi ngen Telephone +49 (0) Telefax +49 (0) [email protected] ebm-papst St. Georgen GmbH & Co. KG Hermann-Papst-Strasse 1 D St. Georgen Telephone +49 (0) Telefax +49 (0) [email protected] ebm-papst Landshut GmbH Hofmark-Aich-Strasse 25 D Landshut Telephone +49 (0) Telefax +49 (0) [email protected] Responsible for content: Kai Halter Editor-in-Chief: Thomas Gruber Text: PR Büro NutzWort, Sasbach Layout and production: Scanner GmbH, Künzelsau Layout concept: pr+co GmbH Photography: ebm-papst, fotolia.com: P. 19 Tiberius Gracchus P. 22 montego6 Print: Druckerei Ziegler GmbH + Co. KG 2
3 EDITORIAL Correct Values "It is only with the heart that one can see rightly. What is essential is invisible to the eye." You could almost imagine Antoine de Saint-Exupéry had the ventilation and air conditioning industry in mind as well when he wrote those words for the Little Prince. Nowadays a lot of regulations have to be observed when choosing the correct fan and installing air handling units. Not without good reason, as air handling units should be designed to operate to the benefit of users and above all the environment. This is also the only way to enable buildings to be used in a sustainable way, minimise CO 2 emissions, save energy and avoid health hazards. Standards, directives and test criteria today provide equipment manufacturers and planners with a whole range of guidelines to help them select the right components and systems. But caution is still called for! The quotation from the "Little Prince" is particularly fitting at this point with its message about not trusting anything blindly but rather listening to the "heart" and one might add to the head as well. This techmag special issue is intended to provide assistance for selecting fans and comes with a promise from ebm-papst. You can only be sure of always taking the right decisions if you have the correct values to work with. And values can only be correct if they have been measured. So the motto is: Measurement takes precedence over calculation. We at ebm-papst consider it of the utmost importance to provide correct and verifiable performance data for our fans. In practical terms this means absolute planning reliability. And in the final analysis you and your customers will find that everything really is as it seems. We play our part by promising to provide the correct values. I hope you will find plenty of useful information in this publication to help you take the right decisions in your planning work and when selecting fans. Because the correct values form the basis for the true values namely trust, reliability and a lasting partnership. And that is what the name ebm-papst stands for! Rainer Hundsdörfer, Chairman of the Board of Directors of the ebm-papst Group 3
4 CORRECT VALUES 4
5 DOCUMENTATION AND PRODUCTION Measurement is best Precise documentation and reliable production The choice of fan is crucial to the reliability and efficiency of air handling units. In this respect, equipment manufacturers have to be able to rely on the documentation provided by the fan manufacturer and on the assurances made with regard to product properties. But where does this product data come from? And how reliable is it? Documentation All the performance data provided by ebm-papst, both in catalogues and the Product Selector, the user-friendly fan selection software, are obtained by taking extensive individual measurements. This involves fitting the test specimens on chamber test rigs set up in accordance with ISO 5801 and performing aeroacoustic measurements. On completion of measurement, the data are validated to guarantee that all the specifications in the documentation actually represent the correct values. So customers can fully rely on the information given when selecting fans. Production In addition to accurate product documentation, a suitable fan production process is required to ensure that the products actually exhibit the properties described. For this purpose, monitoring and checking mechanisms are integrated into the production sequence to reliably detect any tolerance deviations. In practice the products then exhibit exactly the properties specified in the documentation. At the end of the production process every ebm-papst fan is tested for proper operation. Thanks to all the effort invested in precise documentation and reliable production, customers can be sure of obtaining the correct values from ebm-papst. Consequently every fan supplied for use as an air handling unit component can always be trusted to deliver the performance required. 5
6 CORRECT VALUES Fig. 1a: Centrifugal fan set up on test stand with free inlet, noise measurement microphones on suction side Precision measurement Modern chamber test rig guarantees accurate values At ebm-papst, use is made of an aeroacoustic fan test stand for the simultaneous recording of air performance data and noise values. For this purpose the fans are installed in the test chamber with free inlet and free outlet in accordance with installation type A (Fig.1a). The chamber or combination test rig consists of two low-reflection half chambers with high-impedance floor conforming to accuracy class 1 for acoustic measurements. On the combination test rig it is possible to conduct air performance measurements at an air flow of up to 100,000 m³/h with a static pressure increase of up to 3,000 Pa (Fig. 1b). The characteristic curve of the fan is determined on the combination test rig by operating the test specimen at a constant speed and gradually throttling the air flow. The noise, air flow, static pressure increase, speed and reaction torque required to determine Physical quantity Measuring range / unit Measurement accuracy Pressure increase psf 0 to 3,000 Pa 0.5 % of measured value Air flow q v 100 to 100,000 m³/h 1 % of measured value Air power Pu kw 1.2 % of measured value Power input Pe 0 to 30 kw 0.5 % of measured value Torque M 0 to 200 Nm 1 % of measured value Total efficiency e % 1.3 % points Speed N 0 to 99,999 rpm 1 rpm Air density approx. 1.2 kg/m³ 0.1 % of measured value Fig. 1b: Measurement quantities and accuracy levels attained by aeroacoustic test stand Sound power level L wa as of 30 db(a) 1 db(a) Test stand design and tests as per ISO 5801 Industrial fans, performance testing using standardised test stands DIN EN ISO 3744, DIN EN ISO 3745, ISO Acoustics 6
7 TEST STAND MEASUREMENTS What the inspection authorities demand of a test stand As a certified manufacturer, ebm-papst fully conforms to the following criteria as specified for test stands by the guidelines of the AHU manufacturers' association: "An expert report/test report for fans will be accepted if testing was performed in accordance with the latest standard DIN EN ISO 5801: (ISO 5801:2007 incl. corr. 1:2008) by a named test body on a suction-side chamber test rig and the component is manufactured without any modifications." Fig. 2: Inspection authority certificate for test stand the power consumption are recorded in the various operating statuses. A fan characteristic curve ment quantities traceable to national and interna- equipment by Quality Assurance with measure- is made up of at least 10 operating points. This tional standards (German Calibration Service DKD, measurement is then repeated at different speeds. Germany's national metrology institute PTB) is The characteristic curves determined in this way standard practice at ebm-papst. Determination of yield the so-called fan map (Fig. 2). the air flow and regular leak testing are based on ISO Since the middle of 2014, calibration of Accurate measurement results To ensure consistently precise, reproducible measurements, the to the national standard of the PTB have been part the air flow measuring instruments and traceability test facilities and test equipment are subjected to of the quality assurance process. The applicable regular checking. The routine monitoring of test range is from 100 m³/h to 40,000 m³/h with a ref Pa 1000 static pressure increase p fs part load nominal speed erence measuring instrument accuracy of ± 0.5 % of the measured value. Internal validation provides both assurance for the company and information for customers. The documentation is available for viewing at all times. The inspection authorities (TÜV Süd) have confirmed that the test stand satisfies all the requirements of DIN EN ISO 5801 in an air flow range of 500 m³/h to 39,000 m³/h with a pressure increase of up to 1,000 Pa (Fig. 2). Acceptance testing for the acoustic properties of the combination test stand was performed by the Fraunhofer Institute, Stuttgart. The institute confirmed the Class 1 rating for the ebm-papst noise measurement chamber. To sum up At ebm-papst the product documentation for all fans is based on measurements taken on certified precision chamber test rigs. Constant internal monitoring of the test facilities used and the values obtained guarantees the consistently high levels of product quality and fan dependability you can always rely on. Volume flow rate q V m³/h Fig. 2 7
8 CORRECT VALUES The fan Combination of impeller, motor and control system Inlet ring For ebm-papst a fan is more than just an impeller. An ebm-papst fan is an optimised assembly made up of at least the following: Precision impeller with inlet nozzle GreenTech EC motor Control electronics Precision impeller GreenTech EC motor Commutation unit Put to the test A chamber test rig is used to take measurements on the minimum fan configuration described above. After testing the measurement results are entered into the product documentation. The ebm-papst centrifugal fan from the RadiPac product range for use in AHUs is fitted with extra mechanical components in addition to the basic features mentioned to create a complete ready-to-install fan unit. "Spider" and "Cube" versions of the mechanical assembly are available. The spider type is the best alternative for smaller sizes as this unit can simply be screwed to the device wall. The cube design is the ideal choice for large and heavy fans. It is mounted on vibration-absorbing elements on the bottom of the device. The name RadiPac is a combination of Radial referring to the centrifugal fan and Package meaning an assembly. The complete RadiPac package is a ready-to-install, optimally designed functional unit which is easy to handle, easy to fit and easy to operate. Simplicity itself: The all-in-one solution Plug & Play. Fig. 1: Fan components 8
9 PLUG & PLAY SOLUTION 9
10 CORRECT VALUES Nominal data Characteristic curve Nominal voltage range Frequency Speed (1) Max. power input (1) Max. input current (1) Perm. ambient temperature Technical equipment and connection diagram Type Motor VAC Hz rpm W A C Centrifugal fan kg Fig. 1a: Catalogue nominal data (source: RadiPac catalogue) *3G 560 M3G 150-IF A 3-phase / , to +40 S.XX/M3) R3G 30.5 Subject to change (1) Nominal data at operating point with maximum load and 400 VAC Documentation and fan selection Reliable data Selection of the right fan on the basis of an application-specific operating point is only possible with reliable data and is generally performed with the aid of appropriate product selection software. The properties of the RadiPac centrifugal fans are documented in product data sheets and printed catalogues (Fig. 1a, b, c) as well as in a product selection program, the Product Selector. At ebmpapst, the origin of the fan performance data contained in the software can always be traced back to measurements as described above. The required air flow and the static pressure increase which the fan subsequently has to achieve in practical use are the minimum criteria employed for the selection process. Optimised software Because the required operating points are not always identical to the measured operating points, there is a need for interpolation between the measured values. Use is often made for this purpose of the familiar affinity laws for flow machines. These are sufficiently accurate in cases where fans merely consist of a flow machine, in other words an impeller. As we already know however (Page 8), ebm-papst fans also include a motor and control electronics. These two assemblies do not conform to the fan affinity laws, but rather exhibit completely different performance characteristics, particularly in the partial load range. The selection software has been appropriately optimised to obtain a highly 10
11 DOCUMENTATION p fs Pa ,8 1,6 2,4 3,2 4,0 4,8 in H 2O 0 q V A B cfm m 3 /h = ηmax. 2 Fig. 1b: Catalogue characteristic curves (source: RadiPac catalogue) Fig. 1c A A A A B B B B n min P ed W I A 3,48 4,55 5,40 4,97 4,47 5,59 7,10 6,42 L W A db(a) accurate forecast of the operating behaviour of the fan unit at any conceivable operating point. Product Selector The Product Selector from ebm-papst provides a particularly user-friendly means of finding the right fan. The selection program makes it possible to check fans at various operating points and determine the performance data. It additionally permits dynamic comparisons closely resembling actual operating conditions. The influence of temperature, altitude and installation space can also be incorporated. If there are several fans in the specified performance range, the aerodynamic and acoustic data displayed can be used to help select the most suitable model. Another option available is calculation of the life cycle costs for the fans selected. The performance data are also output at the specified operating point with suction and pressure side sound power level values over the octave band. The software can be incorporated into customer 11
12 CORRECT VALUES epa 1200 Fig. 2: Validation test on a total of 38 different fan models from ebm-papst EXAMPLE: Family of characteristics for a model from the Product Selector (K3G310-AX69-01, Test_Id , ) 1 15 REFERENCE POINTS: Selected operating points for measuring the actual power consumption Nominal speed Reduced speed Static pressure increase p fs Volume flow rate q V m³/h Fig. 3 device configuration programs by way of a DLL interface. Certified accuracy The performance data output is extremely accurate, as confirmed (Fig. 3) by the inspection authorities (TÜV Süd). Validation measurements performed on all 38 models in the RadiPac product range show that on average the efficiency level indicated by the Product Selector tends to be slightly too low! What procedure was employed for the validation measurements? 15 reference points (Fig. 2) were chosen for each fan in the RadiPac product range. These were measured on the certified chamber test rig and the performance data were then compared to the data from the Product Selector. This revealed that the calculated values from the Product Selector are almost identical to the values actually measured. In accordance with AHU guideline 01, the best possible accuracy class 0 is thus obtained for RadiPac fans (Fig. 4). In other words, ebmpapst RadiPac fans in as-delivered condition tend to exhibit a higher level of efficiency than that indicated by the Product Selector. This guarantees true planning reliability for customers. Fig. 4: In reality, fans from ebm-papst tend to have a higher efficiency level than shown in the product documentation ACCURACY CLASSES AHU guideline 01, 2013, German association of air handling unit manufacturers Class 0 Class 1 Class 2 (based on DIN 24166, refer to Page 14 Fig. 1) % Pkte. Deviation in efficiency Δη se Reference point, consecutive number
13 CONFIRMED ACCURACY Customers agree: You can rely on ebm-papst! The following customer comments confi rm just how important accurate fan data is for air handling units. "We as manufacturers of energy-efficient air handling units demand particularly high standards with regard to the performance data of drive systems. So we check the components we use on our own test stand as part of the prototype measurement process. We have found that drive systems from ebm-papst yield convincing results in comparison with the stated values. The deviation between the calculated data and the measured performance was within a narrow tolerance band of just 1 to 4 %. An extremely positive aspect is that the figures from ebm-papst turned out to be lower than what we actually measured. That doesn't happen very often." "The accuracy of the fan data is of the utmost importance to us and our customers, providing as it does the only basis for clear and reliable information on the power consumption and noise emission level of the ventilation system as a whole. As our air handling units have Eurovent certification, we guarantee our customers compliance with the tightest tolerances in our technical data. We can only be sure of performing our calculations accurately if we receive extremely precise data on the fan concerned from the manufacturer. The quality of the information provided by ebm-papst is outstanding." "The air conditioner manufacturing company Wolf and ebm-papst have enjoyed a long-standing and successful working relationship. The reliable, infinitely variable EC fans are a crucial factor in convincing our customers when it comes to hygiene, air conduction and low power consumption. This common goal will also form the basis for our future cooperation. The performance data and design programs are reliable instruments for the planning and production of modern air conditioning devices." Dr.-Ing. Christoph Kaup Managing Partner of HOWATHERM Klimatechnik GmbH Martin Törpe Product Management AL-KO THERM GMBH Dipl. Ing. (FH) R. Riebesecker A/C + Ventilation Product Management Wolf GmbH 13
14 CORRECT VALUES Production Accuracy classes are a measure of manufacturing accuracy At ebm-papst, the focus of attention is on making top quality fans. Documented performance data and the correct choice of fan are only part of the story. It is also crucial to ensure that the fan is constructed in such a way that it actually attains the specified performance level in operation, regardless of the production date. A certain amount of tolerance is inevitable with any technical product, for example on account of dimensional deviations in components and assemblies (e.g. enamelled wire diameters or electronic components). Tolerance limits can be set and action can be taken to ensure that these are not exceeded. This is the job of a company's Quality Assurance department. And the greater the possible deviations and the resultant performance deficits, the greater the safety allowance required when selecting fans. DIN "Fans; Technical delivery conditions" therefore defines accuracy classes and permits deviations from the documented performance characteristics. The socalled limiting deviations are divided into Classes 0 to 3. The standard allows accuracy class 3 for fans smaller than 10 kw for example (Fig. 1). Planning reliability Comparison of the product Fig. 1: Accuracy class as per DIN (ISO 13348)* Performance characteristics Limiting deviation in class 0 (AN1) 1 (AN2) 2 (AN3) 3 (AN4) Air flow q v ±1 % ±2.5 % ±5 % ±10 % Static pressure increase Δp stat ±1 % ±2.5 % ±5 % ±10 % Drive performance P ed ±2 % +3 % +8 % +16 % Static efficiency stat -1 % -2 % -5 % ( 12 %) Sound power level db(a) +3dB(A) (+2dB(A)) +3dB(A) +4dB(A) +6dB(A) * ISO with other designations and slightly different values documentation and the actual product delivered reveals that in practice the power consumption of the fan will be lower and the total efficiency level higher than the documented figures. Consequently there is no risk of any unpleasant surprises when the air handling system goes into operation and there is also no need for any precautionary over-dimensioning of the fan. Fig. 2: The accuracy classes define production-related deviations from fan performance data. Accordingly the RadiPac product range attains Class 1. Analysis is based on performance measurements on 6,953 fans. Top class RadiPac At the end of the produc- 45 Analysis of RadiPac product range 1400 tion process, all RadiPac fans are checked in the as-delivered condition for any performance deviations. This quality assurance procedure involves recording all the electrical performance data and confirming compliance with the permissible manufacturing tolerances. Based on a size 500 RadiPac fan, analysis shows that ebm-papst attains accuracy class 1 (Fig. 2). For air handling unit frequency (%) number of products manufacturers, this means that the figures given for the fan in the catalogue and Product Selector must not differ from the actual drive performance by more than 2 % and from the total efficiency by more than 1 %. 5 0 P1 [W] class 0: 2 % class 1: 3 % class 2: 8 %
15 PRODUCTION 15
16 CORRECT VALUES Fig. 1: Multiplication of the individual efficiency levels of all fan components yields an incorrect total efficiency value Comparison of fans RadiPac values as compared to calculated values The true efficiency of a fan when measured is not equal to the product of the maximum individual efficiency levels of the motor, drive unit, control system and impeller. But why is that? Correct determination For a retrofit project, enquiries are made about various fans and the performance data of the fans offered are then compared. It is important to remember that performance specifications based on calculations are generally not realistic. They tend to be far too optimistic because the maximum efficiency levels of the individual components (motor, drive unit, control system and fan impeller) are usually taken from catalogues for calculation purposes. It cannot however be assumed that each component will actually achieve maximum efficiency under realistic conditions. Multiplying the optimum individual efficiency levels yields a far more favourable total efficiency than is possible at the actual operating point (Fig. 1). As a result of this error, the values obtained from calculation of the power consumption will be far better than in actual operation. To ensure that realistic values are acquired, ISO 12759:2010 "Fans Efficiency classification for fans" expressly recommends working with measured values when planning. As good as it gets ebm-papst can always be relied on to provide the correct values because what we measure and supply is the minimum configuration of a complete, ready-to-install fan assembly consisting of high-performance impeller, EC motor and control electronics. As these components are optimally matched, it is possible to achieve static total efficiency levels well in excess of 60 %. These levels have been measured and entered in the Product Selector. Far higher figures quoted by other suppliers are always open to question. 16
17 FAN EFFICIENCY Ecodesign The ecodesign directive for fans (EU 327/2011) specifies minimum efficiency requirements for fans driven by electric motors. The requirements first came into force in 2013 and will become more stringent as of They apply to all fans with an input power between 125 W and 500 kw and a drive performance range of 125 W to 500 kw. A specified efficiency level has to be attained based on the type of fan concerned. Calculation of the minimum efficiency values is described in this directive. All GreenTech EC fans in the ebm-papst RadiPac product range now already surpass the requirements applicable as of Minimum efficiency requirements for RadiPac EC centrifugal fans as per the 2015 ecodesign directive Power consumption Minimum efficiency in kw in % kw 42 % 0.5 kw 48.3 % 1 kw 51.5% 3 kw 56.5 % 5 kw 58.5 % 10 kw 62 % In addition to optimum efficiency, a RadiPac with GreenTech EC motor offers a whole range of advantages over other fans for air handling systems. Installation simple and safe The high-performance impeller is mounted directly on the rotor of the external rotor motor. This saves space and permits balancing of the entire rotating unit in one clamping operation (Fig. 2). The electronics and motor are combined in a single unit (Fig. 3). Thanks to the integrated control electronics there is no need for an external frequency converter, which makes installation easy. As the motor and electronics in the motor system are perfectly matched and in close proximity to one another, additional electronic filters and shielded cables are also superfluous and no external motor protection circuit breaker is required. Air handling units can be commissioned without the need for any costly adjustment, earthing or shielding work. In other words "Plug & Play" for ventilation technology. Resource preservation The GreenTech EC motor helps to preserve resources without any supply risks. The efficiency of the mains-powered permanently excited synchronous motor with electronic commutation (also known as BLDC or PM motor) far surpasses efficiency class IE4 and manages to do so without using any potentially problematic rare earth magnets. On account of their design, other permanent magnet motors of the internal rotor type and offering comparable efficiency require rare earth magnets. And so RadiPac is THE compact, efficient, user-friendly, sustainable all-in-one fan solution for air handling units (Fig. 3). AC or PM fans with frequency converter GreenTech EC fan + + = "Lots of trouble" = "Plug & Play" Fig. 2: EC motors require less installation space Fig. 3: GreenTech EC motors the all-in-one solution 17
18 CORRECT VALUES Operation geared to requirements Fans in AHUs generally operate in the partial load range An office complex with a glass facade, a summer's day with temperatures of 35 C in the shade, full of people, maximum demand for ventilation and cooling and no maintenance or servicing due for a long time yet - that would be one way of describing the maximum requirements for an air handling system. In commercial, municipal and industrial applications, maximum load situations only ever occur on a few days in the course of a working year (Fig. 1). But the necessary cooling and heating performance and minimum air exchange rates still have to be reliably provided even then. The maximum load situation is thus the crucial factor for dimensioning of the air handling system and fans but it is not the most important when viewed over the entire operating period! Operating point and efficiency An information brochure* issued by the German energy agency dena contains the following recommendation: "In the short term, the time of day, production fluctuations and weather conditions may cause the operating point to change. Over the medium term, changes may come about due to seasonal influences or the degree of manufacturing capacity utilisation and in the long term as a result of increasing filter resistance etc. Under such circumstances it would be wrong to set the design operating point *dena guide "Ventilation Technology for Industry and Commerce" 18
19 PARTIAL LOAD 19
20 CORRECT VALUES Power requirement of an AHU for a typical office block storey, considered over the course of a week Fig. 1: Power consumption of an AHU over the course of a week [kw] t Electrical power consumption Time [h] (least favourable conditions and maximum performance requirement) at the point with the best efficiency level. It is better to have the operating point sembly and installation costs, less weight and a space-saving design with AC standard motor and VFD savings for the most frequent operating situation set here. The ideal solution is to perform optimisation on the Correct values in partial load operation Partial load is thus of considerable importance when costs/ years with GreenTech EC motor basis of the expected load and select the characteristic curve with the lowest annual energy costs." So the key is to have a technology which provides more or less infinitely variable adaptation of the air flow to the actual requirement. This ability is planning and operating air handling systems with a view to keeping running costs to a minimum. RadiPac EC centrifugal fans provide an ideal solution. The certified Product Selector makes it possible to realistically simulate these operating conditions p sf Pa η ed % q V 25 % 50 % 75 % 100 % Boost η ed :with GreenTech EC motor η ed :with AC standard motor and VFD m 3 /h already integrated into the RadiPac for operation in air handling units. Its capacity for adjustment over a broad speed range ensures excellent efficiency and helps to cut operating costs. This is illustrated by comparing an AC fan with frequency converter to a GreenTech EC fan (Fig. 2). For the load profile shown (Fig. 3a, b, c), the efficiency of the EC fan is around 28 % higher. In addition to reduced power consumption, other benefits include far lower as- because its database contains the measured performance data of the fan. Absolute planning reliability is thus guaranteed. Authentic operating conditions Category A measurements with free inlet and free outlet are definitive for the data given in the product catalogues and Product Selector and permit direct fan comparisons (Fig. 4a). The fans 50 % 40 % 30 % 20 % 10 % q V 25 % 50 % 75 % 100 % Boost m 3 /h Fig. 3a, b, c: As compared to an AC standard motor with converter and the same power rating, the GreenTech EC motor is roughly 28 % more efficient for the load profile under consideration 20
21 PARTIAL LOAD. Fig. 2: System comparison between an IEC-E2 motor with frequency converter, sine filter and protective circuitry and a GreenTech EC motor from ebm-papst in an air handling unit operate in more or less confined spaces. This leads to a reduction in air performance which has to be taken into consideration when selecting the right fan (Fig. 4b). ebm-papst's documented values are based on customer requirements and the possible operating conditions involved. When choosing fans, the Product Selector makes it possible to incorporate various factors of influence, including the location of the air handling system or the available fan installation space. This permits a reliable assessment of energy efficiency, as well as operating and life cycle costs, because here again a whole range of correct values provide the foundation. The realistic consumption and performance figures supplied by ebm-papst help to ensure that the forecast performance values are actually achieved in practice (Fig. 4c). Selection of the correct fan is thus guaranteed. Fig. 4a Fig. 4b Fig. 4c: In the Product Selector the "installation situation" can be represented by selecting the size of the air handling units 21
22 CORRECT VALUES 22
23 NEW IMPELLER Continuous enhancement RadiPac now even more effi cient Further enhancement of the RadiPac was the next logical step for ebm-papst. Following optimisation of the EC motors used in the RadiPac fans, the introduction of an improved fan is now in the pipeline. Something to look forward to! Nothing wrong with checking but trust is even better Reliability and trust are vital to any partnership. Customers must be able to rely entirely on their suppliers - and ebm-papst is well aware of this responsibility. Both the fans and the associated documentation are quality products in which planners and operators of air handling units can always place their trust. Input Transformation Required output AC (direct) driven fan Loss Electrical power P ed VFD* Motor incl. bearing Belt drive Bearing of the impeller Impeller Air performance P u 100 % EC Directly driven fan Loss Electrical power P ed Integrated VFD* Motor Mt incl. bearing No belt drive No impeller Bearing Impeller Air performance P u 100 % EC Directly driven fan future Loss Electrical power P ed Integrated VFD* No belt drive No impeller Bearing New impeller * VFD = variable frequency drive Air performance P u 100 % Fig. 1: The new RadiPac generation 23
24 REFERENCES 499 RadiPacs for a model project in China A ventilation concept guaranteed to meet with applause The new Grand Theatre in Jinan in China is the pride of the city not least in terms of sustainability. Helping to achieve this are 499 extremely efficient and quiet-running RadiPac fans from ebm-papst which supply the giant complex containing an opera house, concert hall, hotels and offices with all the fresh air it needs. ebm-papst was the ideal partner for the air handling unit manufacturers Tsinghua Tongfang Co. who are committed to sustainable solutions. The 710 and 630 mm RadiPac fans employed offer maximum energy efficiency and reliability coupled with minimal maintenance and ease of installation. They are also powerful enough to convey the air through the extensive ducting system at high pressure and quiet enough to not spoil the visitors' enjoyment. Thanks to the use of officially certified ebm-papst measurement technology there was also no doubt that the envisaged system efficiency of the fan units would actually be attained in practice. Technical data ebm-papst product 2 x K3G710-AQ x K3G630-AQ01-01 Air flow m 3 /h 20,000 Fan static pressure P a 550 Power consumption kw 2 x 2.8 No. of units 218 No. of fans 499 The crux of the matter: Model projects such as that in Jinan have to live up to their good name. This demands solutions which both incorporate successful existing concepts and represent the latest state of the art just like our RadiPacs with GreenTech EC technology. 24
25 REFERENCES 25
26 REFERENCES Unique air handling solution for exclusive shopping mall A change of atmosphere in the shopping centre Sandton City is one of Johannesburg's largest and most exclusive shopping centres. In the course of its modernisation, a new air handling concept was developed employing 140 RadiPac fans from ebm-papst. The modular Viking air handling units had to be adapted to the particular conditions and different installation situations encountered. This involved the development of five differently dimensioned units with three modular sections each. An ideal air supply is provided by RadiPac fans with a diameter of 400 mm. These were installed in the form of a vertical wall in a typical fan array and can be individually regulated to suit the installation location and the required air supply by way of a 0-10 V control signal. The manufacturing process was extremely straightforward, as all the RadiPacs are of a standard size with identical impellers and motors. Maintenance work is also reduced to a minimum by not having to adjust any belt drives. Technical data ebm-papst product 11 x K3G400-AQ23-01 Air flow m 3 /h 64,800 Fan static pressure P a 1,100 Power consumption kw 11 x 2.45 (1,700 m above sea level) No. of units 18 No. of fans 140 The crux of the matter: The Viking solution shows just how important it is to have highly efficient motor technology, optimised aerodynamics and intelligent control electronics all working in perfect harmony. This is the key to creating concepts which set new standards. 26
27 REFERENCES 27
28 Discover ebm-papst PM-EN tech.mag 02/2014 SC-2,5' Ralf Mühleck, Project Engineer at ebm-papst We at ebm-papst develop fans for air conditioning systems designed to guarantee maximum measurement accuracy and a reliable planning basis for customers. Our perfectly coordinated complete system not only offers outstanding performance but also provides reliable information on the total efficiency level. Because it is the result which counts. Find out more at entdecken.ebmpapst.com/gebaeudeklimatisierung The engineer s choice
SPECIAL ISSUE PART 2: TRUE VALUES DISCLOSURE
01 2015 Technology from ebm-papst SPECIAL ISSUE PART 2: TRUE VALUES DISCLOSURE Contents: 03 Editorial RadiPac = form + fit + function 04 General An ongoing development process: Plug & Play centrifugal
EC medium pressure axial fans. The effi cient system solution.
EC medium pressure axial fans. The effi cient system solution. GreenTech EC technology in a new dimension. Thanks to the new axial fans, our highly effi cient GreenTech EC technology is now available for
"AC2EC" - Replacement made easy New EC motor design Compact and efficient
"AC2EC" - Replacement made easy New EC motor design Compact and efficient The efficiency of the fans used is a central issue in ventilation and airconditioning technology. This is encouraged not only by
Data Center Cooling. The engineer s choice
Data Center Cooling The engineer s choice About ebm-papst Inc. Headquarters - Farmington, CT» 250K sq. ft.» Acoustic testing chamber» Complete air testing lab on site» Mechanical/Design Engineering» Electrical
Technical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC
Technical Concept Filter Fan Unit COMPACT Type COMPACT AC Type COMPACT EC Ultra Filter Fan Unit COMPACT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide
ebm-papst North America
ebm-papst North America Data Center Cooling The engineer s choice About ebm-papst Inc. Headquarters - Farmington, CT» 250K sq. ft.» Acoustic testing chamber» Complete air testing lab on site» Mechanical/Design
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed
Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Rely on GD to provide the perfect fit The perfect fit to maximise productivity The growing industrial demand for compressed air requires
Top Technology for Industry, Agriculture, Business and Communities
Top Technology for Industry, Agriculture, Business and Communities CHP The Technology with a Potential for Saving Energy Combined Heat and Power (CHP) is a highly efficient technology for the conversion
FAN SYSTEM REPLACEMENTS IN HVAC EQUIPMENT TO IMPROVE ENERGY
FAN SYSTEM REPLACEMENTS IN HVAC EQUIPMENT TO IMPROVE ENERGY Thomas Heine, Dipl.-Ing. (BA), BSc (Hons) Market Manager EC Upgrades, ebm-papst A&NZ 10 Oxford Road, Laverton North VIC 3026 [email protected]
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Filter Fan Unit SILENT. Type SILENT AC Type SILENT EC
Technical Concept Filter Fan Unit SILENT Type SILENT AC Type SILENT EC Filter Fan Unit SILENT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean
EASYAIR flat THE COMPACT WAY TO A COMFORTABLE CLIMATE.
EASYAIR flat THE COMPACT WAY TO A COMFORTABLE CLIMATE. LIFE IN PURSUIT OF QUALITY FROM THE VILLAGE FORGE TO A GLOBAL CORPORATION The Directors of AL-KO KOBER SE (from right to left): Stefan Kober (CEO),
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice A truly international certification The Eurovent Certification Programmes are managed by an autonomous
FULL DC INVERTER SYSTEMS
FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation
How To Save Energy On A Power Supply
Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity Introduction A U.S.
Surface Technology. Centrifugal Fan GMD
Centrifugal Fan ATEX classed adapted for paint shops Wide assortment broad area of application Service friendly low maintenance costs Headquarters: Centrifugal Fan Centrifugal Fan is a direct driven industrial
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
ENERGY-SAVINg DRIVE PACKAGE DE ES FR IT. Overview
ENERGY-SAVINg DRIVE PACKAGE SPriPM Motor & YASKAWA V1000 Inverter Drive EN DE ES FR IT Overview - Super Premium IPM Motor & YASKAWA V1000 Inverter Drive The Motor-Inverter Package was developed to support
QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems
The Professional Choice in Fluid Management QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems The Olaer Group is a global player specialising in innovative, efficient system
How To Use A Flowmeter
INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
OJ L 191, 23.7.2009, p. 26. OJ L 2, 7.1.2014, p. 1.
Table of Contents 1. Purpose of the guidelines and disclaimer... 2 1.1. The Regulations... 2 2. Scope... 2 3. Historic developments... 4 4. Scope and Requirements... 5 4.1. Scope... 5 4.2. Requirements...
Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry.
The perfect solution for basic servo applications Brochure May 2011 SINAMICS Answers for industry. with 1FL5 servomotors The solution for basic servo applications There is a requirement to automate motion
Screw Compressors 11-22kW
INDUSTRIALS GROUP Screw Compressors 11-22kW KSA Plus Fixed Speed, KSV Variable Speed Smart and affordable CHAMPION COMPRESSED AIR TECHNOLOGIES KSA Plus Screw Compressors Up to 45 C ambient temperature
DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor
DMP Industrial Pressure Transmitter for Low Pressure Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 / 0. % FSO from 0... 00 mbar up to 0... 40 bar Output signals
Incubator with mechanical convection
BF series 400 Incubators and cooling incubators Incubator with mechanical convection The BINDER incubator of the BF series with mechanical convection is suitable for all gentle incubation applications,
Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump
Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pumps Eurovacuum Company is offering its various products to meet industrial vacuum
Axial fans. version 07. The engineer s choice
Axial fans version 07 The engineer s choice Axial fans ebm-papst's axial fans prove their reputation as space-saving wonders by moving air for hot or cold air exchange in a wide variety of devices and
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Fan Coil Units. Fan coil units with brushless DC motor with inverter. your comfort. our world. » Up to 70% energy saving with BLDC motor technology
your comfort. our world.» Up to 70% energy saving with BLDC motor technology» Instant adjustment to temperature and relative humidity changes» Low noise levels» Highly flexible solutions Fan Coil Units
Technical Description. Transistor D.C. Chopper Controller Type GS 24 S
Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine
Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
ABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
Electric motor emulator versus rotating test rig
DEVELOPMENT E l e c t r i c m o t o r s Electric motor emulator versus rotating test rig A controversial issue among experts is whether real-time model-based electric motor emulation can replace a conventional
Rotary Screw Compressors SX Series With the world-renowned SIGMA PROFILE Free air delivery from 0.26 to 0.81 m³/min, Pressure 5.
Rotary Screw Compressors SX Series With the world-renowned SIGMA PROFILE Free air delivery from 0.26 to 0.81 m³/min, Pressure 5.5-15 bar SX Series SX Compact and powerful Today s users expect maximum availability
Material test chamber with mechanical convection
FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and
MINIMAT-EC-Servo Screwdriver Spindles
Screwdriving technology Automation Air motors Air tools Screwdriver Spindles electric MINIMAT-EC-Servo Screwdriver Spindles Maximum Flexibility and process Control Straight Spindle Form - Torque range
Series 6000 Torque measured metal bellow coupling
Properties Free of float metal bellow coupling with integrated torque measurement Non-contact measurement system, high robustness High torsional stiffness Limited torque of inertia Performance Measurement
Under sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
Vacuum drying oven for non-flammable solvents
VD series 53 Vacuum drying ovens Vacuum drying oven for non-flammable solvents A BINDER vacuum drying oven of the VD series is impressive while gently drying with its homogeneous temperature distribution.
Energy Saving ECM Motors and Fans. 2010 Ventilation Catalogue
Energy Saving ECM s and Fans 2010 Ventilation Catalogue CONTENTS For ellington, sustainability is about delivering products at competitive prices while preserving the environment for future generations.
Relationship between Sound Pressure and Sound Power Levels
Relationship between Sound Pressure and Sound Power Levels 4 W. T. W. CORY Chairman of the Eurovent WG 1 Fans If we wish to know the sound power transmitted through a fan and ducting system, it is preferable
[ means: Save time, money and space! MAXXMILL 500. Vertical milling center for 5-side machining
[ E[M]CONOMY] means: Save time, money and space! MAXXMILL 500 Vertical milling center for 5-side machining MAXXMILL 500 MAXXMILL 500 is the ideal vertical milling center for the for the 5-axis operation
Multistage high-pressure multistage centrifugal pumps
Series description Wilo-Helix V 2 4 6 8 Wilo-Helix V 19-27 7 6 6 Hz - North America 22 2 18 5 16 14 4 12 3 1 V 1 V 19 V 27 8 2 6 1 5 1 15 2 25 3 4 2 35Q[US gpm] H[ft] H[m] Design Vertical multi-stage,
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,
SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:
OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND
Conlift1, Conlift2, Conlift2 ph+
GRUNDFOS DATA BOOKLET Conlift1, Conlift2, Conlift2 ph+ Small lifting stations 50 Hz CONLIFT1, CONLIFT2, CONLIFT2 ph+ Table of contents 1. Product overview 3 Conlift for condensate applications 3 Applications
Technical data UNIBLOCK UBSF 180 625
Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power
T U R B I N E G A S M E T E R
TURBINE GAS METER TURBINE GAS METER CGT 1 2 3 4 5 6 7 Design and function page 2 General technical data page 3 Measurement outputs page 4 Dimensions and weights page 5 Performance page 7 Pressure loss
NORD GEARED MOTORS F 1000. Getriebebau NORD. www.nord.com D R I V E S Y S T E M S
I N T E L L I G E N T D R I V E S Y S T E M S, W O R L D W I D E S E R V I C E S NORD GEARED MOTORS F 1000 GB www.nord.com Getriebebau NORD D R I V E S Y S T E M S Unicase Housing: The Optimal Design Getriebebau
Fixed displacement vane pumps
Fixed displacement vane pumps RE 1335/1.5 Replaces: 11.2 1/22 Types PVV and PVQ Nominal sizes 18 to 193 Series 1X Maximum operating pressure 21 bar Maximum displacement 18 to 193 cm 3 Doppelpumpe_d_ Double
LENORD. +BAUER... automates motion. PowerDRIVE-Positioning GEL 6109 Compact positioning drive for installation situations with limited space
PowerDRIVE-Positioning GEL 6109 Compact positioning drive for installation situations with limited space LENORD +BAUER... automates motion. Technical information Version 2014-09 General The PowerDRIVE-Positioning
Radial piston pumps type R and RG
Radial piston pumps type R and RG Operating pressure p max = 700 bar Delivery flow Q max = 91.2 lpm (at 1450 rpm) Geometric displacement V g max = 64.2 cm 3 /rev. 1. General Motor pumps and hydraulic power
Oil-Free Screw Compressors. Water-injected Technology. Rely on GD to provide the perfect fit
Oil-Free Screw Compressors Water-injected Technology Rely on GD to provide the perfect fit Why oil-free? Don t compromise on quality If 100% clean and oil-free compressed air is a requirement for your
Photovoltaic Solar Energy Unit EESFB
Technical Teaching Equipment Photovoltaic Solar Energy Unit EESFB Products Products range Units 5.-Energy Electronic console PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION Worlddidac Member ISO 9000: Quality
PERFECT ELECTRONIC TECHNOLOGY FOR MEASURING AND CONTROL.
PERFECT ELECTRONIC TECHNOLOGY FOR MEASURING AND CONTROL. Made in Germany. 2 Responsibility and Commitment GOOD IDEAS AND HARD WORK FROM OUR TEAM IN STUTTGART RESULT IN SUPERIOR, RELIABLE PRODUCTS Störk-Tronic
RPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
Electric Rotary Actuator - On/Off or programmable control actuator
Electric Rotary Actuator - On/Off or programmable control actuator Direct mounting on quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Multi-voltage version Type
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
Installation, operation and maintenance manual TX 35A
Installation, operation and maintenance manual TX 35A Rev.10 may 2012 Page 1 of 18 1.0.0 Table of contents INSTALLATION, OPERATION AND MAINTENANCE MANUAL...1 1.0.0 TABLE OF CONTENTS...2 2.0.0 ILLUSTRATIONS...2
Automotive BL-DC Fans for Commercial Vehicles. Edition 2015-10
utomotive BL-DC Fans for Commercial Vehicles Edition 5- utomotive BL-DC Fans for Commercial Vehicles Our automotive products BL-DC axial fans and BL-DC dual centrifugal fans with housing are ground breakers
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
How To Make A Fronius Cl Power Inverter
Fronius CL PV central inverter with Fronius MIX concept Modular system. Maximum yield. The Fronius CL combines high-yield power electronics with the unique, modular system design of up to 15 identical
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
The compact unit series
The compact unit series The easy way to maintain a good climate i High, efficient energy recovery with an efficiency of 80 90 % i Energy-saving fan motors utilising EC technology for minimal energy consumption
Installation and safety instructions for AC/DC built-in devices
The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further
TELESCOPE Motorized Lighting Suspension
TELESCOPE Motorized Lighting Suspension Mod. 8400 FEATURES The De Sisti TELESCOPE is a single point suspension specifically designed to provide rigidity and stabilization of all moving parts. It can extend
POLARIS AIR COMPRESSOR SERIES. engineering. excellence. stellar. performance. A World Leader for Centrifugal Compressors
POLARIS AIR COMPRESSOR SERIES engineering excellence stellar performance P - 3 0 0 RELIABLE 100% OIL-FREE ENGINEERED AIR A World Leader for Centrifugal Compressors It s simple: The Polaris Air Compressor
Air technology solutions for demanding applications. Product overview. www.elektror.com17
Air technology solutions for demanding applications Product overview www.elektror.com17 Set benchmarks now. Efficient and high-performance solutions from one source. For the past 9 years Elektror airsystems
Unit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 1 HYDRAULIC PUMPS The material needed for outcome 2 is very extensive so there
Series 7500 Torque Sensor
Properties PTO (Power Take-Off) shaft with integrated torque and angle measurement Non-contact measurement system, high robustness Plug & Play solution, no additional electronics required Performance Measurement
Air Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
O-I DUBI PLANT FANS Quotation Spec Data & Specifications
TECHNICAL DATA O-I DUBI PLANT FANS Quotation Spec Data & Specifications 1 page for the global informations + 12 pages for the fans data Revision 2 end april Global informations: These fans are a replacement
EFC 3600. Frequency converters
2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation
INDUSTRIAL DIRECT DRIVEN PISTON COMPRESSORS CL - CH - CK
INDUSTRIAL DIRECT DRIVEN PISTON COMPRESSORS CL - CH - CK CL - CH - CK Direct driven solution for industry Proven technology, solid construction The CL - CH - CK units are directly driven air-cooled, single
Mounting Instructions. Torque Transducer. A0329 3.2 en
Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................
www.kem-kueppers.com [email protected] Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter
www.kem-kueppers.com [email protected] Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter Description The coriolis mass flow meters measure simultaneously mass
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
Rules for Classification and Construction Additional Rules and Guidelines
VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 6 Test Requirements for Electrical Machinery Edition 1999 The following Guidelines
VZ/VZM SERIES Heavy Duty Shredders 600-2,100 kg/h
VZ/VZM SERIES Heavy Duty Shredders 600-2,100 kg/h Technical Specifications VZ/VZM SERIES Heavy Duty Shredders VZ 17.00 / VZ 18.00 Inline set-up VZM 17.00 / VZM 18.00 Inline set-up Technical Data VZ/VZM
MINEX -S. Magnetic coupling. You will find continuously updated data in our online catalogue at www.ktr.com
MINEX - 171 Table of contents NEW MINEX - 171 Coupling description 173 Technical description 174 s A 22/4 to B 60/8 with containment shroud made of stainless steel 175 s A 75/10 to F 250/38 with containment
Your own power station: For continuous power
Mass Combi Ultra Your own power station: For continuous power Compact and lightweight inverter/battery charger Seamless switching between generator and grid Separate second charger Integrated MPPT solar
ROTEX gas hybrid heat pump. A strong team.
ROTEX gas hybrid heat pump A strong team. The new ROTEX HPU hybrid gas hybrid heat pump always selects the most favourable heating mode automatically. For a long time the general opinion was that a heat
Oil / Air Cooling Units for mechanical engineering and mobile hydraulics
Oil / Air Cooling Units for mechanical engineering and mobile hydraulics ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki, Finland tel. +358 40 178 0920 fax +358 9 4789 2800 [email protected] www.viflow.fi
UDSA - UDSBD unit heater
APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the
Competence gives security. A competitive edge in rotary axes through experience, simulation, calculation, testing
Competence gives security A competitive edge in rotary axes through experience, simulation, calculation, testing Bearings for rotary axes Competence gives security Figure 1: Axial/radial bearing YRTSM
Application Information Fully Integrated Hall Effect Motor Driver for Brushless DC Vibration Motor Applications
Application Information Fully Integrated Hall Effect Motor Driver for Brushless DC Vibration Motor Applications By Shaun Milano Vibration motors are used in a variety of applications including mobile phone
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
SUNON SPECIFICATION FOR APPROVAL
SPECIFICATION FOR APPROVAL CUSTOMER : DESCRIPTION : DC BRUSHLESS FAN DIMENSIONS : 60X60X25 mm M O D E L : KDE2406PTB2 APPROVED NO : APPROVED BY : (AUTHORZIED) SPEC.NO D600732 ISSUE DATE 10.01.1998 DAWN.
Visions become real. Temperature control and cooling systems. The innovative and reliable solution
Temperature control and cooling systems The innovative and reliable solution With our PulseTemp equipment you have the option of up to 72 cooling circuits in the impulse cooling, temperature control, temperature
R&S ZCxxx Millimeter-Wave Converters Specifications
ZCxxx_dat-sw_en_3607-1471-22_v0200_cover.indd 1 Data Sheet 02.00 Test & Measurement R&S ZCxxx Millimeter-Wave Converters Specifications 21.07.2015 15:09:16 CONTENTS Definitions... 3 General information...
Gas water heaters. Why Vaillant? Because warm water is our business for more than 135 years.
Gas water heaters Why Vaillant? Because warm water is our business for more than 5 years. atmomag turbomag Innovative Ideas for warm water Vaillant Gas Water Heaters atmomag and turbomag Since the beginning
R&S R-Line Compact Test Chamber Precise measurements of radiated emissions of wireless terminals 800 MHz to 18 GHz
Test & Measurement Data Sheet 02.00 R&S R-Line Compact Test Chamber Precise measurements of radiated emissions of wireless terminals 800 MHz to 18 GHz R&S R-Line Compact Test Chamber At a glance The R-Line