ComfortLink II Installation Guide. 3 Zone Panel (optional) 4 Zone Sensor with Display (optional) 5 Zone Sensor (optional) 6 Zone Dampers (optional)

Size: px
Start display at page:

Download "ComfortLink II Installation Guide. 3 Zone Panel (optional) 4 Zone Sensor with Display (optional) 5 Zone Sensor (optional) 6 Zone Dampers (optional)"

Transcription

1 18-HD64D1-3 ComfortLink II Installation Guide Other Installation Guides may be necessary, based on system configuration. A complete list of other optional components is shown below. 1 Control 2 Relay Panel For use with 24V indoor systems (optional) 3 Zone Panel (optional) 4 Zone Sensor with Display (optional) 5 Zone Sensor (optional) TZONE950AC52ZA 6 Zone Dampers (optional) ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit. These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes, the matter should be referred to your installing dealer or local distributor. Section 1. Safety! WARNING This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.! WARNING LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Table of Contents Section 1. Safety...1 Section 2. General Information...2 Section 3. Physical Installation...5 Section 4. Wiring...7 Section 5. Installer Setup...9 Section 6. Advanced Features...13 Section 7. Troubleshooting...17 Section 8. Installer Setup Parameters...18 NOTE: See the User s Guide for wireless setup information. 08/11

2 Section 2. General Information 2.1 Overview The ComfortLink II Control is a Communicating 7-inch color touch screen that provides an easy-touse interface to the end user. The control is a communicating wall mounted control that allows a user to manage an HVAC and zoning system. With the addition of the 24VAC Relay Panel, conventional HVAC systems can also be controlled. 2.2 Contents in Box The following parts are included in product model TZONE950AC52ZA: 1 - Control 1 - Sub-Base 4 - SnapSkru Wall Anchors 4-1 Screws 2.3 Specifications Specification Product Model: Product: Size: Storage Temperature Operating Temperature: Input Power: Power Consumption: Wire usage: Zone Sensor Wireless Range ( ): Wireless Connectivity Range ( b/g): Communications: System Modes: Fan Modes: Cooling Setpoint Temperature Range: Heating Setpoint Temperature Range: Description TZONE950AC52ZA ComfortLink II Control 7.3 width x 4.3 height x 1.2 depth -40 F to 175 F, 5% to 95% RH non-condensing 25 F to 126 F, 5% to 90% RH non-condensing 24 VAC from HVAC System (Range: VAC) 7 VA* Minimum 18 gauge NEC approved control wiring 60 ft. through 3 standard walls Varies with router model and placement ComfortLink II - 3 wire connection Heat, Cool, Auto, Emergency Heat On, Auto, Circulate 60 F to 99 F, 1 F resolution 55 F to 90 F, 1 F resolution Indoor Temperature Display Range: 20 F to 119 F Outdoor Temperature Display Range: -31 F to 119 F Indoor Humidity Display Range: Minimum Cycle Off Time Delay: 0% to 99%, 1% resolution Compressor: 5 minutes, Heat: 1 minute * On every application, 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized. See the Relay Panel Installer s Guide for guidelines HD64D1-3

3 2.4 ComfortLink II System Connections Communicating System Control TZONE950AC52ZA Wired Remote Sensor* ZZSENSAL0400AA Indoor Unit Outdoor Unit Wired Remote Outdoor Sensor* BAYSEN01ATEMPA *Optional 24V System Relay Panel Control TZONE950AC52ZA Wired Remote Sensor* ZZSENSAL0400AA Relay Panel BAY24VRPAC52DA Indoor Unit Outdoor Unit Wired Remote Outdoor Sensor 18-HD64D1-3 BAYSEN01ATEMPA 3

4 Wired Remote Outdoor Sensor* BAYSEN01ATEMPA 2.4 ComfortLink II System Connections (Continued) 24V System Relay Panel Control TZONE950AC52ZA Wired Remote Sensor* ZZSENSAL0400AA Relay Panel BAY24VRPAC52DA Indoor Unit Wired Remote Outdoor Sensor BAYSEN01ATEMPA Outdoor Unit *Optional 4 18-HD64D1-3

5 Section 3. Physical Installation 1A Temperature Sensing Considerations The control is designed for installation in climate controlled living spaces. It is recommended to place the unit in central locations with good circulation. Avoid exterior walls and areas near windows, doors, vents or concealed pipes or chimneys. NO YES NO NO 5 FEET [1.5 METERS] 1B Wireless Reception Considerations If enabling wireless, choose a mounting location that ensures adequate signal strength. A wireless device may have significantly different signal strengths if its position changes relative to other wireless devices. If the control shows poor signal strength, you may be able to improve the signal strength by moving the control a short distance in any direction. Wireless Considerations to Maximize Signal Strength: Do not mount the control more than 30 feet from the wireless router (through no more than three interior walls). Do not mount the control in areas where electromagnetic emissions from other devices, appliances or wiring can interfere with the control s communication. (i.e. wireless phones, security systems, wireless internet cameras) Do not mount the control in recessed areas, near metal objects, or near structures. (i.e. doors, appliances, entertainment centers or shelving units) Do not mount the control closer than 2 inches to any pipes, duct work, or other metal obstructions. Do not have metal obstructions, concrete or brick walls between the control and the wireless router it will be connected to. NOTE: See the User s Guide for wireless setup information (weather, multi-system and remote software update functionality). 2 Removing Sub-Base Wall Plate Remove sub-base plate from the control by inserting a small flat blade screwdriver into the notch at each of the four tabs as shown. Gently pry the sub-base away from the the control. NOTE: This tight fit is normal and ensures that the control is held securely to the sub-base when mounted on the wall. 18-HD64D1-3 5

6 3 Mounting Sub-Base to Wall Be sure wires are routed through the center of the base plate and are long enough to connect to terminals. Select and mark three holes. NOTE: The three hole locations indicated at right are recommended. The top location is an optional mounting screw location. A level may be used to ensure professional appearance. Optional Hole Three (3) Recommended Screw Locations 4A Mounting to Studs 4B Attach base to wall using 3 screws provided. The locations indicated provide the most secure mounting and are recommended. NOTE: Since moderate force is required when removing the control from the sub-base, the sub-base must be securely attached to the wall. Do not overtighten screws to avoid damaging the sub-base. Mounting to Drywall If mounting to drywall, supplied SnapSkru anchors must be used to mount the control sub-base to the wall. These anchors will ensure that the control is adequately supported. NOTE: Since moderate force is required when removing the control from the sub-base, a firmly mounted sub-base is essential. 1) Press tip of SnapSkru anchor into drywall using #2 Phillips screwdriver or screw gun. Drive anchor clockwise into drywall until anchor stops flush with wall. 2) Place sub-base over anchor and insert screw. 3) Tighten screw flush with subbase. Screw pops open anchor, locking anchor on wall. Do not overtighten screws to avoid damaging the sub-base HD64D1-3

7 Section 4. Wiring! WARNING LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.! CAUTION CAUTION: EQUIPMENT DAMAGE HAZARD - Improper wiring can lead to equipment damage. Follow the terminal connection information carefully to ensure the control is wired properly. After wires are secure, bare wires MUST NOT touch each other. See the Field Wiring Diagrams for specific system applications. NOTE: The maximum total cable length for the entire communicating system is 500 feet 18 AWG. The maximum distance of any single cable from a transformer is 250 feet 18 AWG. NOTE: Use 18-gauge color-coded thermostat cable for proper wiring. Shielded cable is not typically required. Keep this wiring at least one foot away from large inductive loads such as Electronic Air Cleaners, motors, line starters, lighting ballasts and large distribution panels. Failure to follow these wiring practices may introduce electrical interference (noise) which can cause erratic system operation. All unused thermostat wire to be grounded at indoor unit chassis ground only. Shielded cable may be required if the above wiring guidelines cannot be met. Ground only one end of the shield to the system chassis. 5 Power Connections The control is powered via 24 VAC from the indoor unit. On every application, 24VAC loads should be reviewed to be sure the indoor unit power transformer is adequately sized. The ComfortLink II control draws approximately 4VA more than the typical communicating control. 6 Connect Wiring Connect wiring to terminals as shown. Route wiring within the plastic channel as shown so that it does not interfere with control when reinstalling. Do not overlap wires. D R B Optional Connections Terminal Description RS Remote Sensor RS Remote Sensor ODT Outdoor Temperature Sensor ODT Outdoor Temperature Sensor Plug the opening with non-flammable insulation to prevent drafts from affecting the control. Control Connections Terminal Description D Data R 24 VAC (hot) B 24 VAC (common) 7 Replace Control Replace unit flat onto sub-base being careful to align unit correctly with the sub-base before applying force. Control should fit snug and not rock when properly installed. Check wire routing if control is unstable. 18-HD64D1-3 7

8 8 Field Wiring Communicating System Communicating Outdoor Unit Control Communicating Indoor Unit D R B Brown Red Blue D R BK Y1 Y2 G W1 W2 W3 B O Brown Blue Brown Blue Communicating Indoor with Non-Communicating Outdoor 24V Single Stage Cooling Control Communicating Indoor Unit D R B Brown Red Blue D R BK Y1 Y2 G W1 W2 W3 B O Yellow Blue Yellow Blue 24V System Control DRB Relay Panel *See Relay Panel Installer s Guide for specific wiring instructions. Indoor Unit D R B Brown Red Blue Relay Panel 24V Outdoor Unit 8 18-HD64D1-3

9 Section 5. Installer Setup 9 Power-Up Communicating Equipment Discovery mode begins when the control is first installed and power is connected. For communicating equipment, the control automatically configures standard equipment parameters. 24V Equipment (Using a Relay Panel) Equipment will need to be configured manually through the Installer s Setup menu in the control. See the following section for more details. 10 Basic Navigation The home screen displays default temperature settings and parameters. Pressing a button will display additional information or a new menu screen. Example (Air Cleaner Mode): Pressing the Air Cleaner Mode button on the home screen allows selection of options from a list. Help: Screens contain a Help button which provides additional information. Screens that are self-explanatory will not list additional help. Example (Menu): Pressing the Menu button on the home screen shows additional icons to adjust settings. Buttons shown will vary depending on system type and configuration. 18-HD64D1-3 9

10 11 Installer Setup Menu Enter the Installer s Setup screen by navigating to: Home screen --> Menu --> Service --> Technician Access* --> Proceed --> Installer Setup *NOTE: Press and hold the Technician Access button for 5 seconds to enter the Service Menu screen. NOTE: See Section 8 for a complete list of menus and parameters that can be set in the Installer Setup menus HD64D1-3

11 11A Installer Setup Menu - Standard Standard Pressing the Standard button allows manual selection and configuration of basic equipment components. NOTE: In a communicating system, components will be discovered automatically so this manual setup is not required. Example: The Standard screens allows selection of noncommunicating equipment. 11B Installer Setup Menu - Advanced Advanced Equipment settings may be adjusted to alter the default settings to fine-tune a system s operation. Installed accessories and comfort options may be configured in the Advanced screen. NOTE: Icons available in this menu will vary based on equipment configuration. Example: Press the Comfort button to enable or disable comfort settings such as dehumidification (at right). 18-HD64D1-3 11

12 11C Installer Setup Menu - Restore Equipment Defaults CAUTION: Restore Equipment Defaults returns the control to factory settings. ALL settings and data will be lost. 11D Installer Setup Menu - Reset Advanced Settings Reset Advanced Settings resets the Advanced Settings which were configured in the Installer Menu (settings such as system lockouts, accessories, air flow and comfort options). 12 Wireless Networking NOTE: See the control s User s Guide for wireless setup information HD64D1-3

13 Section 6. Advanced Features Feature 1-Touch Presets Aggressive Recovery Air Cleaner Mode Alert Indication Backlight Blower On / Off Delays Brightness Calibration Control Response Rate Customizable Home Screen Description The 1-Touch Presets allows for an immediate change to the setpoint status. Set the desired temperature for the three status modes (Home, Away & Sleep). The control will remain in the selected mode until another mode is selected or the program reaches a new schedule period. Aggressive Recovery: This option disables the 10 minute inhibit anytime the control sees more than a 2 change (such as moving from one program time frame to another). This applies to heating & cooling modes. Heating Aggressive Recovery: This option disables the 10 minute inhibit based on outdoor temperature in heating mode only. The value for outdoor temperature can be set from Heating Aggressive Recovery can only be enabled if Aggressive Recovery is disabled. There is a 10 minute inhibit period between first and second stage compressor as well as compressor heating & supplemental strip heat. This 10 minute inhibit period minimizes the cycling of higher capacity request due to drafts around the control or marginal load conditions. There are three options when setting the Air Cleaner Mode: Auto--the air cleaner will run whenever the blower is running. Quick Clean--the control will energize the air cleaner at 100% output and blower at 100% air flow for a 3-hour run cycle. Allergy Clean--the control will energize the air cleaner at 100% output and blower at 100% air flow for a 24-hour cycle. System alerts will be indicated on the home screen of the control with two options: Close or Dealer Contact Information. Selecting Dealer Contact Information will display the dealer screen. Selecting the Close option will move the alert to the top right corner of the home screen. Pressing the icon button in the top right corner of the screen will recall the alert to the home screen. All alerts will remain until resolved. Critical Alert indicates the loss of heating or cooling operation. Only critical alerts will be displayed on the home screen. These alerts will flash red when closed and moved to the top right corner of the control. Major Alerts indicates the loss of system functionality, but the system is still operational. Major alerts will be displayed as a solid yellow icon in the upper right corner of the control. The backlight of the control will increase anytime the screen is pressed (active mode) and dim after a time period of non-activity (standby mode). This timeout period between active mode and standby mode can be customized from 5 60 seconds. Blower on / off profiles can be set independently for heating and cooling modes. There are blower delays specific for variable speed, non variable speed and hydronic heat applications. The brightness of the screen can be customized for viewing preferences. Screen brightness can be set for daytime and nighttime modes. The Ambient Light Setting icon sets the amount of room light required to shift the display between daytime and nighttime settings. The sensors (indoor, remote and outdoor) can be individually calibrated for temperature and humidity. The indoor sensors may be calibrated to plus or minus 5 or 5% humidity in increments of 1. The outdoor sensor may be calibrated to plus or minus 10 in 1 increments. This feature changes the response rate of the control. Selecting a faster response rate will maintain a tighter tolerance of indoor temperatures, but increases the cycling of the system. Options such as screen brightness, screen savers, background colors, screen calibration and customized shortcuts can all be modified to create a personalized home screen. 18-HD64D1-3 13

14 Feature Cycle Rate Dealer Information Dehumidification Diagnostics Dual Fuel Options Emergency Heat Equipment List Fan Options Help Screens History Runtime Description The cycle rate affects the cycle time of the system. With a 50% load value, a cycle rate of 3 will allow the system to run for 10 minutes and be off for 10 minutes; completing 3 cycles in one hour. A cycle rate of 5 would allow the system to cycle on and off at 6 minute intervals. The higher the cycle rate, the more often the system turns on and off. The actual amount of time the system will be on or off will be reflective in the load value of the home. Higher load value demands will increase system run time and decrease system off time. Lower load value demands will decrease system run time and increase system off time. Dealer contact information, including name, address, website and multiple phone numbers may be entered. In addition, a dealer logo (which must be named dealer.jpg) can be uploaded through the use of an SD card. File size should not exceed 3 MB. There are two requirements before dehumidification is enabled: Dehumidification must be enabled through the Installer Setup. The indoor relative humidity must be above the desired setpoint. The system will take the following actions once this condition is met: The blower will reduce air flow proportional to the amount of RH error. The control evaluates the percentage of humidity error and how long the error has existed to determine the amount of air flow reduction, up to 30% reduction. If overcooling is enabled, the control will engage a 1 degree of overcooling for each 10% of RH error. A maximum amount of overcooling can be configured to 1, 2 or 3 degrees. Fan off delays will be eliminated. Smart Continuous Fan Continuous fan operation will be interrupted when indoor relative humidity exceeds desired humidity setpoint. A humidity icon will be displayed along with the fan icon to indicate that blower on options have been disabled due to high humidity conditions. Smart Continuous Fan will not interrupt the fan circulate mode. Diagnostics are displayed as current alerts (what is currently happening in the system) and alert history (what has occurred in the past, but are no longer present). The alert screen describes the alert, when the alert happened, the severity level of the alert as well as a problem description and possible causes to assist with troubleshooting. Up to the last 30 days are displayed. The change over from heat pump to furnace can be set based on three options: Comfort This is strictly based on indoor temperature demand. The furnace will take over when the heat pump can no longer maintain the indoor heating demand. Operating Cost The HSPF of the heat pump and AFUE of the furnace must be entered along with cost of electricity and fuel. The control calculates an economic balance point for system change over. Outdoor Temperature The changeover from heat pump to furnace is based on outdoor temperature which can be set from 0 70 (thermal balance point). The furnace will take over anytime the HP is unable to maintain indoor temperature, regardless of the dual fuel option chosen. The heat pump will be disabled and the furnace / heat strips are enabled any time the control is set to Emergency Heat. This lists the model and serial number for all communicating components. The model and serial numbers for non communicating components can be manually entered. There are three options available for blower operation: Auto the blower runs when there is a call for cooling or heating. On the blower will run continually with a fan only call. The continuous fan speed for variable speed motors can be adjusted from 35% 100%. A call for heating or cooling will supersede a fan only call and the blower will run at a speed that matches the staging of the equipment. Circulate this provides all the features of fan on, but the blower will only run a percentage of the time when there is no call for heating or cooling. The blower can be set to circulate from minutes of every hour. The bottom left corner of all screens has a Help icon with a question mark. This icon provides assistance for the screen that is currently being displayed. Screens that are self explanatory will not list additional help. Pressing the Help icon on these screens will display No additional help available. The History Runtime screen provides information on system run time in comparison to the indoor and outdoor temperatures (average indoor along with the high & low outdoor temps). This history can be displayed on a weekly or monthly basis HD64D1-3

15 Feature History Screen Humidification Installer Setup Load Value Lockouts Multi Systems Photo Album Reminder Screens Restore Runtime History Description The History Screen provides system cycle information. Cycle counts and run time can be viewed for first stage and second stage compressor operation, W1 & W2 heating and defrost cycles. This information can be viewed in a 24 hour, 1 week or 2 week period. There are two options available for humidification: Indoor RH setpoint this controls the humidifier based on the desired indoor humidity setpoint (options from 10% 45%). Frost Control setpoint--the control references the outdoor temperature and indoor environment to calculate the risk of frost or condensation on interior walls and windows. A scale of 0 to 10 allows for customized settings based on the insulation properties of the home. A higher number may be selected for well insulated homes, whereas a lower number should be selected on poorly insulated homes. A lower number should be utilized if condensation is observed. There are two control options for enabling humidification: Humidification with an active call for heat. Humidification without an active call for heat (control energizes blower and humidifier). Humidification is only available when in the heating mode (or in the auto mode when the last call was for heating). A 60 second minimum blower off delay is enforced if steam humidification is selected. There are two categories for Installer Setup. Standard this is the basic system settings such as heat pump or cooling only, single or multi stage, compressor type, etc. This is the basic system set up that is self discovered in communicating mode, but requires manual input when using a Relay Panel for 24 volt configurations. Advanced this provides advanced configuration of the system such as cycles per hour, minimum run times, humidification and dehumidification setpoints, blower delays and temperature lockouts to name a few of the customizable features in this set up. Load Value is a numerical representation of the needed capacity to satisfy the setpoint. Proportional (distance from setpoint) error plus integral (time away from setpoint) error is used to calculate load value. System lockouts will disable a certain function of the system under specific outdoor temperatures: Compressor Heating Lockout will lockout all compressor operation below a set outdoor temperature (from 5 70 ). This value must be set lower than the auxiliary heat lockout. Auxiliary Heating Lockout will lock out auxiliary heat stages above a set outdoor temperature (from ). This value must be set higher than the compressor heating lockout. Defrost Heater Balance Point for W1, W2 & W3 will lock out specific auxiliary heat stages when above a set outdoor temperature. (W1 setpoint is from 40 55, W2 & W3 setpoints are from 5 55 ). This feature does not apply to dual fuel systems. Compressor Cooling First Stage Lockout will lock out the first stage compressor above a set outdoor temperature. (from ) Compressor Heating First Stage Lockout will lock out the first stage compressor below a set outdoor temperature. (from 0 50 ) Furnace First Stage Heating Lockout will lock out first stage furnace operation below a set outdoor temperature. (from ) First stage lockouts are not available with zoning. Multiple controls that manage individual systems can be linked. Multiple systems can be managed from any control location. A wireless home network is required for multi system functionality. Allows the customization of a photo album screen saver. An SD card is required to view the pictures. Photos may be in.jpg,.jpeg,.bmp,.png, or.gif file formats and must be smaller than 3 MB each. Reminders can be set for filters, UV lamps, humidifier pads, and various other service reminders. There are three levels of restore: Restore from the Setting Screen this restores all personal configurations, such as program schedules and home screen customization to their default setting. Reset Advanced Options from the Install Set Up screen this restores all the advanced set up selections such as system lockouts, accessories, air flow and comfort options to their default setting. Restore Equipment Default this restores the control to its out of the box condition. All settings will be set to their factory default condition. The History Runtime screen provides information on system run time in comparison to the indoor and outdoor temperatures (average indoor along with the high & low outdoor temps). This history is displayed on a weekly or monthly basis. 18-HD64D1-3 15

16 Feature Scheduling Screen Cleaning Mode Screen Layout SD Card Logging Security Setpoint Dead Band Software Updates Stage Inhibit System Report System Status System Test Technician Access Screens Vacation Mode Warm Air Discharge Weather Description Allows for 7 day programming with one to six scheduled time periods per day. There are two options available for setting a schedule: Guided Setup a step by step interactive process for setting up a schedule. Manual Setup a direct modification to an existing schedule which skips the interactive set up wizard from the guided set up. Scheduling is not required. The control can operate as a non programmable control. The Clean Screen Mode creates a 30 second screen lockout. The screen can be touched and cleaned without changing settings. There is an icon Press and Hold to Exit which will exit this mode if necessary--eliminating the 30 second lock out. The Screen Layout icon allows for customization of what is displayed on the home screen. The control has the ability to log all information to a SD Card. A typical 24 hour log will consist of 12 to 20 megabytes of information. The control will overwrite the oldest data once the card becomes full. Security initiates a keypad lockout. The control can only be accessed by a four digit pass code which can be configured in two different formats: Pin Lock: When the Pin Lock is selected, the control is completely locked. The user will need to enter a four digit password to change any setting (the default is 1234 ). Guest mode: The enabling of this mode allows a guest to change the temperature up to 5 in either direction from setpoint and access to the weather, but cannot change the mode or any customized settings. This sets the temperature band between heating and cooling setpoints while in the auto mode. The control is field software upgradable. Insert a SD card and press the Software Update icon, and updates will begin automatically. To prevent the next stage of capacity from being initialized, when the current capacity stage will satisfy the load a stage inhibit function is utilized. The System Report Screen provides a real time in depth look at operating conditions. While similar to the System Status screen, the system report adds additional information for service technicians. The System Status screen shows the snapshot of what the system is doing; including system mode, air flow percentage and reminders. The System Test feature allows a technician to lock the system into a particular mode of operation for up to 30 minutes. The Technician Access icon has a 5 second hold delay to enter the technician service screens. After this 5 second hold delay, the technician will see a Caution! screen noting that only a trained HVAC technician should proceed into this area. Through an interactive calendar, pick the date, time and temperature to begin and end a vacation set back period. Enabling Warm Air Discharge will reduce the variable speed blower air flow by 20% when in compressor heating operation. Warm air discharge only applies to compressor heating and is disabled when hydronic, fossil fuel or electrical heat (including supplement heat) modes are activated. The Weather feature displays the outdoor temperature, 5-day forecast and local Doppler radar. The weather screen is available once Wireless Service to the internet and Remote Services are enabled HD64D1-3

17 Section 7. Troubleshooting Symptom Possible Causes Action Control displays an alert code on the screen. Alert Code is present. Refer to the Alert Code Addendum. Check the Alert icons in the diagnostic screen. Display will not come on Loss of 24VAC between R & B at the control. 1) Check wiring between R & B to see if R & D, or B & D have been reversed. 2) Check transformer for 24VAC output. 3) Check for broken or shorted thermostat wire. Indoor temperature display is incorrect. Indoor humidity display is incorrect. Room temperature overshoots when the Heat/Cool setting is changed more than 2. Heating will not come on. Cooling will not come on. Heating or Cooling is displayed, but no warm or cool air is coming from the registers. Fan runs all the time Fan is set to ON but not running. Cooling or Heating cycles too fast or too slow (narrow or wide temperature swings). Heat pump is not turning on; only furnace or electric heat strips are running. Cannot change system mode to desired setting. Screen does not respond properly to a button press No System Found displayed on the control Slow or no response to any button presses Indoor temperature display needs calibration. Indoor humidity display needs calibration. 1) Oversized heating/cooling equipment under current conditions. Control cannot respond fast enough to prevent overshooting. 2) Improper location of control. 3) Aggressive recovery is activated. 1) System mode is not set to Heat/Auto or setpoint is set too low. 2) Minimum off time delay is being enforced. 3) Heating system may require service. 1) System mode is not set to Cool/Auto or the setpoint is too high. 2) Minimum off time delay is being enforced. 3) Cooling system may require service. 1) There is a fan delay as the heating or cooling equipment turns on. 2) Equipment is not working properly. 1) Fan mode is set to On, Circulate or Clean mode 2) There is a failure in the indoor unit 1) Humidity control is engaged. 2) Blower motor is not functioning. 1) Check the location of the control for drafts. 2) Cycles per hour or aggressive recovery is improperly set. 1) Outdoor temperature is below compressor lockout temperature setting. 2) Compressor heating lockout is enabled and outdoor temp sensor is out of calibration or failed. Equipment is not configured properly. Screen is out of calibration Internal error Internal error Calibrate temperature sensor from control menu. Calibrate humidity sensor from the control menu. 1) Compare heat load calculation to equipment chosen. 2) Relocate control (or use remote sensor) if control is in dead spot (poor or no air circulation). 3) Deactivate aggressive recovery. 1) Set mode to heat and raise the setpoint above the room temperature. 2) Wait for 5 minutes and recheck heating equipment. 3) Check/repair system. 1) Set mode to cool and lower the setpoint below the room temperature. 2) Wait for 5 minutes and recheck cooling equipment. 3) Check/repair system. 1) Wait a minute for blower delays and recheck registers. 2) Check/repair system. 1) Check control settings to see if fan is set to On, Circulate or Clean mode. 2) Check indoor unit for failures (such as tripped heating limit). 1) If indoor humidity is higher than desired setpoint, the blower will cycle off with the equipment. 2) Check/repair system. 1) Seal all air leaks behind control. Relocate control or apply remote indoor temperature sensor. 2) Adjust cycle rates and aggressive recovery features in the advanced installer set up. 1) Adjust the compressor lockout temperature setting if desired. 2) Check/repair outdoor sensor or wiring. Check the standard installer set up screen to ensure equipment is properly configured. Remove control from sub base and reset. Follow the calibration instructions when the control reboots. Reboot the control via onscreen button. Remove the control from the sub base and reset. 18-HD64D1-3 17

18 Section 8. Installer Setup Parameters* *Each Bold heading below corresponds to a menu in the Installer Setup. All possible options are shown for the menu and each submenu. Selections shown in any particular system will be dependent on system type and configuration. Standard Outdoor Unit Type None Cooling Only Heat Pump Outdoor Unit Stages 1 2 Compressor Type Single Compressor Two Stage Two Compressor Two Stage Indoor Unit Type Electric Gas/Oil Hydronic Indoor Unit Heat Stages None Modulating Indoor Unit Blower Type Variable Speed Non Variable Speed Advanced Equipment Compressor Cooling Cycles Per Hour st Stage Compressor Heating Cycles Per Hour nd Stage Compressor Heating Cycles Per Hour Compressor Heating Cycles Per Hour st Stage Compressor Cooling Cycles Per Hour nd Stage Compressor Cooling Cycles Per Hour Compressor Minimum On Time - Minutes 3 1st Stage Compressor Minimum On Time - Minutes 3 2nd Stage Compressor Minimum On Time - Minutes 3 Indoor Heater Cycles Per Hour st Stage Indoor Heater Cycles Per Hour nd Stage Indoor Heater Cycles Per Hour rd Stage Indoor Heater Cycles Per Hour Indoor Heater Minimum On Time - Minutes 1 1st Stage Indoor Heater Minimum On Time - Minutes 1 2nd Stage Indoor Heater Minimum On Time - Minutes 1 3rd Stage Indoor Heater Minimum On Time - Minutes 1 Sensors Select Outdoor Temperature Sensor Calibrate Outdoor Temperature Sensor - Degrees Calibrate Indoor Temperature Sensor - Degrees Calibrate RH sensor None +/- 5 increments Zone x +/- 5 increments Zone x +/- 5 increments Sensor Wired to Control CLII/ AccuLink Outdoor Sensor Sensor Wired to Relay Panel Accessories Filtration Type Installed Comm Air Cleaner Discovered Air Cleaner Number of Air Cleaners Installed 1 2 Humidifier Installed Yes No Humidifier Type Steam Bypass/Powered Humidifier Control RH Control Frost Control Humidifier Control Option Humidify with Humidify without Active Heat Call Active Heat Call UV Light Installed None Yes ERV Installed None Yes Media Filter Comfort Enable Dehumidification Disable Enable Dehumidification Overcooling Limit - Degrees Control Response Rate Normal Fast Aggressive Recovery > 2 Setpoint Change Disable Enable Heating Aggressive Recovery Disable Heating Aggressive Recovery - Outdoor Temperature 0 to HD64D1-3

19 Warm Air Discharge Disable Enable Airflow VS Blower On Delay - Cooling VS Blower Off Delay - Cooling VS Blower On Delay - Compressor Heating VS Blower Off Delay - Compressor Heating No Delay 1 50%, % 1 50%, 4 80% % 4 80% 1 50% 30 35% No Delay % % 30 50% % 3 50% 30 35% No Delay 1 50%, % 1 50%, 4 80% % 4 80% 1 50% 30 35% No Delay % % 30 50% % 3 50% 30 35% Non VS Blower On Delay - Cooling (Seconds) No Delay Non VS Blower Off Delay - Cooling No Delay Non VS Blower On Delay - Compressor Heating No Delay Non VS Blower Off Delay - Compressor Heating No Delay Hydronic Heat Blower On Delay No Delay Hydronic Heat Blower Off Delay No Delay Compressor Low Stage Air Flow % - Cooling Compressor Low Stage Air Flow % - Compressor Heating Lockouts Compressor Heating Lockout Disable Enable Compressor Lockout - Outdoor Temperature 5-70 Auxiliary Heat Lockout Disable Enable Auxiliary Heat Lockout - Outdoor Temperature Defrost Heater Balance Point (W1) Disable Enable Defrost Heater Balance Point (W1) - Outdoor Temperature Defrost Heater Balance Point (W2) Disable Enable Defrost Heater Balance Point (W2) - Outdoor Temperature 5-55 Defrost Heater Balance Point (W3) Disable Enable Defrost Heater Balance Point (W3) - Outdoor Temperature 5-55 Compressor Cooling 1st Stage Lockout Disable Enable Compressor Cooling 1st Stage Lockout - Outdoor Temperature Compressor Heating 1st Stage Lockout Disable Enable Compressor Heating 1st Stage Lockout - Outdoor Temperature 0-50 Furnace Heating 1st Stage Lockout Disable Enable Furnace Heating 1st Stage Lockout - Outdoor Temperature HD64D1-3 19

20 6200 Troup Highway Tyler, TX Trane The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. Representative-only illustrations included in this document.

COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP

COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP ALL phases of this installation must comply with NATIONAL, STATE, AND LOCAL CODES INSTALLER S

More information

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

Installation Instructions

Installation Instructions TP-PRH-A, TP-NRH-A Performance Series Edge Thermidistat Control Installation Instructions Programmable Control A07049 A07048 Non Programmable Control Designed and Assembled in the USA. NOTE: Read the entire

More information

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:

More information

HEAT PUMP PROGRAMMABLE THERMOSTAT

HEAT PUMP PROGRAMMABLE THERMOSTAT HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15

More information

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage

More information

QUICK INSTALLATION GUIDE

QUICK INSTALLATION GUIDE QUICK INSTALLATION GUIDE Read Installer Notes before removing cover from Thermostat. 1F85RF-275 Wireless Remote Kit INSTALLER NOTES IMPORTANT Do not apply power to the thermostat or wireless sensor until

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work. Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

How To Control A Thermostat

How To Control A Thermostat CONTENTS Installation Instructions for Heating & Air Conditioning 1F72 5/2 Day Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

Install Guide CT101. Caution. Caution

Install Guide CT101. Caution. Caution Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

INSTALLER S & OWNER S MANUAL

INSTALLER S & OWNER S MANUAL INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

Install Guide 3M-50. Caution. Caution

Install Guide 3M-50. Caution. Caution PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.

More information

Communicating Wall Control Installation Manual TSTAT0101SC

Communicating Wall Control Installation Manual TSTAT0101SC Communicating Wall Control Installation Manual TSTAT0101SC U.S. Patent No. 7,243,004 U.S. Patent No. 7,775,452 616 01 1017 02 08/07/12 Safety Considerations... 7 Introduction... 8 Quick Start... 9 Set

More information

1F82-0261 5/1/1 Day Programmable. 1F82-0261 Thermostat Thermostat Configuration Options Heat Pump. Maximum Stages Heat/Cool 2/1

1F82-0261 5/1/1 Day Programmable. 1F82-0261 Thermostat Thermostat Configuration Options Heat Pump. Maximum Stages Heat/Cool 2/1 Blue 2 Heat Pump Thermostat Heat Pump Installation and Operating Instructions Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Conserve package Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Gateway Can I have someone install my system for me? If you are concerned

More information

1F82-261 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

1F82-261 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION ELECTRICAL DATA Electrical Rating: 20 to

More information

Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat

Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat MOUNTING LOCATIONS Refer to the guidelines below and Fig. 1 5 for mounting locations of the Discharge and Return Air Temperature Sensors.

More information

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

Installation Questions

Installation Questions Installation Questions How do I determine what type of heat I have? There may be several ways to determine what type of heat you have. First, if you can access the unit that is responsible for creating

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved.

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved. Sensi TM Wi-Fi Programmable Thermostat MANUAL OPERATION Version: March 2016 2016 Emerson Electric Co. All rights reserved. Contents MANUAL OPERATION GUIDE Buttons and Icons 3 Basic Functionality 4 Manual

More information

User Guide ecobee3. 2014 ecobee 250 University Ave Suite 400 Toronto Ontario M5H 3E5 Canada Toll free 1.877.932.6233 www.ecobee.

User Guide ecobee3. 2014 ecobee 250 University Ave Suite 400 Toronto Ontario M5H 3E5 Canada Toll free 1.877.932.6233 www.ecobee. User Guide ecobee3 2014 ecobee 250 University Ave Suite 400 Toronto Ontario M5H 3E5 Canada Toll free 1.877.932.6233 www.ecobee.com e3-ug-r001 1 Table of Contents Overview... 4 Getting Help... 4 Touch Screen...

More information

INSTALLER S SYSTEM SETUP GUIDE

INSTALLER S SYSTEM SETUP GUIDE 2009 Lennox Industries Inc. Dallas, Texas, USA INSTALLER S SYSTEM SETUP GUIDE icomfort Thermostat Touch Screen Programmable Communicating Thermostat CONTROLS 506052 01 11/09 Litho U.S.A. Shipping and Packing

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

CONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014

CONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014 2014 Lennox Industries Inc. Dallas, Texas, USA CONTROLS KITS AND ACCESSORIES 507240-01 12/2014 Supersedes10/2014 Litho U.S.A. Equipment Interface Module Installation Instructions for the Equipment Interface

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

Heating and Cooling Basics Thermostat Control

Heating and Cooling Basics Thermostat Control Heating and Cooling Basics Thermostat Control UNI-LINE PRODUCT KNOWLEDGE 2012 Invensys. All Rights Reserved. The names, logos, and taglines identifying the products and services of Invensys are proprietary

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount

More information

RedLINK Wireless Comfort Systems. RedLINK Connects.

RedLINK Wireless Comfort Systems. RedLINK Connects. RedLINK Wireless Comfort Systems RedLINK Connects. TM THERMOSTATS ZONING AIR CLEANERS HUMIDIFIERS DEHUMIDIFIERS UV SYSTEMS VENTILATION WATER SOLUTIONS wireless TM Your Customers Are Connected. Wireless.

More information

Wireless Alarm System. Panic Button. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location

Wireless Alarm System. Panic Button. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location Wireless Alarm System Panic Button User s Manual Choice ALERT Control all sensors, accessories and remote transmitters from one location Table of Contents Important Safeguards 4 Introduction 5 Activating

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

1 For All Non-Programmable Digital Thermostat

1 For All Non-Programmable Digital Thermostat OWNER'S MANUAL P/N P474-0100 1 For All Non-Programmable Digital Thermostat TOTALINE 68 Dual Setpoint Very easy to program Thermoglow Backlight No batteries required Auto-Changeover Locking Keypad Meets

More information

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump. EHYHBH05AA EHYHBH08AA EHYHBX08AA English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation...

More information

1-877-654-9394. UP400 Programmable Thermostat Installation Instructions & User Guide. For Installation Help. White-Rodgers.com

1-877-654-9394. UP400 Programmable Thermostat Installation Instructions & User Guide. For Installation Help. White-Rodgers.com UP400 Programmable Thermostat Installation Instructions & User Guide For Installation Help 1-877-654-9394 White-Rodgers.com 2011 Printed in China White-Rodgers 8100 West Florissant Avenue St. Louis, MO

More information

Wireless and Prestige Comfort Systems. Frequently Asked Questions Guide

Wireless and Prestige Comfort Systems. Frequently Asked Questions Guide Wireless and Prestige Comfort Systems Frequently sked uestions Guide TM RedLINK Wireless Technology TM The Description What is RedLINK? RedLINK is the first wireless protocol developed specifically for

More information

Installation Instructions

Installation Instructions Installation Instructions Model TSTATG2111 Use with most systems: 2-Heat, 1-ool 1- Day Prog ram m ab l e Digital Thermostat u p t o 2 - H e a t & 1 - o o l ontrol up to 2 Heat & 1 ool Stages Backlit Display

More information

ACONT900AC43UA Communicating, Programmable Comfort Control

ACONT900AC43UA Communicating, Programmable Comfort Control ACONT900AC43UA Communicating, Programmable Comfort Control OWNER S GUIDE Pub No. 69-1820-04 TABLE OF CONTENTS Page Contents 3 Features 4 Home Screen 6 Programming Your Heating and Cooling Schedule 14 Operating

More information

Installation Instructions

Installation Instructions TP --- PAC, TP --- PHP TP --- NAC, TP --- NHP Performance Series AC / HP Thermostat Installation Instructions A07049 Programmable Control A07048 Non-Programmable Control Designed and Assembled in the U.S.A.

More information

User Manual THR840DUK Digital Thermostat

User Manual THR840DUK Digital Thermostat User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical

More information

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ELECTRIC POSITION for electric heat, then confirm with Fan Test below. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

ST815 Illumination Sensor with LCD

ST815 Illumination Sensor with LCD ST815 Illumination Sensor with LCD The Illumination Sensor with LCD (refer to as Illumination Sensor hereafter) is a Z-Wave TM enabled device which is fully compatible with any Z-Wave TM enabled network.

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

Installation Guide. Programmable Thermostat TH6220D

Installation Guide. Programmable Thermostat TH6220D Installation Guide Programmable Thermostat TH6220D Product Application This thermostat provides electronic control of 24 VAC single-stage and multi-stage heating and cooling systems, or 750 mv heating

More information

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING Installer s Guide 18-GJ11D1-2 : Models: BAYUVCLK001-40 Watt, 2 Lamp NOTE: A BAYCC24VK01 can be installed for Series 8 Air Handlers to extend the life of the lamp. This accessory kit will disable the lamp

More information

Simon XT/XTi CDMA Module V4 Installation Instructions

Simon XT/XTi CDMA Module V4 Installation Instructions Simon XT/XTi CDMA Module V4 Installation Instructions Content Contact information... 1 Introduction... 1 Compatibility... 1 Account Creation... 1 Installation... 1 Power Up... 3 CDMA Phone Test (Module

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

WHITE-RODGERS COMFORT-SET 90 SERIES

WHITE-RODGERS COMFORT-SET 90 SERIES INSTALLATI DESCRIPTI WHITE-RODGERS COMFORT-SET 90 SERIES MULTI-STAGE INSTALLATI/CFIGURATI This White-Rodgers Automatic Setback Digital Thermostat uses microcomputer technology to provide precise time and

More information

Home Monitoring and Control service provided by Verizon Online LLC

Home Monitoring and Control service provided by Verizon Online LLC Home Monitoring and Control service provided by Verizon Online LLC A separate subscription to Verizon FiOS TV is required for use with FiOS TV service. About This Manual This manual is designed for online

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

G-100/200 Operation & Installation

G-100/200 Operation & Installation G-100/200 Operation & Installation 2 Contents 7 Installation 15 Getting Started 16 GPS Mode Setup 18 Wheel Sensor Mode Setup 20 Fuel Calibration 23 Basic Operation 24 Telemetery Screen 27 Entering a Distance

More information

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 English Table of Contents Table of Contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview:

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

Nest Learning Thermostat Pro installation & configuration guide

Nest Learning Thermostat Pro installation & configuration guide Nest Learning Thermostat Pro installation & configuration guide Need help? Help online: http://support.nest.com/certified Nest Certified Professional support: 1-855-VIP-NEST (1-855-847-6378) Hours: 5am-9pm

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

Safety & Installation Instructions

Safety & Installation Instructions Home omfort ontrol Model 8910 READ AND SAVE THESE INSTRUTIS Safety & Installation Instructions Table of contents Installation Thermostat installation location recommendations.. 2 Thermostat mounting...

More information

Installer Guide smart connect

Installer Guide smart connect Installer Guide smart connect TM 7330 Wireless Remote Humidity Sensor Please read all instructions before proceeding. The wireless remote humidity sensor monitors the humidity passing through the return

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

Single Zone LCD Thermostat Operating Instructions

Single Zone LCD Thermostat Operating Instructions Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared

More information

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Powers Controls TH 192 HC Heating/Cooling Room Thermostat Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional

More information

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control T Series arge CD Digital Thermostat 0/0 VAC -pipe/-pipe fan coil control Data sheet Application T digital thermostats are designed for application of -speed fan and s in fan coil system. Including: -pipe

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS INSTALLATION MANUAL Before you begin the installation Read the INSTRUCTIONS! Always use a multi-meter when verifying vehicle wiring. Before mounting the

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

NOTE: Append this Operation IB to the Install IB to make one IB-booklet. Need a divider tab between the 2 sections. Blank page remove.

NOTE: Append this Operation IB to the Install IB to make one IB-booklet. Need a divider tab between the 2 sections. Blank page remove. Product Name: CT101 Document Title: CT101 Operation Guide Document Type Code: IBOE Part Number: 1202-004-002 20apr12 Iris inclusion text added mtf 9apr12 bs edits mtf 14mar12 ch edits mtf 13mar12 initial

More information

VisionPRO 8000 with RedLINK

VisionPRO 8000 with RedLINK VisionPRO 8000 with RedLINK PRODUCT DATA Customizable Service Reminders Set up to 10 service reminders. Choose from the pre-set options or customize your own. Reminders can be based on date or the outdoor

More information

YOUR THERMOSTAT REPLACES Assemble tools required as shown below. HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED

YOUR THERMOSTAT REPLACES Assemble tools required as shown below. HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED 1F85-275 Heating & Air Conditioning 5-1-1 Programmable/Non-programmable, Auto Changeover, Multi-Stage/Heat Pump Thermostat INSTALLATION INSTRUCTIONS Operator tor: Save these instructions for future use!

More information

DUCT TYPE AIR CONDITIONER

DUCT TYPE AIR CONDITIONER OPERATING MANUAL OPERATING MANUAL BEDIENUNGSANLEITUNG MODE D EMPLOI MANUAL DE FUNCIONAMIENTO MANUALE DI ISTRUZIONI ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ MANUAL DE INSTRUÇÕES AIR CONDITIONER DUCT TYPE English Deutsch

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation

More information

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump. English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation... 3 3.2 The user interface

More information

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to

More information

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered

More information

SMM. Installation Operation Maintenance

SMM. Installation Operation Maintenance SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,

More information

Mode Switch. Fan Switch Menu button Program button

Mode Switch. Fan Switch Menu button Program button Operation 3M-30 Day Time of day Target Temperature Time Slot Touch Screen Current Room Temperature Thermostat Mode Statement of use: The 3M-30 can be used with millivolt, 24VAC, single and 2 stage conventional

More information

Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable

Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10 Programmable thermostat Thermostat programmable Termostato programable Read and save these instructions. Veuillez lire le mode d

More information

LG Wireless Remote Controller

LG Wireless Remote Controller Visit us at : http://www.lgservice.com LG Wireless Remote Controller Owner's & Installation Manual Models: PQWRHSF0 PQWRCSF0 LG ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH IMPORTANT Please read this installation

More information

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com

More information

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY RV Products Division SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY Airxcel, Inc. RV Products Division P.O. Box 4020 Wichita, KS 67204 1976A376 (1-11) TABLE OF CONTENTS

More information

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

ECO-AIR AIR CONDITIONING www.northamericanhvac.com

ECO-AIR AIR CONDITIONING www.northamericanhvac.com INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...

More information

REMOTE CONTROL MANUAL

REMOTE CONTROL MANUAL REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read

More information

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses? The Only GUY To Call May 2014 412.885.2356 Why are my utility bills so high? What can I do to lower my energy expenses? Did you know... that between 2007 and 2012, the average U.S. household spent more

More information

Recommended Tools and Supplies: Small Flat Blade Screwdriver, 35mm x 7.5mm DIN Rail. Qwik Install

Recommended Tools and Supplies: Small Flat Blade Screwdriver, 35mm x 7.5mm DIN Rail. Qwik Install TPDIN-Monitor-WEB Web Based Monitor and Control Remote Power Stations Backup Power Systems Solar Systems Wind Powered Systems Industrial Sense & Control Process Automation Congratulations! on your purchase

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

Help. Help Software Tutorial. Building a load sizing project with an ME Series Humidifier

Help. Help Software Tutorial. Building a load sizing project with an ME Series Humidifier Help Help Software Tutorial Building a load sizing project with an ME Series Humidifier 502-B 18 Aug 2015 Help Tutorials provide step-by-step examples of complete load sizing projects and browser projects

More information