1 Data Centre Solutions...energy efficient by design Case Study University of Aberdeen University of Aberdeen s Multi-Award Winning Low Carbon Shared Services Data Centre Facility Designed & Built by Workspace Technology
2 University of Aberdeen Creates Low Carbon Shared Services Data Centre Facility. Founded in 1495 the University of Aberdeen is at the forefront of teaching, learning and discovery. As one of the UK s most prestigious University s it has consistently produced graduates of exceptional capability. The University of Aberdeen is an ambitious, research-driven university with a global outlook and is committed to excellence in everything it does. Client Situation As part of a joint venture between the University of Aberdeen, Aberdeen College, Robert Gordon University and Banff and Buchan College it was agreed to create a Shared Services data centre facility. The existing data centre located at the Edward Wright Building on the University of Aberdeen s campus was the preferred location. This data centre was approximately 23 years old supporting the University s core ICT services. This facility had enough space for the combined rack count but was out dated and lacked the required power, cooling capacity, defined installation standards, subject to adhoc growth and suffered from a PUE of 2.6. An open prequalification was published in 2011 and following successful shortlisting Workspace Technology was invited to tender in late 2011/ The project was complex and involved renovation of the Edward Wright facility whilst maintaining essential computing services for the University across a full academic year. 1
3 Mixing Box Arrangement Filtration Wall Industry Leading Energy Performance Freecool Evaporative Free Air Cooling by Workspace Technology was deployed as the primary cooling technology for the University. Freecool is the industry leading Evaporative Free Air Cooling designed to deliver PUE performance figures of less than The solution was designed to support a maximum critical load of 420kW N+1 with an initial deployment of eleven Freecool units supporting a day one cooling capacity of 300kW N+1. The solution was carefully designed to maximise energy efficiency for the University. Workspace Technology s Freecool solution offers essential features that differentiate the technology from other direct fresh air based systems. Dual Filtration The solution has been implemented with a combination of G3 and G4 air intake filtration systems designed to eliminate potential data centre contamination. A simple filter wall reduces time to replace filters during quarterly service visits. Atemperation Workspace Technology implemented its intelligent atemperation system for the University which accurately mixes a percentage of hot exit air with cold intake air to produce a stable equipment intake temperature irrespective of external ambient conditions. This is achieved through a series of air dampers and variable speed low energy fans mounted within a customized mixing box and controlled via a Schneider Electric Crouzet PLC control system. Dynamic Mode Temperature Control Unlike conventional cooling systems that typically require equipment intake temperatures to be increased to support free cool mode, Workspace Technology s Freecool system can be configured in Dynamic mode. This mode of operation allows cold aisle temperatures of 18 C for the vast majority of the operating period without any compromise in energy efficiency. By reducing equipment inlet air temperature power demands of server fans will reduce whilst improving equipment reliability*. During warmer external ambient conditions the Freecool system simply allows the temperature to gradually rise falling back again as external temperatures reduce. *Results will depend on equipment age and type of fan. In Dynamic Mode the Freecool control system can also be programmed to gradually (within the rate of change parameters defined by ASHREA) ramp up / down temperature to ensure humidity levels are maintained within class A1 data centre operating modes (10% to 80% RH). 2
4 Fan Power With the exception of the PLC controller the only power consumed by the Freecool system is fan power. Workspace Technology carefully selected energy efficiency EC Blue fans manufactured by EDM Papst for the University. EC Blue fans use significantly less energy than conventional fan technology. EC stands for Electronically Commutated where the fan is fitted with a permanent magnet motor (PMM). EC technology enables continuous adjustment of the fan speed to the meet the cooling demands of the University s data centre. Each fan is individually speed controlled via the Freecool PLC control system. Freecool fan selections for the University are oversized and support N+1 resilience. This approach ensures that fan speeds are automatically reduced. Because motor power associated with EC fans varies with the cube of the motor speed any reduction in fan speed results in an energy savings. For example a 20% reduction in fan speed results in 49 % energy savings. This approach has been undertaken by Workspace Technology expert data centre design team for the University. Benefits over EC Fans over Traditional Fan Technology: Reduced Energy Consumption Significant noise reduction Intelligent electronic control No need for additional motor protection Remote monitoring via ModBus 3
5 FlexAisle Vendor Neutral Aisle Containment As part of the managed airflow architecture and to help maximise temperature control and minimise fan energy Workspace Technology deployed FlexAisle its multivendor aisle containment system as part of the data centre solution. A combined cold and hot aisle return plenum HARP was deployed for the University. The complete arrangement was self-supporting allowing the simple installation and removal of equipment racks without the need to dismantle aisle containment systems. 4
6 Schneider Electric Integration Partner Workspace Technology designed and implemented a Tier II electrical installation for the University. Electrical Design Workspace Technology s in house data centre design team used AMTECH ProDesign electrical design package as part of the pre installation design process to ensure appropriate cable sizes, discrimination, breaker ratings and settings were implemented for the University. By using AMTECH ProDesign, Workspace Technology s engineers are able to ensure both reliability and electrical safety for the University. Switchgear Designed by our in house data centre team all switchgear was supplied as part of this project. Installed systems were manufactured by Schneider Electric incorporating PM750 full function meter technology combined with an EGX100 Modbus over TCP gateway to allow for remote energy monitoring. APC by Schneider Electric Symmetra PX250/500 UPS In order to meet the levels of redundancy within the limited footprint Workspace Technology deployed APC s Symmetra PX250/500 UPS system for the University of Aberdeen. Designed to expand up to 500kW the Symmetra PX is a true modular system engineered to ensure easy and efficient serviceability. The Symmetra PX architecture scales power and runtime to enable the system to be expanded in a modular cost effective fashion in line with the University s critical load growth demands. The Symmetra PX is made up of dedicated and redundant modules which include power, intelligence, battery and bypass functions. The Symmetra PX serves the University s entire data centre. With excellent manageability the Symmetra PX features self-diagnostics and standardized modules which help reduce human error and result in increased reliability for the University. 5
7 Power Generation Workspace Technology s Power Generation Division supplied a 600KVA generator set designed with MTU low emission engine, Stamford Alternator and Deep Sea Controls. Product Features Long life robust design High stiffness (low powertrain bending) Best in class Noise, Vibrations, Harshness (NVH) behaviour The selected MTU engine is fully compliant to the latest emission meeting both EU- and US-regulatory requirements. Workspace Technology Power Generation included a 24 hour fuel and associated components fuel systems, including, fuel-water separators, pump, tanks level sensing equipment and dump valve. The system replaced the existing generator that no longer had sufficient capacity to support the new data centre. 6
8 I.T Infrastructure As part of the installation Workspace Technology deployed 70 x APX NetShelter SX multivendor equipment racks, APC intelligent metered rack PDU s and Belden Cat6A I/O rack to rack cabling links. Equipment Rack The APC NetShelter is a multi-functional rack enclosure designed to meet a wide range of applications. With an excellent focus on power distribution, cable management, environmental monitoring and cooling, the NetShelter enclosure provides the University with a reliable rack environment to support mission critical equipment. The racks were combined with under floor cable baskets and trays designed to manage both power and data cables. Intelligent PDU s Workspace Technology supplied and installed APC s Intelligent Rack Power Distribution Units (PDUs) as part of the overall solution for the University. The products enable user customizable power control and metering functions. Workspace Technology integrated the PDU s with the Data Centre Infrastructure Management System programming thresholds to help avoid circuit overload. The PDU systems include current and real power monitoring; they also support a temperature/humidity sensor port, and have locking IEC receptacles fitted for additional cable security. Structured Cabling Workspace Technology installed Belden 10GX cabling for the University of Aberdeen. The Belden IBDN 10GX System is specifically designed to support mission critical needs of data centres. Workspace Technology is a Certified Systems Vendors for Belden, the solution was supplied with a full 25 Year System Warranty. 7
9 Data Centre Infrastructure Management Workspace Technology installed APC s StruxureWare Data Centre Expert a vendor-neutral, scalable monitoring system which collects, organizes, and distributes critical alerts, and provides the University with a unified view of the data centre infrastructure from anywhere on their network. The StruxureWare Data Centre Expert was combined with APC s StruxureWare for Data Centres which is a management software suite designed to collect and manage the University s data centre s assets. The DCIM installation has been designed to optimize the University s data centre performance and to help meet its IT, business and service oriented goals. Complete Integration & Support Services Workspace Technology is one of the UK s leading independent Data Centre, Design, Build & Management companies. Workspace Technology works for both private and public sector clients across the UK and has an extensive customer base in Scotland. This project was challenging, in particular the necessity to maintain the existing services which could not be decamped during the project. These issues were readily resolved by Workspace Technology s Project Team and lead to the eventual and successful completion of the project in the spring of On commissioning the PUE was registered at >1.15 proving the effectiveness of Workspace Technology Freecool technology. A planned preventative maintenance programme for the complete Freecool and associated data centre installation backed up with emergency callout for unplanned failures has been implemented for the University. 8
10 The NESS partnership (North East Shared Services) consists of Robert Gordon University, Aberdeen College, Banff and Buchan College and the University of Aberdeen. The NESS partnership identified that the first opportunity was for all institutes to share a common primary data centre. It was to this goal that Workspace set out to deliver what the NESS partners was felt to be a very ambitious programme to completely refurbish the University of Aberdeen's Edward Wright data centre and deliver an environment with a targeted PUE of 1.2. As the main institute affected by the work, the highest risk the University of Aberdeen faced was unplanned down time as Workspace unravelled 23 years of adhoc growth. It is a testament to their professionalism that only 20 minutes of unplanned down time was experienced by 50 out of 20,000 users. Workspace worked to ensure major transition work occurred during student break periods thus helping to minimise impact to them and the rest of the University of Aberdeen. The refurbished data centre which has been delivered to NESS has been built to a very high standard by Workspace. Furthermore the NESS partnership is delighted that the PUE is less than 1.15 during the summer and they recognise this will only improve during the Scottish Winter. The financial benefit to the University of Aberdeen is a reduction in the power bill for the data centre by 94,000 per year whilst improving the environment by reducing the data centre carbon foot print by 612 tonnes per year. Across all the NESS partners the refurbished data centre will produce an annual financial saving of 256,000 with the total carbon foot print being reduced by 1450 tonnes The NESS partnership has been left with a data centre that is fit for purpose and provides a secure foundation from which to deliver IT services to the HE and FE sector in the North East of Scotland. Peter Esson Data Centre & Operations Manager 9
11 About Workspace Technology Workspace Technology s Data Centre Solutions division offer clients Data Centre, Server and Communications Room solutions and services which are Energy Efficient by Design. By engaging you and taking the time to understand the business and performance related issues Workspace Technology is able to effectively address the demands of your business. Workspace Technology welcomes this opportunity to connect with you as a valued customer. We would like to share our vision and expertise through a partnership approach. Our ability to deliver integrated, scalable, energy efficient solutions has made us the preferred choice for many public sector and commercial businesses today. Operating throughout the UK, Workspace Technology offers clients an enthusiastic and refreshing approach, combined with teamwork that takes performance and service to new levels of excellence. Further details of Workspace Technology s products and services can be found at Approved Endorser EU Code of Conduct on Data Centre Efficiency APC Elite Partner Data Centre Certified Workspace Technology s Commitment to help clients reduce their carbon footprint through the deployment of energy efficient technology and design. Technology House, 5 Emmanuel Court, Reddicroft Sutton Coldfield, West Midlands B72 1TJ. Tel : Fax: [email protected]
Case Study Nottingham Trent University
Data Centre Solutions...energy efficient by design Case Study Nottingham Trent University Nottingham Trent University deploys Modular Data Centre Technology (MDC) Designed & Manufactured by Workspace Technology
Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
Data Centre Solutions energy efficient by design
Data Centre Solutions energy efficient by design Mobile & Modular Data Centre Solutions Agile, Scalable, High Performance Mobile and Modular DC solutions Flexible, scalable high performance mobile & modular
Engineering & Support Services
Engineering & Support Services Expert Project, Engineering & Customer Support Services Providing a range of Engineering and Support Services for:- Mission Critical Environments Data Centres & Server Room
Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions
Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
Modular Data Centre. Flexible, scalable high performance modular data centre solutions. Data Centre Solutions...energy efficient by design
Data Centre Solutions...energy efficient by design Modular Data Centre Flexible, scalable high performance modular data centre solutions Creating an effective workspace environment The Modular Data Centre
Colocation Selection Guide. Workspace Technology Ltd
Colocation Selection Guide Workspace Technology Ltd Technology House 5 Emmanuel Court Reddicroft Sutton Coldfield West Midlands B72 1TJ Tel 0121 354 4894 Fax 0121 354 6447 www.workspace-technology.com
How To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
InfraStruxure Data Centre Management Software. Holistic open standards integrated data centre management solution.
Data Centre Solutions...energy efficient by design InfraStruxure Data Centre Management Software Holistic open standards integrated data centre management solution. Creating an effective workspace environment
Portable Energy Efficient Data Centre Solution
Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Data Center Solutions - The Containerized Evolution
Data Center Solutions - The Containerized Evolution Power IT Cooling 7 th Green Connected World Tsikogias Thanassis Data Centers Solutions Architect, IT Business Athens 2015 1 We are the global specialist
scalable data centre energy management solution
scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology
Server Room, Data Centre Management and Monitoring Solutions
Server Room, Data Centre Management and Monitoring Solutions Published in October 2007 Management & Monitoring Solutions The ability to alert a business to disasters or potential performance issues at
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
The Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Galaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
Datacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
PAYGO for Data Center -- Modular Infrastructure
PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Datacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Simplifying Data Center Design/Build
Simplifying Data Center Design/Build A new approach to deliver speed, cost, and performance (availability, efficiency, scalability) Eduard Bodor Data Center Business Development Manager for Central and
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
Rack Power Distribution
The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
Rack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
Energy Management Solutions
Energy Management Solutions Introducing the world s most innovative intelligent Power Distribution Units (ipdus) designed to simplify rack energy and environmental management of your data center. Enlogic
DCIM Data Center Infrastructure Monitoring
DCIM Data Center Infrastructure Monitoring ServersCheck offers a flexible, modular and affordable DCIM solution. It is based on our range of IP & SNMP hardware environmental sensors and management software.
Blade Server & Data Room Cooling Specialists
SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac.
Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire http://rare-idc.herts.ac.uk Making Existing Server Rooms More Efficient Reduction and Re-use
Case study: End-to-end data centre infrastructure management
Case study: End-to-end data centre infrastructure management Situation: A leading public sector organisation suspected that their air conditioning units were not cooling the data centre efficiently. Consequently,
Technologies for Data Centres
Technologies for Data Centres BlueNet at a glance // PHILOSOPHY A passion for innovation page 5 // ENERGY MANAGEMENT The latest in efficiency page 7 // HIGH AVAILABILITY Seamless and systematic security
Data centres that deliver [email protected]
Data centres that deliver [email protected] DATA CENTRE INFRASTRUCTURE MANAGEMENT (DCIM) DCIM solutions are designed to collect and manage information about a data centre s assets, resource use
T: 0344 875 4555 [email protected]
T: 0344 875 4555 [email protected] DATACENTRE UK INTRODUCTION Datacentre UK are specialist providers of energy efficient data centre and physical infrastructure solutions across the UK, Europe
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
The European Programme for Energy Efficiency in Data Centres: The Code of Conduct
The European Programme for Energy Efficiency in Data Centres: The Code of Conduct Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 Why Data Centres? Continuing demand for
Essential NCPI Management Requirements for Next Generation Data Centers
Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently
COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C
COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing
PX100 MBP with Configurable Distribution
PX100 MBP with Configurable Distribution High-performance, right-sized, 3-phase power protection with industry-leading efficiency, availability, and performance for small and medium data centers July 2012
Capgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
Improve competiveness of IDC and enterprise data centers with DCIM
Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Reference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
Zen Internet Case Study
Zen Internet Case Study About Zen Internet Zen Internet is an independent Internet Service Provider (ISP) that offers a full range of data, voice, and hosting services to businesses and residential users
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
RiMatrix S Make easy.
RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power
Solutions for Small to Medium Data Centers
Cisco Systems InfraStruXure Backs Up Cisco Systems San Jose Spyglass Center Cisco Systems Network Management Technology Group (NMTG) provides products and solutions for managing Cisco-based converged networks
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
THE WORLD S MOST EFFICIENT DATA CENTER
THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject
Energy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1
Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier
Symmetra PX. Industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments
Symmetra PX Scalable from 16 kw to 500 kw Parallel-capable up to 2,000 kw High-performance, right-sized, modular, hot-scalable, three-phase power protection with ultra-high availability and efficiency
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
Microsoft Technology Center: Philadelphia
A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities
APC by Schneider Electric
APC by Schneider Electric Energy Efficiency - The Green Power Solution James Taylor Business Development manager, UK APC by Schneider Electric The Efficient Enterprise Components Close Coupled Cooling
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Data Center Trend: Distributed Power in the White Space
Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical